External structure Basic features and interrupting operation Standards and certification Types and ordering information Ratings Accessories Control circuit diagrams Dimensions Side-Mount Type VCB Technical data 26 28 31 32 38 44 76 80 126 128
Susol VCB is full line-up new VCB which has the high interrupting capacity, large current(~50kA, ~4000A), and maximized compatibility with existing products through the dual phases and compact sized models.
2
Vacuum Circuit Breaker, VCB is installed in the medium voltage distribution lines to protect life and load equipment. In case of accidents such as over current, short circuit and ground fault current, VCB works by interrupting the circuit through the inner Vacuum Interrupter which is acted by signal from the outside separate relay. LSIS' Super Solution, Susol VCB responds. - customer needs for the breakers with high interrupting capacity and large current due to the integration and increase of the load capacity. - worldwide trend of diversification in the medium voltage distribution lines. - increase of the reliability for the temperature characteristics of circuit breakers. Premium-type products to improve convenience and reliability of medium voltage switchgear configuration. - full line-up modeling to the high interrupting capacity and large current. - main structure with high reliability application. - a variety of accessories and ability to maximize. Suitable for use as the main circuit breaker to protect key installations in the places such as device industry, power plants, high-rise buildings, large ships.
Interrupting current
20/25/31.5/40/50kA 12.5/25/31.5/40kA 25/31.5/40kA 25/31.5kA
Rated current
400/630/1250/2000/3150/4000A 630/1250/2000/3150/4000A 630/1250/2000/2500/3150A 1250/2000/3150A 1250/2000/3150A
7.2kV 8/12.5/20/25/31.5/40/50kA
Maximizing the durability and reliability of the main circuit contactors (Stego Tulip contactor). Strong structure for the temperature rise (Natural cooling system).
Convenience of switchgear configuration and a variety of
accessories.
CB compartment structure: Metal isolation structures to prevent the accident spread and ensure safety. And the convenience of switchgear building is extended by its module style. A variety of accessories: UVT, Locking Magnet, Plug Interlock, Key lock, Temperature Sensor, MOC, TOC, Earthing S/W. Maximizing compatibility with existing products through the dualistic deployment of phases and compact models.
Type testing is complete for all models according to latest standard, IEC62271-100 (2008) [M2, E2 (List1 or 3), C2].
7.2kV (VL-06)
Rated short-time (for withstand current ): 3sec. Rated operating sequence: O-0.3s-CO-15s-CO Type test level: M2, E2 (List1), C2 Electrical and mechanical life: 30,000 operations 100% Compatibility - with existing fixed type breakers - with existing drawout type breakers Various cradle: E, F and G type A variety of control power - DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V - AC 48V, AC 100~130V, AC 220~250V A variety of accessories - Charge switch, UVT, Secondary trip Coil, Current trip coil, Trip Latch Checking S/W, Position S/W - Key-lock, Button lock, Button cover, Padlock, UVT, Time Delay Controller, Lifting hook, CTD TEST/SERVICE Automatic Position Indicator Standards and certification - IEC62271-100 (2008) [M2, C2, E2 (List1)] - Tested in enclosure - KERI type tested, V-check (KESCO) certification
Ur (kV) 7.2 8
<<
7.2/12/17.5kV (VL-06/12/17)
Rated short-time (to withstand current ): 3sec. 4sec* Rated operating sequence: O-0.3s-CO-15s-CO Type test level: M2, E2 (List3), C2 Electrical and mechanical life: 30,000 operations Compatibility with existing Pro-MEC breakers Various cradle: E, F, G and H type CB Compartment for MCSG available A variety of control power - DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V - AC 48V, AC 100~130V, AC 220~250V A variety of accessories - VCB part: Charge switch, UVT, Secondary trip coil, Latch checking switch, Position switch, Locking magnet, Plug interlock, Key lock, Button cover, Button padlock, Padlock (H type Door interlock), MOC - Cradle part: MOC (Mechanical Operated Cell switch), TOC (Truck Operated Cell switch), Temperature sensor, Earthing switch & accessaries, Door, Door interlock, Door emergency button - Others: Racking in/out handle, UVT Time delay controller, CTD (Condensor Trip Device), Temperature module TEST/SERVICE Automatic Position Indicator Standards and certification - IEC62271-100 (2008) [M2, C2, E2 (List3)] - KEMA, KERI type tested, V-check (KESCO) certification
Note ) * Please contact us
7.2/12/17.5/24/36/40.5kV (VH-06/12/17/24/36/40)
Rated short-time (to withstand current ): 3sec. 4sec* Rated operating sequence: O-0.3s-CO-3min-CO Type test level: M2, E2 (List3), C2 Electrical and mechanical life: 20,000 operations Various cradle: K and H type CB Compartment for MCSG available A variety of control power - DC 48V, DC 110V, DC 125V, DC 220V - AC 48V, AC 110V, AC 220V A variety of accessories - VCB part: UVT, Secondary trip coil, Latch checking switch, Position switch, Locking magnet, Plug interlock, Key lock, Button cover, Button padlock, Padlock (H type Door interlock), MOC - Cradle part: MOC (Mechanical Operated Cell switch), TOC (Truck Operated Cell switch), Temperature sensor, Earthing switch & accessaries, Door, Door interlock, Door emergency button - Others: Racking in/out handle, Lifting hook, UVT Time delay controller, CTD (Condensor Trip Device), Temperature module Standards and certification - IEC62271-100 (2008) [M2, C2, E2 (List3)] - KEMA, KERI type tested, V-check (KESCO) certification
Note ) * Please contact us Ur (kV) 7.2 12 17.5 24 Isc (kA) 50 Ir (A) 1250 2000 2500 3150 4000 2500 1250 2000 3150 1250 2000 3150 1250 2000 3150 1250 2000 3150 1250 2000 3150 1250 2000 3150 1250 2000 3150
Ur (kV) 7.2 20
Isc (kA)
Ir (A) 630 1250 2000 630 1250 2000 630 1250 2000 630 1250 2000 630 1250 2000 630 1250 2000
25 31.5 40 25 31.5 40
25
36
12
20
25
17.5
20
40.5
25 31.5
25
Susol
VCB
Breaker
Insulation rod Lower terminal Shunt Vacuum interrupter Upper terminal Tulip contactor
Contacts
Vacuum Interrupter, VI
The vacuum rate within the VI is very high (approximately 5x10-5 Torr) and the spacing between fixed contact and movable contact is about 6~20mm, depending on the voltage. The contacts are in a structure that arc can easily be extinguished and the surfaces of the contacts are made of special alloy (copperchromium) and the interior is completely sealed to prevent loss of vacuum. Therefore the wearing of the contacts can be minimized in the event of short-circuit and the arc energy by overvoltage or switching can be reduced effectively.
<<
Stego Tulip
Main circuit structure with high reliability
Maximizing the durability and reliability of the main circuit contactors (Stego Tulip contactor) Strong structure for the temperature rise (Natural cooling system)
Tulip finger
Tulip spring
Plate star: Supporting Tulip for position maintaing and torsional flow prevention
10
<<
6/12/17.5/24/36/40kV...
(VH-06/12/17/24/36/40)
Drawout / natural cooling system Improved temperature characteristics and ensured high reliability
11
CB Compartment
Convenience in building switchgears
CB compartment structure: H type cradle Metal isolation structure to prevent the accident spread and ensure safety Convenience of switchgear building
7.2/12/17.5/24/36/40.5kV 20/25/31.5/40/50kA
Metal isolation structure to prevent the accident spread and ensure safety Convenience of operation by Truck - Drawable in the closed position of the switchgear door - Racking-in/out positions indicated mechanically Equipped with safety devices and accessories - Control power connected Interlock - Earthing S/W and interlock, MOC/TOC (ANSI) Convenience in building switchgears - Module assembly with CB compartment
12
<<
LV Compartment
PT Compartment
Key lock for Earthing S/W Locking Magnet for Earthing S/W Position S/W for Earthing S/W TM (Temperature Monitoring Unit)
13
Cradles
E, F, G and H type... Variety of the Cradles
E type
E type
Economic style cradle with the basic structure No safety shutter and bushing For MESG Applies VL type VCB
E type
F type
H type
14
<<
H type
Metal isolation structure to prevent the accident spread and ensure safety Convenience of operation by Truck - Drawable in the closed position of the switchgear door - Racking-in/out positions indicated mechanically - Control power connected Interlock Convenience in building switchgears - Module assembly with CB compartment - Assembly with CT/PT integrated compartment Applies VL/VH type VCB
F type
Safety shutter has been added to the cradle of type E No bushing For MESG Applies VL type VCB
G type
Premium style cradle with safety shutter and bushings For MESG Applies VL type VCB
VL type
VL type
VL, VH type
15
Convenience
Convenience in building switchgears
- Maximizing compatibility with existing products through the dualistic deployment of phases and compact models.
150 150 210 210
VCB rating
Ur (kV) 12 20/25 17.5 20/25 Isc (kA) Ir (A) 630 1250 630 1250
150 150
210
210
VCB rating
Ur (kV) 12 20/25 17.5 20/25 Isc (kA) Ir (A) 2000 2000
210
210
275
275
VCB rating
Ur (kV) 24 25.8 Isc (kA) 31.5/40 31.5/40 Ir (A) 2000 2000
16
<<
17
Accessories
A variety of accessories for VL-06
If accessories are attached to the breaker, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Breaker
Motor Closing coil Trip coil Counter Auxiliary contacts UVT coil Current trip coil Key lock Latch checking switch Button padlock Button cover Position switch Lead wire
18
<<
If accessories are attached to the cradle, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Cradle
Handle for Racking-in and out UVT time delay controller Condenser trip device
19
Accessories
A variety of accessories for VL-06/12/17
If accessories are attached to the breaker, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Breaker
Motor Closing coil Trip coil Counter Auxiliary contacts UVT coil Key lock Latch checking switch Button padlock Button cover Position switch Handle for Racking-in/out UVT time delay controller Condenser trip device (CTD) MOC Padlock (H type Door Interlock) Locking magnet Plug Interlock
20
<<
If accessories are attached to the cradle, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Cradle (H type)
TOC (Truck operated cell s/w) MOC (Mechanical operated cell s/w) Temperature sensor Door Door interlock Shutter padlock Emergency ON/OFF button Earthing switch & Accessary Key lock for Earthing switch Locking Magnet for Earthing switch Position s/w for Earthing switch TM (Temperature monitoring unit)
21
Accessories
A variety of accessories for VH-06/12/17/24/36/40
If accessories are attached to the breaker, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Breaker
Motor AC/DC coil rectifier Trip coil/Closing coil Secondary trip coil AC/DC UVT coil rectifier UVT coil Latch checking switch Auxiliary contact wire Key lock Button cover/Push bar Button padlock Position switch Locking magnet Plug interlock Door Interlock for withdrawable type Lifting hook Charge handle Racking in/out handle UVT Time delay controller CTD (Condenser trip device)
22
<<
If accessories are attached to the cradle, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Cradle (H type)
MOC (Mechanism operated cell switch) TOC (Truck operated cell switch) Shutter padlock Temperature sensor Door Emergency ON/OFF button Earthing switch & Accessaries Key lock for Earthing switch Locking magnet for Earthing switch Position switch for Earthing switch TM (Temperature monitoring unit)
23
IEC62271-100 (2002)
274
268 260
IEC62271-100 (2008)
274
268 260
130
130
116
104
116
104
72
66 36 9 3 10 30 60 100(sym) 100(asym)
72
66 36 9 3 10 30 60 100(sym) 100(asym)
15
15
Arc Energy: List 1 (100%) < List 2 (125%) < List 3 (134%)
E2 List1 E2 List3
E2 List2 E1
24
<<
M2, C2
IEC standards to verify the relibilty of the product allows to select the quality level for the product to be tested according to its real performance and practical usage. The highest quality level of M2, C2 has been applied to Susol VCB.
