You are on page 1of 14

CHAPTER 1

INTRODUCTION

1.1

Introduction

Model SPC211 is developed to study the application of Single Loop controls of some common simulated processes (Flow and Level). The key topics are how to identify and characterize some real plant processes available at some physical Plants and how to tune their control loops using the Ziegler- Nichols, Cohen-Coon and IMC etc Tuning techniques for Quarter Decay Ratio (QDR) or other performance criteria. Model SPC211 was developed to help teach these key topics in Process Control and to provide the hands-on opportunity for controller tuning skills to be acquired. The Simulated Gas Flow Process consists of a main pipeline where process air representing gas/vapour flows and then discharge to atmosphere via the process vent manual valve VF. The process air that flows into the system is conditioned to have air temperature of 100C. With reference to the dynamic graphic of the Simulated Gas Mass Flow Process at Model SPC211, for PID control, mass flowrate measured by Gas Mass Flowmeter (FE91/FT91), is the measurement input into PID Flow controller FIC91A which in turn throttles the Control valve FCV91, via a Current-to-Air Converter (I/P), FCY91, and a Positioner (PP).

Table 1: Instrumentation and control configuration for gas mass flow process Measurement FE91/ FT91 FT91 represents the gas mass

flowmeter

Control Type

FIC91A

PID Controller configured at DCS

Control Output

FCY91 PP

Current-to-Air Converter (I/P) Pneumatic Position

1|Page

FCV91

Air Mass Flow Control Value. Air-to-close (ATC) type

Figure 1: Simulated gas mass flow process diagram

1.2

Objective

The objective of this experiment is toanalyze the behaviour of the gas mass flow process by simulation.

2|Page

CHAPTER 2

LITERATURE REVIEW

2.1

Literature Review

A proportionalintegralderivative controller (PID controller) is a generic control loop feedback mechanism (controller) widely used in industrial control systems a PID is the most commonly used feedback controller. A PID controller calculates an "error" value as the difference between a measured process variable and a desired set point. The controller attempts to minimize the error by adjusting the process control inputs. In the absence of knowledge of the underlying process, PID controllers are the best controllers. However, for best performance, the PID parameters used in the calculation must be tuned according to the nature of the system while the design is generic, the parameters depend on the specific system.

Figure 2: PID Controller

Source: Industrial/Aerospace/Military Specifications by John T. Jackson retrieved online at http://jrmagnetics.com/mtrctrl/mtrctrlpid.php

2.2

Proportional Term

The proportional term (sometimes called gain) makes a change to the output that is proportional to the current error value. The proportional response can be adjusted by multiplying the error by a constant Kp, called the proportional gain.
3|Page

A high proportional gain results in a large change in the output for a given change in the error. If the proportional gain is too high, the system can become unstable (see the section on loop tuning). In contrast, a small gain results in a small output response to a large input error, and a less responsive (or sensitive) controller. If the proportional gain is too low, the control action may be too small when responding to system disturbances.

Figure 3: Proportional Control

Source: Industrial/Aerospace/Military Specifications by John T. Jackson retrieved online at http://jrmagnetics.com/mtrctrl/mtrctrlpid.php

2.3

Integral Term

The contribution from the integral term (sometimes called reset) is proportional to both the magnitude of the error and the duration of the error. Summing the instantaneous error over time (integrating the error) gives the accumulated offset that should have been corrected previously. The accumulated error is then multiplied by the integral gain and added to the controller output. The magnitude of the contribution of the integral term to the overall control action is determined by the integral gain. The integral term (when added to the proportional term) accelerates the movement of the process towards setpoint and eliminates the residual steady-state error that occurs with a proportional only controller. However, since the integral term is responding to accumulated
4|Page

errors from the past, it can cause the present value to overshoot the setpoint value (cross over the setpoint and then create a deviation in the other direction). For further notes regarding integral gain tuning and controller stability, see the section on loop tuning.

