Operating Instructions for the Fire Alarm System

Release 05.00.00

Copyright 25.10.2006 All rights reserved. Without express approval of the publisher this manual may not completely or in part be reproduced or forwarded electronically or mechanically, copied, recorded or stored in any form.
Securiton AG Alpenstrasse 20 CH3052 Zollikofen Switzerland

Contents Table
Chapter 1 Prerequisites for Operation...........................................................................3 Hierarchical Design of the SecuriPro Fire Alarm System...............................................3 Chapter 2 Operation and Display Devices.....................................................................4 The operating devices MIC 732 and MIC 734...................................................................4 The operating device MIC 742........................................................................................11 The fire brigade operating part of the MIC742................................................................18 The fire brigade operating device FBM 732....................................................................19 Chapter 3 Operation and Information............................................................................21 Switching the system to present / absent........................................................................21 Operation on detection areas..........................................................................................22 Operation on detection zones..........................................................................................24 Operation on detectors....................................................................................................27 Local alarm......................................................................................................................30 Alarm transmission..........................................................................................................32 Outputs............................................................................................................................34 Inputs...............................................................................................................................36 Time.................................................................................................................................38 Changing, reprogramming the operator code.................................................................40 Context operation............................................................................................................42 Remote Access................................................................................................................43 Chapter 4 Extended Information...................................................................................44 Polling the system status.................................................................................................44 Polling the event memory................................................................................................45 Polling the maintenance memory....................................................................................46 Polling the alarm counter.................................................................................................46 Chapter 5 Procedure for Alarms and Faults.................................................................47 Procedure for alarm signal..............................................................................................47 Procedure for fault indication...........................................................................................49 Chapter 6 Procedure for Different System States.......................................................50 Resetting the alarms........................................................................................................50 Resetting the setting deviations.......................................................................................51 Chapter 7 Assistance for Troubleshooting..................................................................52 Procedure in case of faults..............................................................................................52

Chapter 1
Subjects in this chapter

Prerequisites for Operation


Hierarchical Design of the SecuriPro Fire Alarm System

Hierarchical Design of the SecuriPro Fire Alarm System


Presentation of the design A SecuriPro fire alarm system is subdivided in descending order into the logical units System Detection area Detection zone Detector .
Legend: DA DZ DET Detection area Detection zone Detector

System Securiton AG Building A DA 00__.__ Office 1st floor DZ 0001.__ Building B DA 01__.__ Staircase DZ 0002.__ Office 104 DET 0001.04 Building C DA 02__.__ Office 2nd floor DZ 0003.__ Office 105 DET 0001.05

Office 101 DET 0001.01

Office 102 DET 0001.02

Office 103 DET 0001.03

Note: A fire alarm system may contain up to 96 detection areas. If several main control units (MCU 211) are networked in a system, each one starts with a new fire detection area.
Configuration of the fire alarm system

The display of commands and information in these operating instructions is based on a standard configuration. Therefore it does not necessarily conform to the displays and functions available at your device. The larger and the more complex the fire alarm system, the more pages can be called with the softkey [MORE] and assigned to corresponding functions.

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

Chapter 2
Subjects in this chapter

Operation and Display Devices


The operating devices MIC 732 and MIC 734The operating device MIC 742 The fire brigade operating part of the MIC742

The operating devices MIC 732 and MIC 734


Purpose Figure

With the MIC 732 and MIC 734, you can operate the fire alarm system and call information concerning its status. The figure shows the operation device MIC 734.

Note: The inscription strip is customer-specific and therefore not binding in these Operating Instructions.
Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

The operating devices MIC 732 and MIC 734, continued


Function description

Components and their functions

D E

Legend

Function description Key-operated switch For enabling display and operation Function keys <F1> to <F5> For entering the functions and softkeys displayed Function key "back" and "clear" respectively Undoes a non-acknowledged entry Moves back stepwise in the menu structure (>2sec to root) Display MIC 731: Display with 4 lines at 40 characters each MIC 734: Display with 8 lines at 40 characters each LED Light-emitting diode Individual inscription strip Inscription of the LED Numerical keyboard [ * ] = Terminate numerical input [ # ] = Discard operator code
Continued on next page

A B C

E F G

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

The operating devices MIC 732 and MIC 734, continued


Softkeys

Keys and their functions:


Function Description Display
Securiton AG F1: F2: F3: F4: 13.02.02 14:54 SYSTEM DETECTION AREA DETECTION ZONE DETECTOR [MORE] 13.02.02 14:54 Displays detailed informa- Securiton AG tion in lists F1: DZ-0023 <OFF> Cafeteria [DOWN] Displays the next element in lists [UP] Displays the previous element in lists [ALL] [ UP ] [DOWN] [ZOOM] [ALL] Executes the function displayed for all elements in lists Note: Appears only at the end of a list 13.02.02 14:54 [ENTER] Executes the function dis- Securiton AG played 01/23 DZ-0023 <OFF> Building F Cafeteria

[MORE]

Displays additional menu items

[ZOOM]

[TO]

For processing several objects from - to within the same higher-order unit (e.g. detector zone)

[ENTER] Securiton AG

[ UP ] [DOWN] 13.02.02 14:54

F1: SWITCH OFF F2: SWITCH ON F3: SWITCH OFF SMOKE PART F4: SWITCH ON SMOKE PART DETECTION ZONE NO. 0001 [TO ] [MORE]

Note: The Softkey [TO] is superimposed on the function key <F4>.


Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 6

The operating devices MIC 732 and MIC 734, continued


Meaning of the display

1st line: 2nd line: 3rd to 6th lines: 7th line: 8th line:

First event or system name with date and time For several event of the same priority, the last one Assignment of the function keys <F1> to <F4> Temporary check-back signals, waiting instructions (busy) etc. Inscription of the softkeys

Below you find an example with the operator code set in the main menu, with 4 specified deviations
1st line 2nd line 3rd line 4th line 5th line 6th line 7th line 7th line 001.SETTING DEVIATION: DZ0002 office 102 004.SETTING DEVIATION: DZ0005 office 105 F1: SETTING DEVIATIONS F2: OPERATION AND INFO F3: EXTENDED INFORMATION [XXXX] [XXXX] [XXXX] [XXXX] [MORE]

Display of events

The priorities for displaying events are set in descending order as follows: Alarm Pre-alarm Fault Set deviation Disconnections Info The display is composed as follows: 001 Fire DZ0001 1st Floor Corridor
001 Event number Fire Designation of the event DZ0001 1st Floor Corridor System-related des- Object-related desigignation of the event nation of the event (e.g. (e.g. detector zone detector zone 0001) "1st Floor Corridor"

Each additional (e.g. criterion) event is incremented by 1

Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

The operating devices MIC 732 and MIC 734, continued


Display of commands and information

The display is divided into the following 3 operational levels: Display without key Display with key Display with operator code (key required) Possible display without key
Securiton AG 13.02.02 14:54

Possible display with the key turned to the right (with entering a code)

Securiton AG F1: LAMP TEST

13.02.02 14:54

CODE:

Possible display with the key turned to the right and after entering a code

Securiton AG

13.02.02 14:55

F1: OPERATION AND INFO F2: EXTENDED INFORMATION

[MORE]

Input of commands

Commands can be entered via the function keys <F1> to <F4>.


Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 8

The operating devices MIC 732 and MIC 734, continued


Operator code

The operator code regulates the authorisation for operating the MIC 732 and MIC 734 and is used to identify persons. It consists of a two-digit operator code ID number plus a freely selectable combination of three to six digits. The two-digit ID number is defined in the operator code profile and cannot be changed.
Securiton AG F1: LAMP TEST 13.02.02 14:54

CODE:

Note: The operator code ID numbers are defined during project planning.
Entering the operator code

To enter your operator code, proceed stepwise as follows:


Step 1. Procedure Turn the key to the right Process/reading on display
Securiton AG F1: LAMP TEST 13.02.02 14:54

CODE:

2.

Enter the ID number and your personal operator code (3 to max. 6 digits) via the numerical keyboard

Securiton AG F1: LAMP TEST

13.02.02 14:54

CODE: ********

3.

Attention: If you have made a typing error, you can discard the entry with the key [ # ] before acknowledgement. Securiton AG 13.02.02 14:55 Acknowledge the entry with the key [ * ] of the numerical F1: OPERATION AND INFO keyboard F2: EXTENDED INFORMATION

Discard operator code

A set operator code can be discarded with the key [ # ] of the numerical keyboard

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

The operating devices MIC 732 and MIC 734, continued


Procedure

To carry out the lamp test, proceed stepwise as follows.


Step 1. Procedure Turn the key to the right Process/reading on display
Securiton AG F1: LAMP TEST 13.02.02 14:54

CODE:

2.

Press the function key for Lamp test

For 5s all points of the display are actuated, all LED's flash, and the buzzer sounds intermittently

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 10

The operating device MIC 742


Purpose

With the MIC 742, you can operate the fire alarm system and call information concerning its status. Included is the Swedish fire brigade operating panel according to SS3654 and SS3654 T1 The figure shows the operation device MIC 742.

Figure

Note: The inscription strip in the right part of the operation panel is customer-specific and therefore not binding in these Operating Instructions.
Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

11

The operating device MIC 742 , continued


Function description

Components and their functions

DEF

Legend

B C D

E F G H

Function description Operating part for the fire brigade Elements within the rectangular white frame are according to the to Swedish standard SS3654 and SS3654 T1 for fire brigade panel. Refer to chapter The fire brigade operating part of the MIC742 on page 18 in this document. Key-operated switch For enabling display and operation Function keys <F1> to <F5> For entering the functions and softkeys displayed Function key "back" and "clear" respectively Undoes a non-acknowledged entry Moves back stepwise in the menu structure (>2sec to root) Display Display with 4 lines at 40 characters each LED Light-emitting diode Individual inscription strip Inscription of the LED Numerical keyboard [ * ] = Terminate numerical input [ # ] = Discard operator code

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 12

Softkeys

Keys and their functions:


Function Description Display
Securiton AG 13.02.02 14:54 F1: SYSTEM F2: DETECTION AREA F3: DETECTION ZONE [MORE] Securiton AG 13.02.02 14:54 F1: DZ-0023 <OFF> Cafeteria

[MORE] [ZOOM]

Displays additional menu items

Displays detailed information in lists [DOWN] Displays the next element [ALL] [ UP ] [DOWN] [ZOOM] in lists [UP] Displays the previous element in lists [ALL] Executes the function displayed for all elements in lists Note: Appears only at the end of a list 13.02.02 14:54 [ENTER] Executes the function dis- Securiton AG 01/23 DZ-0023 <OFF> played Building F Cafeteria [TO] For processing several objects from - to within the same higher-order unit (e.g. detector zone)

[ENTER] [ UP ] [DOWN] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON DETECTION ZONE NO. 0001 [TO ] [MORE]

Note: The Softkey [TO] is superimposed on the function key <F4>.


Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

13

The operating device MIC 742 , continued


Meaning of the display

1st line: 2nd line: 3rd line: 4th line:

First event or system name with date and time For several event of the same priority, the last one Temporary check-back signals, waiting instructions (busy) etc. Assignment of the function keys <F1> to <F4>

Below you find an example with the operator code set in the main menu, with 4 specified deviations
1st line 2nd line 3rd line 4th line 001.SETTING DEVIATION: DZ0002 office 102 004.SETTING DEVIATION: DZ0005 office 105 F1: SETTING DEVIATIONS [XXXX] [XXXX] [XXXX] [XXXX] [MORE]

Display of events

The priorities for displaying events are set in descending order as follows: Alarm Pre-alarm Fault Set deviation Disconnections Info The display is composed as follows: 001 Fire DZ0001 1st Floor Corridor
001 Event number Fire Designation of the event DZ0001 1st Floor Corridor System-related des- Object-related desigignation of the event nation of the event (e.g. (e.g. detector zone detector zone 0001) "1st Floor Corridor"

Each additional (e.g. criterion) event is incremented by 1

Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 14

The operating device MIC 742 , continued


Display of commands and information

The display is divided into the following 3 operational levels: Display without key Display with key Display with operator code (key required) Possible display without key Possible display with the key turned to the right (with entering a code) Possible display with the key turned to the right and after entering a code
Securiton AG 13.02.02 14:54

Securiton AG F1: LAMP TEST

13.02.02 14:54

CODE: Securiton AG 13.02.02 14:55 F1: OPERATION AND INFO F2: EXTENDED INFORMATION [MORE]

Input of commands

Commands can be entered via the function keys <F1> to <F4>.


Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

15

The operating device MIC 742 , continued


Operator code

The operator code regulates the authorisation for operating the MIC 742 and is used to identify persons. It consists of a two-digit operator code ID number plus a freely selectable combination of three to six digits. The two-digit ID number is defined in the operator code profile and cannot be changed.
Securiton AG F1: LAMP TEST CODE: 13.02.02 14:54

Note: The operator code ID numbers are defined during project planning.
Entering the operator code

To enter your operator code, proceed stepwise as follows:


Step 1. Procedure Turn the key to the right Process/reading on display
Securiton AG F1: LAMP TEST CODE: 13.02.02 14:54

2.

3.

13.02.02 14:54 Enter the ID number and your Securiton AG F1: LAMP TEST personal operator code (3 to max. 6 digits) via the numeric- CODE: ******** al keyboard Attention: If you have made a typing error, you can discard the entry with the key [ # ] before acknowledgement. Securiton AG 13.02.02 14:55 Acknowledge the entry with F1: OPERATION AND INFO the key [ * ] of the numerical F2: EXTENDED INFORMATION keyboard

Discard operator code

A set operator code can be discarded with the key [ # ] of the numerical keyboard

Procedure

To carry out the lamp test, proceed stepwise as follows.


Step 1. Procedure Turn the key to the right Process/reading on display
Securiton AG F1: LAMP TEST CODE: 13.02.02 14:54

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 16

2.

Press the function key for LAMP TEST

For 5s all points of the display are actuated, all LED's flash, and the buzzer sounds intermittently

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

17

The fire brigade operating part of the MIC742


Purpose

The fire brigade operating device is an integrated part of the MIC742 and is used for the standardised alarm handling by the fire brigade in Sweden, according to the standards SS3654 and SS3654 T1

Figure Fire brigade part of the MIC742

B C D E F

G LED Displays

A Brand Indicates that at least one fire detector is in alarm B Slckanlgging aktiverad Indicates the activation of extinguishing systems C Brandventilation aktiverad Indicates the activation of smoke ventilation systems D Styrutgng aktiverad Indicates the activation of fire incident controls E Larmsndare aktiverad Indicates the activation of alarm transmission units F Ingen function This LED is disabled and has no function G FLERA LARM This indicator activates as soon that more than one fire detector is in alarm H FLERA LARM Scrolls down the alarm list in the LCD starting from the most recent alarm I LARMDOM TYST Resets the alarm acoustic devices of the fire alarm system *) J ATERSTALLNING Resets the fire alarm system *) Note: *) Functions can be carried out only with the fire brigade key in on position
Continued on next page

Buttons:

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 18

The fire brigade operating device FBM 732


Purpose

The fire brigade operating device is used for the standardised alarm handling by the fire brigade. Depending on customer requirements, the FBM can however also be operated by the operator and/or caretaker. Displays on the FBM 732: K Alarm L Fault M Alarm transmission activated Functions on the FBM 732: N Switch off alarm devices O Reset fire alarm system. Note: Functions can be carried out only with the standardised key-operated switch SAE 12600.

Figure FBM 732

D E

Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

19

The fire brigade operating device FBM 732, continued


Displays and their meaning

Display and function description:


Display Fire alarm without transmission Meaning Automatic detector alarm before expiration of a delay or inspection time.

Fire alarm with transmission

Fault

Fire alarm with immediate transmission with a pushbutton alarm (hand-operated fire alarm) or after a delay or inspection period with automatic detector alarm. The fire alarm system recognizes a fault indication (collective display).

Switching off the siren

Display and procedure:


Display Procedure Turn the key-operated switch and simultaneously press the siren pushbutton.

In this way all buzzers and acoustical alarm devices are switched off.
u n d g l e i c h z e it i g

Resetting the alarm

Display and procedure:


Display Procedure Turn the key-operated switch and simultaneously press the Reset pushbutton. With this procedure the entire fire alarm system is switched back to the normal operating state.
u n d g l e i c h z e i t i g

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 20

Chapter 3
Subjects in this chapter

Operation and Information


Switching the system to present / absentOperation on detection areas Operation on detection zonesOperation on detectorsLocal alarm Alarm transmission Outputs Inputs TimeContext operation Remote Access

Switching the system to present / absent


Procedure

To switch the system to present / absent, proceed stepwise as follows.


Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for System

Securiton AG F1: PRESENT

4.