2000 operation test Sequence C-O C-O C-O O - CO - C Control Voltage 85% 100% 110% 100% Number of operations 500 500 500 250
M2
10,000 10,000 operations operations
M1
operations
2,000
operations
2,000
Pre-test (characteristics, isolation, and temperature) Pre-test (characteristics, isolation, and temperature) Confirmative tests after the completion of 2000 operations Confirmative tests after every 2000 operation Confirmative tests after the completion of 10,000 (Characteristics, isolation, temperature) operations (Characteristics, isolation, temperature)
C1, C2: Capacitive current breaking test is to verify the probability of restriking and C2 class is secured for all Susol VCB.
C1
C2
25
Back side
26
Back side
27
Manual operation
Manual Charge a) VL type: operate the charge handle 7-8 times as a fully stroke. b) VH type: Insert the charge handle into the handle slot first. Rotate the handle clockwise 40 times more and then charge will be complete with a click sound. - When the closing spring is charged fully "CHARGED" is displayed at the charge indicator. Manual closing a) Pressing the ON button the breaker is closed. b) With the closing of the breaker "ON" is displayed at Close/Trip indicator and DISCHARGED the charge at indicator. Manual trip a) Pressing the OFF button the breaker is opened. b) OFF is displayed at Close/Trip indicator. "
Electric operation
Electric charge The breaker is remotely closing with charging of closing spring. If the breaker trips the closing spring is automatically charged by gear motors. Electric closing Remote closing is operated by the closing coil. Electric trip Remote trip can be operated by the trip coil or UVT coil. Main contacts are operated by the energy of the spring mechanism and closing spring is charged by the motor in the mechanism. Breaker is closed by closing coil and tripped by trip coil. These operations are repeated in VCB as shown in the below sequence chart.
Start closing Closing signal Control power ON Charging time of closing spring (VL type : 5 sec, VH type : 12 sec.)
Main contacts Closing coil Motor Closing spring Opening spring Trip coil
Closing time Opening time
28
The interruption of VCB is carried out by the vacuum interrupters. Interrupter contacts as a key part made of copper - chromium (CuCr) material with spiral shape have low contact wear characteristics and withstand voltage is excellent. Spiral contacts make the arc generated between the surfaces of contacts rotated around the surface of contact by the induced magnetic field generated due to the spiral contact structure, which results in preventing local heating, thereby corruption and interrupting instantaneously.
Fixed shield
Contacts
Bellows shield
Bellows
An example of oscillogram obtained through the interrupting test using LC resonant circuit
29
In case of using the flat contact any of the designs do not reflect on when contacts are opening the arc with high temperature is contracted and fixed in the center of the contacts,Which is called pinch effect. To prevent the effect two kinds of contact shapes are designed. One is Axial magnetic field which spreads the arc before its contraction, and the other is Radial magnetic field which permits the contraction of the arc but makes it rotated to disperse the energy. Because contracted arc is shaped like a cylinder it is called Contracted arc or columnar arc.
Arc voltage waveforms and arc image captured during arcing time
Spiral contact structure (Radial magnetic field), using the force (F = jB) generated by the interaction of the radial magnetic field caused by the current flowing through the arc between two contacts, disperse the arc energy evenly on the surface of contact by rotating the arc that is contracted by the pinch effect so as to minimize contact damage. The images show arc behavior during the arcing time of about 8ms by shooting with high-speed camera capable of shooting 10,000 frames per sec. (0.1ms/frame) by focusing on parts of the arcing time on the above graph and simultaneously measured arc voltage also represented to show arc state by section.
30
Susol VCB has been type tested and obtained certifications according to the latest IEC standard at international testing laboratory and can be installed and applied at the environment and conditions in accordance with the standard. Standard - IEC 62271-1 (2007.10) High-voltage switchgear and controlgear - Part 1: Common specifications. - IEC 62271-100 (2008.04) High-voltage switchgear and controlgear - Part 2: Alternating-current circuit breakers. Test and certification Test report (KERI) Test report (KEMA)
31
Breaker
VL
Basic model name VL Susol VCB
06
Rated voltage (kV) 06 7.2 P E F G
P
Version Fixed E type drawout F type drawout G type drawout
08
Interrupting current (kA) 08 13 8 12.5
A
Phase distance/Compatibility A B Standard Compatible with existing breaker Note6)
04
Rated current (A) 04 06 400 630
VL-06E08A04
M1
C1
T1
SA1
U1
14 7
Motor control voltage M0 M1 M2 M3 M4 M5 M6 M7 M8 Without motor DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V T0 T1 T2 T3 T4 T5 T6 T7 T8 T9
Trip coil voltage Without trip coil DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V Current trip coil U0 U1 U2 U3 U4 U5 U6 U7 U8
UVT
Note5)
Without UVT DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
Closing coil voltage C0 C1 C2 C3 C4 C5 C6 C7 Without closing coil DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V SA1 SA3 SA5 SA6 SA7
Connector and wire A type connector, 2a2b A type connector, 6a6b Flame retardant A type connector, 2a2b A type connector, 4a4b A type connector, 6a6b
Note5)
Secondary Trip coil Position S/W (2a2a) Position S/W (2a2b) Latch checking S/W Key lock Button Padlock Button cover Lead wire User Plug (Part)
Note5)
5 6 7 8 9 A B O
Note5)
Note) 1. In the case of selecting accessories such as A1(Secondary C8 AC 200V~250V trip coil), A4(Position S/W 2a2a)and A7(Key lock), A147 is type name in the ordering. 2. Unable to select A1(Secondary Trip coil), U1~U8(UVT)and T9(Current trip coil) simultaneously. 3. A4(Position S/W 2a2a) and A5(Position S/W 2a2b) can not be selected simultaneously. 4. A8 (Button Padlock) and A9 (Button Cover) can not be selected simultaneously. 5. Maximum number of Auxiliary Contacts available are 5a5b, 5a6b and 6a5b in the case of selecting A1(Secondary trip coil),U1~U8(UVT)and A6(Latch checking S/W).
CTD1 Condenser Trip Device (AC 110V) CTD2 Condenser Trip Device (AC 220V) UDC1 UVT Time Delay Controller (AC/DC 110V) UDC2 UVT Time Delay Controller (AC/DC 220V) UDC3 UVT Time Delay Controller (AC/DC 48V) CTU Coil Test Unit VC Vacuum Checker
5a6b
UVT 5a6b
LCS 6a5b
6. In case of using the existing old type cradle and replacing breaker only please order type B (Compatible with existing breaker). Compatibille busbars are required for fixed version. 7. If T9(CTC) is selected, in case of adding Secondary trip coil, CTC is also added.
32
Cradle
VCL
Basic model name VCL Susol VCB Cradle
06
Rated voltage (kV) 06 7.2 E F G
E
Version E type drawout F type drawout G type drawout
08
Interrupting current (kA) 08 13 8 12.5
A
Phase distance/Compatibility A B Standard Compatible with existing cradle Note)
06
Rated current (A) 04 06 400 630
Note) In case of replacing the existing old type VCB with Susol VCB please order type B for cradle and A for breaker.
33
VL
Basic model name VL Susol VCB
06
Rated voltage (kV) 06 12 17 7.2 12 17.5 P E F G H
H
Version Fixed E type drawout (for MESG) F type drawout (for MESG) G type drawout (for MESG) H type drawout (for MCSG)
20
Interrupting current (kA) 20 25 20 25
A
Phase distance/Compatibility A B F 150mm 210mm Compatible with existing breaker Note)
06
Rated current (A) 06 13 20 630 1250 2000
Note) Types of phase distance 1. Only 150mm for 7.2kV VCB 2. In case of 12 and 17.5kV VCB - 150 and 210mm for H type - 150 and 210mm for 630/1250A of P type - 210mm available for E and F type - 630A and 1250A for F (compatible with existing breaker)
VL-06H20A06
M1
Motor control voltage M0 M1 M2 M3 M4 M5 M6 M7 M8 Without motor DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
C1
T1
Trip coil voltage T0 T1 T2 T3 T4 T5 T6 T7 T8 T9 Without trip coil DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V Current trip coil
SB1
U1
UVT U0 U1 U2 U3 U4 U5 U6 U7 U8 Without UVT DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
14 7
Closing coil voltage C0 C1 C2 C3 Without closing coil DC 110V DC 220V DC 125V SA2 SA4 SB2 SB4 SA6 SA8 SB6
Connector and wire A type connector, 4a4b Standard A type connector, 10a10b B type connector, 4a4b B type connector, 10a10b Flame retardant A type connector, 4a4b A type connector, 10a10b B type connector, 4a4b 1 4 5 6 7 8 9 A Optional CTD1 Condenser Trip Device (AC 110V) CTD2 Condenser Trip Device (AC 220V) UDC1 UVT Time Delay Controller (AC/DC 110V) UDC2 UVT Time Delay Controller (AC/DC 220V) UDC3 UVT Time Delay Controller (AC/DC 48V) CTU Coil Test Unit VC Vacuum Checker B C D E F O
Other accessories Note) Secondary Trip coil Position S/W (2a2a) Position S/W (2a2b) Latch checking S/W Key lock Button Padlock Button Cover Lead Wire User Plug (Part) Plug Interlock Padlock (H type Door Interlock) MOC (Mechanical Operating Cell S/W) Locking Magnet Lead Wire special color (Blue)
Note) 1. If A2 (UVT), A4 (Position S/W 2a2b) and A7 (Keylock) are C4 DC 24V~30V selected, A147 is the type name in the ordering. 2. Unable to select A1(Secondary trip coil), U1~U8(UVT) C5 DC 48V~60V simultaneously. C6 AC 48V 3. A4 (Position S/W 2a2a) and A5 (Position S/W 2a2b) can not be selected simultaneously. C7 AC 100V~130V 4. A8 (Button Padlock) and A9 (Button Cover) can not be selected simultaneously. C8 AC 200V~250V 5. When A1 (Secondary Trip coil) is selected the maximum available auxiliary contacts are 9a9b. 6. AC (Plug interlock),AD (H type Door interlock), AE (MOC) and AF (Locking magnet) are available only for H type. 7. In case of B-type connector the flame retardant wire is applicable to auxiliary contacts 4a4b, not to 10a10b. 8. A-type connector is applicable to P/E/F/G type and B-type connector to H type. 9. Lead wire special color (blue) is applicable to A-type connector. 10. In case of using position switch the available connectors are A type connector for P/E/F/G type and B type connector for H type. 11. Locking magnet can be applied only to H type VCB - breaker and cradle. 12. Locking magnet of H type breaker use the same control power supply as motor. 13. Flame retardant type blue wire is not available. 14. If T9(CTC) is selected, in case of adding Secondary trip coil, CTC is also added.
