AS/NZS 1768:2007

Australian/New Zealand Standard



Lightning protection

A
S
/
N
Z
S

1
7
6
8
:
2
0
0
7

For DOD Internal Use ONLY


AS/NZS 1768:2007
This Joint Australian/New Zealand Standard was prepared by Joint Technical
Committee EL-024, Protection Against Lightning. It was approved on behalf of the
Council of Standards Australia on 13 September 2006 and on behalf of the Council
of Standards New Zealand on 6 October 2006.
This Standard was published on 10 January 2007.

The following are represented on Committee EL-024:

Association of Consulting Engineers Australia
Australasian Corrosion Association
Australasian Railway Association
Australian Chamber of Commerce and Industry
Australian Electrical and Electronic Manufacturers Association
Australian Institute of Petroleum Ltd
Bureau of Meteorology
CSIRO Industrial Physics
Department of Defence (Australia)
Department of Natural Resources and Mines (QLD)
Department of Primary Industries, Mine Safety (NSW)
Energy Networks Association
Engineers Australia
ITU NSG5
Master Builders Australia
Ministry of Economic Development (New Zealand)
National Electrical and Communications Association
Telstra Corporation Limited
The University of Queensland
Transpower New Zealand
UniQuest


Keeping Standards up-to-date
Standards are living documents which reflect progress in science, technology and
systems. To maintain their currency, all Standards are periodically reviewed, and
new editions are published. Between editions, amendments may be issued.
Standards may also be withdrawn. It is important that readers assure themselves
they are using a current Standard, which should include any amendments which
may have been published since the Standard was purchased.
Detailed information about joint Australian/New Zealand Standards can be found by
visiting the Standards Web Shop at www.standards.com.au or Standards New
Zealand web site at www.standards.co.nz and looking up the relevant Standard in
the on-line catalogue.
Alternatively, both organizations publish an annual printed Catalogue with full
details of all current Standards. For more frequent listings or notification of
revisions, amendments and withdrawals, Standards Australia and Standards New
Zealand offer a number of update options. For information about these services,
users should contact their respective national Standards organization.
We also welcome suggestions for improvement in our Standards, and especially
encourage readers to notify us immediately of any apparent inaccuracies or
ambiguities. Please address your comments to the Chief Executive of either
Standards Australia or Standards New Zealand at the address shown on the back
cover.

This Standard was issued in draft form for comment as DR 06132.

For DOD Internal Use ONLY


AS/NZS 1768:2007
Australian/New Zealand Standard


Lightning protection





















Originated in Australia as MC11969.
Originated in New Zealand as NZS/AS 1768:1991.
Previous edition AS/NZS 1768(Int):2003.
This edition AS/NZS 1768:2007.
COPYRIGHT
Standards Australia/Standards New Zealand
All rights are reserved. No part of this work may be reproduced or copied in any form or by
any means, electronic or mechanical, including photocopying, without the written
permission of the publisher.
Jointly published by Standards Australia, GPO Box 476, Sydney, NSW 2001 and Standards
New Zealand, Private Bag 2439, Wellington 6020
ISBN 0 7337 7967 0
For DOD Internal Use ONLY
AS/NZS 1768:2007 2


PREFACE
This Standard was prepared by the Joint Standards Australia/Standards New Zealand
Committee EL-024, Protection against Lightning, to supersede AS/NZS 1768(Int):2003,
Lightning protection.
This Standard is intended to provide authoritative guidance on the principles and practices
of lightning protection for a wide range of structures and systems. It is not intended for
mandatory application but, if called up in a contractual situation, compliance with this
Standard requires compliance with all relevant clauses of the Standard such that the level of
protection will be sufficient to achieve a tolerable level of risk as determined by the risk
calculation.
In general, it is not economically possible to provide total protection against all the possible
damaging effects of lightning, but the recommendations in this Standard will reduce the
probability of damage to a calculated acceptable level, and will minimize any lightning
damage that does occur. Guidance is given on methods of enhancing the level of protection
against lightning damage, if this is required in a particular situation.
Where a new structure is to be erected, the matter of lightning protection should be
considered in the planning stage, as the necessary measures can often be affected in the
architectural features without detracting from the appearance of the building. In addition to
the aesthetic considerations, it is usually less expensive to install a lightning protection
system during construction than afterwards.
The decision to provide lightning protection may be taken without carrying out a risk
assessment or regardless of the outcome of any risk assessment, for example, where there is
a desire that there be no avoidable risk. Any decision not to provide lightning protection
should only be made after considering the advice provided in this Standard. Where doubt
exists as to the need for lightning protection, further advice should be sought from a
lightning protection designer or installer.
Unless it has been specified that lightning protection must be provided, the first decision to
make is whether the lightning protection is needed. Section 2 provides guidance to assist in
this decision. Section 3 provides advice on the protection of persons from lightning, mainly
relating to the behaviour of persons when not inside substantial buildings. Once a decision
is made that lightning protection is necessary, Section 4 provides details on interception
lightning protection for the building or structure. This includes information on the size,
material, and form of conductors, the positioning of air terminals and downconductors, and
the requirements for earth terminations. Persons and equipment within buildings can be at
risk from the indirect effects of lightning and Section 5 gives recommendations for the
protection of persons and equipment within buildings from the effects of lightning.
Section 6 describes methods of lightning protection of various items not covered in earlier
sections, such as communications antennas, chimneys, boats, fences, and trees. A clause is
included on methods for protecting domestic dwellings and assorted structures in public
places, where a complete protection system may not be justified, but some protection is
considered desirable.
Section 7 sets out recommendations for the protection of structures with explosive or
highly-flammable contents. Section 8 gives advice on precautions to be taken during
installation, inspecting, testing, and maintaining lightning protection systems.
A number of appendices are included that provide additional information and advice. The
appendices form an integral part of this Standard unless specifically stated otherwise. i.e.
appendices identified as informative only provide supportive or background information
and are therefore not an integral part of this Standard.
For DOD Internal Use ONLY
3 AS/NZS 1768:2007


CONTENTS
Page
SECTION 1 SCOPE AND GENERAL
1.1 SCOPE ........................................................................................................................ 5
1.2 APPLICATION........................................................................................................... 5
1.3 INTRODUCTION....................................................................................................... 5
1.4 REFERENCED DOCUMENTS .................................................................................. 6
1.5 DEFINITIONS ............................................................................................................ 6
SECTION 2 ASSESSMENT AND MANAGEMENT OF RISK DUE TO LIGHTNING
ANALYSIS OF NEED FOR PROTECTION
2.1 INTRODUCTION..................................................................................................... 11
2.2 SCOPE OF SECTION............................................................................................... 11
2.3 CONCEPT OF RISK................................................................................................. 12
2.4 DAMAGE DUE TO LIGHTNING............................................................................ 13
2.5 RISKS DUE TO LIGHTNING.................................................................................. 17
2.6 PROCEDURE FOR RISK ASSESSMENT AND MANAGEMENT......................... 21
2.7 RISK MANAGEMENT CALCULATION TOOL..................................................... 23
SECTION 3 PRECAUTIONS FOR PERSONAL SAFETY
3.1 SCOPE OF SECTION............................................................................................... 28
3.2 NEED FOR PERSONAL PROTECTION.................................................................. 28
3.3 PERSONAL CONDUCT........................................................................................... 29
3.4 EFFECT ON PERSONS AND TREATMENT FOR INJURY BY LIGHTNING...... 31
SECTION 4 PROTECTION OF STRUCTURES
4.1 SCOPE OF SECTION............................................................................................... 32
4.2 PROTECTION LEVEL............................................................................................. 32
4.3 LPS DESIGN RULES ............................................................................................... 32
4.4 ZONES OF PROTECTION FOR LIGHTING INTERCEPTION.............................. 34
4.5 METHODS OF PROTECTION................................................................................. 42
4.6 MATTERS TO BE CONSIDERED WHEN PLANNING PROTECTION ................ 44
4.7 MATERIALS ............................................................................................................ 47
4.8 FORM AND SIZE OF CONDUCTORS.................................................................... 51
4.9 JOINTS...................................................................................................................... 52
4.10 FASTENERS............................................................................................................. 52
4.11 AIR TERMINALS..................................................................................................... 53
4.12 DOWNCONDUCTORS ............................................................................................ 55
4.13 TEST LINKS............................................................................................................. 58
4.14 EARTH TERMINATIONS........................................................................................ 58
4.15 EARTHING ELECTRODES..................................................................................... 59
4.16 METAL IN AND ON A STRUCTURE..................................................................... 61
SECTION 5 PROTECTION OF PERSONS AND EQUIPMENT WITHIN BUILDINGS
5.1 SCOPE OF SECTION............................................................................................... 66
5.2 NEED FOR PROTECTION....................................................................................... 66
5.3 MODES OF ENTRY OF LIGHTNING IMPULSES................................................. 66
5.4 GENERAL CONSIDERATIONS FOR PROTECTION............................................ 69
5.5 PROTECTION OF PERSONS WITHIN BUILDINGS ............................................. 70
5.6 PROTECTION OF EQUIPMENT............................................................................. 73
For DOD Internal Use ONLY
AS/NZS 1768:2007 4


Page
SECTION 6 PROTECTION OF MISCELLANEOUS STRUCTURES AND PROPERTY
6.1 SCOPE OF SECTION............................................................................................... 90
6.2 STRUCTURES WITH ANTENNAS......................................................................... 90
6.3 STRUCTURES NEAR TREES ................................................................................. 90
6.4 PROTECTION OF TREES........................................................................................ 91
6.5 CHIMNEYS, METAL GUY-WIRES OR WIRE ROPES.......................................... 91
6.6 PROTECTION OF MINES ....................................................................................... 92
6.7 PROTECTION OF BOATS....................................................................................... 94
6.8 FENCES.................................................................................................................... 97
6.9 MISCELLANEOUS STRUCTURES ........................................................................ 97
6.10 PROTECTION OF HOUSES AND SMALL BUILDINGS....................................... 99
6.11 PROTECTION OF METALLIC PIPELINES.......................................................... 100
SECTION 7 PROTECTION OF STRUCTURES WITH EXPLOSIVE OR HIGHLY-
FLAMMABLE CONTENTS
7.1 SCOPE OF SECTION............................................................................................. 101
7.2 GENERAL CONSIDERATIONS............................................................................ 101
7.3 AREAS OF APPLICATION ................................................................................... 102
7.4 EQUIPMENT APPLICATION................................................................................ 102
7.5 SPECIFIC OCCUPANCIES.................................................................................... 104
SECTION 8 INSTALLATION AND MAINTENANCE PRACTICE
8.1 WORK ON SITE..................................................................................................... 109
8.2 INSPECTION.......................................................................................................... 109
8.3 TESTING ................................................................................................................ 109
8.4 RECORDS............................................................................................................... 110
8.5 MAINTENANCE.................................................................................................... 110
APPENDICES
A EXAMPLES OF LIGHTNING RISK CALCULATIONS ...................................... 111
B THE NATURE OF LIGHTNING AND THE PRINCIPLES OF LIGHTNING
PROTECTION ........................................................................................................ 133
C NOTES ON EARTHING ELECTRODES AND MEASUREMENT OF EARTH
IMPEDANCE.......................................................................................................... 145
D THE CALCULATION OF LIGHTNING DISCHARGE VOLTAGES AND
REQUISITE SEPARATION DISTANCES FOR ISOLATION OF A LIGHTNING
PROTECTION SYSTEM........................................................................................ 165
E EARTHING AND BONDING ................................................................................ 174
F WAVESHAPES FOR ASSESSING THE SUSCEPTIBILITY OF EQUIPMENT
TO TRANSIENT OVERVOLTAGES DUE TO LIGHTNING ............................... 182
G REFERENCED DOCUMENTS .............................................................................. 186

For DOD Internal Use ONLY
5 AS/NZS 1768:2007

COPYRIGHT
STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND

Australian/New Zealand Standard
Lightning protection

S E C T I O N 1 S C O P E A N D G E N E R A L
1.1 SCOPE
This Standard sets out guidelines for the protection of persons and property from hazards
arising from exposure to lightning. The recommendations specifically cover the following
applications:
(a) The protection of persons, both outdoors, where they may be at risk from the direct
effects of a lightning strike, and indoors, where they may be at risk indirectly as a
consequence of lightning currents being conducted into the building.
(b) The protection of a variety of buildings or structures, including those with explosive
or highly-flammable contents, and mines.
(c) The protection of sensitive electronic equipment (e.g. facsimile machines, modems,
computers) from overvoltages resulting from a lightning strike to the building or its
associated services.
The nature of lightning and the principles of lightning protection are discussed and
guidance is given to assist in a determination of whether protective measures should be
taken.
This Standard is applicable to conventional lightning protection systems (LPSs) that
comprise air terminals, downconductors, earth termination networks and surge protective
devices (SPDs). Nothing contained within this Standard either endorses or implies the
endorsement of non-conventional LPSs that comprise air terminals that claim enhanced
performance or downconductors that claim enhanced magnetic screening over conventional
systems.
The performance of such systems is outside the scope of this Standard. Irrespective of
claimed performance, air terminals shall be placed in accordance with Section 4 to comply
with this Standard.
1.2 APPLICATION
This Standard does not override any statutory requirements but may be used in conjunction
with such requirements.
Compliance with the recommendations of this Standard will not necessarily prevent damage
or personal injury due to lightning but will reduce the probability of such damage or injury
occurring.
1.3 INTRODUCTION
Thunderstorms are natural phenomena and there are no proven devices and methods capable
of preventing lightning flashes. Direct and nearby cloud-to-ground lightning discharges can
be hazardous to persons, structures, installations and many other things in or on them.
Consideration should always be given to the application of lightning protection measures.
For DOD Internal Use ONLY
AS/NZS 1768:2007 6
COPYRIGHT
Realization that it is possible to provide effective protection against lightning began with
Franklin and for over a hundred years national and international manuals and standards
have been developed to provide guidance on the principles and practice of lightning
protection. Until about ten years ago, risk assessment was used to determine if there was a
need to provide lightning protection. However, the modern approach is that of risk
management, which integrates the determination of the need for protection with the
selection of adequate protection measures to reduce the risk to a tolerable level. This
selection takes into account both the efficiency of the measures and the cost of their
provision. In the risk management approach, the lightning threats that create risk are
identified, the frequencies of all risk events are estimated, the consequences of the risk
events are determined, and if these are above a tolerable level of risk, protection measures
are applied to reduce the risk (R) to below the tolerable level (R
a
). This involves a choice
from a range of protection level efficiencies for protection against direct (d) strikes to the
structure and decisions about the extent of other measures for protecting low-voltage and
electronic equipment against indirect (i) lightning stresses incident from nearby strikes. In
summary
R = R
x
= R
d
+ R
i
R
x
= N
x
P
x

x
P
x
= k
x
p
x
R R
a
where N
x
is the frequency of dangerous events, P
x
is the probability of damage or injury,
x

is the relative amount of damage or injury with any consequential effects, and k
x
is a
reduction factor associated with the protection measure adopted and which equals 1 in the
absence of protection measures when P
x
= p
x
.
The lightning protection measures include an LPS for the structure and its occupants,
protection against the lightning electromagnetic pulse (LEMP) caused by direct and nearby
strikes, and transient protection (TP) of incoming services. The LPS for the structure
comprises an air terminal network to intercept the lightning strike, a downconductor system
to conduct the discharge current safely to earth and an earth termination network to
dissipate the current into the earth. The LEMP protection includes a number of measures to
protect sensitive electronic equipment such as the use of a mesh of downconductors to
minimize the internal magnetic field, the selection of lightning protection zones,
equipotential bonding and earthing, and the installation of SPDs. The TP for incoming
services includes the use of isolation devices, the shielding of cables and the installation
and coordination of SPDs.
1.4 REFERENCED DOCUMENTS
The documents referred to in this Standard are listed in Appendix G.
1.5 DEFINITIONS
For the purpose of this Standard, the definitions below apply.
1.5.1 Air terminal
A vertical or horizontal conductor of an LPS, positioned so as to intercept a lightning
discharge, which establishes a zone of protection.
1.5.2 Air terminal network
A network of air terminals and interconnecting conductors, which forms the part of an LPS
that is intended to intercept lightning discharges.
For DOD Internal Use ONLY
7 AS/NZS 1768:2007

COPYRIGHT
1.5.3 Base conductors
Conductors placed around the perimeter of a structure near ground level interconnected to a
number of earth terminations to distribute the lightning currents amongst them.
1.5.4 Bond (bonding conductor)
A conductor intended to provide electrical connection between the LPS and other
metalwork and between various metal parts of a structure or between earthing systems.
1.5.5 Damage ()
Mean relative amount of loss consequent to a specified type of damage due to a lightning
event, when damage factors are not taken into account.
1.5.6 Direct lightning flash
A lightning discharge, composed of one or more strokes, that strikes the structure or its LPS
directly.
1.5.7 Downconductor
A conductor that connects an air terminal network with an earth termination.
1.5.8 Earth impedance (Z)
The electrical impedance of an earthing electrode or structure to earth, derived from the
earth potential rise divided by the impulse current to earth causing that rise. It is a relatively
complex function and depends on
(a) the resistance component (R) as measured by an earth tester;
(b) the reactance component (X), depending on the circuit path to the general body of
earth; and
(c) a modifying (reducing) time-related component depending on soil ionization caused
by high current and fast rise times.
1.5.9 Earth potential rise (EPR)
The increase in electrical potential of an earthing electrode, body of soil or earthed
structure, with respect to distant earth, caused by the discharge of current to the general
body of earth through the impedance of that earthing electrode or structure.
1.5.10 Earthing boss (terminal lug)
A metal boss specially designed and welded to process plant, storage tanks, or steelwork to
which earthing conductors are attached by means of removable studs or nuts and bolts.
1.5.11 Earthing conductor
The conductor by which the final connection to an earthing electrode is made.
1.5.12 Earthing electrodes (earth rods or ground rods)
Those portions of the earth termination that make direct low resistance electrical contact
with the earth.
1.5.13 Earthing resistance
The resistance of the LPS to the general mass of earth, as measured from a test point.
1.5.14 Earth termination (earth termination network)
That part of an LPS intended to discharge lightning currents into the general mass of the
earth. All parts below the lowest test link in a downconductor are included.
For DOD Internal Use ONLY
AS/NZS 1768:2007 8
COPYRIGHT
1.5.15 Electricity supply service earthing electrode
An earthing electrode installed for the purposes of providing the connection of the electrical
installation earthing system to the general mass of earth.
1.5.16 Explosive gas atmosphere
A mixture of flammable gas, vapour or mist with air in atmospheric conditions in which,
after ignition, combustion spreads throughout the unconsumed mixture that is between the
upper and lower explosive limits.
NOTE: The term refers exclusively to the danger arising from ignition. Where danger from other
causes such as toxicity, asphyxiation, and radioactivity may arise this is specifically mentioned.
1.5.17 Finial
A term not used in this Standard owing to its confusion with architectural application but
occasionally used elsewhere in other Standards as referring to short vertical air terminals.
1.5.18 Frequency of lightning flashes direct to a service (N
c
)
Expected annual number of lightning flashes directly striking an incoming service.
1.5.19 Frequency of lightning flashes direct to a structure (N
d
)
Expected annual number of lightning flashes directly striking the structure.
1.5.20 Frequency of lightning flashes to ground near a service (N
I
)
Expected annual number of lightning flashes striking the ground surface near an incoming
service.
1.5.21 Frequency of lightning flashes to ground near a structure (N
m
)
Expected annual number of lightning flashes striking the ground surface near the structure.
1.5.22 Hazardous area
An area where an explosive atmosphere is, or may be expected to be present continuously,
intermittently or due to an abnormal or transient condition (see AS/NZS 2430 series).
1.5.23 Incoming service
A service entering a structure (e.g. electricity supply service lines, telecommunications
service lines or other services).
1.5.24 Indirect lightning flash
A lightning discharge, composed of one or more strokes, that strikes the incoming services
or the ground near the structure or near the incoming services.
1.5.25 Internal installation
An installation or the part of an incoming service that is located inside the structure.
1.5.26 Joint
A mechanical and electrical junction between two or more sections of an LPS.
1.5.27 Lightning flash (lightning discharge)
An electrical discharge in the atmosphere involving one or more electrically charged
regions, most commonly in a cumulonimbus cloud, taking either of the following forms:
(a) Ground flash (earth discharge) A lightning flash in which at least one lightning
discharge channel reaches the ground.
(b) Cloud flash A lightning flash in which the lightning discharge channels do not reach
the earth.
For DOD Internal Use ONLY
9 AS/NZS 1768:2007