Press the function key for the desired function

Securiton AG F1: PRESENT

13.02.02 14:54

DA-00 SWITCHED OFF

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

21

Operation on detection areas


Standard functions

The following functions are present: Switch on and off respectively Poll status Reset To edit detection areas, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

Procedure with list selection

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Detection area

Securiton AG

4.

Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: RESET DETECTION AREA NO.: __ [MORE] Securiton AG 13.02.02 14:54 F1: DA-00 <ON> Building A F2: DA-01 <ON> Building B F3: DA-02 <ON> Building C [DOWN] [ZOOM] 13.02.02 14:54

5.

Press the function key for the desired detection area, or first press the softkey [DOWN] if the desired function is not displayed

Securiton AG

F1: DA-01 <ON> Building B F2: DA-02 <ON> Building C F3: DA-03 <ON> Building D [DOWN] [ZOOM]

Note: Only those detection areas are shown for which the desired function can be executed.
Continued on next page

, continued
Procedure with numerical entries
Copyright by Securiton AG

To edit detection areas, proceed stepwise as follows.

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 22

Step 1.

Procedure Turn the key to the right Enter your personal operator code

Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Detection area

Securiton AG

4.

Enter the detection area via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit detection areas from - to, and enter the "to" detection area as described above

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: RESET DETECTION AREA NO.: __ [MORE] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: RESET DETECTION AREA NO.: 00 [TO] [MORE] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: RESET DETECTION AREA NO.: 00 ok [MORE]

5.

6.

Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON sired function is not displayed F3: POLLING STATUS
F4: RESET DETECTION AREA NO.: __ [MORE]

14:54

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

23

Operation on detection zones


Standard functions

The following functions are present: Switch on and off respectively Switch the smoke part on and off respectively Switch the heat part on and off respectively Poll status Reset To edit detection zones, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

Procedure with list selection

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Detection zone

Securiton AG

F1: DETECTION AREA F2: DETECTOR ZONE

4.

Press the function key for Detection area

Securiton AG

13.02.02 14:54

F1: DETECTOR ZONE

5.

Press the function key for Detector zone

DETECTION AREA NO.: __00.00 Securiton AG 13.02.02 14:54 F1: DA-00 Building A F2: DA-01 Building B F3: DA-02 Building C [DOWN] [ZOOM] Continued on next page

Operation on detection zones, continued


Step 6. Procedure Press the function key for the desired detection area, or first press the softkey [DOWN] if the desired function is not displayed Process/reading on display
Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: SWITCH OFF SMOKE PART F4: SWITCH ON SMOKE PART DETECTOR ZONE NO.: 00__.00 [MORE] Release 05.00

Copyright by Securiton AG

Operating Instructions for the Fire Alarm System SecuriPro 24

7.

Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

13.02.02 14:54

F1: DZ-0001 <OFF> Entrance hall F2: DZ-0002 <OFF> Staircase north F3: DZ-0003 <OFF> Staircase south [DOWN] [ZOOM] 13.02.02 14:54

8.

Press the function key for the desired detector zone, or first press the softkey [DOWN] if the desired detector zone is not displayed

Securiton AG

F1: DZ-0002 <OFF> Staircase north F2: DZ-0003 <OFF> Staircase south F3: DZ-0004 <OFF> Archive [DOWN] [ZOOM] Continued on next page

Operation on detection zones, continued


Procedure with numerical entries

To edit detection zones, proceed stepwise as follows.


Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Detector zone

Securiton AG

F1: DETECTION AREA F2: DETECTOR ZONE

4.

Press the function key for Detector zone

Securiton AG

13.02.02 14:54

5.

Enter the detection zones via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard

F1: SWITCH OFF F2: SWITCH ON F3: SWITCH OFF SMOKE PART F4: SWITCH ON SMOKE PART DETECTOR ZONE NO.: ____ [MORE] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: SWITCH OFF SMOKE PART F4: SWITCH ON SMOKE PART DETECTOR ZONE NO.: 0001 [TO] [MORE]

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

25

6.

Press the softkey [TO] if you want to edit detection zones within a detection area from to, and enter the "to" detector zone as described above

Securiton AG

13.02.02 14:54

F1: SWITCH OFF F2: SWITCH ON F3: SWITCH OFF SMOKE PART F4: SWITCH ON SMOKE PART DETECTOR ZONE NO.: 0001 ok [MORE]

7.

Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON sired function is not displayed F3: SWITCH OFF SMOKE PART
F4: SWITCH ON SMOKE PART DETECTOR ZONE NO.: ____ [MORE]

14:54

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 26

Operation on detectors
Standard functions

The following functions are present: Switch off/on Exchange Switch off/on smoke part Switch off/on heat part Poll status Reset Disconnect/Connect To edit detectors, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

Procedure with list selection

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Detector

Securiton AG

F1: DETECTION AREA F2: DETECTOR

4.

Press the function key for Detection area

Securiton AG

13.02.02 14:54

F1: DETECTOR ZONE

5.

Press the function key for Detector zone

DETECTION AREA NO.: __00.00 Securiton AG 13.02.02 14:54 F1: DA-00 Building A F2: DA-01 Building B F3: DA-02 Building C [DOWN] [ZOOM] 13.02.02 14:54

6.

Press the function key for the desired detection area, or first press the softkey [DOWN] if the desired function is not displayed

Securiton AG F1: DETECTOR

DETECTOR ZONE NO.: 00__.00 [MORE] Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

27

Operation on detectors, continued


Step 7. Procedure Press the function key for Detector Process/reading on display
Securiton AG 13.02.02 14:54 F1: DZ-0001 Entrance hall F2: DZ-0002 Staircase north F3: DZ-0003 Staircase south [DOWN] [ZOOM] 13.02.02 14:54

8.