34
Cradle
VCL
Basic model name VCL Susol VCB Cradle
06
Rated voltage (kV) 06 12 17 7.2 12 17.5
20
Rated short time current (kA) 20 25 20 25
06
Rated current (A) 06 13 20 630 1250 2000
14 7
Version E F G H E type drawout (for MESG) F type drawout (for MESG) G type drawout (for MESG) H type drawout (for MCSG)
Other accessories (H type) 1 2 4 5 6 7 8 9 A B C D E F G H J K L M N O ES (Earthing Switch) without option ES with position S/W (2a2b) ES with position S/W (6a6b) ES with Key lock ES with Locking magnet: DC 110V ES with Locking magnet: DC 220V ES with Locking magnet: DC 125V ES with Locking magnet: DC 24V ES with Locking magnet: DC 48V ES with Locking magnet: AC 48V ES with Locking magnet: AC 110V ES with Locking magnet: AC 220V Shutter padlock TOC (Truck Operating Cell S/W) MOC (Mechanical Operating Cell S/W) Door Door Interlock Door Emergency Push Button Temperature Monitoring Sensor H type Lead wire 4a4b (Flame retardant wire) H type Lead wire 10a10b (Flame retardant wire) H type Lead wire 4a4b (Rated short time current) Optional TM Temperature Monitoring
Note) 1.These accessories for cradle and TM can be applied only to H type. 2. AJ and AK can not be selected without door (AH). 3. TM (Temperature Monitoring) should be used with AL (Temperature Sensor). 4. H type lead wire - one of AM, AN or AO is required for cradle in case of H type breaker. 5. Unable to select AK at the cradle in the case of selecting A8(Button Padlock), A9(Button Cover) for body of H-type.
35
Breaker
VH
Basic model name VH Susol VCB
06
Rated voltage (kV) 06 12 17 20 25 36 40 7.2 12 17.5 24 25.8 36 40.5 P H
H
Version Fixed H type drawout (for MCSG)
50
Interrupting current (kA) 25 32 40 50
Note)
B
Phase distance/Compatibility B D E 210mm 275mm 300mm
13
Rated current (A) 13 20 25 32 40 1250A 2000A 2500A 3150A 4000A
25 31.5 40 50
*Phase distance is different by rating. *Phase distance only E (300mm) for 36/40.5kV VCB Note) only for 24/36kV
VH-06H50B32
M1
Motor control voltage M0 M1 M2 M3 M5 M6 M7 M8 Without motor DC 110V DC 220V DC 125V DC 48V AC 48V AC 110V AC 220V
C1
T1
Trip coil voltage T0 T1 T2 T3 T5 T6 T7 T8 Without trip coil DC110V DC220V DC125V DC48V AC 48V AC 110V AC 220V
SB2
U1
UVT U0 U1 U2 U3 U5 U6 U7 U8 Without UVT DC 110V DC 220V DC 125V DC 48V AC 48V AC 110V AC 220
14 7
Connector and wire Standard B type connector, 4a4b B type connector, 10a10b 1 4 5 6 7 8 Optional LH Lifting Hook 9 A B C D E F P O
Other accessories Note) Secondary Trip coil Position S/W (2a2a) Position S/W (2a2b) Latch checking S/W Keylock Button Padlock Button cover Lead Wire User Plug(Part) Plug Interlock Padlock (H type Door Interlock) MOC (Mechanical Operating Cell S/W) Locking Magnet Trip Coil Monitoring Contact Lead Wire special color (Blue)
Note) C2 DC 220V 1. If A2 (UVT), A4 (Position S/W 2a2b) and A7 (Keylock) are selected, A147 is the type name in the ordering. C3 DC 125V 2. A1 (Secondary Trip Coil) and A2 (UVT) can not be C5 DC 48V selected simultaneously. 3. A4 (Position S/W 2a2a) and A5 (Position S/W 2a2b) can C6 AC 48V not be selected simultaneously. 4. A8 (Button Padlock) and A9 (Button Cover) can not be C7 AC 110V selected simultaneously. 5. AC (Plug interlock),AD (H type Door interlock), AE (MOC) C8 AC 220V and AF (Locking magnet) are available only for H type. 6. In case of B-type connector the flame retardant wire is applicable to auxiliary contacts 4a4b, not to 10a10b. 7. Locking magnet can be applied only to H type VCB - breaker and cradle. 8. Locking magnet of H type breaker use the same control power supply as motor. 8. A-type connector is applicable to P/E/F/G type and B-type connector to H type. 9. In case of selecting UVT A6 (Latch checking S/W) is not allowed. A6 (Latch checking S/W) is installed by default to make electrical interlock with UVT.
CTD Condenser Trip Device UDC UVT Time Delay Controller DH CH VC VCB Draw-out Handle VCB Closing spring Charge Handle Vacuum Checker
10. Lead wire is enclosed in the breaker in case of ordering fixed type or H type breaker without cradle, installed of cradle in case of ordering the breaker with cradle. If user plug is selected it will be enclosed in the breaker.
36
Cradle
VCL
Basic model name VCL Susol VCB Cradle
06
Rated voltage (kV) 06 12 17 20 25 36 40 7.2 12 17.5 24 25.8 36 40.5
25
Interrupting current (kA) 25 32 40 50 25 31.5 40 50
13
Rated current (A) 13 20 25 32 40 1250A 2000A 2500A 3150A 4000A
14 7
Other accessories (H type) ES (Earthing Switch) without option ES with Position S/W (2a2b) ES with Position S/W (6a6b) ES with Key lock ES with Locking magnet: DC 110V ES with Locking magnet: DC 220V ES with Locking magnet: DC 125V ES with Locking magnet: DC 48V ES with Locking magnet: AC 48V ES with Locking magnet: AC 110V ES with Locking magnet: AC 220V Shutter padlock TOC (Truck Operating Cell S/W) MOC (Mechanical Operating Cell S/W) Door Door Interlock Door Emergency Push Button Temperature Sensor H type Lead wire 4a4b (Flame retardant wire) H type Lead wire 10a10b (Flame retardant wire) H type Lead wire 4a4b (Rated short time current) Optional TM Temperature Monitoring
Note) 1.These accessories for cradle and TM can be applied only to H type. 2. AJ and AK can not be selected without door (AH). 3. TM (Temperature Monitoring) should be used with AL (Temperature Sensor). 4. H type lead wire - one of AM, AN or AO is required for cradle in case of H type breaker.
37
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
VL-06 0804
7.2 400 50/60 8 8/3 100 2.5 * Isc (50Hz)/2.6 * Isc (60Hz) 3 20 60 O-0.3s-CO-15s-CO (V) (V)
VL-0613 06
630
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class Mechanical Electrical Capacitive current switching Installation version Fixed Drawout Phase distance Weight Breaker (E, F, G type) Cradle (E, F, G type) Dimensions Breaker (E, F, G type) Cradle (E, F, G type) Standards (mm) (kg) (kg) 37 18, 25, 32 (sec) (sec)
AC/DC 100~130V, AC/DC 200~250V, DC 125V, DC 24~30V, DC 48~60V, AC 48V AC/DC 100~130V, AC/DC 200~250V, DC 125V, DC 24~30V, DC 48~60V, AC 48V 2a2b, 4a4b, 6a6b 0.04 0.06 M2 E2 (List1) C2 P type E, F, G type (for MESG) 130 37 19, 26, 33 Page 80~81 Page 81~82 IEC 62271-100 (2008), KS C 4611, JEC 2300/JIS C 4603, V-check (KESCO)
38
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class
Installation version **
Fixed Drawout
Dimensions
Standards
** H type is a box type cradle with CB compartment style structure. *** ( ) displays option of phase distance.
39
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class
Installation version **
Fixed Drawout
Dimensions
Standards
** K type is a 4000A exclusive cradle.
40
24kV (VH-20)
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
VH-202525
2500
VH-203212/20/32
24/25.8 1250 2000 60 3150
VH-20 40 12/20/32
1250 2000 3150
25 25/3 1039/1117
31.5 31.5/3 1309/1407 2.6 * Isc (60Hz) 3 60 (65) Note1) 125 O-0.3s-CO-3min-CO
40 40/3 1662/1787
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class Mechanical Electrical Capacitive current switching Installation version ** Fixed Drawout Phase distance *** Weight Breaker (H type) Cradle (H type) Dimensions Breaker (H type) Cradle (H type) Standards
** H type is a box type cradle with CB compartment style structure. *** ( ) displays option of phase distance. Note) 1. Contact us.