COPYRIGHT
1.5.28 Lightning flash density (N
g
)
The number of lightning flashes of the specified type occurring on or over unit area in unit
time. This is commonly expressed as per square kilometre per year (km
2
year
1
). The
ground flash density is the number of ground flashes per unit area and per unit time,
preferably expressed as a long-term (>10 years) average value.
1.5.29 LPS (LPS Type I to IV)
Complete system used to reduce the danger of physical damages and of injuries due to
direct flashes to the structure. It consists of both external and internal LPSs and is defined
as a set of construction rules, based on corresponding protection level.
1.5.30 Lightning protection zone (LPZ)
With respect to the lightning threat, a zone may be defined, inside of which is sensitive
equipment. Extra protection is applied at the zone boundary to minimize the risk of damage
to equipment inside the zone.
1.5.31 Lightning strike
A term used to describe the lightning flash when the attention is centred on the effects of
the flash at the lightning strike attachment point, rather than on the complete lightning
discharge.
1.5.32 Lightning strike attachment point
The point on the ground or on a structure where the lower end of the lightning discharge
channel connects with the ground or structure.
1.5.33 Lightning stroke
A term used to describe an individual current impulse in a complete ground flash.
1.5.34 Loss
Due to lightning strike, the loss can be of human life, loss of service to the public or
economic loss.
1.5.35 Multiple earthed neutral (MEN) system
A system of earthing in which the parts of an electrical installation are connected to the
general mass of earth and in addition are connected within the electrical installation to the
neutral conductor of the supply system.
1.5.36 Partial probability of damage (p)
Probability of a lightning flash causing a specified type of damage to the structure,
depending on one characteristic of the structure or of an incoming service.
1.5.37 Probability of damage (P)
Probability of a lightning flash causing a specified type of damage to the structure. It may
be composed of one or more simple probabilities of damage.
1.5.38 Protection level (I to IV)
Four levels of lightning protection. For each protection level, a set of maximum (sizing
criteria) and minimum (interception criteria) lightning current parameters is fixed, together
with the corresponding rolling sphere radius.
1.5.39 Protection measures
Protection measures taken to reduce the probability of damage. These may include an LPS
on the building, isolation transformers and/or surge protection on incoming services
(primary protection) and internal equipment (secondary protection).
For DOD Internal Use ONLY
AS/NZS 1768:2007 10
COPYRIGHT
1.5.40 Resistibility
Ability of equipment to withstand an overvoltage or an overcurrent without damage.
1.5.41 Risk (R)
Probable average annual loss (humans and goods) in a structure due to lightning flashes.
1.5.42 Risk assessment
The process of designing an LPS to achieve a probable frequency of damage and injury. It
is based on determining the likely number of lightning discharges and also estimates the
probability and consequences. A range of protection measures can be selected to reduce the
risk to less than a target value. This process is also known as risk management.
1.5.43 Risk component
Partial risk assessed according to the source of damage and the type of damage.
1.5.44 Side-flash
A discharge occurring between nearby objects or from such objects to the LPS or to earth.
1.5.45 Special damage factors (k
n
)
Factors affecting the value of the damage , with respect to the existing peculiar conditions
in the structure, that may decrease or increase the loss.
1.5.46 Striking distance (d
s
)
The distance between the tip of the downward leader and the eventual lightning strike
attachment point at the moment of initiation of an upward intercepting streamer.
1.5.47 Structure or object
Any building or construction, process plant, storage tank, tree, or similar, on or in the
ground.
1.5.48 Surge protective device (SPD)
A device that is intended to mitigate surge overvoltages and overcurrents.
1.5.49 Test link
A joint designed and situated so as to enable resistance or continuity measurements to be
made.
1.5.50 Thunderday
A calendar day during which thunder is heard at a given location. Thunderstorm occurrence
at a particular location is usually expressed in terms of the number of calendar days in a
year when thunder was heard at the location, averaged over several years.
1.5.51 Tolerable risk (R
a
)
Maximum value of the risk that can be tolerated in the structure to be protected. Also
referred to as acceptable risk, being the maximum value of risk acceptable based on
community expectations.
1.5.52 Zone of protection
The portion of space within which an object or structure is considered to be protected from
a direct strike by an LPS.
For DOD Internal Use ONLY
11 AS/NZS 1768:2007

COPYRIGHT
S E C T I O N 2 A S S E S S M E N T A N D
M A N A G E M E N T O F R I S K D U E T O L I G H T N I N G
A N A L Y S I S O F N E E D F O R P R O T E C T I O N
2.1 INTRODUCTION
Cloud-to-ground lightning discharges can be hazardous to structures, people and
installations or equipment in, on or connected to the structure. Lightning can cause damage
to all or part of a structure or to the contents of a structure, especially to electrical and
electronic systems. Consequential effects of lightning damage may extend to the
surroundings of a structure.
To reduce lightning damage and its consequential effects, lightning protection measures
may be required. The need for protection and the level of protection applied should be
considered in terms of the assessment of risk due to lightning, and management of that risk
to an acceptable level.
The approach outlined in this section is based on the principles of the management of risk
due to lightning outlined in initial work by IEC Committee TC 81 on this subject. The
approach has been simplified by reducing the number of variables and options requiring
selection to a minimum (based on assumptions for general conditions in Australia and New
Zealand) and providing a Microsoft

Excel calculation tool as an integral part of this


Standard.
The Microsoft

Excel calculation tool provides only an estimate of the lightning risk. The
risk assessment calculator is a simplified tool for the more common structure types. For
specialized structures (e.g. telecommunication exchanges, substations), a detailed lightning
risk assessment may be undertaken. This may involve the application of industry specific
Standards. Where other information exists, such as the damage/hazard history of existing
similar structures in the nearby area, then this should be taken into account when deciding
whether or not to install lightning protection and the appropriate level of lightning
protection required. A decision to provide lightning protection may be taken regardless of
the outcome of any risk assessment, for example, where there is a desire that there be no
avoidable risk. In such cases, the required protection level for the structure (Level I, II, III
or IV as defined in Section 4) should be specified. It may also be important to specify
other protection measures such as SPDs on incoming conductive electrical service lines and
internal equipment. Risk assessment for protection of specific conductive electrical services
may also be undertaken in isolation based on specific Standards and performance criteria.
For telecommunication overvoltages, AS 4262.1 deals with protection of persons,
AS 4262.2 deals with protection of equipment and the ITU-T K series of recommendations
provide requirements for protecting telecommunication networks.
Before any decision is made not to install lightning protection to a structure, consideration
should be given to the factors outlined in other sections of this Standard.
2.2 SCOPE OF SECTION
This Section is applicable to the management of risk caused by lightning discharges to
earth.
The object of this Section is to give a procedure for evaluation of the risk to a structure,
people and installations or equipment in, on or connected to the structure. This evaluation
considers mechanical damage of the structure and contents, damage and failure of
equipment, potential differences causing deaths of people and livestock from step and touch
voltages, and fire damage that may result from the lightning discharge.
For DOD Internal Use ONLY
AS/NZS 1768:2007 12
COPYRIGHT
The procedure involves the comparison of the evaluated risk to the tolerable or acceptable
limit of the risk and allows for the selection of appropriate protective measures to reduce
the risk to below the tolerable limit.
This Standard does not consider the risk of personal injury when using telecommunication
equipment during a lightning storm.
2.3 CONCEPT OF RISK
2.3.1 General considerations
In this Standard, risk R is defined as the probable annual loss due to lightning. Expressed as
a number, it represents the probability of loss occurring over the period of a year. Thus a
risk of 10
-3
represents a chance of 1 in 1000 of a loss occurring during a year.
To increase understanding of the risk concept, some risks associated with everyday living
are provided in Table 2.1. Many human activities imply a judgement that the benefits
outweigh the related risks. Table 2.1 gives a scale of risk of loss of human life associated
with different activities.
TABLE 2.1
COMPARATIVE PROBABILITY OF DEATH FOR AN INDIVIDUAL PER YEAR
OF EXPOSURE (ORDER OF MAGNITUDE ONLY)
*

Risk Activity
Chance of occurrence Probability per year
1 in 400 2.5 10
3
Smoking (10 cigarettes per day)
1 in 2000 5 10
4
All accidents
1 in 8000 1.3 10
4
Traffic accidents
1 in 20 000 5 10
5
Leukaemia from natural causes
1 in 30 000 3.3 10
5
Work in industry, drowning
1 in 100 000 1 10
5
Poisoning
1 in 500 000 2 10
6
Natural disasters
1 in 1 000 000 1 10
6
Rock climbing for 90 s

,
driving 50 miles (80 km) by road


1 in 2 000 000 5 10
7
Being struck by lightning
* The source of this table is BS 6651:1999.
These risks are conventionally expressed in this form rather than in terms of exposure for a year.
2.3.2 Types of risk due to lightning
The types of risk due to lightning for a particular structure or facility may include one or
more of the following:
(a) R
1
risk of loss of human life.
(b) R
2
risk of loss of service to the public.
NOTE: Only applicable to structures involved in the provision of public service utilities (e.g.
water, electricity, gas, telecommunications, rail).
(c) R
3
risk of loss of cultural heritage.
(d) R
4
risk of loss of economic value.
For DOD Internal Use ONLY
13 AS/NZS 1768:2007

COPYRIGHT
2.3.3 Tolerable values of risk
In order to manage risk, a judgement must be made of what is an acceptable or tolerable
upper limit for the risk.
In relation to human fatalities, various societal risk guidelines or criteria have been
proposed. Generally for a single human fatality, risks of greater than 10
3
per year (i.e.
chance of 1 in 1000 of occurrence in a year) are considered unacceptable. Public money
would normally be spent to try to eliminate (or reduce to a level as low as reasonably
practical) the causes of risks greater than 10
4
per year (i.e. chance of 1 in 10 000 of
occurrence). Risks less than 10
5
per year (i.e. chance of 1 in 100 000 of occurrence) are
generally considered tolerable although public money may still be spent on an education
campaign to reduce those risks regarded as avoidable.
In terms of the risk of various types of losses due to lightning, a value of the tolerable risk,
R
a
needs to be specified. For each type of loss due to lightning, R
a
represents the tolerable
probability of that loss occurring over the period of a year. Regarding the potential types of
risk due to lightning listed in Clause 2.3.2, typical values of the tolerable or acceptable risk,
R
a
are given in Table 2.2.
TABLE 2.2
TYPICAL VALUES OF TOLERABLE RISK, R
a

Type of loss Tolerable risk per year,
R
a

Loss of human life 10
5

Loss of service to the public 10
3

Loss of cultural heritage 10
3

For a loss of economic value, the tolerable risk, R
a
may be fixed by the facility owner or
user, often in consultation with the designer of the protection measures, based on economic
or cost/benefit considerations.
For example, at a particular facility, it may be considered that a chance of 1 in 1000 of
economic loss due to lightning occurring over a period of a year is tolerable. Alternatively,
this would mean that it is considered acceptable for such a loss to occur, on average, once
every 1000 years. In such a case the tolerable risk, R
a
for loss of economic value would be
set at 10
-3
. Similarly, if it were considered acceptable for such a loss to occur, on average,
once every 100 years, R
a
for loss of economic value would be set at 10
-2
.
2.4 DAMAGE DUE TO LIGHTNING
2.4.1 Sources of damage
The current in the lightning discharge is the potential source of damage. In this Section, the
following sources of damage, relating to the proximity of the lightning strike, are taken into
account (see Table 2.3):
(a) S1direct strike to the structure.
(b) S2strike to the ground near the structure.
(c) S3direct strike to a conductive electrical service line.
(d) S4strike to ground near a conductive electrical service line.
Conductive electrical service lines include electricity supply service lines (underground or
overhead) and telecommunications service lines.
For DOD Internal Use ONLY
AS/NZS 1768:2007 14
COPYRIGHT
The number of lightning strikes influencing the structure depends on
(i) the dimensions and the characteristics of the structure;
(ii) the dimensions and characteristics of the incoming conductive electrical service lines;
(iii) the environment around the structure; and
(iv) the density of lightning strikes in the region where the structure is located.
The greater the height and collection area, the more lightning strikes will influence the
structure. Tall trees and surrounding buildings may shield a structure from lightning strikes.
Incoming conductive electrical service lines add to the lightning collection area as they can
conduct lightning current into the building.
2.4.2 Types of damage
The type of damage that a lightning strike may cause depends on structure or facility
characteristics such as
(a) type of construction;
(b) contents and application;
(c) incoming conductive electrical service lines; and
(d) measures taken for limiting the risk.
The damage may be limited to a part of the structure or may extend to the whole structure.
Damage may also extend to the surrounding environment (e.g. contamination caused by
consequential chemical spills or radioactive emissions).
Direct strikes to the structure or to incoming conductive electrical service lines may cause
mechanical damage, injury to people and animals and may cause fire and/or explosion.
Indirect strikes as well as direct strikes may cause failure of electrical and electronic
equipment due to overvoltages resulting from coupling of the lightning current.
For practical applications of risk assessment, it is useful to distinguish between three basic
types of damage that can appear as the consequence of a lightning strike. They are as
follows:
(i) D1Injury to people (shock of living beings) due to step and touch voltages and
side-flash contact.
(ii) D2Fire, explosion, mechanical destruction, chemical release due to physical effects
of the lightning channel (including dangerous sparking).
(iii) D3Failure of electrical and electronic systems due to overvoltages.
2.4.3 Consequences of damage (types of loss)
The value amount of damage caused by the consequential effects of lightning depends on
factors such as
(a) the number of people and the time they are in the facility;
(b) the type and importance of the service provided to the public; and
(c) the value of goods and/or services affected by the damage.
Some special hazard factors also need to be considered. For example, in theatres and halls
there can be a significant risk of panic if a lightning strike causes loss of electricity supply
or other mechanical or fire-related damage. As a result, people may be injured in the panic
to evacuate the building.
Museums and heritage listed buildings have a cultural value. There may be significant loss
of revenue (economic loss) associated with damage to computer centres and communication
nodes.
For DOD Internal Use ONLY
15 AS/NZS 1768:2007

COPYRIGHT
For a particular facility or structure, the following consequences of damage due to lightning
or types of loss should be taken into account.
(i) L1Loss of human life.
(ii) L2Loss of services to the public.
NOTE: Only applicable to structures involved in the provision of public service utilities (e.g.
water, electricity, gas, telecommunications, rail).
(iii) L3Loss of cultural heritage.
(iv) L4Loss of economic value (structure, content and loss of activity).
Table 2.3 illustrates the relationship between the sources of damage, types of damage
and types of loss selected according to the point of strike.
TABLE 2.3
SOURCES OF DAMAGES (S1, S2, S3, S4), TYPES OF DAMAGES
(D1, D2, D3) AND TYPES OF LOSS (L1, L2, L3, L4)
SELECTED ACCORDING TO THE POINT OF STRIKE
Structure Service
Point of strike
Source of
damage
Type of
damage
Type of loss Type of
damage
Type of loss
D1 L1, L4
1)

D2 L1, L2, L3, L4 D2 L1
2)
, L2, L4

S1
D3 L1, L2, L4 D3 L2, L4

S2 D3 L1
3)
, L2, L4
D1 L1, L4
1)

D2 L1, L2, L3, L4 D2 L1
2)
, L2, L4

S3
D3 L1, L2, L4 D3 D2, D4

S4 D3 L1
3)
, L2, L4 D3 L2, L4
1)
In the case of agricultural properties (loss of animals).
2)
In the case of pipelines, with no metallic gasket on flanges, conveying explosive fluid.
3)
In the case of hospitals and of structures with risk of explosion.
For DOD Internal Use ONLY
AS/NZS 1768:2007 16
COPYRIGHT
Figure 2.1 illustrates the relationship between the types of loss, types of damage and
components of risk (discussed in Clause 2.5.1) that can be associated with lightning
discharges to earth.

F
I
G
U
R
E


2
.
1



L
O
S
S
E
S
,

D
A
M
A
G
E
S

A
N
D

R
I
S
K

C
O
M
P
O
N
E
N
T
S

For DOD Internal Use ONLY
17 AS/NZS 1768:2007

COPYRIGHT
2.5 RISKS DUE TO LIGHTNING
2.5.1 Risk components
For each type of loss relevant to the structure or facility, the total risk due to lightning, R,
is the probability of that loss occurring over the period of a year. The total risk, R, is made
up of the sum of a number of risk components associated with the four possible sources of
damage (according to the point of strike) as listed below:
(a) S1 Lightning strikes directly to the structure
These may generate:
(i) Component R
h
due to step and touch voltages outside the structure (mainly
around downconductors) causing shock to living beings (D1).
(ii) Component R
s
due to mechanical and thermal effects of the lightning current or
by dangerous sparking causing fire, explosion, mechanical and chemical effects
inside the structure (D2).
(iii) Component R
w
due to overvoltages on internal installations and incoming
services causing failure of electrical and electronic systems (D3).
(b) S2 Lightning strikes to ground near the structure
These may generate component R
m
due to overvoltages on internal installations and
equipment (mainly induced by the magnetic field associated with the lightning
current) causing failure of electrical and electronic systems (D3).
(c) S3 Lightning strikes directly to conductive electrical service lines
These may generate:
(i) Component R
g
due to touch overvoltages transmitted through incoming lines
causing shock of living beings inside the structure (D1).
(ii) Component R
c
due to mechanical and thermal effects including dangerous
sparking between external installation and metallic parts (generally at the point-
of-entry of the incoming line into the structure) causing fire, explosion,
mechanical and chemical effects on the structure and/or its content (D2).
(iii) Component R
e
due to overvoltages, transmitted through incoming lines to the
structure, causing failure of electrical and electronic systems (D3).
(d) S4 Lightning strikes to ground near conductive electrical service line conductors
These may generate component R
l
due to induced overvoltages, transmitted through
incoming lines to the structure, causing failure of electrical and electronic systems
(D3).
Figure 2.1 illustrates the relationship between the types of loss, types of damage and
risk components that can be associated with lightning discharges to earth. Table 2.4
summarizes the various risk components and the ways that these can be summed to give the
total risk.
For DOD Internal Use ONLY
AS/NZS 1768:2007 18
COPYRIGHT
For each type of loss, the total value of the risk due to lightning, R, may be expressed in the
following ways:
(i) With reference to the type of lightning strike
R = R
d
+ R
i
. . . 2.5.1(1)
where
R
d
= R
h
+ R
s
+ R
w
risk due to direct strikes to the structure
R
i
= R
g
+

R
c
+

R
m
+

R
e
+

R
l
risk due to indirect strikes to the structure
(including direct and indirect strikes to
conductive electrical service lines)
(ii) With reference to the types of damage
R = R
t
+

R
f
+

R
o
. . . 2.5.1(2)
where
R
t
= R
h
+

R
g
risk due to shock to living beings (D1)
R
f
= R
s
+ R
c
risk due to fire, explosion, mechanical
destruction and chemical release (D2)
R
o
= R
w
+ R
m
+ R
e
+ R
l
risk due to the failure of electrical and
electronic systems due to overvoltages (D3)
2.5.2 Calculation of risk components
Each component of the risk R
x
depends on the number of dangerous events N
x
, the
probability of damage P
x
and the damage factor
x
. The value of each component of risk R
x

may be calculated using an expression similar to that shown below:
R
x
= N
x
P
x

x

NOTE: Details of the parameters, factors and equations required to calculate each of the risk
components are given in Appendix A.
For each risk component, the damage factor,
x
, represents the mean damage and takes into
account the type of damage, its extent, and the consequential effects that may occur as the
result of a lightning strike. Typical values of the damage factors for each type of loss are
given in Appendix A and in the risk management calculation tool.
NOTE: Where specific information is known regarding the function or use of a particular
structure, alternative damage factor values may be selected based on these relations.
The damage factors are related to the structures function or use and may be determined
from the following approximate relations below:
Loss of human life (L1)

x
=
t
8760
n t
n
(relative number of victims)
. . . 2.5.2(1)
where
n = the number of possible victims from a lightning strike
n
t
= the expected total number of people associated with the structure
t = the time, in hours per year, for which the people are present in a
dangerous place
For DOD Internal Use ONLY
19 AS/NZS 1768:2007

COPYRIGHT
Unacceptable loss of service to the public (L2)

x =
t
8760
n t
n
(relative amount of possible loss)
. . . 2.5.2(2)
where
n = the mean number of users not served
n
t
= the total number of users served
t = the annual period of loss of service, in hours.
Loss of cultural heritage (L3)

x =
t
c
c

(relative amount of possible loss)
. . . 2.5.2(3)
where
c = the insured value of possible loss of goods (monetary amount)
c
t
= the total insured value of all goods present in the structure
(monetary amount)
Economic loss (L4)

x =
t
c
c

(relative amount of possible loss)
. . . 2.5.2(4)
where
c = the mean value of the possible loss of the structure, its contents and
associated activities (monetary amount)
c
t
= the total value of the structure, its content and associated activities
(monetary amount)

For DOD Internal Use ONLY


COPYRIGHT
20
AS/NZS 1768:2007
T
A
B
L
E



2
.

4

P
O
S
S
I
B
L
E

R
I
S
K

C
O
M
P
O
N
E
N
T
S

C
A
U
S
E
D

B
Y

D
I
F
F
E
R
E
N
T

E
F
F
E
C
T
S

L
i
g
h
t
n
i
n
g

D
i
r
e
c
t

I
n
d
i
r
e
c
t

C
a
u
s
e

o
f

d
a
m
a
g
e

T
y
p
e

o
f

d
a
m
a
g
e

S
1

S
t
r
i
k
e

t
o

t
h
e

s
t
r
u
c
t
u
r
e

S
2

S
t
r
i
k
e

t
o

g
r
o
u
n
d

n
e
a
r

t
h
e

s
t
r
u
c
t
u
r
e

S
3

S
t
r
i
k
e

t
o

i
n
c
o
m
i
n
g

c
o
n
d
u
c
t
i
v
e

e
l
e
c
t
r
i
c
a
l

s
e
r
v
i
c
e

l
i
n
e

S
4

S
t
r
i
k
e

t
o

g
r
o
u
n
d

n
e
a
r

i
n
c
o
m
i
n
g

c
o
n
d
u
c
t
i
v
e

e
l
e
c
t
r
i
c
a
l

s
e
r
v
i
c
e

l
i
n
e


D
1

I
n
j
u
r
y

o
f

l
i
v
i
n
g

b
e
i
n
g
s

R
h

C
o
m
p
o
n
e
n
t

d
u
e

t
o

s
t
e
p

a
n
d

t
o
u
c
h

v
o
l
t
a
g
e
s

o
r

s
i
d
e
-
f
l
a
s
h

a
r
c

f
r
o
m

E
P
R

o
u
t
s
i
d
e

t
h
e

s
t
r
u
c
t
u
r
e

c
a
u
s
i
n
g

s
h
o
c
k

t
o

l
i
v
i
n
g

b
e
i
n
g
s


R
g

C
o
m
p
o
n
e
n
t

d
u
e

t
o

t
o
u
c
h

v
o
l
t
a
g
e
s

t
r
a
n
s
m
i
t
t
e
d

t
h
r
o
u
g
h

i
n
c
o
m
i
n
g

c
o
n
d
u
c
t
i
v
e

e
l
e
c
t
r
i
c
a
l

s
e
r
v
i
c
e

l
i
n
e
s

c
a
u
s
i
n
g

s
h
o
c
k

t
o

l
i
v
i
n
g

b
e
i
n
g
s

i
n
s
i
d
e

t
h
e

s
t
r
u
c
t
u
r
e


R
t

=

R
h

+

R
g

R
i
s
k

d
u
e

t
o

s
h
o
c
k

t
o

l
i
v
i
n
g

b
e
i
n
g
s

D
2

P
h
y
s
i
c
a
l

d
e
s
t
r
u
c
t
i
o
n

R
s

C
o
m
p
o
n
e
n
t

d
u
e

t
o

m
e
c
h
a
n
i
c
a
l

a
n
d

t
h
e
r
m
a
l

e
f
f
e
c
t
s

o
r

d
a
n
g
e
r
o
u
s

s
p
a
r
k
i
n
g

c
a
u
s
i
n
g

f
i
r
e

o
r

p
h
y
s
i
c
a
l

d
a
m
a
g
e


R
c

C
o
m
p
o
n
e
n
t

d
u
e

t
o

m
e
c
h
a
n
i
c
a
l

a
n
d

t
h
e
r
m
a
l

e
f
f
e
c
t
s

o
r

d
a
n
g
e
r
o
u
s

s
p
a
r
k
i
n
g

f
r
o
m

i
n
c
o
m
i
n
g

c
o
n
d
u
c
t
i
v
e

e
l
e
c
t
r
i
c
a
l

s
e
r
v
i
c
e

l
i
n
e
s

(
m
a
i
n
l
y

a
t

t
h
e

p
o
i
n
t
-
o
f
-
e
n
t
r
y

t
o

t
h
e

s
t
r
u
c
t
u
r
e
)