Press the function key for the desired detector zone, or first press the softkey [DOWN] if the desired detector zone is not displayed Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

F1: SWITCH OFF F2: SWITCH ON F3: EXCHANGE F4: SWITCH OFF SMOKE PART DETECTOR NO.: 0001.__ Securiton AG 13.02.02 14:54

9.

F1: DET-0001.01 <DISCONNECT> front F2: DET-0001.02 <DISCONNECT> middle F3: DET-0001.03 <DISCONNECT> rear [DOWN] [ZOOM] 13.02.02 14:54

10.

Press the function key for the desired detector, or first press the softkey [DOWN] if the desired detector is not displayed

Securiton AG

F1: DET-0001.02 <DISCONNECT> middle F2: DET-0001.02 <DISCONNECT> rear [DOWN] [ZOOM] Continued on next page

Operation on detectors, continued


Procedure with numerical entries

To edit detectors, proceed stepwise as follows.


Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Detector

Securiton AG

F1: DETECTION AREA F2: DETECTOR

[MORE] Copyright by Securiton AG Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 28

4.

Press the function key for Detector

Securiton AG

13.02.02 14:54

5.

Enter the detector number via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit detectors within a detector zone from - to, and enter the "to" detector as described above

F1: SWITCH OFF F2: SWITCH ON F3: EXCHANGE F4: SWITCH OFF SMOKE PART DETECTOR NO.: ____.__ [MORE] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: EXCHANGE F4: SWITCH OFF SMOKE PART DETECTOR NO.: 0001.01 [TO] [MORE] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: EXCHANGE F4: SWITCH OFF SMOKE PART DETECTOR NO.: 0001.01 ok [MORE]

6.

7.

Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON sired function is not displayed F3: EXCHANGE

14:54

F4: SWITCH OFF SMOKE PART DETECTOR NO.: ____.__ [MORE]

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

29

Local alarm
Standard functions

The following functions are present: Switch on and off respectively Poll status Reset Switch maintenance on and off To edit the local alarm, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

Procedure with list selection

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Local alarm, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

4.

Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON LOCAL ALARM NO.: __ [MORE] Securiton AG 13.02.02 14:54 F1: F2: F3: F4: AE-01 BUZZER [OFF] BUZZER ALARM AE-02 BUZZER [OFF] BUZZER FAULT AU-03 BUZZER [OFF] BUZZER PREALARM AU-04 AU [OFF] SIREN [DOWN] 13.02.02 14:54

5.

Press the function key for the desired local alarm, or first press the softkey [DOWN] if the desired function is not displayed

Securiton AG

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON LOCAL ALARM NO.: __ [MORE] Continued on next page

Local alarm, continued


Procedure with numerical entries

To edit the local alarm, proceed stepwise as follows.


Step Procedure Process/reading on display
Release 05.00

Copyright by Securiton AG

Operating Instructions for the Fire Alarm System SecuriPro 30

1.

Turn the key to the right Enter your personal operator code

Securiton AG

13.02.02 14:54

F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Local alarm, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

4.

Enter the local alarm number via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit local alarms from - to, and enter the "to" local alarm as described above

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON LOCAL ALARM NO.: __ [MORE] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON LOCAL ALARM NO.: 01 [TO] [MORE] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON LOCAL ALARM NO.: 01 ok [MORE]

5.

6.

Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON sired function is not displayed F3: POLLING STATUS
F4: MAINT. SWITCH ON LOCAL ALARM NO.: __ [MORE]

14:54

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

31

Alarm transmission
Standard functions

The following functions are present: Switch on and off respectively Poll status Reset Switch maintenance on and off To edit the local alarm, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

Procedure with list selection

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Alarm transmission, or first press the softkey [MORE] if the desired function is not displayed Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

4.

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON ALARM TRANSMISSION NO.: __ [MORE] Securiton AG 13.02.02 14:54 F1: F2: F3: F4: TU-01 TU-02 TU-03 TU-04 TU TU TU TU <OFF> <OFF> <OFF> <OFF> FIRE FIRE MCP FAULT SC SYSTEM

5.

Press the function key for the desired alarm transmission, or first press the softkey [DOWN] if the desired function is not displayed

Securiton AG

[DOWN] [ZOOM] 13.02.02 14:54

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON ALARM TRANSMISSION NO.: __ [MORE] Continued on next page

Alarm transmission, continued

Procedure with numerical entries

To edit the local alarm, proceed stepwise as follows.


Step Procedure Process/reading on display
Release 05.00

Copyright by Securiton AG

Operating Instructions for the Fire Alarm System SecuriPro 32

1.

Turn the key to the right Enter your personal operator code

Securiton AG

13.02.02 14:54

F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Alarm transmission, or first press the softkey [MORE] if the desired function is not displayed Enter the local alarm transmission number via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit alarm transmissions from - to, and enter the "to" alarm transmission as described above

Securiton AG

4.

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON ALARM TRANSMISSION NO.: __ [MORE] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON ALARM TRANSMISSION NO.: 01 [TO] [MORE] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: POLL STATUS F4: MAINT. SWITCH ON ALARM TRANSMISSION NO.: 01 ok [MORE]

5.

6. 7.

Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON sired function is not displayed F3: POLL STATUS

14:54

F4: MAINT. SWITCH ON ALARM TRANSMISSION NO.: __ [MORE]

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

33

Outputs
Standard functions

The following functions are present: Switch on and off respectively Poll status Switch maintenance on and off To edit the local alarm, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

Procedure with list selection

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Outputs, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

4.