(V) (V)
DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V 4a4b, 10a10b
(sec) (sec)
41
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
VH-362512/20/32
1250 2000 3150
VH-363212/20/32
36 1250 2000 50/60 3150
VH-364012/20/32
1250 2000 3150
25 25/3 1559
31.5 31.5/3 1964 2.5 * Isc (50Hz)/2.6 * Isc (60Hz) 3 70 (95) Note1) 170 O-0.3s-CO-3min-CO
40 40/3 2494
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class Mechanical Electrical Capacitive current switching Installation version ** Fixed Drawout Phase distance Weight Breaker (H type) Cradle (H type) Dimensions Breaker (H type) Cradle (H type) Standards
** H type is a box type cradle with CB compartment style structure. Note) 1. Contact us.
(V) (V)
DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V 4a4b, 10a10b
(sec) (sec)
(mm) (kg) (kg) 400 700 Page 114 Page 124 490 750 Page 115 Page 125 400 700 Page 114 Page 124
300 490 750 Page 115 Page 125 400 700 Page 114 Page 124 490 750 Page 115 Page 125
42
40.5kV (VH-40)
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV) 1250
VH-402512/20/32
40.5 2000 3150 50 25 25/4 1754 2.5 * Isc (50Hz) 3 95 180 O-0.3s-CO-3min-CO (V) (V) 1250
VH-403212/20/32
2000 3150
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class Mechanical Electrical Capacitive current switching Installation version ** Phase distance Weight Dimensions Standards
** H type is a box type cradle with CB compartment style structure.
DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V 4a4b, 10a10b
(sec) (sec)
Fixed (mm) Breaker (H type) Breaker (H type) (kg) 400 Page 116 490 Page 117
43
Accessory
Supplied as Type Accessory VL: 7.2kV 8/12.5kA Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option VL: 20/25kA VH Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Remarks page
Motor CC TC A1 T9 Closing Coil Trip Coil Secondary Trip Coil Current Trip Coil Auxiliary Contact (2a2b) SA (SB) Auxiliary Contact (4a4b) Auxiliary Contact (6a6b) Auxiliary Contact (10a10b) U A4 A5 A6 C A7 A8 A9 AA AB AC AD AE AF AO AP Under Voltage Trip Coil Position Switch (2a2a) Position Switch (2a2b) Latch Checking Switch Counter Keylock Button Padlock Button cover Lead Wire: A/B type connector Plug/Terminal for Lead Wire Plug Interlock Padlock (Type H Door Interlock) MOC (Mechanical Operated Cell Switch Locking Magnet Lead Wire: A type connector (Special Color: Blue) Trip Coil Monitoring Contact Condenser Trip Device (AC 110V) Condenser Trip Device (AC 220V) UVT Time Delay Controller (AD 110V) UVT Time Delay Controller (AD 220V) UVT Time Delay Controller (AD 48V) Coil Test Unit Vacuum Checker Temperature Monitoring
Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory
46 47 48 49 50 51 51 51 51 52 53 53 54 54 55 56 57 58 59 59 59 60 61 58 62 64 64 65 65 65 63 66 67
Breaker (External)
* : Basic Installation
44
Supplied as Type Accessory VL: 7.2kV 8/12.5kA VL: 20/25kA VH Option Option Option Option Remarks page
A1 A2
ES (Earthing Switch) without Option ES (Earthing Switch) with Position Switch (2a2b) ES (Earthing Switch) with Position Switch (6a6b) ES (Earthing Switch) with Keylock ES (Earthing Switch) with Locking magnet: DC 110V ES (Earthing Switch) with Locking magnet: DC 220V ES (Earthing Switch) with Locking magnet: DC 125V ES (Earthing Switch) with Locking magnet: DC 24V ES (Earthing Switch) with Locking magnet: DC 48V ES (Earthing Switch) with Locking magnet: AC 48V ES (Earthing Switch) with Locking magnet: AC 110V ES (Earthing Switch) with Locking magnet: AC 220V Shutter padlock TOC (Truck Operated Cell Switch) MOC (Mechanical Operated Cell Switch) Door Door Interlock Door Emergency Push Button Temperature Sensor Type H Lead Wire 4a4b (Normal cable) Type H Lead Wire 10a10b (Normal cable) Type H Lead Wire 4a4b (Flame retardant cable) Door padlock
68 68
A4 A5 A6
68 69 69
A7
Option
Option
69
A8
Option
Option
69
A9
Option
Option
69
AA
Option
Option
69
AB
Option
Option
69
AC
Option
Option
69
AD AE AF AG AH AJ AK AL AM AN AO
Option Option Option Option Option Option Option Option Option Option Option Option
Option Option Option Option Option Option Option Option Option Option Option Option
Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory
69 70 70 71 71 72 72 73 74 74 74 74
45
Accessory
Motor: M
Installed inside of a breaker as standard
VL type
Motor
Charge the closing spring of a circuit breaker by the external power source. When the charging is complete, control power of the motor will be "OFF" by the built-in Limit S/W. Without the external power source, charge manually.
Gear
Main shaft
Motor
VL type Input voltage (Vn) Load current (A) Starting current (A) Charge time
Note) Rated operation and control voltage range, see page 50.
DC 24~ 30V 5
DC 48~ 60V 3
DC 110V 1
DC 125V 1
DC 220V 0.5
AC 48V 3
AC 100~ 130 1
VH type
Motor
VH Type Input voltage (Vn) Load current (A) Starting current (A) Charge time
Note) Rated operation and control voltage range, see page 50.
DC 48V 6 30
DC 110V 3 20
DC 125V 3 20
AC 48V 6 30
AC 110V 3 20
AC 220V 2.6 17
46
Closing Coil: C
VL type
It is a control device which closes a circuit breaker, when applying voltage continuously or instantaneously over 200ms to the coil control terminals.
Closing coil
VL type Input voltage (Vn) Power consumption (inrush, W) Power consumption (steady, W)
Note) Rated operation and control voltage range, see page 50.
DC 24~ 30V
DC 48~ 60V
DC 110V
DC 125V 200 5
DC 220V
AC 48V
AC 100~ 130
AC 200~ 250V
VH type
It is a control device which closes a circuit breaker, when applying voltage continuously about 45ms to the coil control terminals. Electrical pumping preventing circuit is built in.
Closing coil
VH Type Input voltage (Vn) Rated current (A) DC 48V 8 DC 110V 3 DC 125V 3 DC 220V 2.5 AC 48V 8 AC 110V 3 AC 220V 2.5
Note) Rated operation and control voltage range, see page 50.
47
Accessory
Trip Coil: T
Installed inside of a breaker as standard
VL type
It is a control device which trips a circuit breaker from remote place, when applying voltage continuously or instantaneously over 35ms to coil control terminals. When UVT coil is installed, its location is changed.
Trip coil
VL type Input voltage (Vn) Power consumption (inrush, W) Power consumption (steady, W)
Note) Rated operation and control voltage range, see page 50.
DC 24~ 30V
DC 48~ 60V
DC 110V
DC 125V 200 5
DC 220V
AC 48V
AC 100~ 130
AC 200~ 250V
VH type
It is a control device which trips a circuit breaker, when applying voltage continuously or instantaneausly over 35ms to the coil control terminals.
Trip coil
VH Type Input voltage (Vn) Rated current (A) DC 48V 8 DC 110V 3 DC 125V 3 DC 220V 2.5 AC 48V 8 AC 110V 3 AC 220V 2.5
Note) Rated operation and control voltage range, see page 50.
48
VL type
It is a control device which trips a circuit breaker doubly from the outside. If the trip coil (T ) fails, it can trip a circuit breaker safely. Trip coil: Install it at existing location. Secondary trip coil: Install it on the right side of the trip coil. It is not available with UVT coil when installing secondary trip coil.
VL type Input voltage (Vn) Power consumption (inrush, W) Power consumption (steady, W) DC 24~ 30V DC 48~ 60V DC 110V DC 125V 200 5 DC 220V AC 48V AC 100~ 130 AC 200~ 250V
VH type
It is a control device which trips a circuit breaker doubly from the outside. If the trip coil (T) fails, it can trip a circuit breaker safely. It is not available with UVT coil when installing secondary trip coil.
VH Type Input voltage (Vn) Rated current (A) DC 48V 8 DC 110V 3 DC 125V 3 DC 220V 2.5 AC 48V 8 AC 110V 3 AC 220V 2.5
49
Accessory
Rated operation and control voltage range
Item Motor Closing Trip AC 85~110% DC 75~110% AC 85~110% DC 75~125% AC 60~125% DC 60~125%
Susol VCB VL: 7.2kV 8/12.5kA VL: 20/25kA 85~110% 85~110% 85~110% 85~110% 85~110% 70~110% IEC62271-100 (2008) KSC4611 IEC62271-100 (2008) VH 85~110% 85~110% 85~110% 85~110% 85~110% 70~110% IEC62271-100 (2008)
Remarks
Applied standards
VL type
Current Trip Coil
This trip coil uses the output of the CT as its control power source and is used with over current relay in combination. Two current trip coils are supplied. Coil burden is 90VA. Coil impedance (Z) is 10 or less. (Operating current is AC 3A) CT must be installed at load side. If it is installed at bus side there is the danger of malfunction or damage to CT. Dont disconnect the control power connector on main power is live condition at service position. Otherwise there is the danger of malfunction or damage to CT.
50
Auxiliary Contact: SA
VL type
Auxiliary contact
It is a contact used to monitor ON/OFF status of a breaker from remote place. The auxiliary contacts supplied as standard configuration is 4a4b. 10a10b is also available on request. For 7.2kV 8/12.5kA VCB standard configuration is 2a2b. 4a4b and 6a6b are optional.
VH type
Auxiliary contact
VL/VH Type Item AC Contact configuration DC 125V 30V 10 250V 10 125V 10 250V 10 10 Resistive load (A) Inductive load (A) 5 5 5 5 5 For all models Remarks
51
Accessory
Under Voltage Trip Coil: U
Installed inside of a breaker as an option
VL type
VH type
VL type
It is installed inside of a breaker to trip when the main power or control power voltage drops below certain value. Instantaneous type is only available with UVT coil and Time delay type is available by connecting UVT coil and UVT time delay controller. The closing of a circuit breaker is impossible mechanically or electrically if control power is not supplied to UVT. To close the circuit breaker, 65~85% of rated voltage should be applied. UVT and secondary trip coil will not be selected together.
VH type
1. UVT rated voltage and characteristic - Operating voltage range: Pick up 0.65~0.85Vn, Drop out 0.4~0.6Vn - Operating voltage ranges based on the minimum value of each rated voltage (Vn)
VL type Input voltage (Vn) Power consumption (inrush, W) Power consumption (steady, W) DC 24~ 30V DC 48~ 60V DC 110V DC 125V 200 5 DC 220V AC 48V AC 100~ 130 AC 200~ 250V
VH Type Input voltage (Vn) Power consumption (inrush, W) Power consumption (steady, W) DC 48V DC 110V DC 125V DC 220V 350 10 AC 48V AC 110V AC 220V
52
This switch is used to indicate the breaker position (SERVICE, TEST), and contact configuration is 2a2a or 2a2b.
