Professional Documents
Culture Documents
Page 1 of 5
You are here: Home > Products > Uninterruptible Power Supply (UPS) > Smart-UPS
Technical Specifications
Output
Product Overview
Documentation
Options
Compare Models
Output Power Capacity Max Configurable Power Nominal Output Voltage Output Voltage Note
1980 Watts / 2200 VA 1980 Watts / 2200 VA 230V Configurable for 220 : 230 or 240 nominal output voltage
http://www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SUA2200XLI&tab=models&page_type=print
24/10/2011
Page 2 of 5
Efficiency at Full Load Output Voltage Distortion Output Frequency (sync to mains) Waveform Type Output Connections
95.0% Less than 5% at full load 47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal Sine wave (8) IEC 320 C13 (1) IEC 320 C19 (2) IEC Jumpers
Input
230V 50/60 Hz +/- 5 Hz (auto sensing) IEC-320 C20 Schuko CEE 7 / EU1-16P British BS1363A
Input voltage range for main operations 160 - 286V Input voltage adjustable range for mains 151 - 302V operation
Batteries & Runtime
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof 3 hour(s) RBC55 1
http://www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SUA2200XLI&tab=models&page_type=print
24/10/2011
Page 3 of 5
Extended Run Options Runtime Graph Curve A B C D E Part Number(s) SUA2200XLI SUA2200XLI + (1)SUA48XLBP SUA2200XLI + (2)SUA48XLBP SUA2200XLI + (3)SUA48XLBP SUA2200XLI + (4)SUA48XLBP
Hover over the line on the graph above to view the runtime at any desired load Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output. View Enlarged Graph
Communications & Management
Interface Port(s)
DB-9 RS-232,SmartSlot,USB
Available SmartSlot Interface Quantity 1 Control panel LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : and Overload Indicators
http://www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SUA2200XLI&tab=models&page_type=print
24/10/2011
Page 4 of 5
Alarm when on battery : distinctive low battery alarm : configurable delays Optional
480 Joules Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Physical
Maximum Height Maximum Width Maximum Depth Rack Height Net Weight Shipping Weight Shipping Height Shipping Width Shipping Depth Color Units per Pallet
Environmental
444.00 mm 221.00 mm 495.00 mm 5U 55.00 KG 80.00 KG 530.00 mm 600.00 mm 780.00 mm Black 3.00
http://www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SUA2200XLI&tab=models&page_type=print
24/10/2011
Page 5 of 5
Audible noise at 1 meter from surface of 53.00 dBA unit Online Thermal Dissipation
Conformance
305.00 BTU/hr
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.
http://www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SUA2200XLI&tab=models&page_type=print
24/10/2011