Press the function key for the desired function, or first press the softkey [ZOOM] if the desired function is not displayed

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON OUTPUT NO.: ___ [MORE] Securiton AG 13.02.02 14:54 F1: OUT-001 [OFF] IOM LB1 ACTIVATED F2: OUT-002 [OFF] IOM LB1 ACTIVATED F3: OUT-003 [OFF] IOM LHT ACTIVATED [DOWN] [ZOOM] 13.02.02 14:54

5.

Press the function key for the desired output, or first press the softkey [ZOOM] if the desired function is not displayed

Securiton AG

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON OUTPUT NO.: ___ [DOWN] [ZOOM] Continued on next page

Outputs, continued
Procedure with numerical entries

To edit the local alarm, proceed stepwise as follows.


Step Procedure Process/reading on display

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 34

1.

Turn the key to the right Enter your personal operator code

Securiton AG

13.02.02 14:54

F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Outputs, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

4.

Enter the output number via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit outputs from - to, and enter the "to" output as described above

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON OUTPUT NO.: ___ [MORE] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON OUTPUT NO.: 001 [TO] [MORE] Securiton AG 13.02.02 14:54 F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS F4: MAINT. SWITCH ON OUTPUT NO.: 001 ok [MORE]

5.

6. 7.

Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON sired function is not displayed F3: POLLING STATUS
F4: MAINT. SWITCH ON OUTPUT NO.: ___ [MORE]

14:54

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

35

Inputs
Standard functions

The following functions are present: Switch on and off respectively Poll status To edit the local alarm, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

Procedure with list selection

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Inputs, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS INPUT NO.: ___ [MORE] 13.02.02 14:54

4.

Press the function key for the desired function, or first press the softkey [ZOOM] if the desired function is not displayed

Securiton AG

F1: IN-001 [OFF] Extinguisher released F2: IN-002 [OFF] Extinguisher fault

5.

Press the function key for the desired input, or first press the softkey [DOWN] if the desired function is not displayed

Securiton AG

[DOWN] [ZOOM] 13.02.02 14:54

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS INPUT NO.: ___ [MORE] Continued on next page

Inputs, continued
Procedure with numerical entries

To edit the local alarm, proceed stepwise as follows.


Step Procedure Process/reading on display

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 36

1.

Turn the key to the right Enter your personal operator code

Securiton AG

13.02.02 14:54

F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Inputs, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS INPUT NO.: ___ [MORE] 13.02.02 14:54

4.

Enter the input number via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the softkey [TO] if you want to edit inputs from - to, and enter the "to" input as described above

Securiton AG

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS INPUT NO.: 001 Securiton AG [TO] [MORE] 13.02.02 14:54

5.

F1: SWITCH OFF F2: SWITCH ON F3: POLLING STATUS INPUT NO.: 001 ok [TO] [MORE]

6. 7.

Note: The Softkey [TO] is superimposed on the function key <F4>. 13.02.02 Press the function key for the Securiton AG desired function, or first press F1: SWITCH OFF the softkey [MORE] if the de- F2: SWITCH ON sired function is not displayed F3: POLLING STATUS
INPUT NO.: ___ [MORE]

14:54

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

37

Time
Standard functions

The following functions are present: Input time Input date To edit the time, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

Procedure

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Time, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: TIME INPUT F2: DATE INPUT

4.

Press the function key for Time input

Securiton AG F1: TIME INPUT F2: DATE INPUT

13.02.02 14:54

TIME INPUT: 14:54:49

5.

Enter the correct time via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard Press the function key for Date input

Securiton AG F1: TIME INPUT F2: DATE INPUT

13.02.02 14:54

6.

Securiton AG F1: TIME INPUT F2: DATE INPUT

13.02.02 14:54

DATE INPUT: 13.02.02

7.

Enter the correct date via the numerical keyboard Acknowledge the entry with the key [ * ] of the numerical keyboard

Securiton AG F1: TIME INPUT F2: DATE INPUT

13.02.02 14:54

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 38

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

39

Changing, reprogramming the operator code


Changing the operator code

To change your operator code, proceed stepwise as follows:


Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:55 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Operation and info

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTION ZONE DETECTOR [MORE] 13.02.02 14:55

3.

Press the function key for Code, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: CHANGE

4.

Press the function key for Change

Securiton AG F1: CHANGE

13.02.02 14:55

PCODE NEW ______

5.

Enter the new operator code without operator code ID (3 to max. 6 digits) via the numerical keyboard

Securiton AG F1: CHANGE

13.02.02 14:55

PCODE NEW ******

6.

Attention: If you have made a typing error, you can discard the entry with the key <CLEAR> before acknowledgment. Securiton AG 13.02.02 14:55 Acknowledge the entry with the key [ * ] of the numerical F1: CHANGE keyboard
CONFIRM PCODE
------

7.

Confirm the new operator code once more as described above

Securiton AG F1: CHANGE

13.02.02 14:55

Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 40

, continued
Reprogramming the operator code

To reprogram an operator code, proceed stepwise as follows: Note: You need the appropriate authorisation to reprogram an operator code.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:55 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Operation and info

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTION ZONE DETECTOR [MORE] 13.02.02 14:55

3.

Press the function key for Code, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

F1: CHANGE F2: NEW PROGRAMMING

4.

Press the function key for New programming

Securiton AG

13.02.02 14:55

F1: CHANGE F2: NEW PROGRAMMING ID/PCCODE NEW ______

5.

Enter the existing operator code ID and the new operator code (3 to max. 6 digits) via the numerical keyboard

Securiton AG

13.02.02 14:55

F1: CHANGE F2: NEW PROGRAMMING ID/PCCODE NEW ******

6.

Acknowledge the entry with the key [ * ] of the numerical keyboard

Securiton AG

13.02.02 14:55

F1: CHANGE F2: NEW PROGRAMMING CONFIRM ID/PCCODE

------

7.