Position switch
Position switch
Contact configuration
1 3 5 7 1 3 5 7
2a(TEST)
2a(SERVICE)
1a1b(TEST)
6 8 1a1b(SERVICE)
53
Accessory
Latch checking switch: A6
Installed inside of a breaker as an option
VL type
This switch works in conjunction with the mechanism of the breaker. It checks if the breaker is ready to be closed. When the mechanism is OFF and the closing spring is at charged status the switch becomes "ON", which means the mechanism is ready to be closed. If the latch is not in a proper position the switch prevents the breaker from closing. In case of VL type, if it is connected in series with the closing coil, it is possible to prevent the breaker from closing electrically even though the closing signal happening when trip latch is in wrong position.
VH type
In case of VH type it is connected internally in series with the closing coil.
Counter: C
VL/VH type
54
Keylock: A7
VL type
The key is to unlock the locking device first to close the breaker electrically and mechanically. *How to operate - It is not possible to pull out the key in the unlocked position, possible only in locked status. - Pushing "OFF" switch of a breaker turn the key counter-clockwise to the locked position and pull it out. - It is not possible to close the breaker electrically and mechanically in the locked position. - Insert the key and turn clockwise and then the breaker can be closed electrically and mechanically.
Keylock
VH type
*How to operate - It is not possible to pull out the key in the unlocked position, possible only in locked status. - Trip the breaker first and then turn the key counter-clockwise to the locked position and pull it out. - It is not possible to close the breaker electrically and mechanically in the locked position.
Keylock
55
Accessory
Button Padlock: A8
Installed outside of a breaker as an option
VL type
It is to prevent manual operation of ON/OFF button due to users wrong handling. It is not possible to handle ON/OFF operation under the Button lock status.
Button Padlock
VH type
Button Padlock
56
Button Cover: A9
VL type
It is a protection cover to prevent an accident due to unintended operation of ON/OFF button. Use the push-bar to operate the ON/OFF button.
Push Bar
Button Cover
VH type
Push Bar
Button Cover
57
Accessory
Lead wire : AA
Supplied separately from a breaker as an option
VL/VH type
Lead wire
It is to connect with the control circuit of a breaker from outside. (supply wire length: 2m) A type connector is supplied for P/E/F/G type of VL VCB.
A type connector
B type connector is supplied for P type of VH VCB. In case of H type breaker of VL and VH models the Lead wire is installed in the cradle when supplied.
B type connector
VL/VH type
A type connector
B type connector
It is connector to connect with the connector installed in the breaker. (supply connectors and terminal only for lead wire) Type of connector is depends on the type of connector installed in the breaker- A or B.
58
Plug interlock: AC
It checks if the control power connector on the cradle (H type) is connected with the connecting terminal of the breaker before the proceeding of draw-in or out. It is not allowed to seperate the control power connector from the breaker in the position of draw-in /out or SERVICE, but TEST position.
Door interlock
59
Accessory
MOC drive device: AE
Installed inside of a breaker as an option
MOC
VH type
MOC
60
Locking magnet: AF
VL type
It allows the drawing-in of the breaker in the TEST position under the condition that the control power connector on the cradle (H type) is connected with the connecting terminal of the breaker and the power is supplied. During the drawing-in or in the SERVICE position draw-in/out is allowed without supplying power.
* Control power rating is the same as that of a motor.
Locking magnet
VH type
Locking magnet
61
Accessory
Trip coil monitoring contact: AP
Installed inside of a breaker as an option
VL type
Device for monitoring the functions of the trip coils.
10a 4a 4b 10b
Supplied as standard for VL model and optional for VH model. To monitor the trip coils connect its terminals with the trip coil monitoring relay as shown on the circuit diagram. - If the trip coil is normal: closed-circuit consisting - If the trip coil is damaged: open circuit 1) Terminals A5 and A6 monitor the trip coils in closed position of the breaker. 2) Terminal A6 and aux. contact terminal 34 monitor the trip coils in trip position of the breaker. Coil Test Unit is opional, which enable monitoring the coils by connecting in parallel with the trip coil operation switch.
VH type
10a 4a 4b
10b
62
When no current flows through the coil it gives the test current which does not cause the coil to operate to check whether the coil is disconnected or not. - If the test current flows normally: coil normal - If the test current does not flow through: coil disconnected As it is connected in parallel with the control part of the coil the normal operation of the coil is not affected. Monitoring of the running coils is not possible. One test unit can monitor up to two coils. 1. Input voltage: AC/DC 75V~264V 2. Contact output 1) 2a contacts for Fail indication and 2a contacts for Alarm 2) 250Vac/10A Resistive, 30Vdc/10A Resistive 3. Disconnection test cycle is 12 seconds (Test LED blinks) 4. The default operation If Fail happens (coil disconnected), Fail LED turns on and the Fail contacts become short state. If Fail happens three times in series, Alarm LED turns on and the Alarm contacts become short state. In order to clear the Alarm status push up DIP switch on the front and then push down it (Off On Off)
Shunt 1
24~250V (AC/DC)
Shunt 2
CTU CTU Input voltage Input voltage (+) (+) Coil drive power 1 5 7 Coil test current 2
Fail (LED) Fail (RELAY) Alarm (LED) Alarm (RELAY)
Coil
Coil drive power(-)
63
Accessory
Condenser trip device: CTD
Installed outside of a breaker as an option
Ratings
Ratings Model Rated input voltage (V) Frequency (Hz) Rated charge voltage (V) Charging time Trip possible time Range of Input voltage Condenser capacity ( F) Specification CB - T1 AC 100/110 50/60 140/155 Within 10sec. Within 30sec. 85%~110% 1,000 CB - T2 AC 200/220 50/60 280/310 Within 10sec. Within 30sec. 85%~110% 560
It gets a circuit breaker tripped electrically within regular time when control power supply is broken down and is used with Shunt coil, SHT. In case there is no DC power, It can be used as the rectifier which supplies DC power to a circuit breaker by rectifying AC power. Tripping within 30 seconds on the power failure is possible. However after that automatic trip circuit must be configured separately in the switchgear.
Terminal arrangement
External dimension
(Mounting hole)
Circuit diagram
1 D1 R1 SW1 for discharge R2 3 R3 DC Output 6
AC Input
TNR
1000/ 560uF
LAMP
64
UVT time delay, UDC is to delay the trip signal from UVT. Without UDC the breaker will be tripped instantaneously by the trip signal from UVT installed inside of the breaker even in the the momentary power failure. UDC can delay the trip time to avoid this unintended instantaneous trip in the event of such power failure. It can be installed on the cradle or inside of the switchgear. UDC provides output contacts for indication of trip status due to the UVT coil inside of the breaker. b contact is closed at normal state and a contact is closed at trip.
1. Characteristics
Rated voltage (Vn) DC (V) 48~60 48 100~130 200~250 200~250
- Operating voltage ranges are based on the minimum value of each rated voltage (Vn)
AC (V) 100~130
0.5, 1, 1.5, 3
3. Wiring diagram
UVT
18 19 20 a c b Signal for tripping DC48~60V AC48 5 7 0.5 1 1.5 3
18(a)
[sec]
UVT
65
Accessory
Vacuum Checker: VC
Portable item, optional
VL/VH type
It is a portable device to check the vacuum degree of the vacuum interrupter for stable operation of VCB.
Model Type Input voltage Output voltage Weight Environment Standard accessories Handling
VC 1030DC AC -DC Converter AC 85~245V DC 10~30kV 11kg Humidity below 80%, -20~40 Less than 1,000m above sea level High-voltage cable (2m): 1 set Power plug (1m): 1 ea Portable
66
Temperature Alarm Unit displays the input temperature detected through the temperature sensor installed in H-type cradle. Temperature sensor can be installed up to three (R, S, T phase). Temperature Alarm Unit converts the temperatures detected from the senser in the cradle and displays the maximum value and can transmit it throug communication. If the input temperature is above standard it may cause alarm. Temperature Alarm Unit supports Modbus/RS485 communication and contact us Profibus-DP communication.
Temperature Sensor
Temperature sensor input Temperature sensor input Temperature sensor input Temperature sensor input Child * communication Parent communication
LED temperature display (): 10 ~150, Warning Display maximum value of temperatures
67
Accessory
Earthing Switch: A1
Built-in a cradle as an option
Earthing Switch
Circuit diagram
E1 E3 E5 E7 E9 E11 E13 E15 E17 E19 E21 E23
E2
E4
E6
E8
68
In case of using earthing switch it can be added for two types of interlocking. 1) Interlock to keep opening 2) Interlock to keep earthing
69
Accessory
Shutter padlock: AE
Built-in a cradle as an option
Shutter padlock
Circuit diagram
VH Type
121 122 124 125 127 128 130 131
TOC
123
126
129
132
a Contact: 122-123, 125-126, 128-129, 131-132, b Contact: 121-123, 124-126, 127-129, 130-132
70
This auxiliary switch is used to indicate the Close/Trip of VCB. It is operated mechanically at the SERVICE position and installed in the bottom of a H type cradle and operated by the frame of a breaker. MOC is consisted of 4 cell switches with changeover contacts as below diagram.
VL type
Circuit diagram
102 101 105 104 108 107 111 110
MOC
VH Type
103
106
109
112
a Contact: 101-103, 104-106, 107-109, 110-112, b Contact: 102-103, 105-106, 108-109, 111-112
Door: AH
Door
71
Accessory
Door Interlock: AJ
Built-in a cradle as an option
Door Interlock
It is used to enable the Close/Trip of the breaker manually from outside of the door installed to H type cradle during an emergency. Push the ON/OFF button by ON/OFF handle supplied seperately.
72
Temperature Sensor: AC
B C D
73
Accessory
Type H Cradle Lead Wire: AM~AO
Built-in a cradle as an option
Lead Wire
Door Padlock
Door Padlock
74
Auxiliary guide frame is provided in order to move safely 36/40.5kV breaker into the switchgear. It can be used in combination with the hand pallet which meets the requirement shown below.
If dimension A in Fig. 1 is less than 120mm B type pallet can be used. In case of more than 120mm C type must be applied.