c
a
u
s
i
n
g

f
i
r
e

o
r

p
h
y
s
i
c
a
l

d
a
m
a
g
e


R
f

=

R
s

+

R
c

R
i
s
k

d
u
e

t
o

f
i
r
e

o
r

p
h
y
s
i
c
a
l

d
a
m
a
g
e

D
3

F
a
i
l
u
r
e

o
f

e
l
e
c
t
r
i
c
a
l

a
n
d

e
l
e
c
t
r
o
n
i
c

s
y
s
t
e
m
s

R
w

C
o
m
p
o
n
e
n
t

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

o
n

i
n
t
e
r
n
a
l

i
n
s
t
a
l
l
a
t
i
o
n
s

a
n
d

i
n
c
o
m
i
n
g

s
e
r
v
i
c
e
s

c
a
u
s
i
n
g

f
a
i
l
u
r
e

o
f

e
l
e
c
t
r
i
c
a
l

a
n
d

e
l
e
c
t
r
o
n
i
c

s
y
s
t
e
m
s

R
m

C
o
m
p
o
n
e
n
t

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

o
n

i
n
t
e
r
n
a
l

i
n
s
t
a
l
l
a
t
i
o
n
s

a
n
d

e
q
u
i
p
m
e
n
t

(
i
n
d
u
c
e
d

b
y

t
h
e

m
a
g
n
e
t
i
c

f
i
e
l
d

a
s
s
o
c
i
a
t
e
d

w
i
t
h

t
h
e

l
i
g
h
t
n
i
n
g

c
u
r
r
e
n
t
)

c
a
u
s
i
n
g

f
a
i
l
u
r
e

o
f

e
l
e
c
t
r
i
c
a
l

a
n
d

e
l
e
c
t
r
o
n
i
c

s
y
s
t
e
m
s

R
e

C
o
m
p
o
n
e
n
t

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

t
r
a
n
s
m
i
t
t
e
d

t
h
r
o
u
g
h

i
n
c
o
m
i
n
g

c
o
n
d
u
c
t
i
v
e

e
l
e
c
t
r
i
c
a
l

s
e
r
v
i
c
e

l
i
n
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

c
a
u
s
i
n
g

f
a
i
l
u
r
e

o
f

e
l
e
c
t
r
i
c
a
l

a
n
d

e
l
e
c
t
r
o
n
i
c

s
y
s
t
e
m
s

R
1

C
o
m
p
o
n
e
n
t

d
u
e

t
o

i
n
d
u
c
e
d

o
v
e
r
v
o
l
t
a
g
e
s

t
r
a
n
s
m
i
t
t
e
d

t
h
r
o
u
g
h

i
n
c
o
m
i
n
g

c
o
n
d
u
c
t
i
v
e

e
l
e
c
t
r
i
c
a
l

s
e
r
v
i
c
e

l
i
n
e
s

c
a
u
s
i
n
g

f
a
i
l
u
r
e

o
f

e
l
e
c
t
r
i
c
a
l

a
n
d

e
l
e
c
t
r
o
n
i
c

s
y
s
t
e
m
s

R
o

=

R
w

+

R
m

+

R
e

+

R
1

R
i
s
k

d
u
e

t
o

t
h
e

f
a
i
l
u
r
e

o
f

e
l
e
c
t
r
i
c
a
l

a
n
d

e
l
e
c
t
r
o
n
i
c

s
y
s
t
e
m
s

f
r
o
m

o
v
e
r
v
o
l
t
a
g
e
s


R
d

=

R
h

+

R
s

+

R
w

R
i
s
k

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
i

=

R
g

+

R
c

+

R
m

+

R
e

+

R
1

R
i
s
k

d
u
e

t
o

i
n
d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

(
i
n
c
l
u
d
i
n
g

d
i
r
e
c
t

a
n
d

i
n
d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

c
o
n
d
u
c
t
i
v
e

e
l
e
c
t
r
i
c
a
l

s
e
r
v
i
c
e

l
i
n
e
s
)

R

=

R
t

+

R
f

+

R
o

T
o
t
a
l

r
i
s
k

d
u
e

t
o


l
i
g
h
t
n
i
n
g

R

=

R
d

+

R
i

T
o
t
a
l

r
i
s
k

d
u
e

t
o

l
i
g
h
t
n
i
n
g

For DOD Internal Use ONLY
21 AS/NZS 1768:2007

COPYRIGHT
2.6 PROCEDURE FOR RISK ASSESSMENT AND MANAGEMENT
The procedure for risk assessment and the subsequent selection of protection is outlined in
flow chart form in Figure 2.2.
2.6.1 Procedure for risk assessment
The procedure for the assessment of the risk requires:
(a) Identification of the structure or facility to be protected.
This involves defining the extent of the facility or structure being assessed. In most
cases the structure or facility will be a stand-alone building. The structure may
encompass a building and its associated outbuildings or equipment supports.
Under certain conditions, a facility that is a part of a building may be considered as
the structure for risk assessment purposes. An example of this might be a
communications installation at the top of an office building. This segregation of a part
of a building is only valid under the following conditions:
(i) There is no risk of explosion in the remainder of the building.
(ii) Suitable fire barriers exist around the structure being considered (fire rating of
not less than 120 min).
(iii) Overvoltage (SPD) protection is provided on all conductive electrical service
lines at their point-of-entry to the structure being considered.
(b) Determination of all the relevant physical, environmental and service installation
factors applicable to the structure.
(c) Identification of all the types of loss relevant for the structure or facility.
For most structures, only L1 and L4 will need to be considered. L3 will apply to
museums, galleries, libraries and heritage listed buildings while L2 applies to
structures involved in the provision of public service utilities such as water, gas,
electricity and telecommunications.
(d) For each type of loss relevant to the structure, determine the relevant damage factors

x
and special hazard factors.
(e) For each type of loss relevant to the structure, determine the maximum tolerable risk,
R
a
.
(f) For each type of loss relevant to the structure, calculate the risk due to lightning by
(i) identifying the components R
x
that make up the risk (see Figure 2.1);
(ii) calculating the identified risk components R
x
; and
(iii) calculating the total risk due to lightning, R.
(g) Compare the total risk R with the tolerable value R
a
for each type of loss relevant to
the structure.
If R R
a
(for each type of loss relevant to the structure) lightning protection

is not
necessary.
If R >R
a
(for any type of loss relevant to the structure) the structure shall be equipped with
protection measures against lightning.
The selection of the most suitable protection measures shall be made by the designer
according to the contribution of each risk component to the total risk, and according to the
technical and economic aspects of the different protection measures available. Technical
considerations include addressing the highest risk components while economic
considerations involve minimizing the total cost to achieve a suitable level of protection.
For DOD Internal Use ONLY
AS/NZS 1768:2007 22
COPYRIGHT
It is appropriate to consider separately the risk R
d
due to direct lightning strikes and the risk

R
i
due to indirect lightning strikes.
2.6.2 Protection against direct lightning strikes if R
d
> R
a

When the risk due to direct lightning strikes is greater than the acceptable risk (R
d
> R
a
),
then the structure shall be protected against direct lightning strikes with an LPS designed
and installed in accordance with the recommendations given in Section 4.
In Section 4, four protection levels (I, II, III, IV) with corresponding interception
efficiencies (99%, 97%, 91%, 84%) and resulting LPS efficiencies, E (98%, 95%, 90%,
80%) are defined.
To determine the required protection level, the final calculation for the protected structure
may be repeated successively for the protection levels IV, III, II, I until the condition R
d

R
a
is fulfilled.
NOTE: A previous edition, AS 17681991, specified LPSs with protection equivalent to IEC
Level III (interception efficiency 91%)Rolling sphere with a = 45 m)
If an LPS of protection level I cannot fulfil this condition, consider surge protection on all
incoming conductive electrical service lines at the point-of-entry to the structure or other
specific protection measures according to the values of the risk components (refer to
detailed calculations and assumptions in Appendix E). These may include
(a) measures limiting step and touch voltages;
(b) measures limiting fire propagation;
(c) measures to mitigate the effects of lightning-induced overvoltages (e.g. additional,
coordinated surge protection or isolation transformers); and
(d) measures to reduce the incidence of dangerous discharges (e.g. bonding of structural
elements).
2.6.3 Protection against indirect lightning strikes if R
d
R
a
but R
i
> R
a

When R
d
R
a,
then the structure is protected against direct lightning strikes. However, if the
risk due to indirect strikes is greater than the acceptable risk (R
i
> R
a
)
,
then the structure
must be protected against the effects of indirect lightning strikes.
Possible protection measures include
(a) suitable application of SPDs on all external conductive electrical service lines at the
point-of-entry to the structure (primary or point-of-entry surge protection); and
(b) suitable application of SPDs on all internal equipment (secondary surge protection at
the equipment).
NOTE: Suitable application of surge protection requires correct installation, earthing and
coordination of appropriately rated SPDs.
To determine the required protection, the final calculation for the protected structure shall
be repeated with one or both of these protection measures in place until the condition R
i

R
a
is fulfilled.
If the application of these protection measures cannot fulfil this condition, specific
protection measures shall be provided according to the values of the risk components (refer
to detailed calculations and assumptions in Appendix A). These may include magnetic
shielding of the structure and/or of the equipment and/or of cable ways and/or by using
cable screening. It may also be appropriate to have extra zones of protection around
sensitive areas with an extra level of SPD protection at the boundary of that zone.
For DOD Internal Use ONLY
23 AS/NZS 1768:2007

COPYRIGHT
2.6.4 Final check if R
d
+ R
i
> R
a

When R
d
R
a
and R
i
R
a
it is still possible that the total risk R = R
d
+ R
i
> R
a.

In this case, the structure does not require any specific protection against direct lightning
strikes or against overvoltages due to nearby strikes or transmitted through the incoming
conductive electrical service lines.
However, since R

> R
a,
protection measures shall be taken to reduce one or more risk
components to reduce the risk to R R
a
. Critical parameters have to be identified to
determine the most efficient measure to reduce the risk R.
For each type of loss, there are a number of protection measures that, individually or in
combination, may make the condition R R
a
.
Those measures that make R R
a
for all the types of loss must be identified and adopted
with due consideration of the associated technical and economic issues.
2.7 RISK MANAGEMENT CALCULATION TOOL
A Microsoft

Excel spreadsheet file has been included as a risk management calculation


tool. This file (LIGHTNING RISK.XLS) is provided as an integral part of the Standard and
is designed to operate using Microsoft

Excel 97 (or later versions).


The spreadsheet implements the risk calculations detailed in Appendix A with the required
inputs and outputs presented on a single page for ease of use. The risk calculations
implemented represent a simplification of the approach outlined in initial work by IEC
Committee TC 81 with the number of variables and options requiring selection reduced to a
minimum based on assumptions for general conditions in Australia and New Zealand.
In addition, a simplified form of the equation for risk component R
s
(risk related to physical
destruction) has been used, and the classification descriptions for fire risks based on
structure type and content (p
s
) have been modified, in order to reduce the fire risk
sensitivity of the draft IEC model. These modifications have been made to give more
practical values based on experience in Australia and New Zealand.
2.7.1 General operation
When the file is opened using Microsoft

Excel, a front page spreadsheet is displayed. This


front page presents all of the inputs and final calculation outputs required in the risk
management process. Other work sheets showing the calculated values of all of the
individual risk components for each type of risk are also accessible if a more in depth
analysis is required.
On the front page, the required inputs are subdivided into various categories with input cells
highlighted with a border. The possible input options are explained in a comment box,
which is displayed when the cursor is positioned over the input cell.
For most input cells, the input option is selected from a pull-down menu of key words that
are defined in the associated comment box. Some inputs require numerical values (e.g.
structure dimensions), which should be entered in the usual way from the keyboard.
When all of the inputs have been entered, the output values in the Risk section represent
the calculated risk components and overall risk for the particular set of structure parameters
and conditions specified.
For DOD Internal Use ONLY
AS/NZS 1768:2007 24
COPYRIGHT
2.7.2 Using the calculation tool in the risk management procedure
The calculation tool can be used in the following way to implement the risk assessment and
management procedure outlined in Clause 2.6.
(a) Identify the structure and input the structure dimensions.
(b) Input the structure attributes relating to fire risk, screening effectiveness and internal
wiring.
(c) Determine the average annual lightning ground flash density (N
g
) for the structure
location from the appropriate Ground Flash Density map (Figure 2.3 or 2.4) and input
the value in the environment section.
NOTES:
1 Earlier editions of AS/NZS 1768 provided thunderday maps, refer Appendix B2.3.
2 An approximate relationship between ground flash density (N
g
) and thunderdays (T
d
) for
Australia is N
g
= 0.012 T
d
1.4
.
(d) Input the other environment attributes relating to surrounding feature height and
service density.
(e) Specify the details of the conductive electrical service lines associated with the
structure in the following way:
(i) Input the type of electricity supply service line and identify whether or not a
transformer is installed on this service line at the structure.
(ii) Input the number and type of other overhead or underground conductive
electrical service lines connected to the structure via divergent routes.
NOTES:
1 Different service lines that follow the same physical route from the nearest
distribution node to the structure should be considered as one service line
connection.
2 Typically a structure will have one electricity supply service connection (overhead
or underground) and one telecommunications service connection (overhead or
underground) that could be considered as being connected via divergent routes.
(f) Identify the loss types relevant to the structure and for each type input the damage
factors and special hazard factors as appropriate.
(g) Determine and input an appropriate value for the acceptable risk of loss of economic
value as it applies to the structure.
(h) Input details of any protection measures installed. The surge protection options
offered are for:
(i) Suitable application of SPDs on all external conductive electrical service lines
at the point-of-entry to the structure (primary or point-of-entry surge
protection).
(ii) Suitable application of SPDs on all electrical equipment inside the structure
(secondary surge protection at the equipment).
NOTE: Suitable application of surge protection requires correct installation, earthing and
coordination of appropriately rated SPDs.
For each type of loss relevant to the structure, compare the acceptable risk with the total
risk calculated. Review the risk components and follow the Risk Management procedure
detailed in Clause 2.6 and Figure 2.2.
Use the spreadsheet to recalculate the risk components and total risk figures for any
protection measures proposed. Successive calculations can be performed to observe the
effects of various protection measures.
A number of completed spreadsheet examples are provided for information in Appendix A.
For DOD Internal Use ONLY
25 AS/NZS 1768:2007

COPYRIGHT

* Refer to Section 4.
NOTE: A previous edition, AS 17681991, specified an LPS with protection equivalent to Level IIIRolling
sphere with a=45 m.
FIGURE 2.2 RISK MANAGEMENT PROCEDURE FOR SELECTION OF LIGHTNING
PROTECTION MEASURES
For DOD Internal Use ONLY


COPYRIGHT
26
AS/NZS 1768:2007

N
O
T
E
:

T
h
e

A
u
s
t
r
a
l
i
a
n

G
r
o
u
n
d

F
l
a
s
h

D
e
n
s
i
t
y

m
a
p

h
a
s

b
e
e
n

c
o
m
p
i
l
e
d

a
n
d

k
i
n
d
l
y

s
u
p
p
l
i
e
d

b
y

t
h
e

A
u
s
t
r
a
l
i
a
n

B
u
r
e
a
u

o
f

M
e
t
e
o
r
o
l
o
g
y

a
n
d

t
h
e

U
n
i
v
e
r
s
i
t
y

o
f

Q
u
e
e
n
s
l
a
n
d
.

F
I
G
U
R
E


2
.
3



A
V
E
R
A
G
E

A
N
N
U
A
L

L
I
G
H
T
N
I
N
G

G
R
O
U
N
D

F
L
A
S
H

D
E
N
S
I
T
Y

M
A
P

O
F

A
U
S
T
R
A
L
I
A

For DOD Internal Use ONLY
27 AS/NZS 1768:2007

COPYRIGHT

NOTE: This figure has been derived from ground flash density data obtained from the Lightning Detection
Network of New Zealand for the period January 1, 2001 through February 9, 2006. Data supplied by
Transpower New Zealand Ltd and the Meteorological Service of New Zealand Ltd (MetService).
FIGURE 2.4 AVERAGE ANNUAL LIGHTNING GROUND FLASH DENSITY MAP
OF NEW ZEALAND
For DOD Internal Use ONLY
AS/NZS 1768:2007 28
COPYRIGHT
S E C T I O N 3 P R E C A U T I O N S F O R P E R S O N A L
S A F E T Y
3.1 SCOPE OF SECTION
This Section provides guidance for personal safety during thunderstorms.
Measures for the protection of persons, which should be incorporated in LPSs for buildings
and structures, are outlined in other sections.
For shelters designed for the protection of persons during storm activity, reference should
be made to Clause 6.9.1.
3.2 NEED FOR PERSONAL PROTECTION
A hazard to persons exists during a thunderstorm. Each year a number of persons are struck
by lightning, particularly when outdoors in open space such as an exposed location on a
golf course, or when out on the water. Between six and ten people are killed by lightning in
Australia each year. This is equivalent to a probability of about 5 10
7
per year for an
individual being killed by lightning in Australia.
Lightning strikes to a person, or close by, may cause death or serious injury. A person
touching or close to an object struck by lightning may be affected by a side-flash, or receive
a shock due to step, touch or transferred potentials. There is a significant risk of side-flash
for people in small, public structures such as picnic shelters, particularly those with
unearthed metallic roofs. In built-up areas protection is frequently provided by nearby
buildings, electricity supply service lines or street lighting poles.
Persons within a substantial structure are normally protected from direct strikes, but may be
exposed to a hazard from conductive electrical services entering the structure or from
conductive objects within the structure that may attain different potentials.
The first recorded electrical accident involving the use of a telephone occurred in 1860
and was caused by lightning being conducted through the telephone system. Telephone
related injuries include acoustic and/or electric shock. About 10% of injuries are severe. No
telephone related deaths have been reported in Australia. This is probably because of
warnings not to use the telephone, except in an emergency, during a lightning storm and the
use of SPDs on telephone installations in lightning prone areas. Around 80% of incidents
involve a lightning strike to or close to a building or a strike to the electricity supply service
line all of which result in a rise of the local earth potential rather than surges on the
telecommunications service line. This rise in local earth potential can result in a breakdown
between the person and the telephone, (which is connected to a nominal remote earth via
the telecommunications service line).
In some workplaces employees who work within larger buildings may be unaware of the
changing outside weather conditions, and may not be aware that it may be unsafe to use
telephone systems. Where modern fixed line telephonist headsets are used, this increases
the risk of human injury through external transients being conducted through to those
wearing the headsets.
When moderate to loud thunder is heard, persons out of doors should avoid exposed
locations and should seek adequate shelter. Persons indoors should avoid using the
telephone and contacting metallic structures. These warnings apply particularly if thunder
follows within 15 s of a lightning flash (corresponding to a distance of less than 5 km).
For DOD Internal Use ONLY
29 AS/NZS 1768:2007

COPYRIGHT
3.3 PERSONAL CONDUCT
3.3.1 General
The threat to personal safety is greatest if a person is out of doors when the thunderstorm is
local. In the absence of specific information from weather radar, a lightning location system
or a specialized lightning warning device, the 30/30 safety guideline (Paragraph G2, Ref.
1) should be used. An approaching thunderstorm is treated as local when the time interval
between seeing a lightning flash and hearing the thunder is less than 30 s and then the
appropriate safety measures described in Clause 3.3.2 should be implemented. A receding
local thunderstorm is no longer a threat when more than 30 min have elapsed after the last
thunder is heard.
3.3.2 Outdoors
When outdoors, some of the measures for reducing the risk of injury that may be caused by
lightning strikes to ground during a local thunderstorm are as follows:
(a) Seek shelter in a substantial building with at least normal headroom or within a
totally enclosed, metal-bodied vehicle such as car or truck with metallic roof. If in a
car, close the windows and avoid contact with metallic parts and remove any hands-
free mobile telephone attachments from the body. Avoid driving the car as a strike to
the car may blow out the tyres. Do not stay in open vehicles such as tractors, beach
buggies, or any other type of open or enclosed vehicle without a metallic roof.
Conventional fabric tents offer no protection; small sheds offer uncertain protection.
(b) Do not ride or sit on horses, bicycles or motorcycles, or otherwise elevate the body
above the surroundings.
(c) Do not shelter under trees, particularly an isolated tree. If surrounded by trees, seek a
position outside the foliage and crouch, keeping the feet together.
(d) Do not shelter in small sheds, pagodas, walkways etc. with low unearthed metallic
roofs supported on wooden or other electrically insulating materials.
(e) Do not touch or stand close to any metallic structures, including wire fences and
clothes lines. Do not stand on or under bridges or other elevated structures. Do not
carry metallic objects such as umbrellas or golf clubs and remove metallic chains and
other jewellery, particularly from the head and upper parts of the body.
(f) If on open field or on the beach and remote from any shelters, keep as low and as
small a profile as possible, i.e. crouch keeping the feet together and do not touch any
objects or people near you. A dry ditch, valley or any depression in the ground is
safer than an elevated or flat terrain. Do not lie on the ground as this could cause
dangerous voltage to develop across the body by earth currents generated by a nearby
strike. Footwear or a layer of non-absorbing, insulating material, such as plastic
sheets, can offer some protection against earth voltages.
(g) Do not swim or wade in the sea, lake, river, pool or any other body of water.
Exit the water and move to a safe place.
(h) If on a boat deck, keep a low profile and avoid contacts with or being close to masts,
rails, stay wires or any other metallic objects. Avoid unnecessary contacts with
communication or navigation equipment. Do not enter the water, and in general avoid
contact with water. Additional protection may be gained by anchoring under
relatively high objects such as jetties and bridges, provided that direct contact is not
made with them. Isolated buoys and pylons should be avoided.
For DOD Internal Use ONLY
AS/NZS 1768:2007 30
COPYRIGHT
In addition, the following checks should be made when planning outdoor activities:
(i) Check weather reports for likely thunderstorms.
(ii) When engaged in outdoor activities, monitor the surroundings for indications of the
onset of thunderstorms. These checks are particularly important when planning and
undertaking activities involving groups and large numbers of people.
3.3.3 Indoor and outdoor swimming pools
Certain locations are extremely hazardous during thunderstorms and should be avoided if at
all possible. Statistics show that more than 10% of lightning-related injuries and deaths are
water related (e.g. fishing, boating and swimming). Swimming pool facilities are connected
to a large surface area via underground water pipes, gas lines, electric and telephone wiring,
etc. Hence, lightning strikes to the ground anywhere on this metallic network may cause
shocks elsewhere. Indoor and outdoor pools are treated the same with regard to lightning
dangers.
The following swimming pool safety procedures are recommended:
(a) A person should be designated as the pools weather safety lookout. That person
should keep an eye on the weather and use the appropriate means to obtain localized,
advanced weather information.
(b) Identify in advance safe/not safe places
(i) Safedry areas inside large permanent buildings.
(ii) Not safenear electrical conductors, electrical equipment, metal objects
(lifeguard stands, ladders, diving board stanchions) and water, including
showers.
(c) When thunder and/or lightning are first noticed, use the 30/30 method described in
Clause 3.3.1. The pool should be evacuated in a time interval of less than 30 s and
people should be directed to a safe shelter nearby.
3.3.4 Indoors
When indoors, some of the measures for reducing the risk of injury that may be caused by
lightning strikes to ground during a local thunderstorm are as follows:
(a) Avoid unnecessary use of telephones particularly in suburban and rural dwellings
during local thunderstorms. If unavoidable, keep it brief and try not to touch electrical
appliances, personal computers, metal pipes, stoves, sinks, and any other metallic
objects at the same time. Mobile and cordless telephones are safe to use indoors.
Where headsets are used for a large percentage of the time, or where operators may
be unaware of local lightning storms, the risk of injury from lightning can be
dramatically reduced by the use of wireless headsets.
(b) Do not take a bath or a shower and do not wash hands or dishes. Do not use personal
computers and other electronic and electrical equipment, and avoid contacts with
sinks, stoves, refrigerators, metallic pipes and other large metallic objects in the
house.
(c) Disconnect television sets, personal computers, video recorders and other electronic
and electrical appliances from antennas, conductive telecommunication connections
and electricity supply outlets to avoid damage to them. This should be done before
the storm is local to minimize risk of personal injury.
NOTES:
1 Switching off an appliance does not disconnect neutral and earth wiring.
2 Switching off the electricity supply at the switchboard may also reduce the chances of
damage to the electrical wiring and to permanently wired electrical appliances.
For DOD Internal Use ONLY
31 AS/NZS 1768:2007