Confirm the new operator code once more as described above

Securiton AG

13.02.02 14:55

F1: CHANGE F2: NEW PROGRAMMING

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

41

Context operation
Procedure

Context operation, also called alternative operation, is a form of operation meant to facilitate switch on, switch off, disconnect and connect operations. This means: If one tries to again switch off an already switched off detector zone, the system proposes to switch on this detector zone. If one tries to again switch on a detector zone with bad AR (e.g. smashed pushbutton glass), the system proposes partial switching off of this detector zone. Note: You need the appropriate authorisation to reprogram an operator code.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:55 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Operation and info

Securiton AG F1: F2: F3: F4:

13.02.02 14:55

SYSTEM DETECTION AREA DETECTION ZONE DETECTOR [MORE] 13.02.02 14:55

3.

Try to switch on a zone (or a detector) which is already switched on. Press <F1> [COMMAND]

Securiton AG

01/01 DZ-0001 ALREADY ON BUILDING A STAIRCASE NORD DETECTION ZONE-NO: 0001 [COMMAND] Securiton AG 13.02.02 14:55 01/01 DZ-0001 ALREADY ON BUILDING A STAIRCASE NORD DETECTION ZONE-NO: 0001 [ENTER]

4.

Press <F1> [ENTER] in order to carry out the context operation

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 42

Remote Access
Standard functions

The following functions are present: Release remote access Delete Installer Password To operate remote acces functions, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

Procedure

2.

Press the function key for Operation and info, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM DETECTION AREA DETECTOR ZONE DETECTOR [MORE] 13.02.02 14:54

3.

Press the function key for Remote Access, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

F1: RELEASE REMOTE ACCESS F2: DELETE INSTALLER PASSWORD

4.

Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

13.02.02 14:54

F1: RELEASE REMOTE ACCESS F2: DELETE INSTALLER PASSWORD

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

43

Chapter 4
Subjects in this chapter

Extended Information
Polling the system statusPolling the event memoryPolling the maintenance memoryPolling the alarm counter

Polling the system status


Standard functions

The following functions are present: Polling the pre-alarm, alarm and fault lists Polling the setting deviations Polling the disconnections Polling In maintenance Polling bad switch-on check Polling bad arming readiness To query the system status, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Press the function key for Extended information, or first press the softkey [MORE] if the desired function is not displayed Press the function key for System status Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION Securiton AG 13.02.02 14:54

Procedure

2.

F1: SYSTEM STATUS F2: EVENT MEMORY F3: ALARM COUNTER Securiton AG F1: F2: F3: F4: ALARM LIST PREALARM LIST FAULT LIST INFO LIST 13.02.02 14:54

3.

4.

Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG

[MORE] 13.02.02 14:54

01/02 DZ-0001 SETTING DEVIATION entranc 02/02 DZ-0003 SETTING DEVIATION stairca

[ZOOM]

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

44

Polling the event memory


Standard functions

The following functions are present: Polling Print all Print alarms Print faults Print on/off switchings Print last 100 events To query or print the event memory, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

Procedure

2.

Press the function key for Extended information, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Event memory

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM STATUS EVENT MEMORY ALARM MEMORY MAINTENANCE MEMORY 13.02.02 14:54

3.

Securiton AG F1: F3: F3: F4: POLLING PRINTS ALL PRINTS ALARMS PRINTS FAULTS

4.

Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed

Securiton AG 01: 02: 03: 04 DZ-0006 DZ-0005 DZ-0004 DZ-0003

[MORE] 13.02.02 14:54 SWITCHED SWITCHED SWITCHED SWITCHED ON ON ON ON

[P-DOWN][ UP ] [DOWN] [ZOOM]

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

45

Polling the maintenance memory


Procedure

To query the maintenance memory, proceed stepwise as follows.


Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Extended information, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Maintenance memory

Securiton AG F1: F2: F3: F4:

13.02.02 14:54

SYSTEM STATUS EVENT MEMORY ALARM MEMORY MAINTENANCE MEMORY 13.02.02 14:54

3.

Securiton AG

01:DZ-0001 IN MAINT. entrance hall

Polling the alarm counter


Procedure

To query the alarm counter, proceed stepwise as follows.


Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
Securiton AG 13.02.02 14:54 F1: OPERATION AND INFO F2: EXTENDED INFORMATION

2.

Press the function key for Extended information, or first press the softkey [MORE] if the desired function is not displayed Press the function key for Alarm counter

Securiton AG

13.02.02 14:54

F1: SYSTEM STATUS F2: EVENT MEMORY F3: ALARM COUNTER

3.

Securiton AG

13.02.02 14:54

01:MEMORY ALARM COUNTER VALUE: 092

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 46

Chapter 5
Subjects in this chapter

Procedure for Alarms and Faults


Procedure for alarm signalProcedure for fault indication

Procedure for alarm signal


Alarms for different system states

Transmission of alarms for different system states System state Present


The alarm message from automatic detectors is transmitted to the fire brigade with a three-minute delay.

System state Absent


All alarm messages are immediately transmitted to the fire brigade.

During this lag phase, it is possible to effect another delay of 5 minutes by pressing the corresponding function key INSPECTION. Alarm messages from hand-operated fire alarms are always transmitted to the fire brigade directly and without delay.
Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

47

Procedure for alarm signal, continued

Procedure for fire alarm/status "Present"

If an alarm is signaled in the "Present" state, i.e. without immediate transmission to the fire brigade, proceed stepwise as described below. Display on the FBM 732: Attention: Also mind the indications on the PIM 731 and the group alarm indication on the PIM 734.
Possible reading on the MIC 732 or MIC 734 display
001 FIRE DZ0002 1ST FLOOR CORRIDOR F1: SWITCH OFF BUZZER F2: ALARM LIST

Step 1.