550
Bottom
<Fig 1>
75
UVT
TC1
TC
76
Auxiliary switch
VL-06
P
4a 2a 2b
TEST SERVICE
P P
4b
6a(5a)
Note5)
6b(5b)
A1
13
A3
D1
11
A5
22 24 26 28 40 (42) 34 36 38 50 52 54 (56)
LS2
CS
LCS
Note1)
24 36 5 LS5 6 8 2 4* 6 8* 3* LS4* 7*
LS7*
26 38 50 7 LS6 52 54 56
28
40
42
M
23 35 37 39 51 53 55 57 25 27 29 41 43 2 4
52a
52a
Note3) Note4)
A2 A6 N
23 25 27 29 41 (43) 37 39 51 53 55 (57)
10
14
A4
D2
12
Indicating Contact
10 9 D1/11 13
D2/12 2 8
23
25 22 24 34
37 36
39 38
A
A1
(2a2b)
A2 A6
/43 /57 /56
A4 14 1 A3 A5
/42
10 9 D1/11 13
D2/12 2
4 3
6 5
8 7
23
25
27
29
37
39
51
53
A
A1
B
22
24
26
28
34
36
38
50
52
(4a4b)
23
/57
: External terminal of VCB 52 : Vacuum circuit breaker M : Spring charging motor TC : Trip coil(SHT) TC1 : Secondary Trip coil(SHT1) C : Closing coil(CC) UVT : Under Voltage Trip 52a : Auxiliary switch (a) 52b : Auxiliary switch (b) LS2 : Motor stop limit switch
14 D1/11
/42
CS : Closing spring charged indication limit switch LCS : Latch Checking Switch "ready to close" position of circuit breaker or preventing closing unless opening latch is properly reset LS4, LS5 : Position s/w (close in TEST position) LS6, LS7 : Position s/w (close in SERVICE position) LS4* : Position s/w (close in TEST position) LS5* : Position s/w (open in TEST position) LS6* : Position s/w (close in SERVICE position) LS7* : Position s/w (open in SERVICE position)
2 13
/56
4 1 3
6 5
8 7
25
27
29
41
37
39
51
53
55
A
A1
B
22
24
26
28
40
34
36
38
50
52
54
D2/12
/43
/57
14 D1/11
/42
Option
/56
13
Note) 1. LCS - Latch Checking Switch 2. Position S/W - TEST 2a, SERVICE 2a(Terminal No. 1, 2, 3, 4, 5, 6, 7, 8) 1a1b at TEST position and 1a1b at SERVICE position are also available. (In case of 1a1b * marked contact is b - nomally close contact) 3. UVT - Under Voltage Trip (Terminal No. D1, D2) 4. TC1 - Secondary Trip Coil (Spare trip coil, terminal No. 11, 12) 5. CTC - Current Trip Coil ( Terminal No. A5, A6) CTC1 - Secondary Current Trip Coil (Terminal No. 11, 12) - Closing and Trip coils are one pulse system. (Exception : trip coil DC 110V and 220V) - In case of selecting UVT as an option TC1 is not an option. - In case of using LCS/UVT/TC1 the maximum available of auxiliary contacts is 4a4b. - Above circuit diagram is based on OFF status of VCB and closing spring is charged. - CTC and CTC1 are options, which are used at the positions of TC and TC1, to be connected with current transformer of the switchgear. 6. Please make sure that keep the direction of P, N on this circuit diagram.
VL-06/12/17
Note1)
Note4)
Note4)
Indicating Contact
: External terminal of VCB 52 : Vacuum circuit breaker M : Spring charging motor TC : Trip coil(SHT) TC1 : Secondary Trip coil(SHT1) C : Closing coil(CC) UVT : Under Voltage Trip 52a : Auxiliary switch (a) 52b : Auxiliary switch (b) LS2 : Motor stop limit switch
Position switch <1a1b (TEST), 1a1b (SERVICE)>
CS : Closing spring charged indication limit switch LCS : Latch Checking Switch "ready to close" position of circuit breaker or preventing closing unless opening latch is properly reset LS4, LS5 : Position s/w (close in TEST position) LS6, LS7 : Position s/w (close in SERVICE position) LS4* : Position s/w (close in TEST position) LS5* : Position s/w (open in TEST position) LS6* : Position s/w (close in SERVICE position) LS7* : Position s/w (open in SERVICE position)
(10a10b)
B type connector
Option
Note) 1. LCS - Latch Checking Switch 2. Position S/W - TEST 2a, SERVICE 2a(Terminal No. 1, 2, 3, 4, 5, 6, 7, 8) 1a1b at TEST position and 1a1b at SERVICE position are also available. (In case of 1a1b *marked contact is b - nomally open contact) 3. UVT - Under Voltage Trip (Terminal No. D1, D2) 4. TC1 - Secondary Trip Coil (Spare trip coil, terminal No. 11, 12) If TC1 is selected, a contact(Terminal No. 40, 41) and b contact (Terminal No. 54, 55) are not available at aux. contacts 10a10b. 5. LM - Locking Magnet (Terminal No. 15, 16), only B type connector available - Closing and Trip coils are one pulse system. (Exception : trip coil DC 110V and 220V) - In case of selecting UVT as an option TC1 is not an option. - Above circuit diagram is based on OFF status of VCB and closing spring is charged. 6. Please make sure that keep the direction of P, N on this circuit diagram.
(4a4b)
(10a10b)
77
LS1
Note3)
Note4)
UVT
TC1
TC
78
Auxiliary switch Trip coil monitoring contact
Note6)
P
P CS
TEST SERVICE
P
4a 4b
34 36 38 50 52 54 56 58 70 72 74 1 3 5 7
Position switch <2a(TEST), 2b(SERVICE)>
10a
Note2)
10b
CS 15
22 24 26 28 40 42 44 46 48 60
A1
A3
D1
11
A5
LS2 1
LS3
Ya
VH-06/12/17/24/36/40
Yb 2
Note5)
Position switch <1a1b(TEST),1a1b(SERVICE)>
22 34 1 3 LS4 LS7
LS4*
LM
Note1)
24 5 LS5
1 3*
LS5*
5 1 26 7 LS6
5
LCS1 28 40 42 44 46 48 60 36 38 50 52 54 56 58 70 72 74
M
23 49
2
52b 25 61 35 37 39 51 53 55 57 59 71 73 75 27 29 41 43 45 47 2 4 8 6
4*
30
82
52a
LS6*
7*
LS7*
31
83
6'
8*
A2 N
10
A4
D2
12
A6
16
23 25 27 29 41 43 45 47 49 61 37 39 51 53 55 57 59 71 73 75 2 4 6
29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1 39 38 37 36 34 53 52 51 50
D2 D1 10 /12 /11
: External terminal of VCB 52: Vacuum circuit breaker M: Spring charging motor TC: Trip coil TC1: Secondary trip coil C: Close coil Y: Anti-pump relay UVT: Under voltage trip 52a: Auxiliary switch (a) 52b: Auxiliary switch (b) LS1: Close interlock limit switch (only withdrawable type)
Position switch <1a1b (TEST), 1a1b (SERVICE)>
D
9 16 15
LS2: Motor stop, close spring charged indication limit switch LS3: Anti-close, anti-pumping limit switch LCS1: Trip latch checking switch (preventing closing unless the trip latch is properly reset) LS4, LS5: Position S/W (close in TEST position) LS6, LS7: Position S/W (close in SERVICE position) LS4* : Position s/w (close in TEST position) LS5* : Position s/w (open in TEST position) LS6* : Position s/w (close in SERVICE position) LS7* : Position s/w (open in SERVICE position) LM: Locking magnet (only withdrawable type)
16 15 14 13 12 A B 11 10 9 8
(4a4b)
7 6 5 4 3 2 1
41 40 29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1 39 38 37 36
C D
34 61 60 49 48 47 46 45 44 43 42 75 74 73 72 71 70 59 58 57 56 55 54 53 52 51 50
D2 D1 10 /12 /11
Option
9 16 15
Note) 1. LCS - Latch Checking Switch 2. Position S/W - TEST 2a, SERVICE 2a(Terminal No. 1, 2, 3, 4, 5, 6, 7, 8) 1a1b at TEST position and 1a1b at SERVICE position are also available. (In case of 1a1b *marked contact is b - nomally open contact) 3. UVT - Under Voltage Trip (Terminal No. D1, D2) 4. TC1 - Secondary Trip Coil (Spare trip coil, terminal No. 11, 12) 5. LM - Locking Magnet (Terminal No. 15, 16) 6. Trip coil monitoring contact - In case of fixed version LS1(Closing-interlock Limit Switch) is not applied (terminal No. 15, 16) - In case of selecting UVT as an option TC1 is not an option (82 and 83 contacts are available in case of selecting TC1) - Above circuit diagram is based on OFF status of VCB and closing spring is charged. 7. Please make sure that keep the direction of P, N on this circuit diagram.
(10a10b)
Compartment
6b
Note3) Note4)
2a
2b
E1
E5
E3
E1
E5
E3
E7
E2
E6
E4
E8
Note1)
E4
LM
TM
TM
TM
12(R-)
12(S-)
12(T-)
: External terminals for auxiliary contacts and locking magnet LM : Locking magnet for earthing swtich MOC : Mechanism operated cell switch (for H type cradle) TOC : Truck operated cell switch (for H type cradle) TM : Temperature alarm (for H type cradle)
Note) 1. LM - If it is energized with the rated power the earthing switch can be closed or opened (for H type cradle) 2. MOC - This auxiliary switch is used to indicate the Close/Open of VCB (for H type cradle) It is composed of 4 cell switches with 4 changeover contacts. 3. TOC - This auxiliary switch is used to indicate the 'SERVICE' position of VCB (for H type cradle) It is composed of 4 cell switches with 4 changeover contacts. 4. TM - Temperature Alarm Unit displays the input temperature detected through the temperature sensor installed in H-type cradle. Temperature sensor can be installed in each phase and can be connected with the temperature module.
Option
* Above circuit diagram is based on the status that the earthing S/W is Open and the breaker is at Test or between Test and Service position. MOC indicates the Open of the breaker. If the breaker is Closed from Service, the contacts configuration is displayed on the contrary.