COPYRIGHT
3.4 EFFECT ON PERSONS AND TREATMENT FOR INJURY BY LIGHTNING
The severity of the injuries inflicted on a person by a lightning strike will depend upon the
intensity of the strike and for any given strike, on the fraction of the current that flows over
the skin outside the body and the fraction that flows through the body, and its path. The
worst situation would arise when a person is struck on the head, in which case the current
through the body could cause fatal injuries to the brain, the heart and the lungs. A less
dangerous situation is where the person is subjected to step or touch potentials, and only a
small fraction of the total current passes through the body, although the pathway taken by
this fraction is still important.
The effects of lightning include burns to the skin, which are usually superficial, damage to
various bodily organs and systems, unconsciousness and, most dangerously, cessation of
breathing and cessation of heart beat. Independently of these electrically-related effects,
temporary or permanent hearing impairment may be experienced as a consequence of the
extremely high sound pressure levels associated with a nearby lightning strike.
In the first aid treatment of a patient injured by lightning, it is essential that breathing be
restored by artificial respiration and blood circulation be restored by external cardiac
massage, if appropriate. These procedures should be continued until breathing and heart
beat are restored, or it can be medically confirmed that the patient is dead. It should also be
noted that the usual neurological criteria for death may be unreliable in this situation. There
is no danger in touching a person who has been struck by lightning.
Lightning strike victims are sometimes thrown violently against an object, or are hit by
flying fragments of a shattered tree, so first aid treatment may have to include treatment for
traumatic injury.
Subsequent treatment of a lightning strike patient is a specialized area with important
differences from the treatment of injuries inflicted by electric power current. For example,
the nature of the burns and the extent of damage to underlying muscle tissue tend to be
severe with electric power current, but mild with lightning current. Neurological and
cardiac injuries also are different, and follow different courses.
NOTE: For a more comprehensive treatment of the subject covered by this Clausesee
Paragraph G2, Ref. 2.
For DOD Internal Use ONLY
AS/NZS 1768:2007 32
COPYRIGHT
S E C T I O N 4 P R O T E C T I O N O F S T R U C T U R E S
4.1 SCOPE OF SECTION
This Section sets out recommendations for installation practices and for the selection of
equipment to prevent or to minimize damage or injury that may be caused by a lightning
discharge. The recommendations apply generally to the protection of structures using LPSs
comprising air terminals, downconductors, equipotential bonding and earth terminations.
If, after completing the LPS risk assessment, it is evident that surge protection is required to
protect internal systems within the building and services at entry to the buildings then the
requirements of Section 5 shall be applied.
4.2 PROTECTION LEVEL
Four protection levels (PL) I, II, III, IV are used to define the efficiency with which the
LPS is designed to protect the structure against physical damage and life hazard. The
protection level efficiency () has two componentsinterception protection efficiency (
I
),
which characterizes the effectiveness of the air terminals, and sizing protection efficiency
(
S
), which characterizes the effectiveness of the downconductors and the earth
terminations. Each is determined independentlyby the minimum lightning current (I, kA)
that will be intercepted, and by the maximum sizes of lightning current, charge (Q, C) and
current steepness (di/dt, kA/s) that will be discharged safely. The four protection levels
are based on IEC TC 81 documents and are defined in Table 4.1.
TABLE 4.1
PROTECTION LEVELS
Protection level Interception efficiency Sizing efficiency LPS efficiency
PL
I

S

I
II
III
IV
0.99
0.97
0.91
0.84
0.99
0.98
0.97
0.97
0.98
0.95
0.90
0.80
4.3 LPS DESIGN RULES
4.3.1 General
The following Clauses provide the details of the recommendations for the design and
installation of all the LPS elements. This Clause lists the overriding design rules that shall
normally be observed to provide minimum requirements for air terminals,
downconductors and earth terminations. Observance of these rules will ensure that
appropriate interception protection is provided by air terminals for the parts of structures
most likely to be damaged by direct lightning strikes, that the conduction of the lightning
current by the downconductors is adequate and that it is dissipated into the earth by the
earth terminations.
These rules are the first step in the process of the design of a complete LPS. The remaining
steps are referred to in the design rules and their application is referred to in subsequent
sections.
NOTE: These design rules may not apply to some small structures.
For DOD Internal Use ONLY
33 AS/NZS 1768:2007

COPYRIGHT
Field data of damage caused by lightning flashes terminating on structures (See
Paragraph G2, Refs. 3 and 4) identify the parts that are vulnerable to strikes. The most
vulnerable, associated with over 90% of observed lightning damage, are nearly always
located on the upper parts of structures, such as
(a) pointed apex roofs, spires and protrusions;
(b) gable roof ridge ends; and
(c) outer roof corners.
Other areas of vulnerability, in decreasing order, are
(d) the exposed edges of horizontal roofs, and the slanting and horizontal edge of gable
roofs (<10%);
(e) lower horizontal edges and vertical edges on outer-sides just below corners (<5%);
(f) flat surfaces near points and corners (<3%); and
(g) intruding surfaces and other surfaces, particularly flat surfaces (<1%).
As discussed in later Sections, the vulnerability is caused mainly by the electric field
intensification associated with exposed points and corners on the upper surfaces of
structures. It is obvious that air terminals must be installed to provide interception for the
most vulnerable parts.
As well as providing conductive paths for the lightning current from the air terminals to the
earth terminals, the downconductors should assist in preventing side-flashes to nearby metal
elements (including reinforcing bars). This is best done by locating downconductors
immediately below the air terminals used to protect the most vulnerable parts.
4.3.2 Rules for air terminals
(a) First, provide air terminals to protect the most vulnerable parts (points and corners);
second, use the rolling sphere method (RSM) to check if the less vulnerable parts
(edges) are protected and, if not, add more terminals to protect them; third, also check
if the least vulnerable parts (such as flat surfaces) are protected and, if not, add more
terminals.
(b) Air terminals shall be placed on or close to the most vulnerable parts; if a strip
conductor is used, it shall be directly on the part it is to protect; if a vertical rod is
used, its length shall be not less than 500 mm, and it shall preferably be mounted on
the part it is to protect or within 1 m or 1/2 its length, whichever is the smaller (this
rule is supported by recent research see Paragraph G2, Ref. 5). The maximum
allowable length of a rod terminal is 6 m.
(c) If the structure has horizontal or gently sloping upper parts that are essentially
cylindrical or oval in shape, then the edges are the vulnerable parts and shall be
protected by air terminals; if a strip conductor is used, it shall be run along the
edge(s); if vertical rods are used, there shall be a minimum of two evenly spaced
terminals.
(d) Non-conventional LPS using air terminals that claim enhanced performance are
outside the scope of this Standard. To comply with this Standard and irrespective of
claimed performance, air terminals shall be placed in accordance with the relevant
clauses of this Section.
4.3.3 Rules for downconductors
(a) Main conductors shall interconnect all air terminals and shall form one or more paths
to earth via downconductors, such that the spacing between the downconductors does
not exceed 20 m.
For DOD Internal Use ONLY
AS/NZS 1768:2007 34
COPYRIGHT
(b) A downconductor shall be connected directly below an air terminal used to protect the
most vulnerable parts; if the air terminal is on an exposed roof corner, its
downconductor will also act as a continuation of the air terminal to protect the
vertical edge below it, as is required for tall structures.
4.3.4 Rules for earth terminations
(a) Low earth resistance is desirable and all practical measures should be taken to
achieve 10 or less for the whole interconnected LPS earth termination network.
There shall be equipotential bonding at ground level for all metallic surfaces.
If the risk assessment indicates a need for SPDs, these shall be installed and bonded
in accordance with Section 5.
(b) There shall be one earth termination per downconductor.
4.4 ZONES OF PROTECTION FOR LIGHTING INTERCEPTION
4.4.1 Basis of recommendations
The selected interception protection efficiency against direct lightning strikes is achieved
by installing an LPS in such a way that its air terminals establish zones of protection
enclosing the whole structure. For the calculation of these zones of protection, the RSM,
with a modification for large flat surfaces, is used.
The RSM generally ensures that for lightning striking distances determined by the radius of
the rolling sphere, the shortest distance between a lightning leader tip and any part of the
structure is an air terminal.
This method of analysis is suitable for conventional lightning terminals, which may be
vertical rods, horizontal wires or strip conductors, railings, metal sheets, fascias and so on.
4.4.2 Rolling sphere method (with a modification for large flat surfaces)
In the rolling sphere technique of determining zones of protection, a sphere of specified
radius (a) is theoretically brought up to and rolled over the total structure. All sections of
the structure that the sphere touches are considered to be exposed to direct lightning strokes
and would need to be protected by air terminals. In general, air terminals need to be
installed so that the sphere only touches their interception surfaces. This is illustrated in
Figure 4.1, which shows that the top corner/edge of the structure requires protection by an
air terminal but the sides and lower section do not. The values of the rolling sphere radius
(a) for the four protection levels (PL) I, II, III, IV are given in Table 4.2 together with the
corresponding minimum lightning current (I
min
) that will be intercepted.
TABLE 4.2
ROLLING SPHERE RADIUS FOR EACH PROTECTION LEVEL
Protection level Sphere radius Interception current


PL a, m (a
i
)* I
min
, kA
I
II
III
IV
20 (60)
30 (60)
45 (90)
60 (120)
2.9
5.4
10.1
15.7
* The values in brackets are for increased radius (a
i
), see below.
Values from IEC documents, which use distributions of lightning current parameters that
differ slightly from those in Table B1 of Appendix B.
For DOD Internal Use ONLY
35 AS/NZS 1768:2007

COPYRIGHT

FIGURE 4.1 ZONE OF PROTECTION ON A STRUCTURE ESTABLISHED BY
A ROLLING SPHERE OF RADIUS a
It is common to consider that PL III using a sphere of radius a, 45 m provides standard
protection (as in AS/NZS 1768(Int):2003 and NFPA 7802004). PL I and II with a, 20 and
30 m provide higher degrees of protection and should be used if required by the risk
management calculations of Section 2 and Appendix A. Conversely, PL IV with a, 60 m
provides a lower degree of protection. For PL III, the protection ensures that, for striking
distances of 45 m or more, the shortest distance to the structure is to an air terminal. From
Tables 4.1 and 4.2, such striking distances correspond from empirical observations to peak
currents of 10 kA or more, and an interception efficiency of 91%, there being only of the
order of 9% of strikes having a lower current. In the RSM, lightning is considered most
likely to follow the path of shortest distance. This path will have the highest average
electric field produced by the potential difference between the tip of the lightning leader
(likely to be at more than 10 MV) and the structure (approximately at earth potential).
The RSM produces a conservative design since it makes no allowance for field
intensification at the edges and corners of structures. Using a constant radius for the rolling
sphere the sides and tops of structures are assigned an equal probability of lightning strike
to the corners and edges.
In particular, the rolling sphere method is unduly conservative for large flat surfaces, such
as on the roof of a structure and on the sides of tall structures, both of which are unlikely to
be struck by lightning. Further advice on the protection of roofs is given in Clause 4.11.2.
A simple modification to the RSM can overcome the former problem (See Paragraph G2,
Ref. 6). The basis of the modification is that the application of the RSM will be a two-step
process in which
(a) the air terminal network is first selected and positioned to provide interception
protection for points, corners and edge surfaces using a rolling sphere of radius (a)
selected from Table 4.2; and
(b) the selected and positioned air terminal network is then used to determine if
protection is provided to all plane (flat) surfaces using a rolling sphere with the
corresponding increased radius (a
i
) in Table 4.2; if not, more air terminals are added
to protect the exposed plane surface(s) still using the rolling sphere of radius (a
i
).
For the purposes of this modification to the RSM, a plane surface is defined as any large
flat surface that has no projection from it exceeding 300 mm. Any flat surface is considered
to be large if, after step (b), it is apparent that more air terminals are required to protect it.
For DOD Internal Use ONLY
AS/NZS 1768:2007 36
COPYRIGHT
According to the RSM, an air terminal of height h above the edge of a flat roof or
horizontal plane is considered to protect the edge of that roof or plane up to a horizontal
distance r from a vertical rod or a horizontal conductor, where r is given by:
( )
2
2 h h a r =
. . . 4.4.2(1)
in which a is the sphere radius from Table 4.2 and r, a and h are in metres.
For points on the flat surface, according to the modification to the RSM, the protection
extends to a distance r
i
from the air terminal, given by:
( )
2
i i
2 h h a r =
. . . 4.4.2(2)
in which a
i
is the increased radius from Table 4.2. For all but small horizontal surfaces, an
array of air terminals is required at spacing distances that ensure that no parts of the surface
are unprotected. If the array is a square grid, the spacings must not exceed d
vr
for vertical
rods and d
hc
for horizontal conductors, given by:
2
i vr
r d and
i hc
2 r d
. . . 4.4.2(3)
Some numerical values are given to illustrate the magnitudes; for protection level III, a is
45 m and a
i
is 90 m, then when the air terminal of height h is 1 m, r is 9.4 m, r
i
is 13.4 m,
d
vr
is 19 m and d
hc
is 26.8 m. Table 4.3 provides information on the spacings of air
terminals required to protect roofs at each of protection levels I to IV for the three most
common heights of air terminals used in Australia and New Zealand.
Figures 4.2 and 4.3 illustrate the application of the RSM (with the modification for flat
surfaces) to a rectangular structure using either vertical rods or horizontal conductors.
Figure 4.2 (Step (a)) deals with the interception protection for the vulnerable corners and
horizontal edges and Figure 4.3 (Step (b)) shows how Equations 4.4.2(2) and 4.4.2(3) are
used for the flat roof.
For more complex structures, the technique of rolling the sphere must be used directly to
determine the required configuration of air terminals needed to achieve the interception
protection efficiency that has been selected.
For DOD Internal Use ONLY
37 AS/NZS 1768:2007

COPYRIGHT

Step (a): Protect corner and edge surfaces
Either,
Place vertical rods at 4 corners, try h = 1 m (shown).
Using Equation 4.4.2(1) r = ah h
2
(2 ) = 9.4 m
Max spacing along edge = 2 9.4 = 18.6 m
Therefore, 3 additional rods are needed along each edge
Check with rolling sphere of radius 45 m, okay (shown)
or Place metal railings h = 1 m along the 4 edges (not shown)
This protects all 4 corners and 4 edges
FIGURE 4.2 APPLICATION OF STEP (a) OF RSM (WITH THE MODIFICATION FOR
FLAT SURFACES) FOR PROTECTION LEVEL III FOR A RECTANGULAR STRUCTURE
OF DIMENSIONS 70 X 50 X 20 m USING EITHER VERTICAL ROD OR RAISED
HORIZONTAL CONDUCTOR AIR TERMINALS
For DOD Internal Use ONLY
AS/NZS 1768:2007 38
COPYRIGHT

Step (b): Using increased sphere radius ai to determine if more terminals are required
14 1 m rods plus 4 1.25 m rods
Using Equation 4.4.2(2),
ri = a h h
2
i
(2 ) = 15 m
The building is protected
FIGURE 4.3(a) APPLICATION OF STEP (b) OF RSM (WITH THE MODIFICATION FOR
FLAT SURFACES) FOR PROTECTION LEVEL III FOR A RECTANGULAR STRUCTURE
OF DIMENSIONS 70 50 20 m USING 4 1.25 m VERTICAL RODS ON THE INTERIOR
PLANE SURFACE
For DOD Internal Use ONLY
39 AS/NZS 1768:2007

COPYRIGHT

Step (b): Using increased sphere radius ai to determine if more terminals are required
14 1 m rods plus 2 1.6 m rods
Using Equation 4.4.2(2),
ri = a h h
2
i
(2 ) = 16.9 m
The building is protected
FIGURE 4.3(b) AN ALTERNATIVE APPLICATION OF STEP (b) OF RSM (WITH THE
MODIFICATION FOR FLAT SURFACES) FOR PROTECTION LEVEL III FOR A
RECTANGULAR STRUCTURE OF DIMENSIONS 70 50 20 m USING 2 1.6 m
VERTICAL RODS ON THE INTERIOR PLANE SURFACE
For DOD Internal Use ONLY
AS/NZS 1768:2007 40
COPYRIGHT


Step (b): Using increased sphere radius ai to determine if more terminals are required
Either,
1 (or more) additional raised horizontal conductors h = 1 m to protect the flat roof
Using Equation 4.2.2(2), ri = a h h
2
i
(2 ) = 13.4 m
Using Equation 4.2.2(3), dhc 2ri = 26.8 m, but is < the 70 m between the
edge railings, and so the 4 railings along the edges do not protect all the roof
Add 2 additional raised horizontal conductors h = 1 m and all the roof is protected
(shown)
So need 4 1 m high railings plus 2 additional 1 m high raised horizontal conductors
or The 2 additional raised horizontal conductors could be replaced by 2 1.5 m vertical
rods (r = 16.4 m) as shown
FIGURE 4.3(c) AN ALTERNATIVE APPLICATION OF RSM (WITH MODIFICATION FOR
FLAT SURFACES) FOR PROTECTION LEVEL III FOR A RECTANGULAR STRUCTURE
OF DIMENSIONS 70 50 20 m USING RAISED HORIZONTAL CONDUCTORS ONLY
OR RAISED HORIZONTAL CONDUCTORS ON BUILDING CORNERS AND EDGES AND
VERTICAL RODS ON THE INTERIOR PLANE SURFACES

For DOD Internal Use ONLY


COPYRIGHT
41
AS/NZS 1768:2007
T
A
B
L
E



4
.
3

H
E
I
G
H
T

A
N
D

S
P
A
C
I
N
G

O
F

A
I
R

T
E
R
M
I
N
A
L
S

T
O

P
R
O
T
E
C
T

R
O
O
F
S

d
i
m
e
n
s
i
o
n
s

i
n

m
e
t
r
e
s

E
d
g
e
s

a
n
d

c
o
r
n
e
r
s

o
f

r
o
o
f

p
r
o
t
e
c
t
e
d

b
y

v
e
r
t
i
c
a
l

r
o
d

o
r

r
a
i
s
e
d

h
o
r
i
z
o
n
t
a
l

c
o
n
d
u
c
t
o
r

M
i
d
d
l
e

o
f

f
l
a
t

r
o
o
f

H
o
r
i
z
o
n
t
a
l

d
i
s
t
a
n
c
e

f
o
r

w
h
i
c
h

r
o
o
f

i
s

p
r
o
t
e
c
t
e
d

M
a
x
i
m
u
m

s
p
a
c
i
n
g

f
o
r

a
r
r
a
y

H
o
r
i
z
o
n
t
a
l

d
i
s
t
a
n
c
e

f
o
r

w
h
i
c
h

r
o
o
f

i
s

p
r
o
t
e
c
t
e
d

M
a
x
i
m
u
m

s
p
a
c
i
n
g

f
o
r

a
n

a
r
r
a
y

o
f

v
e
r
t
i
c
a
l

r
o
d
s

M
a
x
i
m
u
m

s
p
a
c
i
n
g

f
o
r

r
a
i
s
e
d

h
o
r
i
z
o
n
t
a
l

c
o
n
d
u
c
t
o
r
2
)

P
r
o
t
e
c
t
i
o
n

l
e
v
e
l

H
e
i
g
h
t

o
f

a
i
r

t
e
r
m
i
n
a
l

1
)


h

r

(
(
)
2
2
h
h
a

=
)

d

(
=

r
.
2
)

r
i

(
(
)
2
i
2
h
h
a

=
)

d
v
r

(
2
i
r
=
)

d
h
c

(
=

r
i
.
2
)

I

(
a

=

2
0

m
,

a
i

=

6
0

m
)

0
.
5

1

2

4
.
4

6
.
2

8
.
7

8
.
9

1
2
.
5

1
7
.
4

7
.
7

1
0
.
9

1
5
.
4

1
0
.
9

1
5
.
4

2
1
.
7

1
5
.
5

2
1
.
8

3
0
.
7

I
I

(
a

=

3
0

m
,

a
i

=

6
0

m
)

0
.
5

1

2

5
.
5

7
.
7

1
0
.
8

1
0
.
9

1
5
.
4

2
1
.
5

7
.
7

1
0
.
9

1
5
.
4

1
0
.
9

1
5
.
4

2
1
.
7

1
5
.
5

2
1
.
8

3
0
.
7

I
I
I

(
a

=

4
5

m
,

a
i

=

9
0

m
)

0
.
5

1

2

6
.
7

9
.
4

1
3
.
3

1
3
.
4

1
8
.
9

2
6
.
5

9
.
5

1
3
.
4

1
8
.
9

1
3
.
4

1
8
.
9

2
6
.
7

1
8
.
9

2
6
.
8

3
7
.
7

I
V

(
a

=

6
0

m
,

a
i

=

1
2
0

m
)

0
.
5

1

2

7
.
7

1
0
.
9

1
5
.
4

1
5
.
5

2
1
.
8

3
0
.
7

1
0
.
9

1
5
.
5

2
1
.
8

1
5
.
5

2
1
.
9

3
0
.
9

2
1
.
9

3
0
.
9

4
3
.
6

1
)

F
o
r

o
t
h
e
r

a
i
r

t
e
r
m
i
n
a
l

h
e
i
g
h
t
s

(
h
)

u
s
e

e
q
u
a
t
i
o
n
s

4
.
4
.
2
(
1
)
,

(
2
)

a
n
d

(
3
)
.