Figure 4: Integral Control

Source: Industrial/Aerospace/Military Specifications by John T. Jackson retrieved online at http://jrmagnetics.com/mtrctrl/mtrctrlpid.php

2.4

Derivative Term

The rate of change of the process error is calculated by determining the slope of the error over time (i.e., its first derivative with respect to time) and multiplying this rate of change by the derivative gain Kd. The magnitude of the contribution of the derivative term (sometimes called rate) to the overall control action is termed the derivative gain, Kd. The derivative term slows the rate of change of the controller output and this effect is most noticeable close to the controller setpoint. Hence, derivative control is used to reduce the magnitude of the overshoot produced by the integral component and improve the combined controller-process stability. However, differentiation of a signal amplifies noise and thus this term in the controller is highly sensitive to noise in the error term, and can cause a process to become unstable if the noise and the derivative gain are sufficiently large. Hence an

5|Page

approximation to a differentiator with a limited bandwidth is more commonly used. Such a circuit is known as a Phase-Lead compensator.

Figure 5: Derivative Control

6|Page

CHAPTER 3

METHODOLOGY

1.

The operator workstation is switched ON. (Acknowledge button was pressed to silence the alarm buzzer sound).

2. 3.

Gas Mass Flow Process was selected. The following Preliminary Exercises are for Dynamic Graphic is checked for the Simulated Gas Mass Flow Process. a) Familiarize and identify the single loop simulated plant process at Model SPC211. Single Loop Simulated Process Simulated Process at Syntek MODEL SPC211 Gas Mass Flow Process Simulated Gas Mass Flow Process

b)

For the Single Loop Simulated process, its control loop was identified (i.e. measuring instrument, controller and final control element with the tag name).

c)

The engineering units for the measured variable (PV), setpoint (SP) and controller output (MV (OUT)) for the process at the DCS Controller is checked.

7|Page

4.

The following Preliminary Exercises are for dynamic behaviour of the process when the controller output is changed (Operating Data Check) at the Simulated Gas Mass Flow Process. a) The dynamic graphic of the Simulated Gas Mass Flow Process at the operator workstation of Model SPC211 was viewed. b) Solenoid valve SV90 at the dynamic graphic page was OPEN. It should be green in colour. c) The PID control scheme was selected; call up the controller FIC91A Faceplate. The controller FIC91A to Manual (MAN) mode is switched. Quickly step change the controller output, MV (OUT) to 100%. d) Call up the Process History View from the FIC91A Faceplate to observe the gas mass flow response (red trend). Wait till the flow response reaches a new steady state (check the PV value). Note the steady state air mass flowrate. e) Then, step change MV (OUT) to 50%. Note that FIC91A is still in Manual (MAN) mode. At the Process History View, the gas mass flowrate (red trend) was observed until it increases. Note the steady state air mass flowrate. f) Step change the controller output, MV(OUT) further to 0% with FIC91A still remain in Manual (MAN) mode. At the Process History View, the gas mass flowrate (red trend) was observed until it increases. Note the steady state gas mass flowrate. g) Print screen the observed gas mass flow response and enclose together with the results sheets. h) With FIC91A in Manual (MAN) mode, step change the controller output, MV(OUT) back to 100%.

5.

Observations and Results of Experiments. The DCS trending records at the Process History View of each respective controller constitute the results of the experiments. During any experiments, note down the observations corresponding to the obtained response. The OBSERVATIONS AND RESULTS SECTION is checked for the types of results to observe collect and submit them as results of your exercise and experiments.

6.

To Shut down Model SPC211 a) All the windows (including DeltaV Operate page) at the operator workstation is closed.

8|Page

b) c)

Log Off from the operator workstation. Shut down the operator workstation.