79
Dimensions - VL type
7.2kV, 8/12.5kA, 400/630A
Fixed (P type)
(Mounting hole)
80
VL-06
(Earthing hole)
81
Dimensions - VL type
7.2kV, 8/12.5kA, 400/630A
Withdrawable (F type cradle)
Racking in/out Stroke:150
VL-06
82
Dimensions - VL type
7.2kV, 20/25kA, 630/1250A
Fixed (P type, phase distance 150mm)
VL-06/12/17
281
6(10)
83
Dimensions - VL type
7.2kV, 20/25kA, 630/1250A
Withdrawable (F type unit, phase distance 150mm)
84
VL-06/12/17
20
46.8
96.5
85
Dimensions - VL type
7.2kV, 20/25kA, 2000A
Withdrawable (E type unit, phase distance 150mm)
86
VL-06/12/17
46.8
96.5
87
Dimensions - VL type
12/17.5kV, 20/25kA, 630/1250A
Fixed (P type, phase distance 210mm)
670
311.5
613.5
302
670
94.5
78
483
88
310
650
295
46.8
96.5
VL-06/12/17
670
311.5
613.5
302
670
94.5
78
483
169.5 310
650
295
89
Dimensions - VL type
12/17.5kV, 20/25kA, 630/1250A
Withdrawable (F type unit, phase distance 210mm)
90
VL-06/12/17
46.8
96.5
91
Dimensions - VL type
12/17.5kV, 20/25kA, 2000A
Withdrawable (E type unit, phase distance 210mm)
92
VL-06/12/17
93
Dimensions - VL type
7.2kV, 20/25kA, 630/1250A
Withdrawable (H cradle, phase distance 150mm)
317 323.4 42.3 M12 (DP:25) 150 150
550
(Mounting hole)
(Mounting hole)
(Mounting hole)
65
285
(Mounting hole)
87.3
20
Connecting busbar method (with earthing switch) Busbar : 8t40 (2 sheets) <1250A>
550
87.3
20
Connecting busbar method (with earthing switch) Busbar : 8t40 (1 sheet) <630A>
TUBE
10.0
TUBE
Detail A
30
Detail A
87.3
20 2-M8 (DP:18)
See Detail A
Detail A
94
86.8
30
VL-06/12/17
(Mounting hole) 150 150 (Mounting hole) 725 202.7 1017.7 (Mounting hole)
550.4
(Mounting hole)
65
285
(Mounting hole)
68.3
20
TUBE
10.0
550
25 Detail A
30
See Detail A
Detail A
86.8
465
310
95
Dimensions - VL type
12/17.5kV, 20/25kA, 630/1250A
Withdrawable (H cradle, phase distance 150mm)
317 (For assembly of lifting hook and LV compartment mounting hole) 323.4 42.3 M12 (DP:25)
550
600
1120
400
400
400
212.5
65
285
150 150
258.7
87.3
20
Connecting busbar method (with earthing switch) Busbar : 8t40 (2 sheets) <1250A>
550
(Mounting hole)
212.5
87.3
20
Connecting busbar method (with earthing switch) Busbar : 8t40 (1 sheet) <630A>
10.0
TUBE
TUBE
30
445
87.3 20 2-M8 (DP:18) Detail A 43.4 30
Detail A
Detail A
See Detail A
96
205
VL-06/12/17
700
(Mounting hole)
210
(Mounting hole)
210
(Mounting hole)
65 285
87.3
20
Connecting busbar method (with earthing switch) Busbar : 8t40 (2 sheets) <1250A>
700
(Mounting hole)
87.3 10.0
20
Connecting busbar method (with earthing switch) Busbar : 8t40 (1 sheet) <630A>
TUBE
TUBE
30
Detail A
Detail A
87.3
20 2-M8(DP:18)
See Detail A
Detail A
63.4
30
97
Dimensions - VL type
12/17.5kV, 20/25kA, 2000A
Withdrawable (H cradle, phase distance 150mm)
317 323.4 42.3
25
150 150
550
(Mounting hole)
2-M12 (DP:25)
725
(Mounting hole)
(Mounting hole)
65 285
(Mounting hole)
68.3
20
TUBE
10.0
550
25 Detail A
30
See Detail A
Detail A
98
86.8
VL-06/12/17
(Mounting hole)
700
(Mounting hole)
(Mounting hole)
87.3
20
TUBE
10.0
Detail A
25 30
700
(Mounting hole)
87.3
20 2-M8(DP:18)
See Detail A
Detail A
127
99
Dimensions - VL type
7.2kV, 20/25kA, 630/1250A
Withdrawable (E type cradle)
(Mounting hole)
Rating A B C
630A 6 55 95
1250A 10 60 90
(Mounting hole)
Rating A B C
630A 6 55 95
1250A 10 60 90
100
VL-06/12/17
Type
(Mounting hole)
(Earthing hole)
Type
(Mounting hole)
(Earthing hole)
Type
101
Dimensions - VL type
7.2kV, 20/25kA, 630/1250/2000A,
Withdrawable (G type cradle)
(Earthing hole)
(Earthing hole)
(Earthing hole)
G Type
G Type
G Type
Rating A
630A 6
1250A 10
2000A 20
102
Dimensions - VL type
12/17.5kV, 20/25kA, 630A
Withdrawable (Compatible with existing E cradle, phase distance 210mm)
164 70 Racking in/out Stroke:182 40 20 (Earthing hole) 139 210 270 440 340 860 1050 40 164 70 Racking in/out Stroke:182 40 20 (Earthing hole) 139 210 270 440 340 860 1050 40 10 326 720.2 295 800 87.2 60 210 326 6 720.2 800 295 50 210
2-M6 TAP
11.8
87.2
103
12/17.5kV, 20/25kA, 630A
VL-06/12/17
104
87.2
VL-06/12/17
(Earthing hole)
(Mounting hole)
(Earthing hole)
(Mounting hole)
105
Dimensions - VL type
12/17.5kV, 20/25kA, 2000A
Withdrawable (E cradle, phase distance 210mm)
VL-06/12/17
(Earthing hole)
(Mounting hole)
(Earthing hole)
(Mounting hole)
106
Dimensions - VH type
VH-06/12/17/24/36/40
2-M12 (DP:25)
610
130
862.5
816
25
285
M12 (Mounting hole) 108 115.5 360 602 695 94 144 137
653 644
12
130
48
335
193.5
380
340
107
Dimensions - VH type
7.2/12/17.5kV, 50kA, 2500/3150A
Fixed (P type, phase distance 275mm)
4-M12 (DP:25)
79
50
750
130
862.5
50
285
130
(870)
53
400 447
656
108
3.5 42
89 193.5 380
335
340
VH-06/12/17/24/36/40
(Earthing hole)
(Mounting hole)
109
Dimensions - VH type
24kV, 25kA, 2500A
Fixed (P type, phase distance 275mm)
287.5
142
853 850
445
130
53
110
3.5 41.5
80 225 440
335
340
VH-06/12/17/24/36/40
2-M12 (DP:25)
610
130
287.5
137
653 652
130
53
788
3.5 41.5
497 535
80 225 440
335
340
111
Dimensions - VH type
24kV, 31.5/40kA, 2000A
Fixed (P type, phase distance 275mm)
2-M12 (DP:25)
750
130
287.5
115.5
118 174
142
853 850
130
53
788
112
3.5 41.5
497 535
80 225 440
335
340
VH-06/12/17/24/36/40
4-M12 (DP:25)
750
130
287.5
118 174
853 850
12 857
335
130
53
497 535
788
113
Dimensions - VH type
36kV, 25/31.5/40kA, 1250/2000A
Fixed (P type)
(Mounting hole)
1042.5
551.5
294.1
220.1
8.5
114
8.5
VH-06/12/17/24/36/40
(Mounting hole)
1042.5
551.5
294.1
220.1
8.5
8.5
115
Dimensions - VH type
40.5kV, 25/31.5kA, 1250/2000A
Fixed (P type)
300 300 157
247
50
420
914 830
50 551.5 400
136.5 107
130
1042.5
(Earthing hole)
294.1
220.1
866 944
500 837
207
157
830
570
136.5 107
1446
130
697.6
403
104
115.5
623.6
8.5
1015
116
8.5
463.6
487.4
52 65
955
400
115.5
1.5
VH-06/12/17/24/36/40
80
420
914 830
80 551.5 400
130
1042.5
294.1
866 944
1.5
500 837
207
157
830
570
136.5 107
130
1446
697.6
403
623.6
104
8.5
1015
8.5
463.6
487.4
52 65
955
400
117
Dimensions - VH type
7.2/12/17.5kV, 50kA, 1250/2000A
Withdrawable (H cradle, phase distance 210mm)
42.3 317 378.4 2-M12 (DP:25)
210
780 750
1073
705
49
210
25
(Mounting hole)
1325
450
450
65
285
200
200
217
(Mounting hole)
84.3 60
20
Connecting busbar method (with earthing switch) Busbar : 12t60 (1 sheet) <1250A>
84.3 60
212.5
20
Connecting busbar method (with earthing switch) Busbar : 12t60 (2 sheets) <2000A>
12
12
30
12
212.5
TUBE
TUBE
84.3
20 2-M8 (DP:18)
See Detail A
Detail A
118
63.3
30
565
340
VH-06/12/17/24/36/40
(Mounting hole)
1325
450
450
212.5
60
300
210
230 264.5
(Mounting hole)
90.8
20
Connecting busbar method (with earthing switch) Busbar : 12t80 (2 sheets) <2500A >
90.8 100
20
Connecting busbar method (with earthing switch) Busbar : 12t100 (2 sheets) <3150A>
80
12
TUBE
12
30
TUBE
25
90.8
20 2-M8 (DP:18)
See Detail A
Detail A
49.4
25
30
25
25
212.5
25
25
565
340
119
Dimensions - VH type
24kV, 31.5/40kA, 1250/2000A
Withdrawable (H cradle, phase distance 210mm)
30 4-M12 (For assembly of lifting hook and LV compartment mounting hole) (Mounting hole) 239.5 1302 37.5 (Mounting hole) 500 500 750 (Mounting hole) 352 558 (Mounting hole) 25 2-M12 (DP:25) 500 20
Connecting busbar method (with earthing switch) Busbar : 12t60 (2 sheets) <2000A>
970
800
895
210 210
1380
500
212.5
60
300
280
300
269.5
(Mounting hole)
85.8 60
20
Connecting busbar method (with earthing switch) Busbar : 12t60 (1 sheet) <1250A>
85.8 60
12
12
30
12
212.5
TUBE
TUBE
85.8
20 2-M8 (DP:16)
See Detail A
Detail A
120
49.4
30
625
340
VH-06/12/17/24/36/40
210 210
239.5
500
1380
60
300
280
300
269.5
(Mounting hole)
212.5
500
121
Dimensions - VH type
24kV, 31.5/40kA, 2000A
Withdrawable (H cradle, phase distance 275mm)
30
4-M12 (For assembly of lifting hook and LV compartment mounting hole)
352
558 (Mounting hole) 25 275 2-M12 (DP:25) 970 (Mounting hole) 239.5 1302 37.5 (Mounting hole) 950 (Mounting hole) 500 895 500 275
1000
1380
500
500
60
300
280
300
269.5
(Mounting hole)
85.8 60
20
Connecting busbar method (with earthing switch) 2000A Busbar : 12t60 (2 sheets)
12
212.5
TUBE
30
212.5
85.8
20 2-M8 (DP:18)
See Detail A
Detail A
122
49.4
625
340
VH-06/12/17/24/36/40
970
1000
895
275
1380
500
500
60
300
280
300
270
90.3 80
20
12
Connecting busbar method (with earthing switch) Busbar : 12t80 (2 sheets) <2500A>
90.3 100
20
Connecting busbar method with earthing switch) Busbar : 12t100 (2 sheets) <3150A>
212.5
212.5
12
30
TUBE
TUBE
25
90.3
20 2-M8 (DP:18)
See Detail A
Detail A
49.4
25
30
25
12
12
25
25
25
625
340
123
Dimensions - VH type
36kV, 25/31.5/40kA, 1250/2000A
Withdrawable (H type cradle)
25 1194 466 14 300 300 296.5 201.5 40 1200 A 48 505
2200
1520
855
400
50.5
290
56.12
46
60
14
30 40 87.5 30
104 604
203.8
Remove the plate for both sides when assembled in panel 185 300 563 300
25
1194
66
124
53.5
120
1226.7
61
203.8
140.5
563
463
216.5
12 15
VH-06/12/17/24/36/40
2200
1520
855
400
50.5
290
56.12
46
30 40 87.5 30 110 40
7 28.5 BUS BAR: 100 12t Detail A See Detail A 28.5 For connecting busbar
14
25
1194
104 604
66
203.8
300
120
1226.7
61
203.8
140.5
563
463
221.5
125
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit breaking current Rated short-time withstand current (3 sec) Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik (kA) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
VL-25 16B 06
25.8 630 50/60 16 16 665/715 40/41.6 3 60 125 O-0.3s-CO-3min-CO (V) (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 200~250V DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 200~250V 5a5b (sec) (sec) Mechanical Electrical Capacitive current switching 0.04 0.06 M1 E1 C1 (time) (time) Right Left 2,000 2,000 R type L type 210 95 IEC 62271-100
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contact Rated opening time No-load closing time Type test class
Lifetime *
Mechanical Electrical
Installation
Fixed
(mm) CB (kg)
126
P
9
P
D1
5a
22 24 26 28 40
Auxiliary switch
5b
36 38 50 52 54
A3
CLOSE POWER SOURCE
A5
TRIP POWER SOURCE
22
24
26
28
40
36
38 50
52
54
52a
M C
23
25
27
29
41
37
39
51 53
55
Note1)
UVT
D2
TC
A2
10
A4
Closing Spring Contact (Charge switch)
A6
N
A2 A4 A6 10 D2 A5 9 D1
23 25 27 29 41
37 39 51 53 55
: External terminal of VCB 52 : Vacuum circuit breaker M : Spring charging motor TC : Trip coil(SHT)
C : Closing coil(CC) UVT : Under Voltage Trip 52a : Auxiliary switch (a) 52b : Auxiliary switch (b)
LS2 : Motor stop limit switch CS : Closing spring charged indication limit switch
22
(5a5b)
Note) 1. UVT : Under Voltage Trip (No. D1, D2) Option * Closing and Trip coil : One Pulse type * This circuit diagram is based on 'OFF' status of CB and Closing spring is charged.