2
)

F
o
r

f
u
r
t
h
e
r

i
n
f
o
r
m
a
t
i
o
n

o
n

r
a
i
s
e
d

h
o
r
i
z
o
n
t
a
l

c
o
n
d
u
c
t
o
r
s

p
l
a
c
e
d

o
n

t
h
e

r
o
o
f
,

s
e
e

C
l
a
u
s
e

4
.
1
1
.
2
.

For DOD Internal Use ONLY
AS/NZS 1768:2007 42
COPYRIGHT
4.5 METHODS OF PROTECTION
4.5.1 Structural steel-framed buildings
Buildings with structural steel framing may be protected by the installation of metal air
terminals at the high parts of the building, the air terminals being connected to the steel
framing and the framing earthed in the vicinity of the foundation. A typical LPS is shown in
Figure 4.4 (see also Clause 4.16.1).
4.5.2 Buildings without structural steel frames
4.5.2.1 General
The required conditions of protection for non-metallic buildings are generally met by
placing metal air terminals on the uppermost parts of the building or its projections, with
conductors connecting the air terminals to each other and to earth. By this means a
relatively small amount of metal properly positioned and distributed can afford a
satisfactory degree of protection and, if desired, the material may be placed so as to give
minimum interference to the appearance of the building. A typical LPS is shown in
Figure 4.5. Additional methods utilizing the individual characteristics of particular types of
building construction are given in Clauses 4.5.2.2 to 4.5.2.4, and in Figure 4.4.
4.5.2.2 Structures with continuous metal
Structures containing continuous metal, e.g. metal within a roof, wall, floor or covering
may, if the amount and arrangement of the metal is adequate in terms of the
recommendations of Clauses 4.12 to 4.16, utilize such metal as part of the LPS.
4.5.2.3 Metal-roofed buildings
Lightning tends to strike the ridges, corners, parapets and edges of building roofs.
Generally these attachment points coincide with the metal roof sheeting, capping or
guttering being fixed by multiple screws, rivets or clips directly to the supporting steel
purlins, beams and trusses below.
While a direct strike can puncture a hole in thin metal sheeting the instances of such
damage are rare (refer to Paragraph B3, Appendix B for more information). For many
buildings that are roofed, or roofed and clad, with metal, it may be possible to dispense with
some or all air terminals provided the supporting roof steelwork is directly connected to a
downconductor network or the earthing system. Any decision on dispensing with use of air
terminals should consider the consequences of possible damage to the integrity of the roof
and the contents within the building.
4.5.2.4 Reinforced concrete buildings
The following recommendations apply to the use of steel reinforcement in reinforced
concrete buildings as part of the LPS (see also Paragraph B5.5.2, Appendix B):
(a) General As far as possible, the steel reinforcement should be made electrically
continuous in all concrete elements having a structural purpose, e.g. columns, beams
and also in non-structural concrete elements, e.g. concrete wall panels, where the
element, or a part of it, if dislodged, could endanger persons below.
Where the steel reinforcement is used as the downconductor system, an effective
electrical connection should be made from the air terminal network to the steel
reinforcement at the top of the building. Such connections should be made, by means
such as welding or clamping to a minimum of four vertical and/or horizontal bars, to
ensure a multiplicity of conductive paths for the discharge of lightning current.
NOTE: Steel reinforcement that is overlapped and tied by means of wire is not considered to
provide an effective electrical connection for the purpose of air termination connection,
however, such joints are acceptable elsewhere as part of the downconductor system where
current sharing is assured.
For DOD Internal Use ONLY
43 AS/NZS 1768:2007

COPYRIGHT
Modern reinforced concrete structures frequently involve several structural
techniques including in situ reinforced concrete, prestressed reinforced concrete and
precast concrete; recommendations for these are listed in Items (b), (c) and (d).
(b) In situ reinforced concrete Reinforcing steel rods are tied together by steel tie wire at
splice points where reinforcing steel bars are overlapped for mechanical strength.
Despite the fortuitous nature of the metallic connection, the very large number of rods
and crossing points assures a subdivision of the total lightning current into a
multiplicity of parallel discharge paths. Experience shows that with this splicing
technique the rods can also be readily utilized as part of the LPS without thermal or
mechanical damage to the structure.
NOTE: Particular recommendations on the size, material or number of tie wires are not given
in this Standard, normal building practice being relied upon to provide adequate continuity.
Normal building practice also ensures the multiple conducting paths continue into the
building foundations (see Note). The foundations are deep in the mass of earth and
the resistivity of concrete is generally comparable with that of clay or other
moderately conductive ground. Hence, except in soils of low resistivity, the resistance
to earth from the foundation reinforcement is often lower than can be obtained
economically with driven rods, because of the much greater surface area. Concrete
foundations themselves constitute a satisfactory earth termination network but their
use, as such, precludes the inclusion of base conductors. It is desirable, however, that
a metallic connection to the reinforcing be installed, in a position suitable for the
bonding of metallic services associated with the building.
NOTE: Conductive paths may not be ensured if special building techniques are used,
e.g. grouting reinforcing bars into drilled holes in concrete after it has set, using an insulating
epoxy-based material.
(c) Prestressed reinforced concrete Prestressed reinforced concrete is used most
commonly in the horizontal structural elements in a building, such as the beams and
floor slabs, and only rarely in vertical elements such as columns. Consequently, the
principal reason for avoiding insulating gaps in prestressed concrete relates to side-
flashing rather than to the ability of the reinforcement to carry a lightning discharge
to earth. See Clause 4.16.2 for details of the treatment of prestressed concrete in order
to avoid side-flashing. These principles should be used in the rare instance where
vertical prestressed elements, such as prestressed columns, occur in a building.
Although prestressed concrete affords a large reduction in the cross-sectional area of
steel reinforcement compared with conventionally reinforced concrete, calculations
indicate that prestressed cables of 10 mm diameter or more, will not be damaged
thermally by lightning and that thermal effects become negligible when several cables
are connected in parallel.
(d) Precast concrete Where electrical continuity is required through precast concrete
elements, the structural connection details, e.g. attachment plates, threaded ferrules,
bolt or dowel connections, should be carefully examined from an electrical continuity
standpoint. In most cases, the attachment device will be a metallic one and continuity
can be achieved by simply welding the attachment device to electrically continuous
reinforcement within the precast concrete element.
4.5.3 Structures with flammable or explosive atmosphere
Structures in which very small induced sparks present an appreciable element of danger,
such as structures containing explosive atmospheres of flammable vapour or gas and
structures in which easily ignitable fibres or materials producing combustible fines are
stored, e.g. cotton, grain or explosives, usually require much more than the standard
protection. Such structures can be protected by tall conducting masts earthed at the bottom,
by bonding as detailed in Clause 4.16.2.2, or by overhead earthed wires (see Section 7).
For DOD Internal Use ONLY
AS/NZS 1768:2007 44
COPYRIGHT
4.6 MATTERS TO BE CONSIDERED WHEN PLANNING PROTECTION
4.6.1 Structures to be erected
For structures that are to be erected, the matter of lightning protection should be considered
in the planning stage, as the necessary measures can often be effected in the architectural
features without detracting from the appearance of the building. In addition to the aesthetic
considerations, it is usually less expensive to install lightning protection during
construction than afterwards.
4.6.2 Design considerations
4.6.2.1 General considerations
The structure or, if the structure has not been built, the drawings, should be examined with
due regard to all the relevant details of this Standard and in particular to the following:
(a) Metal used in the roof, walls, framework or reinforcement above or below ground,
e.g. sheet piling, to determine the suitability of such metal in place of, or for use as,
components of the LPS.
NOTE: For a non-metallic roof, the position of any conduit, piping, water mains or other
earthed metal immediately beneath the roof should be noted, as this may inadvertently attract
a discharge if not shielded by an adjacent roof or structure, or downconductor on or above the
roof.
(b) Available positions for downconductors providing the required number of low
impedance paths from the air terminal network to the earth termination; this is
particularly important for internal downconductors.
(c) The nature and resistivity of the soil as revealed by trial bore holes for foundation
purposes or soil resistivity tests with, where economically practicable, the driving and
testing of a trial earthing electrode with the object of designing a suitable earth
termination.
(d) Services entering the structure above and below ground.
(e) Radio and television antennas and microwave communications antennae.
(f) Flag masts, roof level plant rooms, e.g. lift motor rooms, ventilating plant and boiler
rooms, water tanks and other salient features.
(g) The construction of roofs to determine methods of fixing conductors with special
regard to maintaining weatherproofing of the structure.
(h) Possible penetration of waterproofing membrane where earth terminations are to be
sited beneath the structure.
(i) The provision of holes through, or fixing to, reinforced concrete.
(j) The provision of bonding connections to steel frame, reinforcement rods or internal
metalwork, and for any holes through the structure, parapets, cornices, and the like, to
allow for the free passage of the lightning conductor.
(k) The choice of metal most suitable for the conductor, e.g. aluminium conductors for
structures where aluminium is employed externally.
(l) Accessibility of test joints; protection by non-metallic casing from mechanical
damage or pilferage and hazard to persons; lowering of flagmasts or other removable
objects; facilities for periodic inspection, especially on tall chimneys.
(m) The preparation of an outline drawing incorporating the foregoing details and
showing the positions of the main components to form a basis for the record drawing
recommended in Clause 8.4.
(n) Requirements for the coordination of the structures lightning protection earthing and
the earthing of electricity supply and telecommunications services.
For DOD Internal Use ONLY
45 AS/NZS 1768:2007

COPYRIGHT

FIGURE 4.4 TYPICAL LPS USING METAL IN OR ON A STRUCTURE
For DOD Internal Use ONLY
AS/NZS 1768:2007 46
COPYRIGHT

FIGURE 4.5 TYPICAL LPS EMPLOYING VERTICAL AIR TERMINALS, FOR
PROTECTION LEVEL III
For DOD Internal Use ONLY
47 AS/NZS 1768:2007

COPYRIGHT
4.6.2.2 Route for conductors
Conductors should be installed with a view to offering the least impedance to the passage of
discharge current between the air terminals and earth. The most direct path is the best (see
Clause 4.12.2). The impedance to earth is approximately inversely proportional to the
number of widely separated paths, so that from each air terminal there should be as many
paths to earth as practicable. The number of paths is increased and the impedance decreased
by connecting the conductors to form a cage enclosing the building.
4.6.2.3 Trouble-free installation
Since an LPS, as a general rule, is expected to remain in working condition for long periods
with little attention, the mechanical construction should be strong, and the materials used
should offer resistance to corrosion.
4.6.2.4 Economy of installation
Economy of installation can be effected by keeping the variety of equipment to a minimum,
avoiding the use of unusual air terminal ornaments and similar features, and taking
advantage of constructional features as far as practicable.
4.7 MATERIALS
4.7.1 General
Copper is recommended for its conductivity and durability; however, alternative materials
may be used if suitable for the environment in which they are installed and are otherwise
satisfactory for the purpose (see Clause 4.8). Typical materials from which the current-
carrying component parts of LPSs may be chosen are given in Table 4.4 (see also
Clause 4.7.2).
Where insulating coatings are used, due regard should be given to their durability and non-
flammability.
For the protection of conductors at the tops of chimneys, see Clause 4.7.2.2(a).
4.7.2 Corrosion
4.7.2.1 Basic considerations
The materials used in LPSs should be resistant to corrosion resulting from the environment
in which they are installed. This includes the effects of atmospheric, soil or water-borne
electrolytes or contaminants, and of contact with those metals or alloys that will lead to
galvanic corrosion in the presence of moisture.
Corrosion resulting from contact of dissimilar metals can exist where a conductor is held by
fixing devices on or against external metal surfaces of a building or structure. Corrosion of
this nature can also arise where water passes over a relatively cathodic metal such as copper
carrying small amounts of copper corrosion product that is deposited as a fine film of
metallic copper on relatively anodic metals such as aluminium, zinc or steel. This causes
destructive galvanic corrosion of the latter metals, which are commonly used in building
cladding or roofing. The metallic components of the LPS should therefore be compatible
with the metals used externally on the structure over which these components pass or with
which they may make contact.
The components of LPSs may be constructed from a variety of materials as described in
Clauses 4.7.2.2 and 4.7.2.3.
4.7.2.2 Air terminals and downconductors
Specific recommendations for air terminals and downconductors are given in Clauses 4.11
and 4.12 respectively. Account should be taken of the principles outlined in Clause 4.7.2.1
in the selection of materials for those components.
For DOD Internal Use ONLY
AS/NZS 1768:2007 48
COPYRIGHT
Where there is a risk of metallic building elements being contaminated by corrosion
products, e.g. from copper conductors, the use of insulated conductors should be
considered. Such insulation may need protection against ultraviolet radiation, e.g. by
enclosure in conduit or by the application of appropriate paints or coatings.
Where insulated cables are used as downconductors, bonding to the air terminal network
should be effected at the specified intervals (see Clause 4.16.2.2) and bonding connections
should be sealed against the ingress of moisture.
Where structural steel or reinforcing bars form part of the downconductor system no further
corrosion-protection will normally be required.
With the common conductor materials, several specific precautions are necessary as
follows:
(a) Bare copper Copper should be of the grade ordinarily used for commercial electrical
work.
NOTE: Where any part of a copper conductor used in an LPS is exposed to the direct action
of chimney gases or other corrosive gases, it should be protected by a continuous coating of
tin, lead or other material suitable for the environment to which it is exposed. Such a coating
should extend not less than 500 mm below the top of a chimney or outside the area of
exposure. The coating should not be removed at joints.
(b) Bare alloys Galvanized iron or alloys of metals should be substantially as resistant to
corrosion as copper under similar conditions. Galvanized iron may be used as part or
the whole of the downconductor system provided it has adequate current-carrying
capacity and is fastened with fittings having compatible corrosion characteristics. The
galvanized iron may comprise the structural or decorative elements of the building
subject to these requirements.
(c) Bare aluminium or aluminium alloys Care should be taken not to use aluminium in
contact with concrete, mortar, the ground, or in other situations where moisture may
be retained causing the aluminium to deteriorate. Precautions should be observed at
connections with dissimilar metals.
In aluminium LPSs, copper, copper-covered and copper alloy fixtures and fittings
should not be used. Aluminium or aluminium alloy fixtures and fittings or
non-metallic components of adequate strength and durability are required. Special
arrangements will be needed at any earth terminations for this class of LPS.
Other materials may be used to the extent recommended elsewhere in this Standard.
For DOD Internal Use ONLY
49 AS/NZS 1768:2007

COPYRIGHT
TABLE 4.4
TYPICAL MATERIALS FOR CURRENT-CARRYING COMPONENTS
Material Standard Grade or type
Castings
Leaded gunmetal
Aluminium alloy

AS 1565
AS 1874

C92410
EA401 or AA607
Bars and rods
Copper, hard-drawn or annealed
Phosphor-bronze
Naval brass
Aluminium bronze
Aluminium
Aluminium alloy
Galvanized steel
Stainless steel

AS/NZS 1567
AS/NZS 1567
AS/NZS 1567
AS/NZS 1567
AS/NZS 1866
AS/NZS 1866



110
518
464
627
1050
6063 or 6463A


Tubes
Copper
Galvanized steel

AS 1432 or NZS 3501
AS 1074



Strip
Copper, annealed
Aluminium
Galvanized steel
Stainless steel

AS 1566
AS/NZS 1866
AS 1397
ASTM A240M

110
1200


Stranded conductors
Copper, hard-drawn
Aluminium
Galvanized steel
Stainless steel

AS 1746 AS/NZS 5000.1
AS 1531 AS/NZS 5000.1
AS 1222.1






Fixing bolts and screws for copper
Phosphor-bronze
Naval brass
Aluminium bronze
Common brass
Stainless steel

AS/NZS 1567
AS/NZS 1567
AS/NZS 1567
AS 2738


518
464
627
272

Fixing bolts and screws for aluminium and
aluminium alloys

Aluminium alloy
Galvanized iron or steel
BS 1473
AS 1214
HB30

4.7.2.3 The earth termination network
The design of the earth termination network should assume that each earthing electrode will
be bonded, directly or fortuitously, to the following
(a) the electrical installation earthing system and the MEN of the electricity supply
service (see AS/NZS 3000);
(b) the building structural steelwork or reinforcing material;
(c) any incoming service earth(s);
(d) any water, sewer and fire system supply pipes, if metallic; and
(e) any pipelines for gaseous or liquid fuels, if metallic.
For DOD Internal Use ONLY
AS/NZS 1768:2007 50
COPYRIGHT
Some supply authorities attempt to isolate services (d) and (e) from (a), for galvanic
corrosion control reasons, by inserting insulating spacers at the pipe entry. Consideration
should be given to the fitting of SPDs across the insulating spacers, in consultation with the
supply authority, to prevent arc discharge without prejudicing the corrosion control
measures.
The earth termination network should be capable of satisfactory performance for the
expected life of the LPS under the corrosion conditions existing at the site when bonded
to
(i) copper-based earthing systems (in most electrical installations);
(ii) steel-based structural material;
(iii) incoming service earths; which may be stainless steel, galvanized iron, copper or
lead; and
(iv) other metallic incoming services, e.g. steel or copper pipes for water or gas.
There are two hazards that arise from the bonding of other service earthing electrodes or
service lines to the MEN of the electricity supply service. Firstly, if the earthing system of
the electricity supply service is copper-based (as is mostly the case), it will cause
progressive galvanic destruction of less cathodic metals, such as steel, to which it is
connected. Secondly, the electricity supply service has many loads connected to it that
generate a direct current component; this direct current is an electrolytic hazard to other
earthing systems to which the electricity supply service earth is bonded. The amount of
direct current that can be generated by each appliance is limited by AS/NZS 3100, but it is
still sufficient to place at risk some types of earthing electrodes. In particular, steel rods
clad with copper or stainless steel suffer premature failure when a small amount of direct
current such as this perforates the cladding, initiating a process of self-destruction of the
rod core.
It will be clear that the selection of any common metal or alloy for the earth termination
network places either itself or other systems or services at some risk from galvanic
corrosion.
For lower-cost installations the use of one of the common metals or alloys may be
satisfactory. A list of these, with comments relating to their corrosion performance, is
provided in Table 4.5.
The extent to which the material combination can be damaging is related to soil moisture,
the type and nature of electrolytes present, and area and resistance relationships. Inherently,
if such materials are used, a maintenance checking routine is essential.
NOTE: For further information see Paragraph C9, Appendix C.
Where soil conditions are particularly aggressive from a corrosion viewpoint (soil
resistivity typically below 30 .m, especially if combined with a pH value of less than 5.5),
such as may exist in reclaimed marine areas, the use of an inert anode material (see
AS 2832.1) may be necessary. Expert advice on the selection of an appropriate earth
termination network should normally be sought where such soil conditions exist.
For DOD Internal Use ONLY
51 AS/NZS 1768:2007

COPYRIGHT
TABLE 4.5
CORROSION PERFORMANCE OF COMMON METALS AND ALLOYS
USED AS EARTHING ELECTRODES
Metal/alloy
Deleterious effect of this
metal/alloy on other bonded
underground ferrous metals
Deleterious effect on this metal/alloy from
bonding to MEN (copper-based) systems
Galvanized iron or steel Nil Damaging
Solid copper Damaging Nil
Copper-clad steel Damaging Can be damagingmay be acceptable
Solid stainless steel or nickel
iron alloy
Generally acceptable Can be damagingmay be acceptable
Stainless-steel-clad steel Generally acceptable Can be damaging
Bronze Generally damaging May be acceptable
Brass Can be damaging May be acceptablecan be dezincified
Zinc Nil Damaging
Aluminium Nil Extremely damaging
Magnesium Nil Extremely damaging
4.8 FORM AND SIZE OF CONDUCTORS
4.8.1 Factors influencing selection
The form and size of the conductors of the LPS should be selected having regard to their
(a) electrical and thermal characteristics (see Clause 4.8.2); and
(b) mechanical strength, if required, and the likelihood of corrosion (see Clause 4.8.3).
The minimum cross-sectional area required of a main current-carrying component of a
LPS is 35 mm
2
. The dimensions of typical conductors are given in Table 4.6.
4.8.2 Electrical and thermal considerations
Air terminals, downconductors and other conductors of the LPS that may carry the full
lightning current, should have a cross-sectional area and electrical conductivity such that
they are able to carry the expected current without deterioration and without attaining
temperatures that may give rise to risk of fire. Copper conductors having a cross-sectional
area of not less than 35 mm
2
will normally be necessary for this purpose. Conductors of
other materials may be used provided they satisfy the above criteria for current-carrying
capacity and temperature rise. (For further details, see Table 4.6).
Conductors, which because of their arrangement in the LPS, will carry only a proportion of
the lightning current, may have a cross-sectional area that is proportionately reduced but
should be not less than one-fifth of the cross-sectional area needed to carry the full
lightning current, or 6 mm
2
, whichever is the greater.
Conductors of larger cross-sectional area than recommended above may be needed as
indicated in Clause 4.8.3.
For DOD Internal Use ONLY
AS/NZS 1768:2007 52
COPYRIGHT
4.8.3 Mechanical strength and corrosion considerations
Conductors of larger cross-section than those recommended in Clause 4.8.2 may be needed
where
(a) a significant reduction of cross-sectional area is likely to be experienced in service
due to the effects of corrosion; or
(b) an increase in cross-sectional area or section of different shape (e.g. tubular instead of
solid) is required to provide adequate mechanical strength, e.g. for air terminals (see
Clause 4.11.1).
Consideration should also be given to the use of a larger cross-sectional area than that
recommended in Clause 4.8.2 in situations where inspection or repair of the conductor is
unusually difficult.
4.9 JOINTS
4.9.1 Effectiveness of joints
The LPS should have as few joints as possible. Joints and bonds should be mechanically
and electrically effective, e.g. clamped, screwed, bolted, crimped, riveted or welded. Where
overlapping joints are used, the length of the overlap should be not less than 20 mm for all
types of conductor. Contact surfaces should first be cleaned then inhibited from oxidation
with a suitable corrosion-inhibiting compound.
All mechanical connections should be inspected on a regular basis in accordance with
Section 8 to ensure the integrity of the connection over time.
4.9.2 Protective covering
Joints and bonds may be protected with bitumen or embedded in a plastics compound
according to the local conditions. Particular attention should be given to joints of dissimilar
metals.
4.10 FASTENERS
Conductors should be securely attached to the building or other object upon which they are
placed. Fasteners should be substantial in construction and not subject to breakage, and
should be, together with the nails, screws, or other means by which they are fixed, of the
same material as the conductors, or of such nature that there will be no serious tendency
towards galvanic corrosion in the presence of moisture because of contact between the
different parts.
Fasteners should be spaced so as to give adequate support to the conductor.
Downconductors should be fastened at spacings not exceeding 1.0 m on horizontal runs and
not exceeding 1.5 m on vertical runs.
The method of fastening should not result in a reduction of the conductor cross-section
below the minimum recommended in Clause 4.8.
NOTE: Plastics materials may be used for the fixing of conductors provided such materials are
suitable for long-term exposure to the outdoor environment (e.g. stabilized against the harmful
effects of ultraviolet radiation) and otherwise satisfy the recommendations of this Clause.
For DOD Internal Use ONLY
53 AS/NZS 1768:2007