9|Page

CHAPTER 4

RESULT & DISCUSSION

4.1

Result

Table 2: Dynamic Graphic Check (Visual and Static Check) Single Loop Simulated Process Control Loop PlantProcess Gas Mass Flow Process Tag Name Measuring Instrument Controller Final Control Element FIC 91 FCV 91 SP MV(OUT) m/h % FT 91 Process Parameter PV Kg/h Units Engineering units

Table 3: Dynamic Behaviour of the process (Operating Datas Check) Actions Observations Remarks

With FIC91A in Manual (MAN) mode, i) at MV (OUT) = 100% What is the current air mass flowrate at steady state? 1. 0 kg/h 2. Is the control value FCV91 Yes ii) at MV (OUT) = 50% What is the air mass flowrate at steady state? iii) at MV (OUT) = 0% What is the air mass flowrate at steady state? 4. 38.7 kg/h 5. Is the control value FCV91
10 | P a g e

fully

shut?

3. 34.1 kg/h

fully

open?

Yes

4.2

Discussion

I.

From the result obtained, discuss the dynamic behavior of the process (i.e order of the response)

In this particular experiment, the behavior of the gas mass flow rate that is operating under first order process is observed. The changes of this process are basically much related to the changes of MV at the FIC 91.The process input is a step input. Step input was characterized as an industrial process that can be subjected to a sudden and sustained input change.

II.

Give suggestions to improve the process performance.

In this experiment, the process performance can be improved by introducing feedback controller. The proportional control should be introduced to the process. The key concept in proportional control are that the controller gain can be adjusted to make the controller output changes as sensitive as desired to deviation between set point and controlled variable. The gain can be chosen to make the controller output increase or decrease as the error signal increases.

11 | P a g e

CHAPTER 5

CONCLUSION AND RECOMMENDATION

5.1

CONCLUSION

Based from the results and observations, the objective for this experiment is successfully achieved since the behavior of the gas mass flow process has been analyzed and identified. Here, we can conclude that when the FIC91 in Manual (MAN) mode as the value decreases, the values of gas mass flow rate are increased. At the value of MV (OUT) which is 100 percent, the control value FCV91 is fully shut. For the value of MV (OUT) is equal to 0 percent, the control value FCV91 is fully opened.

5.2

RECOMMENDATION

The tuning process should be done uniformly according to the timing process. Make sure the graph of the tuning is constant at steady state to get the actual value as the set point. Do not overdo the simulation as it could affect the readings.

12 | P a g e

CHAPTER 6

REFERENCES

Franklin et al. (2002). Feedback Control of Dynamic Systems (4 ed.). New Jersey: Prentice Hall. Christopher Kilian (2005). Modern Control Technology. Thompson Delmar Learning Levine, William S. et al (1996). The Control Handbook. New York: CRC Press Industrial/Aerospace/Military Specifications by John T. Jackson retrieved online at http://jrmagnetics.com/mtrctrl/mtrctrlpid.php on 18/3/2011 Open-Loop Control System by Electrical Engineering Training Service retrieved online at http://www.tpub.com/content/neets/14187/css/14187_92.htm on 19/3/2011

13 | P a g e

CHAPTER 7

APPENDIX

Table 2: Dynamic Graphic Check (Visual and Static Check) Single Loop Simulated Process Control Loop PlantProcess Gas Mass Flow Process Tag Name Measuring Instrument Controller Final Control Element FIC 91 FCV 91 SP MV(OUT) m/h % FT 91 Process Parameter PV Kg/h Units Engineering units

Table 3: Dynamic Behaviour of the process (Operating Datas Check) Actions Observations Remarks

With FIC91A in Manual (MAN) mode, i) at MV (OUT) = 100% What is the current air mass flowrate at steady state? 1. 0 kg/h

2. Is the control value FCV91 Yes fully shut?

ii) at MV (OUT) = 50%

What is the air mass flowrate at steady state?

3. 34.1 kg/h

iii) at MV (OUT) = 0%

What is the air mass flowrate at steady state?

4. 38.7 kg/h 5. Is the control value FCV91 Yes fully open?

14 | P a g e

You might also like