210
210
212.5
600 605
818 355.5
38.5
169 300
1000
873 M10-DP 20
Ordering information VL
Basic model name e-VCB 25
25
Rated voltage (kV) 25.8 R L
R
Installation type On the right (Fixed type) On the left (Fixed type) 16
16
Breaking 16 B
B
Phase distance/Compatibility 210mm 06
06
Rated current (A) 680
VL-2516B06
Motor control voltage M0 M1 M2 M3 M4 M5 M6 M7 M8 Without Motor DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V Closing coil voltage C0 C1 C2 C3 C4 C5 C6 C7 C8 Without Closing coil DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
M1
C1
T1
Aux. contact & wire ass'y SA5 A type connector, 5a5b
SA5
UVT U0 U1 U2 U3 U4 U5 U6 U7 U8
U1
AAB
Other accessories AA AB Lead Wire User Plug(Part)
Trip coil voltage T0 T1 T2 T3 T4 T5 T6 T7 T8 Without Trip coil DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
Without UVT DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
100
120
M10-DP 25
145
Dimension
210
210
127
Technical data
Electrical endurance by interrupting current
Number[ops.]
Interrupting current [kA] VI model LV2 at 7.2kV N : Operation numbers I : Interrupting current N : Operation numbers I : Interrupting current
Number[ops.]
Number[ops.]
Interrupting current [kA] VI model LV4 at 24kV N : Operation numbers I : Interrupting current
Number[ops.]
Interrupting current [kA] VI model LV5 at 17.5kV N : Operation numbers I : Interrupting current
128
Number[ops.]
Interrupting current [kA] VI model LV8 at 17.5kV N : Operation numbers I : Interrupting current
Number[ops.]
Interrupting current [kA] VI model LV7-P1 at 24kV N : Operation numbers I : Interrupting current
Number[ops.]
Interrupting current [kA] VI model LV8 at 36kV N : Operation numbers I : Interrupting current
Note) 1. Above graphs represent the characteristics of the electrical life of LS Susol VCB. 2. Life characteristics of each model in each rating represents the LOG-LOG graphs.
129
Technical data
If a standard circuit breaker is used in high temperature exceeding 40, you are advised to use it according to the current corrected for each level of ambient temperature in catalog. If used in conditions of high humidity, the dielectric strength or electric performance may be degraded.
It is highly recommended to use a dust cover or anti-humid agent if it is used in dusty and humid conditions. Excessive vibration may cause a trip breaker such as connection fault or flaw on mechanical parts.
If it is left ON or OFF for a long time, it is recommended to switch load current on a regular basis. It is recommend to put it in the sealed protection if corrosive gas is prevalent.
130
The circuit breaker is designed for use in standard use environment specified in Section 2. 1 of IEC62271-1. Concerning the special use environments as below the special use conditions are required to be considered, thus please contact us in advance. - where altitude and ambient temperature are out of standard use environment. - where a strong sea breeze blows - when usually used in a humid place - where a lot of steam or oil steam exists - where explosive, flammable and other harmful gases might permeate the breaker - In a dusty place - where abnormal vibration or shock exists - where a lot of ice and snow exist - other special conditions
170 125
Up [kV/1.2
50
131
Technical data
Special Use Environment
Altitude (m)
<Fig.1 > withstand voltage correction parameter 1 by altitude (based on a required withstand voltage)
Correction parameter 2
1 0.95 0.9 0.85 0.8 0.75 0.7 0.65 0.6 0.55 0.5 1000
1500
2000
2500
3000
3500
4000
Altitude (m)
<Fig.2 > withstand voltage correction parameter 2 by altitude (based on a applicable withstand voltage)
Ex) Selecting a breaker to be used in a place of 2500m above sea level with a rated voltage 7.2kV (correction parameter 1 applied) - correction parameter at 2500m is 1.2 - criteria of withstand voltage by rated voltage: Power Frequency Withstand Voltage (Ud) = 20kV, Impulse Withstand Voltage (Up) = 60kV - requirements withstand voltage criteria: Power Frequency Withstand Voltage (Ud) = 201.2 = 24kV, Impulse Withstand Voltage (Up) = 72kV Therefore rated voltage 12kV breaker shall apply to satisfy the required withstand voltage. Ex) To apply a breaker with a rated voltage 12kV to the place of 2,500m above sea level (correction parameter 2 applied) - correction parameter at 2500m is 0.825 - dielectric strength of VCB : Power Frequency Withstand Voltage (Ud) = 280.825 = 23.1kV, Impulse Withstand Voltage (Up) = 750.825 = 62kV/1.250 Therefore above breaker with rated voltage 12kV shall apply to rated voltage system 7.2kV at the altitude.
132
Rated current (A) 4000 4000 3150 2000 1250 1250 630 630
Ambient temperature () 20 25 4000 3150 3150 2000 2000 1250 630 30 4000 3150 2000 1250 630 35 4000 3150 2000 1250 630 40 4000 3150 2000 1250 630 45 50 3843 3026 1922 1201 605 3679 2898 1840 1150 580 55 3508 2763 1754 1096 553 60 3328 2621 1664 1040 524
4000A
3150A
2000A
1250A 630A
Ambient temperature()
<Figure 3> Allowable load current by ambient temperature
133
Technical data
Comparison of GCB & VCB
In the system of medium voltage lines VCB uses a vacuum which is an eco friendly medium for arc extinguishing. It also offers excellent interrupting properties and ease of maintenance and has expanded the area to the scope of the GCB as the overlap increases.
Items Images
GCB
VCB
Comparison results
Remarks
VI
SF6 gas - Greenhouse gas that causes global warming. - The toxic gas generated by chemical reactions due to arc energy. - 5kgf/ high pressure required.
Vacuum - Green clean medium. - 510-5 Torr vacuum rate to maintain. VCB is better than GCB
- Periodic check and supplement the gas pressure required. - Automatic locking if gas pressure falls below the certain value. In the event of an accident while the gas valve is locked trip is disable and the load equipment can not be protected.
- Available until the product life. - Always keep trip-first feature. VCB is When an accident occurs the trip-first feature functions to protect the equipment. better than GCB
Rated voltage range (kV) 3.6~550 3.6~36 GCB is better than VCB Applicable rate of transient recovery voltage (RRRV) Development and trends Decline - Company M discontinued producing GCB. - Company A manufactures VCB in medium voltage GCB production factory. - GCB Maker S started the production of VCB. Increasing - Companies A and S have developed new VCBs. - Development trend that the voltage coverage of VCB expands. - VI increased coverage. (GIS, DAIS, SIS, etc.) VCB is better than GCB Low High
VCB has been increasing rapidly in the medium voltage systems. IEC62271-100 Annex M applied/ Interrupting performance verified.
134
Memo
135
For your safety, please read user's manual thoroughly before operating. Contact the nearest authorized service facility for examination, repair, or adjustment. Please contact a qualified service technician when you need maintenance. Do not disassemble or repair by yourself!
Safety Instructions
Any maintenance and inspection shall be performed by the personnel having expertise concerned.
eng.lsis.biz
HEAD OFFICE
LS Tower 1026-6, Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do 431-848, Korea Tel. (82-2)2034-4887, 4873, 4918, 4148 Fax. (82-2)2034-4648
Global Network LSIS (Middle East) FZE Dubai, U.A.E. Dalian LSIS Co., Ltd. Dalian, China LSIS (Wuxi) Co., Ltd. Wuxi, China
Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: jungyongl@lsis.biz Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn
CHEONG-JU PLANT
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Cheong Ju, 361-720, Korea
LSIS-VINA Co., Ltd. Hochiminh , Vietnam LSIS Shanghai Office Shanghai, China
LSIS Beijing Office Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District, LSIS Guangzhou Office Guangzhou, China LSIS Chengdu Office Chengdu, China LSIS Qingdao Office Qingdao, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz Address: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. China Tel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The Netherlands Tel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: junshickp@lsis.biz Address: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, India
Specifications in this catalog are subject to change without notice due to continuous product development and improvement.
2011. 10