Procedure Press the function key for Switch off buzzer

Process/reading on display
001 FIRE DZ0002 1ST FLOOR CORRIDOR F1: F2: F3: F4: INSPECT ALARM LIST ABSENT LAMP TEST [MORE]

2.

3.

Note: The delay period of 3 minutes counts from the triggering of the alarm until its transmission to the fire brigade Press the function key for Inspect Go to the source of the fire Note: The inspection time lasts 5 minutes The alarm is transmitted immediately. If the alarm is genuine: Press the nearest pushbutton 001 FIRE DZ0002 1ST FLOOR CORRIDOR If the alarm is false: Turn the key to the right F1: INSPECT Enter your personal operator F2: RESET SYSTEM F3: ALARM LIST code F4: OPERATION AND INFO
[MORE]

Press the function key for RESET SYSTEM

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro 48

Procedure for fault indication


Procedure for fault indication

If a fault is indicated, proceed stepwise as follows. Display on the FBM 732: Attention: Also pay attention to the group fault indication on the PIM 731 On the FBM, faults cannot be acknowledged!
Possible reading on the MIC 732 or MIC 734 display
001 FIRE DZ0002 1ST FLOOR CORRIDOR F1: SWITCH OFF BUZZER F2: FAULT LIST

Step 4.

Procedure Press the function key for Switch off buzzer

Process/reading on display
001 FAULT DZ0099 SYSTEM FAULT F1: F2: F3: F4: SWITCH OFF REMOTE ALARM RESET SYSTEM FAULT LIST OPERATION AND INFO [MORE]

Note: Further procedure see chapter 7

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

49

Chapter 6
Subjects in this chapter

Procedure for Different System States


Resetting the alarmsResetting the setting deviations

Resetting the alarms


Standard functions

The following functions are possible: Switch off buzzer (without operator code) Inspect (without operator code) Switch off local alarm Switch off alarm transmission Reset system Poll pre-alarm Poll alarm Poll fault list Info list Maintenance list In case of an alarm, proceed stepwise as follows.
Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
001. Brand: DZ0001 Entrance hall F1: F2: F3: F4: SWITCH OFF LOCAL ALARM SWITCH OFF REMOTE ALARM RESET SYSTEM ALARM LIST

Procedure

2.

Press the function key for the desired function, or first press the softkey [MORE] if the desired function is not displayed

[MORE] 001. Fire: DZ0001 Entrance hall F1: RESET SYSTEM F2: ALARM LIST F3: OPERATION AND INFO F4: EXTENDED INFORMATION DA-00 ACKNOWLEDGED Securiton AG 13.02.02 14:54

The system is reset

F1: OPERATION AND INFO F2: EXTENDED INFORMATION

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

50

Extended Information

Resetting the setting deviations


Procedure

To reset setting deviations, proceed stepwise as follows.


Step 1. Procedure Turn the key to the right Enter your personal operator code Process/reading on display
001. SETTING DEVIATION: DZ0001 Entrance 004. SETTING DEVIATION: DZ0004 Archive F1: SETTING DEVIATIONS F2: OPERATION AND INFO F3: EXTENDED INFORMATION

2.

Press the function key for Setting deviations, or first press the softkey [MORE] if the desired function is not displayed

001. SETTING DEVIATION: DZ0001 Entrance 004. SETTING DEVIATION: DZ0004 Archive F1: DZ0001 <ON> Entrance hall F2: DZ0002 <ON> Staircase north F3: DZ0003 <ON> Staircase south [DOWN] [ZOOM] 001. SETTING DEVIATION:: DZ0001 Entrance hall 004. SETTING DEVIATION:: DZ0004 Archive F1: DZ0002 <ON> Staircase north F2: DZ0003 <ON> Staircase south F3: DZ0004 <ON> Archive [ZOOM]

Press the function key for the desired set deviation, or first press the softkey [DOWN] if the desired set deviation is not displayed

Copyright by Securiton AG

Release 01.05.00

Bedienungsanleitung fr das FAS R0X00meldesystem SecuriPro

51

Chapter 7
Subjects in this chapter

Assistance for Troubleshooting


Procedure in case of faults

Procedure in case of faults


Procedure

The table below shows a list of frequently occurring faults and offers help for their correction: Note: If the fault cannot be corrected by these means, call your service company.
Kind of fault Fault of a specific detector Possible cause Detector optics defective Defective electronics Battery defective or not charged Power failure > 1 hour Correction Replace detector Wait 5 minutes Reset fault Call Service Wait until power is switched on again Reset fault Switch circuit breaker on Reset fault Call Service Call Service

Accu failure Power failure

Circuit breaker activated Power supply unit defective Short-circuit to earth, e.g. Water in a detector Leakage currents by soiling Electromagnetic disturbances System overload Defective LAN device Fuse faults in MCU

Short to earth

Communication fault

Call Service

Fault SI300 (FA) SI302 (DIVERS) SI302 (OA1) SI303 (OA1) SI303 (OA2) SI304 (LAN1)

Call Service

SI305 (LAN2)
Continued on next page

Copyright by Securiton AG

Release 05.00

Operating Instructions for the Fire Alarm System SecuriPro

52

Extended Information
Procedure in case of faults, continued
Fault Fault L1 xxxxxxxxx Fault L2 xxxxxxxxx Possible cause Correction Technical problem (tempor- Reset fault ary or permanent) in the de- If the fault cannot be actector line. knowledged: Usually caused by the reCall Service moval of a detector Communication fault in the Call Service LAN Poll alarm list Bring faulty detector into normal position or Switch off pertinent detector zone Reset system

LAN channel A fault LAN channel B fault System cannot be reset following an alarm Common alarm LED alarm is not reset