Substation

Bay Name
Bay Type
Meter Type
Serial No.
Device Address

: Taji power plant


: Transformer 1
: (132KV Transformer)
: ALPHA 1500 _ ELESTER
: 00431410
: A101

V.T. Ratio
C.T. Ratio

: 11500/100 =115
: 3000/1 =3000

Theoretical:

MWH=3 V*I cos ()*5/60

MvarH=3 V*I sin ()*6/60

MWH = 3*11 500 *3000*Cos (0)*5/60


= 4.98 MWH

MvarH=3*11 500*3000*Sin (90)*5/60


= 4.98 MvarH

MWH = 3*11 500*3000*Cos (45)*6/60


= 3.52 MWH

MvarH=3*11 500*3000*Sin (45)*5/60


= 3.52 MvarH

Practical :
INJECTED CURRENT : 1 A
INJECTED VOLTAGE : 57.73V (PH)
Injection by omicron tester
TEST TIME
: 5 min.

: the angle between injected current and injected voltage ( voltage angle is reference )
ANGLE

Old

MWH (+A)
EXPORT
1.1.8.0
New

Difference

Old

MWH (-A)
IMPORT
1.2.8.0
New

Difference

Old

M varH (+R)
REACTIVE
1.3.8.0
New

Difference

Old

MvarH (-R)
CAPACITIVE
1.4.8.0
New

Difference

0
45

15.9
27.5

20.9
31.0

5
3.5

3.3
8.3

3.3
8.3

0
0

6.2
11.2

6.2
11.2

0
0

4.4
16.0

4.4
19.5

0
3.5

90
135
180

20.9
31.0
20.9

20.9
31.0
20.9

0
0
0

8.3
8.3
3.3

8.3
11.8
8.3

0
3.5
5

6.2
11.2
6.2

6.2
11.2
6.2

0
0
0

4.4
19.5
4.4

9.4
23.0
4.4

5
3.5
0

225
270
315

31.0
20.9
31.0

31.0
20.9
34.5

0
0
3.5

12.6
8.3
16.2

16.2
8.3
16.2

3.6
0
0

11.2
6.2
14.8

14.8
11.2
18.3

3.6
5
3.5

23.8
9.4
23.8

23.8
9.4
23.8

0
0
0

Substation
Bay Name
Bay Type
Meter Type
Serial No.
Device Address

: Taji power plant


: Transformer 1
: (132KV Transformer)
: ALPHA 1500 _ ELESTER
: 00431409
: A102

V.T. Ratio
C.T. Ratio

: 11500/100 =115
: 3000/1 =3000

Theoretical:

MWH=3 V*I cos ()*5/60

MvarH=3 V*I sin ()*6/60

MWH = 3*11 500 *3000*Cos (0)*5/60


= 4.98 MWH

MvarH=3*11 500*3000*Sin (90)*5/60


= 4.98 MvarH

MWH = 3*11 500*3000*Cos (45)*6/60


= 3.52 MWH

MvarH=3*11 500*3000*Sin (45)*5/60


= 3.52 MvarH

Practical :
INJECTED CURRENT : 1 A
INJECTED VOLTAGE : 57.73V (PH)
Injection by omicron tester
TEST TIME
: 5 min.

: the angle between injected current and injected voltage ( voltage angle is reference )
ANGLE

Old

MWH (+A)
EXPORT
1.1.8.0
New

Difference

Old

MWH (-A)
IMPORT
1.2.8.0
New

Difference

Old

M varH (+R)
REACTIVE
1.3.8.0
New

Difference

Old

MvarH (-R)
CAPACITIVE
1.4.8.0
New

Difference

0
45

9.9
14.9

14.9
18.4

5
3.5

0.6
5.6

0.6
5.6

0
0

1.3
6.2

1.3
6.2

0
0

1.0
5.9

1.0
9.4

0
3.5

90
135
180

14.9
18.4
14.9

14.9
18.4
14.9

0
0
0

5.6
5.6
0.6

5.6
9.1
5.6

0
3.5
5

1.3
6.2
1.3

1.3
6.2
1.3

0
0
0

1.0
9.4
1.0

5.9
12.9
1.0

4.9
3.5
0

225
270
315

18.4
14.9
18.4

18.4
14.9
21.9

0
0
3.5

9.1
5.6
12.6

12.6
5.6
12.6

3.5
0
0

6.2
1.3
9.7

9.7
6.2
13.2

3.5
4.9
3.5

12.9
5.9
12.9

12.9
5.9
12.9

0
0
0

Substation
Bay Name
Bay Type
Meter Type
Serial No.
Device Address

: Taji power plant


: Transformer 2
: (132KV Transformer)
: ALPHA 1500 _ ELESTER
: 00431407
: A101

V.T. Ratio
C.T. Ratio

: 11500/100 =115
: 3000/1 =3000

Theoretical:

MWH=3 V*I cos ()*5/60

MvarH=3 V*I sin ()*6/60

MWH = 3*11 500 *3000*Cos (0)*5/60


= 4.98 MWH

MvarH=3*11 500*3000*Sin (90)*5/60


= 4.98 MvarH

MWH = 3*11 500*3000*Cos (45)*6/60


= 3.52 MWH

MvarH=3*11 500*3000*Sin (45)*5/60


= 3.52 MvarH

Practical :
INJECTED CURRENT : 1 A
INJECTED VOLTAGE : 57.73V (PH)
Injection by omicron tester
TEST TIME
: 5 min.

: the angle between injected current and injected voltage ( voltage angle is reference )
ANGLE

Old

MWH (+A)
EXPORT
1.1.8.0
New

Difference

Old

MWH (-A)
IMPORT
1.2.8.0
New

Difference

Old

M varH (+R)
REACTIVE
1.3.8.0
New

Difference

Old

MvarH (-R)
CAPACITIVE
1.4.8.0
New

Difference

0
45

5.0
10.0

10.0
13.5

5
3.5

0.3
0.3

0.3
0.3

0
0

0.8
0.8

0.8
0.8

0
0

0.5
0.5

0.5
4.0

0
3.5

90
135
180

13.5
13.5
13.5

13.5
13.5
13.5

0
0
0

0.3
0.3
3.8

0.3
3.8
8.8

0
3.5
5

0.8
0.8
0.8

0.8
0.8
0.8

0
0
0

4.0
9.0
12.5

9.0
12.5
12.5

5
3.5
0

225
270
315

13.5
13.5
13.5

13.5
13.5
17.0

0
0
3.5

8.8
12.3
12.3

12.3
12.3
12.3

3.5
0
0

0.8
4.3
9.3

4.3
9.3
12.8

3.5
5
3.5

12.5
12.5
12.5

12.5
12.5
12.5

0
0
0

Substation
Bay Name
Bay Type
Meter Type
Serial No.
Device Address

: Taji power plant


: Transformer 2
: (132KV Transformer)
: ALPHA 1500 _ ELESTER
: 00431408
: A102

V.T. Ratio
C.T. Ratio

: 11500/100 =115
: 3000/1 =3000

Theoretical:

MWH=3 V*I cos ()*5/60

MvarH=3 V*I sin ()*6/60

MWH = 3*11 500 *3000*Cos (0)*5/60


= 4.98 MWH

MvarH=3*11 500*3000*Sin (90)*5/60


= 4.98 MvarH

MWH = 3*11 500*3000*Cos (45)*6/60


= 3.52 MWH

MvarH=3*11 500*3000*Sin (45)*5/60


= 3.52 MvarH

Practical :
INJECTED CURRENT : 1 A
INJECTED VOLTAGE : 57.73V (PH)
Injection by omicron tester
TEST TIME
: 5 min.

: the angle between injected current and injected voltage ( voltage angle is reference )
ANGLE

Old

MWH (+A)
EXPORT
1.1.8.0
New

Difference

Old

MWH (-A)
IMPORT
1.2.8.0
New

Difference

Old

M varH (+R)
REACTIVE
1.3.8.0
New

Difference

Old

MvarH (-R)
CAPACITIVE
1.4.8.0
New

Difference

0
45

5.6
10.5

10.5
14.0

4.9
3.5

0.3
0.3

0.3
0.3

0
0

0.4
0.4

0.4
0.4

0
0

3.0
3.0

3.0
6.5

0
3.5

90
135
180

14.0
14.0
14.0

14.0
14.0
14.0

0
0
0

0.3
0.3
3.9

0.3
3.9
8.9

0
3.6
5

0.4
0.4
0.4

0.4
0.4
0.4

0
0
0

6.5
11.4
15.0

11.4
15.0
15.0

4.9
3.6
0

225
270
315

14.0
14.0
14.0

14.0
14.0
17.5

0
0
3.5

8.9
12.4
12.4

12.4
12.4
12.4

3.5
0
0

0.4
3.9
8.9

3.9
8.9
12.4

3.5
5
3.5

15.0
15.0
15.0

15.0
15.0
15.0

0
0
0