COPYRIGHT
TABLE 4.6
TYPICAL SECTION DIMENSIONS OF MAIN CURRENT-CARRYING
COMPONENTS
Component Typical section dimensions
Air terminals
Strip 25 mm 3 mm
Rods 10 mm dia.
Stranded conductors 35 mm
2

Downconductors
Strip 25 mm 3 mm
Rods 10 mm dia.
Stranded conductors 35 mm
2

Galvanized materials 35 mm
2

Earthing electrodes and buried conductors
Earth rods 12 mm dia.
Galvanized star stakes (star pickets) Y 25 mm 19 mm 19 mm
Galvanized steel water pipe 25 mm dia.
Galavanized steel strip 50 mm 3 mm
Copper strip 25 mm 3 mm
Stranded conductor 70 mm
2

Main current-carrying bonding conductors
Strip 25 mm 3 mm
Cable 35 mm
2

4.11 AIR TERMINALS
4.11.1 General requirements
An air terminal may consist of a vertical rod as for a spire, a single horizontal conductor as
on the ridge of a small dwelling, or a network of horizontal conductors with vertical rods
for the protection of roofs of large horizontal dimensions (see Figure 4.5). Protection may
also be provided with a horizontal overhead wire supported, if necessary, independently of
the building to be protected or by a vertical air terminal network (see Figures 4.2 and 4.3).
Salient points of the structure should be incorporated in the air terminal network.
The upper portions of the downconductors on tall buildings should be regarded as a
continuation of the air terminal network and should be positioned so as to intercept side
strikes to the building. Preference should be given to placing downconductors as near as
possible to the exposed outer vertical corners of a building.
All metallic projections, on or above the main surface of the roof, should be bonded to, and
form part of, the air terminal network. In the case of telecommunications antennas, which
have to be insulated from earth, a spark gap connection to earth or an SPD should be
provided.
Where roof construction consists of electrically continuous metallic materials, such metallic
roofs may form part of an LPS, obviating the need for air terminals.
If portions of a structure vary considerably in height, any necessary vertical air terminal or
air terminal network of the lower portions should, in addition to their own downconductors,
be bonded to the downconductors of the taller portions (see Figures 4. 4 and 4.5).
For DOD Internal Use ONLY
AS/NZS 1768:2007 54
COPYRIGHT
Air terminals may be of any form provided the section used and the means of attaching it to
the building structure have adequate mechanical strength to withstand the expected wind
loading and natural harmonic resonances. Vertical air terminals of greater than three metres
in height will generally need a form of additional fixing using brackets, bracing or guy
wiring for suitable support.
4.11.2 Protection of roofs
The parts of roofs most likely to be struck by lightning are parapets, the corner and edges of
flat roofs, chimneys, and the ridges and eaves of sloping roofs. Preference should be given
to positioning the air terminals so as to protect these highly exposed parts.
The height of a vertical air terminal should be such that the tip will be not less than 500 mm
above the object to be protected. On large flat and gently sloping roof areas a number of
vertical rods of greater than 500 mm in height may be needed to establish a zone of
protection over the whole roof area in accordance with Clause 4.4.
Horizontal conductors such as strap or cable on parapets and metallic objects such as
architectural features, flagpoles, metal railings, steel plant surrounds and roof access
ladders may be used as air terminals to protect a planar roof surface. When positioned at a
height of not less than 500 mm above the area to be protected and in accordance with the
design rules (see Clause 4.3) and the RSM (see Clause 4.4.2), the conductors or objects will
be at a suitable height to achieve the selected interception efficiency.
In special circumstances, such as where it is desired to preserve the appearance of a historic
building, horizontal air terminals may be installed immediately underneath the cladding
(e.g. tiles) of a non-conductive roof. However, it should be noted that, in the event of a
lightning strike to the roof, the cladding will be punctured and may suffer some damage.
Horizontal and vertical air terminals and interconnecting conductors of the air terminal
network should be located so as to constitute, as nearly as local conditions permit, an
enclosing network that joins each air terminal to each other and to all downconductors.
All metallic objects at roof level such as sheeting, plant, plant screens, tanks, gutters,
walkways, ladders, antennas, masts, poles, vents, chimneys, conduits, piping, cable tray,
enclosures, etc should be bonded to the air termination network.
4.11.3 Protection of the sides of tall buildings
4.11.3.1 Influence of forms of construction
The consequences of a strike to the sides of a building may result in damage of a minor
nature. Unless there are specific reasons for side protection, as would be the case with a
structure containing explosives, it is considered that the cost of side protection will not
normally be justified.
Many buildings will have perimeter columns in which the reinforcement (or structural steel)
is used as a part of the downconductor system. Where these columns on the external facade
are no further than 20 m apart, no further protection will be required in respect of strikes to
the side of the building.
In the event of a strike to such a column or to isolated metal components such as small
window frames, it is likely that a small section of masonry cladding material may be
dislodged.
Where the risk of this is unacceptable, conductors should be installed on the external faces
of the columns to receive the strikes. These conductors will take the form of lightning air
terminals/downconductors and should be bonded at the bottom into the LPS.
Where side protection is a requirement of an LPS and suitable columns do not exist to
receive strikes to the sides of buildings, vertical conductors should be installed for this
purpose. These conductors should be spaced around the perimeter of the building at
intervals not exceeding 20 m.
For DOD Internal Use ONLY
55 AS/NZS 1768:2007

COPYRIGHT
4.11.3.2 Curtain wall construction
It has become commonplace for tall buildings to have external glass curtain walls, with the
curtain wall external to perimeter columns. The majority have major glass elements
contained (and restrained) within a metallic framework. This framework is often inherently
connected, electrically, to the metal in the building structure via the standard connection
details used to mechanically fix the curtain wall structure to the structural frame of the
building itself.
Where this inherent connection occurs and where the frame of the building is incorporated
into the LPS, no further bonding of the curtain wall to the LPS is necessary.
In other cases, the curtain wall metal framing shall be bonded into the LPS at roof and
ground level. It is essential that bonding be undertaken at the corners of the structure and
around the perimeter of the building at intervals not exceeding 20 m. (See Clause 4.16.2.2
for further details).
4.12 DOWNCONDUCTORS
4.12.1 StructuresGeneral
Downconductors should be installed at each external corner of the building and additional
downconductors installed, as necessary, at spacings not exceeding 20 m.
4.12.2 Route
The route followed by downconductors should be in accordance with the following
recommendations:
(a) Downconductors should be distributed around the outside walls of the structure. It is
undesirable to locate downconductors in areas where persons are liable to congregate.
The walls of light wells may be used for fixing downconductors, but lift shafts should
not be used for this purpose.
(b) Where the provision of suitable external routes for downconductors is impracticable
or inadvisable, e.g. buildings of cantilever construction from the first floor upwards,
downconductors may be housed in an air space provided by a non-metallic,
non-combustible internal duct. Any covered recess or any vertical service duct
running the full height of the building may be used for this purpose, provided that it
does not contain any unarmoured or non-metal-sheathed service cable (see
Clause 4.16.2.3).
(c) Any extended metal running vertically through the structure should be bonded to the
lightning downconductor at the top and bottom unless the clearances are in
accordance with Clause 4.16.
(d) A downconductor should follow the most direct path possible between the air
terminal and the earth termination. Right angle bends may be used when necessary
but deep re-entrant loops should be avoided.
(e) A structure on bare rock, protected in accordance with Clause 4.14.3.1, should be
provided with at least two downconductors equally spaced.
NOTE: The positioning and spacing of downconductors on large structures has often to be
decided in practice by architectural considerations. However, their number should be governed by
the recommendations above.
For DOD Internal Use ONLY
AS/NZS 1768:2007 56
COPYRIGHT
It is now recognized that sharp bends in a downconductor, such as occur at the edge of a
roof, do not significantly impede the discharge of a lightning current, nor are the
mechanical forces produced by a lightning current likely to endanger the conductor or its
fixings. In contrast, re-entrant loops in a conductor can produce high inductive voltage
drops so that the lightning discharge may jump across the open side of the loop. As a rough
guide it can be stated that this risk may arise when the length of the conductor forming the
loop exceeds 8 times the width of the open side of the loop. It follows from the above that
there is no need to round the path of the downconductors at the edge of a roof and that an
upturn within the limits stated is acceptable. Where large re-entrant loops as defined cannot
be avoided, e.g. for some cornices or parapets, the conductor should be arranged in such a
way that the distance across the open sides of the loop complies with the principles given
above. Alternatively, such cornices or parapets should be provided with holes through
which the conductor can pass freely. (See Figures 4.6 and 4.7).
An exception to the above practice is necessary for a building cantilevered out from the first
storey upwards. The downconductors in this case should be taken straight down to the
ground since, by following the contour of the building, a hazard could be created to persons
standing under the overhang formed by the cantilever. In such a case, the use of internal
ducts for downconductors is recommended (see Figure 4.8).

FIGURE 4.6 GENERAL PRINCIPLES OF A RE-ENTRANT LOOP
IN A CONDUCTOR TAKEN OVER A PARAPET WALL
For DOD Internal Use ONLY
57 AS/NZS 1768:2007

COPYRIGHT

FIGURE 4.7 ACCEPTABLE METHOD OF TAKING A CONDUCTOR THROUGH A
PARAPET WALL

FIGURE 4.8 ROUTES FOR DOWNCONDUCTORS IN A BUILDING WITH
CANTILEVERED UPPER FLOORS
4.12.3 Mechanical damage
Where any part of an LPS is exposed to mechanical damage it should be protected by
covering it with moulding or tubing preferably of non-conductive material. If metal is used,
the conductor should be electrically connected to both ends of the protective covering.
For DOD Internal Use ONLY
AS/NZS 1768:2007 58
COPYRIGHT
4.13 TEST LINKS
Where practicable, test links should be provided to enable the continuity of each individual
parallel path of the lightning conductor system to be measured.
Where a driven or buried earthing electrode is provided as part of the LPS, test links should
be provided to permit measurement of the resistance of the individual earth terminations, in
such a position that, while not inviting unauthorized interference, is convenient for use
when testing. Such resistance measurements are indicative only and provide the basis of
comparison to determine whether any deterioration in the earth termination network has
occurred in service (see also Appendix C).
4.14 EARTH TERMINATIONS
4.14.1 General principles
Each downconductor should be connected to an earthing electrode or to the earth
termination network. The design of earth terminations should be such that lightning currents
are discharged into the earth in a manner that will minimize step and touch potentials and
the risk of side-flashing to metal in or around a structure. This can be achieved by ensuring
that the potential with respect to the general mass of the earth at each earth termination is
limited by a sufficiently low resistance to earth, so that the discharged current flows in as
close to uniform manner as possible in all directions away from the structure.
Ionization of the soil near an earthing electrode carrying lightning current tends to reduce
the potential of the earthing electrode relative to remote earth to a lower value than the
potential that would be calculated using the earth resistance measured at low currents.
Appendix C provides information on the effectiveness of various forms of earth termination
networks for lightning protection purposes and on the associated calculation/measurement
procedures.
4.14.2 Earthing resistance
4.14.2.1 Basis for measurements
The term earthing resistance is used in this Clause and elsewhere in this Standard because
the most common measuring instruments available are low frequency devices. A more
appropriate measurement for lightning protection purposes is that of earth impedance and
such measurements are preferred when suitable high frequency or impulse type instruments
are available.
4.14.2.2 Recommended values
In general, the whole of an interconnected LPS should have an earthing resistance not
exceeding 10 before any bonding is effected to services that are not part of the LPS. In
addition, each earthing electrode of an interconnected LPS that is not interconnected at or
below ground level should have an earthing resistance not exceeding the product obtained
by multiplying 10 by the number of downconductors.
NOTE: Where the installation has two or more air terminal networks not directly interconnected,
such as a twin-tower building, then for the purpose of determining the required earthing
resistance, it should be considered as consisting of separate LPSs.
Where buildings are primarily used for telecommunications services or information
technology installations, or installation of multiple items of other sensitive electronic
equipment, an earthing resistance not exceeding 5 should be required.
A reduction of earthing resistance can be achieved by extending or adding to the earth
termination network or by interconnecting the individual earth terminations of
downconductors.
For DOD Internal Use ONLY
59 AS/NZS 1768:2007

COPYRIGHT
Notwithstanding the above recommendations, earthing electrodes complying with either of
the following, need not comply with the 10 criterion:
(a) For a substantial structure effectively encircled by a buried earthing electrode, an
earthing resistance not exceeding 30 should be satisfactory. A buried earthing
electrode covering at least three sides of the structure may be regarded as effectively
encircling the structure.
(b) For any system incorporating two or more downconductors, it should not be necessary
to install a total length of more than 50 m of widely separated horizontal or vertical
earthing electrodes per downconductor, regardless of the earthing resistance.
Where reinforced concrete footings are used as earthing electrodes for a building,
compliance with the recommended maximum resistance values should be determined by the
measurement of resistance of typical footings that support the building structure. The
measurements should be made at the stage of building construction when the footings are
structurally isolated and may be treated as independent earthing electrodes.
4.14.3 Common earthing electrode and potential equalization
4.14.3.1 Common earthing electrode
Where conditions permit potential equalization techniques to be used, a common earthing
electrode may be installed to serve the LPS and other appropriate services. The earthing
electrode should comply with the recommendations in this Standard and with any
regulations that may govern the appropriate services (for telecommunications services, see
Clause 4.14.3.2). The earthing resistance should be the lowest required by any of the
regulations for such services.
Where isolation is required, a common earthing electrode should not be used, but the
separate earthing electrodes should be bonded via an SPD to minimize potential differences
between the LPS earth termination network and other earthing systems in the event of a
lightning strike.
4.14.3.2 Communications earths
Where a communications earth is installed at a dwelling or similar small building, that earth
should be connected to other earths present (see Paragraph B5.6, Appendix B). However,
where a communications earth, such as a Telecommunications Functional Earthing
Electrode (TFEE), is required to be isolated from other earths, because of noise or direct
current conduction considerations, this earth should be bonded through a normally non-
conducting protector or SPD.
4.15 EARTHING ELECTRODES
4.15.1 General considerations
An earthing electrode may be of any type provided
(a) it achieves a low resistance to the general mass of earth, as recommended in this
Standard;
(b) it has adequate mechanical strength and corrosion resistance to ensure that the desired
service life will be achieved when installed in the environment concerned; and
For DOD Internal Use ONLY
AS/NZS 1768:2007 60
COPYRIGHT
(c) it has adequate current-carrying capacity for the discharge of lightning currents
without sustaining damage that might jeopardize its continued effectiveness.
NOTES:
1 Electrode earthing resistance may be measured by standard methods (see Paragraph C10,
Appendix C).
2 If the soil resistivity is known, the electrode earthing resistance may be calculated as
shown in Paragraph C3, Appendix C. It should be noted, however, that such calculations
are only approximate and it is important that the electrode earthing resistance should in
fact be determined by field test.
3 It is fairly easy to determine soil resistivity by test as set out in Paragraph C10.1,
Appendix C.
The selection and design of the earth termination network should therefore take account of
the following:
(i) Soil resistivity.
(ii) The corrosion aggressiveness of the soil.
(iii) The physical structure of the soil (rocks, obstructions and other services).
(iv) The corrosion compatibility of the earth termination network with other structures to
which it will be, or may become, bonded.
(v) The options available for installation at the site (trenching, driving, drilling, land
excavation or use of structural metalwork).
(vi) The effects that it may have on other systems (electrical or telecommunications).
If the structure has a reinforced concrete floor and/or footings (see Clause 4.5.2), it may not
be necessary to install lightning protection earthing electrodes, (see Clauses 4.5.2.4 and
Paragraph C8, Appendix C). Generally speaking, the impedance to earth of a reinforced
concrete floor and footings will be lower than that of an earth termination system utilizing
vertical earthing electrodes.
4.15.2 Connections to earthing electrodes
4.15.2.1 Mechanical protection
Where conductors that are connected to earthing electrodes are accessible, such conductors
and connections should be protected against mechanical damage and vandalism.
Where conductors connecting driven earthing electrodes in parallel are not installed above
the ground, they should be buried not less than 500 mm below the surface.
4.15.2.2 Selection of materials
Care should be exercised in the selection and application of materials for connections to
earthing electrodes to avoid the possibility of galvanic corrosion, e.g. because of
differences between the materials of such connections and the earthing electrodes.
4.15.2.3 Joints
Joints between earthing conductors and earthing electrodes should be of adequate strength
and current-carrying capacity, and be arranged so as to ensure that there will be no failure
of the connection under conditions of use or exposure that can reasonably be expected. For
suitable methods, refer Clause 4.9.
4.15.2.4 Test links
If test links are inserted in earthing conductors connected to earthing electrodes, they
should be secured in the closed position and be arranged so that the opening of any one link
does not interfere with earth connections other than the one under test.
For DOD Internal Use ONLY
61 AS/NZS 1768:2007

COPYRIGHT
4.15.3 Inspection and testing of earthing electrodes
The earthing resistance of electrodes should be determined by test both at the time of
installation and regularly during the life of the installation.
For details of inspection and testing, see Section 8.
4.16 METAL IN AND ON A STRUCTURE
NOTE: The term metal in or on a structure includes all metal such as reinforcement rods and
bars, pipes, conduits, chimneys, corrugated iron, roof sheeting, rails, ladders, screens, sunshades,
etc. Metal hidden from view should not be overlooked. Tubing, containing electrical conductors
or metal-sheathed cables, is, for instance, often embedded in an external wall and may be quite
close to the LPS.
4.16.1 Use of metal in or on a structure as a part of the lightning protection system
Where a structure contains electrically continuous metal, e.g. continuous steel frame, or
metal within a roof, wall, floor or covering, this metal suitably bonded in accordance with
Clause 4.16.2.2 may be used as part of the LPS, provided that the amount and the
arrangement of the metal render it suitable for use, as recommended in Clauses 4.11 to 4.15
inclusive.
Where a structure is simply a continuous metal frame without external metal covering e.g.
tower pole, it requires no air terminal or downconductor; it is sufficient to ensure that the
conducting path is electrically continuous and that the base is adequately earthed.
A steel frame structure or reinforced concrete structure may have foundations with
sufficiently low inherent earthing resistance and, if connections are brought out from the
reinforcement, a test may be made to verify its suitability for use as part of the LPS (see
Clause 4.15.1).
4.16.2 Prevention of side-flashing
4.16.2.1 Methods of prevention
When an LPS is struck, its electrical potential with respect to earth is raised and, unless
suitable precautions are taken, the discharge may seek alternative paths to earth by side-
flashing to other metal. Two methods exist to prevent side-flashing: bonding and isolation.
Bonding is the procedure whereby metal parts are positively connected to one another so as
to prevent inadvertent electrical connection occurring due to side-flash. Isolation is the
separation or insulation of metal parts in such a way that electrical breakdown or side-flash
to them is prevented. Isolation may be achieved by separation of the LPS from the structure
protected or by separating metal parts and services in a non-conductive structure from the
LPS.
Bonding effectively eliminates any local potential difference between the metal parts that
are bonded together. However, it is possible to obtain large potential differences for very
short times between adjacent metallic objects that are connected together at a remote
location. These potential differences could be hazardous if the bonding system is
inadequate. Many structures can be effectively bonded so as to eliminate any hazard,
however, care should be taken to prevent subsequent installation of a metallic service
creating a hazard. It should be noted that any conductive element that is bonded into the
LPS can be expected to carry a proportion of the lightning current. Therefore, the bond and
bonded element should be capable of carrying such current. (Refer to Table 4.6 for typical
dimensions of bonding conductors).
With isolation, it is often difficult to obtain and to maintain the necessary safe clearances,
and to prevent connection of an isolated LPS back to the structure via earth and buried
metallic services. To achieve isolation it may be necessary to utilize a protection system
that is completely separate from the protected structure, and is remotely earthed.
For DOD Internal Use ONLY
AS/NZS 1768:2007 62
COPYRIGHT
If the structure is constructed with conductive materials such as reinforced concrete or steel
frames, isolation of a protection system mounted on the structure requires the use of high
impulse strength, high voltage insulation.
In general, where the LPS is mounted on the structure, isolation can only be achieved at low
cost if the structure is small.
4.16.2.2 Bonding
The conditions under which bonding should be effected are as follows:
(a) Where practicable, all structural steel and metallic reinforcement in a structure, if not
used as a part of the LPS, should be bonded to that system (and hence become part of
that system).
As indicated in Clause 4.5.2.4(b), metal rods in in situ reinforced concrete may be
considered to be electrically continuous. Consequently, bonding may be achieved
with a reasonable number of connections to the rods, a bonding connection to each
rod being unnecessary.
Where prestressed or post-tensioned concrete elements are involved, it has been
found that the stressing cables frequently remain electrically isolated from other
structural metal at the completion of the stressing process. Such cables should be
bonded at both ends to the LPS, particularly where the structural element is exposed
to the weather.
NOTE: This bonding is recommended, not out of concern for a side-flash causing immediate
structural damage, but rather to avoid the chance of the side-flash causing cracking of the
corrosion-protecting concrete grout used around the cable. Prestressed cables under stress are
highly susceptible to corrosion.
Where metal exists in a structure, such as reinforcement in a precast concrete
spandrel panel or post-tensioned concrete slab, which cannot be bonded into a
continuous conducting network and which is not or cannot be equipped with external
earthing connections, its presence should be disregarded. The hazard presented by the
presence of such metal should be minimized by keeping it entirely isolated from the
LPS, which includes consideration of the numbers of downconductors.
(b) Where the roof structure is wholly or partly covered by metal, care should be taken
that such metal is provided with a continuous conducting path to earth.
(c) Metal that is attached to the outer surface of a structure should preferably be bonded
as directly as possible to the LPS. Where bonding is difficult and where the
consequences of side-flashing to isolated metalwork is not considered serious,
bonding may be omitted.
Where such metal has considerable length, e.g. cables, pipes, gutters, stairways, and
runs approximately parallel to a downconductor or column, it should be bonded to the
LPS at each end and at vertical intervals of not more than 20 m.
(d) In curtain wall construction, where the framework would otherwise be electrically
isolated, the frame should be made electrically continuous and should be bonded to
the LPS at intervals not exceeding 20 m around the perimeter of the building. This
should occur at the top and bottom of each curtain wall and at levels separated by not
more than 20 m vertically, including those sections that are less than 45 m above
ground.
For DOD Internal Use ONLY
63 AS/NZS 1768:2007

COPYRIGHT
(e) Where there is insufficient clearance from the LPS, metal entering or leaving a
structure in the form of sheathing, armouring or piping for electricity supply, gas,
water, telephone, steam, compressed air or other services, should be bonded as
directly as possible to the earth termination at the point-of-entry or exit outside the
structure. In this operation, the appropriate Standards and any regulations that may
apply to such services should be observed.
(f) Masses of metal in a building, such as a bell-frame in a church tower, should be
bonded to the nearest downconductors by the most direct route available.
4.16.2.3 Isolation
The necessary separation distance from any point on the LPS depends on the electric
potential, or voltage, generated at that point by the lightning discharge.
To achieve a sufficiently low probability of side-flash, the responses of the protection
system to a range of severe stroke current waveshapes have to be considered. Because the
time for a lightning stroke current waveshape to significantly change its steepness is similar
to the time taken by the incident wave to travel from the point of strike to the earth
termination, travelling wave techniques are used to calculate the voltage waveforms
generated. However, an approximate voltage waveform sufficient to estimate the required
separation distance can generally be calculated from the resistive and inductive voltage
drops in the system.
Isolation may be provided by appropriate air clearance from bare metal downconductors or
by appropriately insulated downconductors. The requirements for insulated downconductors
are detailed in IEC 62305.3.
NOTE: Appendix D gives examples of calculation procedures.
For conventional LPSs using typical bare metal downconductors, the separation distance in
air at a given point on the protection system is required to be not less than D, where D, in
metres, is the greater of D
1
and D
2
as defined below and shown in Figure 4.9:
(a) D
1
is the required clearance associated with the discharge voltage of the design first
stroke of a severe lightning flash and takes account of the design maximum lightning
current. D
1
is defined only for H/n < 30.
(b) D
2
is the required clearance associated with the discharge voltage of the design
subsequent stroke of a severe lightning flash and takes account of the design
maximum steepness of the current wavefront.
To take account of systems with a common earthing electrode it is necessary to separate D
1

into two components as follows:
D
1
= D
i
+ D
e
. . . 4.16.2.3
where
D
i
=
30 for ,
12
<
n
H
n
H

D
e
= 0.3R
H = length of downconductor from the point considered to earth, in metres
n = number of downconductors connected to a common air terminal
R = combined earthing resistance of the LPS, in ohms
D
i
is the component of the first stroke separation distance associated with potential
difference generated within the structure.
For DOD Internal Use ONLY
AS/NZS 1768:2007 64
COPYRIGHT
D
e
is the component of the first stroke separation distance associated with local EPR, and is
independent of the point on the LPS considered. This term is applicable to any remotely
earthed objects, such as services entering the building, that do not share a common earthing
electrode with the LPS, and to any long unearthed objects within a relatively
non-conductive structure. Where a common earthing electrode in accordance with
Clause 4.14.3 is used, the term D
e
may be neglected (R = 0 in Figure 4.9). Where it is
applicable, the clearance D
e
should be maintained throughout the structure and thus
determines the minimum separation distance at the base of the structure.
The required clearance for steep-fronted surges, D
2
, may be read from the dotted curve
given in Figure 4.9. As the separation distance D
2
varies with the length of downconductor
from the point considered to earth, D
2
normally determines the required separation in the
upper parts of tall structures.
The shortest separation distance over the surface of non-conductive structural material
should be 2D for protected dry surfaces and 3D for external surfaces. The separation
distance through solid non-conductive structural material should exceed 0.5D.
NOTES:
1 For a substantial reinforced or structural steel frame building that utilizes the structure as part
of the LPS, the separation distance may be obtained from Figure 4.9 by taking n to be 1.5
times the number of reinforced or steel columns. The term D
e
may be neglected for these
buildings by assessing D for R = 0, except when considering remotely earthed services
entering the building.
2 The extent to which uninsulated services may be considered to be affected by local EPR can
be determined by a test in which a known current is injected into the LPS and potential
differences to the electrical installation earthing system are surveyed.

FIGURE 4.9 REQUIRED SEPARATION DISTANCES IN AIR
4.16.2.4 Effects of bonding on cathodically-protected metal
In the bonding of adjacent metalwork to the LPS, careful consideration should be given to
the possible effects such bonding would have upon metalwork that may be cathodically-
protected (see AS 2832 series).
For DOD Internal Use ONLY
65 AS/NZS 1768:2007

COPYRIGHT
4.16.2.5 Bonding of underground services
In the ground, bonding between the LPS earth termination network of any structure and
buried metallic service pipes is essential, unless the service can be effectively isolated. If
this is not done, an electrical breakdown can occur through the soil between these systems
and the resulting electric arc can cause structural damage or may puncture a service pipe
(see also Clause 4.16.2.2 (e)) SPDs may usually be fitted where direct connection is
unacceptable.
For DOD Internal Use ONLY
AS/NZS 1768:2007 66
COPYRIGHT
S E C T I O N 5 P R O T E C T I O N O F P E R S O N S A N D
E Q U I P M E N T W I T H I N B U I L D I N G S
5.1 SCOPE OF SECTION
This Section sets out recommendations for the protection of persons and equipment within
buildings from the effects of lightning. The provision of an LPS for the building structure
will not automatically guarantee such protection. These recommendations may be applied
irrespective of whether an LPS for the building structure is provided in accordance with
other sections of this Standard. The recommendations principally consist of installation of
equipotential bonding of services, conductive parts, earthing systems, and the provision of
SPDs as appropriate on services.
5.2 NEED FOR PROTECTION
Whilst persons and equipment within buildings may be protected from a direct lightning
strike, many circumstances arise where the effects of lightning are transmitted within the
building, by various means as described below, placing persons and equipment at risk.
Communications and electronic equipment are particularly susceptible to damage from
lightning impulses and such damage may occur at energy levels well below those needed to
cause injury to persons. In addition, there is a significant fire risk associated with impulse
failure of many types of electrical and electronic equipment.
Installation of protective measures, including primary and/or secondary SPDs on services,
depends on many factors which may be included in an appropriate risk assessment.
From a telecommunications perspective, AS 4262 provides a method to determine when
protection is required (AS 4262.1 for person protection and AS 4262.2 for equipment
protection). Further information on protection of customer premises may be found in ITU-T
Recommendation K.66.
5.3 MODES OF ENTRY OF LIGHTNING IMPULSES
There are four principal modes of entry of lightning impulses into buildings, as described
below and shown in Figure 5.1, and these may occur separately or in combination. The
modes are:
(a) Directly by the interception of lightning on exterior metalwork Lightning impulses
may be transmitted in the interior of the building as a consequence of a strike to
exterior metal that has a direct conductive connection to the interior of the building,
e.g. via telecommunications antennas, plumbing fittings and the like. This mode of
entry is characterized by a series path for the full impulse energy and is capable of
conveying the full destructive effect of the lightning discharge. The waveshape of the
lightning impulse is usually not significantly modified.
(b) Indirectly by the interception of lightning on other structures or services A lightning
strike to other structures or services that have conductive connection to the building,
e.g. the low-voltage electricity distribution system or other services, may result in an
impulse being transmitted into the building. The impulse is characterized by a lower
energy level compared to that involved in Item (a), being a parallel path to the
interior of the building served by the low-voltage mains. It is an EPR effect caused by
the lightning impulse passing to earth through the neutral/earth connection and
resulting in a increase in potential because of the impedance of the earth termination
network.
For DOD Internal Use ONLY
67 AS/NZS 1768:2007

COPYRIGHT
The magnitude of the impulse at the structure is governed by the neutral/earth
impedance at the interception point, the length of the service line, the number of
earthing features per unit length on the line adjacent to the interception point and,
lastly, the electrical characteristics of the lightning discharge.
Where a combined MEN electricity supply service exists (high voltage earth bonded
to low-voltage earth), the regulatory authorities require an earthing resistance of not
more than 1 . As might be expected this limits the EPR impulse voltage
considerably. In addition, in urban areas the number of electricity supply services
with an earth (i.e. neutral/earth) connection is considerable, perhaps 100 per km.
Consequently, the EPR lightning impulse is rapidly reduced, perhaps to insignificant
levels in about 60 m. On the other hand, sparsely settled areas with distribution
systems other than the MEN type can give rise to high EPR values that may not
reduce to safe levels for some hundreds of metres.
The impulse wave is normally modified by the transmission path in the EPR mode by
distributed electrostatic capacity and transmission line effects. This reduces the
severity of the impulse but prolongs the time that the protection equipment must
conduct the pulse to earth.
Although the energy levels involved in an EPR impulse are substantially less than
those that apply for Item (a), they may still be of a high order. Based on sparks or
arcs observed in incidents involving personal injury or equipment damage under EPR
conditions, voltages of the order of 100 000 V are not uncommon and cases involving
voltages of about 1 000 000 V have been observed. Impulse currents in this mode can
range from a few amperes to several thousand amperes.
It should be noted that EPR conditions can arise singly or as a combination of
occurrences. In addition to lightning intercepting the overhead low-voltage electricity
distribution system, other lightning leaders may intercept trees, clothes lines, sheds or
other nearby structures, giving rise to a quite complex overall EPR condition.
NOTE: Of the lightning incidents involving electrical equipment that have been investigated
by Telstra, some 80 percent can be attributed to the entry mode described in the preceding
paragraphs.
(c) Inductively by electric and magnetic field coupling In general, this mode of entry
happens more frequently but involves lower energy levels in comparison with the
mode of entry in Item (b). Induction occurs when a lightning strike to ground gives
rise to electromagnetic and electrostatic fields. These fields induce an impulse in
conductors that intercept them. The conductors that are most affected are electricity
reticulation and telecommunications lines. Commonly, the former are not damaged
but the impulse may be transmitted to customer terminals and appear as a lower level
lightning-induced impulse. This may damage or disable some forms of
telecommunications equipment.
(d) Direct induction into internal building wiring This mechanism is similar to Item (c),
but the induction occurs directly into the building wiring itself. For this to be
significant, the lightning strike needs to be very near by, typically to the LPS itself.
Measures to reduce this effect, including reduction of installed conductor loop areas,
are discussed in Clause 5.6.4.
Protection systems designed to counteract EPR and other impulses will normally provide
adequate protection against impulses arising from the entry modes described in Items (b),
(c) and (d).
For DOD Internal Use ONLY
AS/NZS 1768:2007 68
COPYRIGHT

FIGURE 5.1 MODES OF ENTRY OF LIGHTNING IMPULSES
For DOD Internal Use ONLY
69 AS/NZS 1768:2007

COPYRIGHT
5.4 GENERAL CONSIDERATIONS FOR PROTECTION
Because of the many variables involved, each building will require specific consideration of
the protective measures that should be applied. Particular attention should be given to
possible entry and exit points for lightning current, which may include one or more of the
following:
(a) Rooftop or external structures (e.g. TV antennas, communications hardware such as
microwave dishes, metallic flues and ventilation outlets) or other exposed metal work
not protected by the LPS for the building structure (e.g. metallic guttering and
downpipes, metallic fences) These features will invariably be possible entry points for a
lightning discharge.
(b) The electricity supply service entry This will normally be an entry point for lightning if
the service is aerial or overhead. It may be either an entry point or an exit point if the service
is underground but it is more likely to be an exit point in such cases.
(c) The telecommunications services entry This may be an entry point if the service is
overhead using a dropwire or aerial cable. The service is more commonly underground and in
such cases could be either an entry point or exit point.
(d) Gas supply systems These are usually exit points for lightning but may occasionally
present an EPR entry condition.
(e) Metallic water supply and sewerage systems These are usually exit points for lightning
but may occasionally present an EPR entry condition.
(f) Other conductive services These are usually exit points for lightning but may
occasionally present an EPR entry condition.
(g) Building earthing systems (often there are several) These are usually exit points for
lightning but may occasionally present an EPR entry condition.
(h) The LPS for the building (if provided) By design these systems provide both an entry
and exit point for a lightning discharge but, because of bonding, will present an EPR
condition to other services.
An illustration of the possible entry and exit points for a lightning discharge is provided in
Figure 5.2.
For DOD Internal Use ONLY
AS/NZS 1768:2007 70
COPYRIGHT

FIGURE 5.2 POSSIBLE ENTRY AND EXIT POINTS FOR A LIGHTNING DISCHARGE
5.5 PROTECTION OF PERSONS WITHIN BUILDINGS
5.5.1 Objectives of protection
The principal objective of measures for the protection of persons within buildings is to
prevent hazardous potential differences between conductive parts with which the person(s)
may be in contact. This is normally achieved by applying equipotential bonding between
any conductive path into and out of the building, i.e. the entry points and exit points
referred to in Clause 5.4.
If such bonding has been installed it does not matter if a person is subject to an EPR with
respect to distant earth as all conductive materials in the vicinity will be at approximately
the same potential.
An important consideration in the installation of equipotential bonding is how to install
such bonding without adversely affecting the operation of the various services involved,
particularly the protection systems associated with the respective systems. This is explained
further in Clause 5.5.2.
AS 4262.1 provides further information on the protection of users of telecommunications
equipment from overvoltages that may exist between a user environment and
telecommunications facilities in that environment.
For DOD Internal Use ONLY
71 AS/NZS 1768:2007

COPYRIGHT
5.5.2 Installation of equipotential bonding
In general, if made of copper, bonding conductors shall have a cross-sectional area as given
below, unless they are main current-carrying conductors of the LPS. The typical dimensions
of the main current-carrying conductors of a LPS are given in Table 4.6.
All possible entry and exit points for the lightning discharge should be electrically bonded
together in as direct a manner as practicable. The route taken by the bonding conductors is
important. If incorrectly routed the bonding conductors themselves may damage other
circuits or equipment by induction or side-flashing as currents of the order of tens of
kiloamperes and voltages of the order of several thousand volts with respect to remote earth
may be involved. Consequently, bonding conductors should not be grouped with other
cables that are sensitive to induction unless the other cables are also bonded to the LPS. If
the bonding conductor is long (some tens of metres) it shall be considered as an impulse
transmission line, in which mode the protection afforded by the bonding will be limited.
Some specific recommendations applicable to bonding of the entry and exit points referred
to in Clause 5.4 are given below:
NOTE: Appendix E provides additional information on earthing and bonding.
(a) Rooftop antennae and communications hardware The bonding conductor should be
attached to the most substantial part of the structural metal supporting the equipment
consistent with it fulfilling the requirements of an air terminal for the LPS of a
building. The bonding conductor to the antenna or communications hardware should
be insulated to at least the level required in AS/NZS 3191, if run within the building,
but may be uninsulated if run externally. The cross-sectional area of the bonding
conductor should be not less than 16 mm
2
if made of copper.
(b) The electricity supply service entry There are two distinct considerations that apply.
Firstly, the electrical installation earth should be bonded to the LPS earth termination
network with a copper conductor of not less than 6 mm
2
cross-sectional area.
Secondly, SPDs should be installed for each active conductor of the electricity supply
service. Where an SPD is mounted on, or in, the building, its earthing system should
be bonded to the LPS by a conductor having a cross-sectional area of not less than
that utilized for its own earthing conductor. Where SPD equipment is separated from
the building (e.g. mounted on a customers electricity supply service pole), the SPD
earth should not be used as the earthing termination for the building LPS, however,
the LPS earth termination network and the SPD earth may be bonded together, if
desired.
(c) The telecommunications service entry This may be either aerial (overhead) or
underground. If aerial, the service should be regarded as a potential entry point for
lightning and an SPD should be fitted, subject to the requirements of the
telecommunications regulatory authority*. The telecommunications service earthing
system shall be bonded to the LPS earth termination network.
If the telecommunications service is underground, the service will act essentially as
an exit point for lightning. In this mode it may be necessary to fit an SPD to the
service to provide a bonding point for potential equalization.
The bonding conductor should have a cross-sectional area of not less than 6 mm
2
if
made of copper.

* In Australia, these requirements are set out in AS/ACIF S009, Installation requirements for customer
cabling.
For DOD Internal Use ONLY
AS/NZS 1768:2007 72
COPYRIGHT
(d) Metallic water supply and sewerage systems Metallic water supply and drainage
systems should be bonded to the LPS and connected to the electricity supply service
earth. However, some water supply authorities fit insulating spacers or ferrules for
galvanic corrosion control at customers installations. These may require bridging by
an SPD as determined in consultation with the water supply authority. Bonding
conductors to these services should have a cross-sectional area of not less than 4 mm
2

if made of copper. Metallic piping systems associated with fire sprinklers, water, hot
water or flammable liquid, that are unavoidably in contact with the exposed
conductive parts of wiring enclosures, cable components or other electrical equipment
shall be connected to such equipment by means of an equipotential bonding
conductor.
If calculation or local experience indicates that the water supply system is of very low
resistance to earth (e.g. less than 0.5 ), it may well be the principal exit point for the
lightning impulse. In such circumstances, consideration should be given to upgrading
the current-carrying capacity of the bonding conductor between the LPS earth and the
water supply system to a cross-sectional area of not less than 35 mm
2
if made of
copper.
(e) Other service lines Specific considerations may apply for some structures. For
example, a radio telephone tower should be bonded to its associated equipment
building; similarly, a pump station should be bonded to an elevated water tower. For
both examples given, the bonding conductor is likely to carry the full lightning
current and should therefore have a cross-sectional area of not less than 35 mm
2
if
made of copper.
(f) Building earthing systems Buildings frequently have several earthing systems that
may be installed independently at different times. These include the electricity supply
service earthing system, the telecommunications earthing system (sometimes more
than one), the LPS earth termination network and other special purpose earthing
systems.
It is generally desirable to bond all such earthing systems but there may be specific
reasons for not doing so. Direct-current-carrying earths, e.g. older telex systems,
should usually be isolated to prevent corrosion damage to other services and earths.
In such cases consideration should be given to bonding these earths through a
galvanic isolator, to facilitate the protection of persons from lightning surges. This
type of isolator can be used where there is a corrosion-based objection to bonding,
e.g. copper-based earths to galvanized iron earths or structures, of which the latter
would suffer galvanic corrosion. If 50 Hz or audio frequency bonding is not needed, a
gas discharge arrestor may serve the purpose. Bonding conductors between earthing
systems should have a cross-sectional area of not less than 4 mm
2
if made of copper.
(g) The LPS earth termination network Where an LPS is in place all of the services
described in Items (a) to (f) should be bonded to the LPS earth termination network.
Caution should be applied when bonding the LPS earth termination network to
cathodically-protected earthing systems, such as cathodically-protected concrete
reinforcing of fuel tanks. Bonding to such systems will require galvanic isolation as
in (f) above.
(h) Bonding of conductive parts Where a reinforced concrete pad, reinforced concrete
walls or metallic building components, e.g. a metal roof, are used as part of an LPS,
these should be interconnected with each other and bonded to the LPS. This bonding
should be performed regardless of whether the building is in a high risk lightning
area.
For DOD Internal Use ONLY
73 AS/NZS 1768:2007

COPYRIGHT
5.6 PROTECTION OF EQUIPMENT
5.6.1 General
Lightning induces overvoltages in electrical service lines, including electricity supply,
telecommunications service lines, signalling, data, and coaxial lines. Cables carrying these
services usually have different points of entry to a structure and may have protective
devices connected to different earthing systems.
Equipment overvoltages may be experienced in the following ways:
(a) By direct conduction of lightning current on the conductors feeding into the building.
An example would be lightning striking overhead power lines. This mechanism is of
lower probability, but involves higher surge currents.
(b) Indirectly, (through magnetic induction, or electrostatic coupling) where lightning
strikes nearby, and surges are induced on the conductors feeding into the building.
This mechanism has a higher probability, but typically results in lower surge currents.
(c) Lightning striking the LPS or other nearby objects, resulting in an EPR. This can
cause potential differences in earthing systems, causing flashover and equipment
damage.
(d) Temporary overvoltages at mains a.c. system frequency that can occur for a number
of reasons.
The strategies to deal with this problem involve equipotential bonding of the earthing
systems, the provision of SPDs, and consideration of wiring practices and shielding
techniques, as appropriate.
AS 4262.2 provides further information on the protection of telecommunications equipment
from overvoltages.
5.6.2 Equipotential bonding for equipment protection
Equipotential bonding is dealt with in other sections of this Standard (Clause 5.5.2 and
Appendix E). The important aspect to note is that for effective protection of equipment,
very good attention needs to be paid to the implementation of the equipotential bonding
scheme. Voltage differences that are insufficient to cause injury to persons can be
extremely damaging to equipment. It is possible to have voltage drops in bonding
conductors that are carrying lightning surges in excess of 1000 V per metre.
It is important that bonding conductors be kept short to reduce this voltage difference, and
to achieve this, all services should enter in close proximity. For protection of equipment,
this concept can be extended to particular areas within the building. For example, consider
the case of a multistorey building with incoming underground services, and a telephone
system installed on an upper floor. On the lower level, the required equipotential bonding
will be performed, and primary surge protection to both power and telecommunications
lines can be fitted at that location, and will connect to the same equipotential earth system.
On this lower level, it may well be that the bonding conductor lengths are not ideal,
depending on where the services enter, and thus the protection provided is compromised.
However, on the upper floor where the telephone system is installed, the same concept can
be repeated, but at this point more control is possible over wiring and equipment locations.
That is, at this location all the services should enter the room at the same point, and
secondary surge protection to both power and telecommunications lines can be provided at
this location with short, direct connections to the common earthing point.
For DOD Internal Use ONLY
AS/NZS 1768:2007 74
COPYRIGHT
5.6.3 Surge protective devices (SPDs)
5.6.3.1 Introduction to SPDs
An SPD is a device intended to mitigate surge overvoltages and overcurrents. To perform
this function, it generally has at least one non-linear component. That is, it behaves in a
relatively benign state until a voltage or current exceeds a predetermined value, then the
SPD begins to act to reduce the voltage or current, in order to prevent damage to equipment
being protected.
Although single components can be used as SPDs, often greater functionality is achieved by
combining components in various arrangements, and SPDs often have other features, such
as mechanisms to indicate their operational status.
5.6.3.2 Components
Overvoltage protective components usually fall into one of the following categories:
(a) Gas discharge devices These devices usually consist of glass or ceramic tubes filled
with an inert gas sealed at each end with a metal electrode. They have breakdown
voltages in the range 70 V to 1 kV with surge current ratings up to 100 kA. The strike
time and firing voltage of these devices are dependent on the rate of increase of
voltage. Unlike clamping devices, gas discharge devices conduct at a much lower
voltage than their firing voltage. This conduction voltage is typically below 30 V.
This fold-back behaviour generally precludes their use by themselves on a.c power
circuits.
Gas discharge devices are available in both two electrode and three electrode
configurations. The latter provide a means of clamping a pair of wires to earth if
either or both conductors are subjected to an overvoltage.
(b) Spark gaps These devices are similar in principle to a gas discharge device, but they
use air, rather than an inert gas, between the electrodes. The devices are inherently
rugged and can handle high surge energies, but typically suffer from relatively high
firing voltages. Devices are available that have been designed to operate on a.c.
power circuits, and their design incorporates mechanisms to extinguish the arc, and
prevent excessive follow-on current. Care needs to be exercised in their installation to
ensure that adequate clearances are provided, and that fusing is chosen that reduces
the incidence of nuisance fuse operation that may occur especially on low current
circuits. The manufacturers advice should be followed on these matters.
(c) Varistors Most modern varistors are made from metal oxide and are known as metal
oxide varistors (MOVs). The resistance of varistors drops significantly when the
voltage exceeds a limit thus clamping the voltage near the limit. The MOV is widely
used in SPD construction and offers a good balance between surge rating and
clamping voltage. Varistors are used on circuits operating at voltages between 10 V
and in excess of 1 kV. They can handle surges in the range of 3 to 100 kA and
respond in tens of nanoseconds. Because MOVs deteriorate with repeated operation,
it is usual to allow a high safety margin in the selection of the device rating in
lightning prone areas. Alternatively, facilities should be provided to give an
indication of device failure.
(d) Solid state devices One form consists of special zener diodes that exhibit voltage-
limiting characteristics and are optimized to handle surge currents. The breakdown
voltages of such devices are typically in the range 5 V to 200 V. They have current
ratings up to several hundred amperes and response times of the order of
10 picoseconds. Another form consists of thyristors, that switch when their operation
voltage is exceeded, and act to clamp overvoltages. Their reduced voltage during
conduction means they can handle higher surge currents, compared with the zener
diode type.
For DOD Internal Use ONLY
75 AS/NZS 1768:2007

COPYRIGHT
The main overvoltage protective components discussed in Items (a) to (d) belong to two
categories:
(i) Voltage-limiting components Sometimes referred to as clamping components, these
include varistors, avalanche or suppressor diodes.
(ii) Voltage-switching components Sometimes referred to as crowbar components, these
include air gaps, gas discharge tubes, thyristors (silicon-controlled rectifiers), triacs.
Care needs to be exercised when using voltage-switching components to make sure that the
devices will cease conduction once the surge has dissipated. The benefit of a voltage-
switching type component is their ability to handle relatively high surge currents.
Overcurrent protective components act to limit excessive currents. These are often used in
telecommunications and signalling circuits, and include fuses, and solid state components
providing the fusing function, but in a resettable manner.
5.6.3.3 SPD configuration
SPDs are configured as being either shunt or series protectors, defined as follows:
(a) Shunt protector Sometimes known as a one-port SPD, it is an SPD connected in
shunt with the circuit to be protected, as shown in Figure 5.3(a). A one-port device
may have separate input and output terminals without a specific series impedance
between these terminals, as shown in Figure 5.3(b). This latter arrangement is
sometimes known as a series connected, shunt protector.
A shunt protector with just two terminals (i.e. does not have separate input and output
terminals) has no inherent limitation with regard to the load current of the circuit to
which it is applied. However, its ability to clamp overvoltages is reduced by the
additional voltage drop that occurs across its connecting leads. For this reason, some
shunt protectors are manufactured with separate input and output terminals. This
arrangement substantially reduces the connecting lead voltage drop problem, but does
mean that the full load current passes through the device, which needs to be designed
to handle this current.

FIGURE 5.3 EXAMPLES OF SHUNT (ONE-PORT) PROTECTORS
(b) Series protector Sometimes known as a two-port SPD, it is an SPD with two sets of
terminals, input and output. A specific series impedance is inserted between these
terminals. Typical examples are shown in Figure 5.4.
For DOD Internal Use ONLY
AS/NZS 1768:2007 76
COPYRIGHT
A series protector also has virtually no connecting lead voltage drop problem, and the
inclusion of the series component does allow coordination between different
overvoltage components, and also enables the creation of a true low pass filter
(generally by the addition of shunt capacitance after the series impedance) that allows
further surge attenuation. The series current limitation of the series protector will
typically be determined by the series impedance. Sometimes a protector is referred to
as an n-stage protector, and although this term is not consistently applied, the n
should refer to the number of shunt overvoltage stages that are separated by series
elements.

FIGURE 5.4 EXAMPLES OF SERIES (TWO-PORT) PROTECTORS
5.6.3.4 Multi-service surge protection device (MSPD)
An MSPD is a combination protector that combines both power protection and
signalling/telecommunications protection in the one device. It is an effective way of
protecting IT and associated equipment that has more than one connected service. By
including all the protection in the one device, the distance between the SPD earth
connections is very short, which dramatically reduces the potential difference between these
services under incident surge conditions. A general diagram of an MSPD is shown in
Figure 5.5.

FIGURE 5.5 MSPD CONFIGURATION
An example of an MSPD, and its installation, is given in Clause 5.6.5.3, Item (d).
For DOD Internal Use ONLY
77 AS/NZS 1768:2007

COPYRIGHT
5.6.3.5 Parameters of an SPD
There are many parameters that could be specified and measured or tested for an SPD, but
the primary parameters relate to how well an SPD limits overvoltages, how much surge
current it handles, and what voltage system is it designed for. The following parameters are
listed together with the IEC symbols for these parameters. It is suggested that
manufacturers and users adopt these parameters and symbols.
NOTES:
1 A product marked using these IEC symbols does not mean that it has been tested to the
relevant IEC Standards.
2 See Appendix F for definitions of the waveshapes.
Maximum continuous operating voltage (U
c
)This is the maximum voltage that can be
continuously applied to the protector. For the Australian and New Zealand power system,
this should be at least 275 V for SPDs connected between the phase and neutral conductors.
Rated load current (I
L
)Maximum continuous rated r.m.s. or d.c. current that can be
supplied to a load connected to the protected output of an SPD.
Maximum surge current (I
max
)This is the peak value of the 8/20 s waveshape current
impulse that the protector can handle. The protector only has to be able to withstand this
surge current once, and so this is known as the single shot rating.
Nominal surge current (I
n
)This is the peak value of the 8/20 s waveshape current
impulse that the protector can handle many times. A protector must be able to withstand at
least 15 impulses at I
n
.
Voltage protection level (U
p
)This is the peak voltage that the protector protects to (limits
the voltage to). It is sometimes referred to as the let-through, or residual, voltage. Under
IEC 61643-1, it is measured at the value of I
n
. However, there are practical issues with
gaining consistent voltage measurements at such high currents, and so it is recommended
that manufacturers quote the value of U
p
for a.c. power systems protectors at least for the
value of surge current equal to 3 kA, so that comparisons between protectors can be made.
In any case, the value stated for U
p
must be clearly coupled with the value of surge current
for which it applies.
NOTE: Where the SPD protects multiple modes (e.g. A-N, A-E and N-E) the surge ratings above
apply to each mode.
There are many other parameters that could be listed, for example, signalling protectors are
often tested with a 10/700 s voltage waveshape, and have parameters such as insertion
loss, return loss, longitudinal balance, bit error rate, near-end crosstalk, etc, but such detail
is beyond the scope of this Standard.
The performance specification for a.c power systems SPDs incorporating filters is not well
specified in other Standards. The primary advantages of incorporating filters into SPD
designs is that they reduce the maximum dv/dt that occurs on the output of the filter, and
this can reduce equipment damage and upset. A suggested performance measure for filters
is
SPD filter dv/dtThe average dv/dt occurring on the output of an SPD measured between
the 20% and 80% of the maximum voltage output, when the SPD is tested with a 6 kV
1.2/50 s, 3 kA 8/20 s waveform as shown in Figure F1. The filter should be loaded with a
resistive load representing 50% of the full load current.
Some SPDs include shunt capacitance that provides a filtering effect at EMI/RFI
frequencies, but provides little benefit at typical lightning surge frequencies. Similarly,
surge current levels may cause inductor saturation in standard EMI/RFI filters, which will
degrade the filter action.
For DOD Internal Use ONLY
AS/NZS 1768:2007 78
COPYRIGHT
The use of an effective filter also typically reduces the let-through voltage of the SPD as
well, and this effect is captured by the U
p
parameter defined above.
5.6.3.6 Temporary overvoltage (TOV)
A TOV is the situation whereby the power frequency voltage on an a.c power system rises
above its normal value. This can be caused by many factors including poor regulation,
faults on the LV or HV distribution system (including phase shorts to neutral or earth, and
loss of neutral conductor), capacitor switching, sudden load rejection, and HV contact on
LV circuits. These events typically last from 0.2 s up to 5 s. The voltages that can occur
during these events are worse for TT and IT power systems, but even on the TN-C-S system
(the MEN system as used in Australia and New Zealand) may be up to 1.7 times the
nominal system voltage.
The effect of these TOVs on SPDs can be catastrophic. Manufacturers of SPDs should
consider this aspect in their product design, and ensure that if the product fails under these
conditions, that it does so safely, which generally means failing in a manner that cannot
cause a fire. The Standards IEC 61643-1 and UL 1449 have specific TOV tests to verify
safe failure mechanisms.
5.6.3.7 Application of SPDs
The following aspects should be considered in the application of SPDs:
(a) Modes of protection With any signal or electrical transmission system employing
two lines and a separate protection earth, two types of transients can occur. The first
type appears as a difference between the two lines, independent of their potential
differences to earth; this is known as a differential mode transient (also called
transverse mode or normal mode). It is illustrated in Figure 5.6 where the transient
voltage source is superimposed onto the normal signal carried by the lines.
The second type appears as a transient between each line and the earth, and is known
as a common mode transient (sometimes called a longitudinal transient). It is
illustrated in Figure 5.7 where the transient voltage sources are superimposed onto the
normal potentials between the lines and earth. This mode is that commonly
experienced by twisted pair circuits as each wire is equally exposed to the transient
voltage source.

FIGURE 5.6 DIFFERENTIAL MODE TRANSIENT
For DOD Internal Use ONLY
79 AS/NZS 1768:2007

COPYRIGHT

FIGURE 5.7 COMMON MODE TRANSIENT
The use of two non-earthed lines is common. The a.c. mains use the active and
neutral lines to supply electricity, with an accompanying earth line for protection.
Telephone lines use two wires over which the signal is transmitted, with neither line
tied to earth. RS-422 signalling for computer data uses two lines for each data
channel, which is known as balanced-pair signalling.
When protective equipment is connected to such lines, both differential and common
mode transients must be suppressed. Placing a protective device across the two
signalling lines alone is not sufficient. The high potentials to earth created by
common mode transients can cause insulation breakdown and arc-over, and can
damage electronic components. Protection against transients can be achieved by the
provision of voltage clamping or diversion devices between the lines, and between the
lines and earth. These will shunt common mode transients to earth before they are
allowed to reach breakdown potentials.
Equipment to be protected is typically more robust to transients from line to earth
(LE) than for transients from line to line (LL). This aspect can be capitalized on in
the design and application of SPDs. Telephone line and signalling line SPDs often use
a three terminal gas arrester as the primary energy handling component, and this
component provides both common mode and differential mode transients. Although a
gas arrester has a relatively high striking voltage, it typically provides sufficient
protection against the LE transient, and if required, a varistor or solid state device
can provide additional LL protection.
Similarly, experience has shown that a.c. equipment is more easily damaged from line
to neutral (LN) transients, and although protection could be provided in all modes
(LN, LE, NE), good protection is usually obtained by providing LN and NE
protection modes only. Indeed, at the building point-of-entry in a TN-C-S system, the
neutral conductor is connected to earth, and SPDs applied as recommended adjacent
to this MEN link, need only comprise of the LN protection mode.
(b) SPD location There are many possible locations where SPDs could be installed
within a facility. The aim is to install SPDs in locations that provide effective
protection to the equipment nominated for protection, and to do so economically.
The most effective method of providing effective surge protection for a facility is to
provide SPDs at the building service point-of-entry (known as primary protection),
and then, if necessary, to provide additional surge protection within the building
closer to the equipment to be protected (known as secondary protection). Primary
protection is important because the main function of such an SPD is to keep most of
the surge current from entering the building, by diverting it directly to earth.
For DOD Internal Use ONLY
AS/NZS 1768:2007 80
COPYRIGHT
When considering a.c. power circuit protection, the concept of location categories can
be used (see Figure F3). Location category C is the building point-of-entry and is
where primary protection would be installed. Location categories A and B are further
within the building and are potential locations for secondary protection, to be fitted as
required, especially in the following situations:
(i) Sensitive equipment is present. An example would be a computer room.
(ii) The distance between the SPD located at the entrance and the equipment to be
protected is too long (see Coordination in Item (d)).
(iii) There is internal equipment generating switching surges, or other internal
interference sources, inside the building.
(c) Surge ratings Having defined location categories, appropriate surge ratings for these
categories can be recommended. Before considering these ratings several aspects
need to be discussed
(i) a lightning surge travelling within a building is attenuated by the SPDs it
encounters and the impedance from the building wiring itself. Thus higher
levels of surge current are likely to be encountered at the building point-of-
entry, compared to the distant end of a branch circuit;
(ii) in choosing an appropriate surge rating, it needs to be understood that the surge
rating of a SPD is a major factor in determining its useful lifetime. An SPD
with a particular I
max
rating is not chosen on the basis of handling a single event
of that magnitude, but rather it will be expected to handle many events of a
lower amplitude;
NOTE: For example an SPD with an I
max
rating of 40 kA might typically handle 15
surges of 15 kA.
(iii) the lightning surge current to be handled by a point-of-entry SPD has
traditionally been considered to come into the building via the service
conductors. However, another mechanism is now understood to exist. If
lightning strikes the building LPS, or even the ground or an object nearby, a
local EPR occurs. The incoming service conductors are typically referenced to a
distant earth (such as the neutral conductor grounded at the secondary
transformer some distance down the street, with the phase conductor also being
referenced to that distant earth by virtue of the transformer winding). The effect
of the local EPR is that a proportion of the lightning current flows out through
the point-of-entry SPDs on its way to reaching the distant earth. The surge
current in the SPDs in this case is very large, being a significant proportion of
the lightning current itself.
While Table 5.1 gives a surge rating for SPDs in this case (Category C3) using
the 8/20 s waveshape, it should be acknowledged that the IEC standards make
reference to a 10/350 s waveshape for use in this case, and the symbol given
to the current rating using this waveshape is I
imp
. It has been found that a factor
of 10 may loosely be used to provide an indication of the equivalence between
these two waveshapes for typical SPD ratings. For example, an SPD
withstanding a 100 kA 8/20 s impulse might be expected to withstand a 10 kA
10/350 s impulse. The actual factor can only be determined for a particular
SPD by testing.
Given this discussion, for a.c. power system SPDs, the following surge current ratings
are recommended, where the surge rating is the I
max
, or single shot, 8/20 s value, and
apply for each SPD from the phase to neutral conductors.
For DOD Internal Use ONLY
81 AS/NZS 1768:2007

COPYRIGHT
TABLE 5.1
RECOMMENDED SURGE RATINGS FOR A.C. POWER SYSTEM
SPDs PER PHASE
Category SPD location I
max
rating
A Long final subcircuits and electricity supply outlets 3 10 kA
B Major submains, short final subcircuits and load centres 10 40 kA
C1 Service entrance, other than below 40 kA
C2 Service entrance, building fed by long overhead service lines, or is
a large industrial or commercial premises
40 100 kA
C3 Service entrance, building in a high lightning area, or fitted with a
LPS
100 kA
(d) Coordination Often the approach taken is to have the primary SPD handle the bulk
energy (surge current) and not be too concerned about the U
p
value for that protector.
A secondary protector that will not need to handle such a high value of surge current,
can be installed close to the equipment and can be chosen to have an acceptable U
p

value. However, to achieve this result, careful coordination between the two devices
needs to be undertaken. This is quite a complex matter, and a total examination of the
issues is beyond the scope of this Standard. However, a simple rule to apply is to
ensure that there is at least 10 to 20 m of electrical cabling between the two SPDs. If
this cannot be achieved, purpose built inductors are available that can be placed in the
circuit to achieve this effective separation.
A more complex primary SPD may incorporate multiple stages with the decoupling
impedance within the device itself, and such an approach ensures the stages are
properly coordinated and typically results in an SPD with good energy handling
capability and relatively low U
p
values.
(e) Fusing and wiring considerations It is essential to provide a fuse or circuit breaker
ahead of the SPD to provide for the safe disconnection of a failed SPD.
Manufacturers usually recommend an appropriate rating for such a fuse, and often the
value specified has been used in approval testing of the SPD. Safe disconnection of a
failed SPD would point toward a low amperage fuse, but too low a value will cause
nuisance operation as the SPD diverts surge currents. In the absence of any specific
guidance from the SPD manufacturer, a high rupturing capacity (HRC) 32 A or 63 A
fuse or circuit breaker with a fault rating compatible with the switchboard could be
used. SPDs should be installed after the main switch but prior to any residual current
device (RCD). The connection wiring from the main switch via the protective circuit
breaker and the SPD back to the neutral near the MEN point should be at least 6 mm
2

and as short and direct as possible. This total connection lead length must be less than
1 m in length (ideally 300600 mm). When carrying a lightning surge, the voltage
dropped across a conductor can be 1000 V/m, and is caused by the inductance, and
not the resistance, of the conductor. This is shown in Figure 5.8(a), and the voltage
drop across the connecting conductor adds to the U
p
of the protector. For example, if
the U
p
of the SPD was 600 V, and the interconnecting cable had a voltage drop of
1000 V, then the effective protection provided by the installed protector would be the
sum of these, at 1600 V.
If the terminals of the SPD are rated for the required load current level, a
configuration as shown in Figure 5.8(b) is preferred. This wiring method is
sometimes known as a Kelvin connection, and eliminates the interconnecting lead
problem. Failing this, twisting the connecting conductors together as shown in
Figure 5.8(c) can have a substantial impact on reducing the voltage drop.
For DOD Internal Use ONLY
AS/NZS 1768:2007 82
COPYRIGHT

FIGURE 5.8 WIRING OF SPDs
(f) Failure modes of SPDs Typically an SPD initially fails to a low impedance state,
and the resulting a.c. current that then flows into the SPD either causes the SPDs
internal fusing to operate, or causes external fusing to operate. Consideration needs to
be given to the most desirable location for the external fuse, and whether it is
desirable for power to be disconnected from the load when the SPD fails. If the
external fuse is in series with the load current, power will be disconnected from the
load when the SPD fails. In some applications this is considered beneficial, since the
SPD is no longer protecting the load. However, locating the fuse in the non-load
carrying SPD connection wiring, means that a ruptured fuse will isolate the SPD, but
allow power to continue to the load.
SPDs are often fitted with some form of visual status indication to show their
operational status, and may additionally be fitted with contacts to allow for remote
monitoring.
(g) Withstand voltage of equipment The equipment to be protected may have a level of
resistability to surges designed into it. In particular, a resistance level to
electromagnetic interference (EMI) disturbances is mandated. Ideally, the U
p
of the
externally provided SPDs should be lower than the U
p
of any equipment internal
surge protection components, otherwise the internal components may be damaged
instead of being protected by the external SPDs. At some point in the future,
equipment to be protected may be marked with a surge voltage level that it will
withstand, and a symbol of U
w
has been proposed for this withstand voltage.
Selection of SPDs to protect such equipment would be straightforward.
Lightning surges need not physically damage equipment for it to experience
problems. Erratic operation, that may or may not require manual resetting, can occur
and lead to data loss at surge levels which are lower than those required to cause
hardware failure. Rapid changes in the voltage supply, even those for which the
amplitude does not exceed the normal a.c. power peak, can cause problems. This
dv/dt problem can be reduced by utilizing SPDs with filters.
Figure F2 contains a curve that illustrates the typical voltage/time tolerance of
computing equipment.
5.6.4 Magnetic shielding and line routing
Magnetic shielding reduces incident electromagnetic fields, and can also provide a
reduction in the emissions from electrically noisy equipment being operated within the
building. The complexity of shielding can range from the use of metallic conduits, to simple
metal enclosures or cabinets, and up to whole rooms being comprised of shielding
materials. Such shields need to be earthed to be effective, and any SPDs provided to
conductors entering the shielded area need to be effectively connected to the shield.
For DOD Internal Use ONLY
83 AS/NZS 1768:2007

COPYRIGHT
The amount of surge energy directly induced into building conductors from nearby
lightning strikes depends on the closeness of the current source, and the loop area formed
by the conductors. Conductors of the same service should be run together, along with an
earthing conductor, or otherwise run in close proximity to other earthed components, such
as earthed cable trays. To reduce the inductive loop area, such cables should be neatly tied
together and not allowed to splay out over the whole tray width, for example.
5.6.5 Practical installation examples
5.6.5.1 Determine protection needs
There are many aspects to providing effective lightning protection to equipment as has been
detailed in preceding clauses. However, it is useful to consider some examples that show a
simple methodology for determining where SPDs are required, and how to correctly apply
them.
The method consists of firstly determining what it is that requires protection, and then
drawing an imaginary box around it. Each location where electrical lines cross the box is a
potential location for SPDs, and they should be provided where the particular electrical line
is long or otherwise prone to having surges on it. Then the earths of the SPDs are connected
together as well as to the earths of the equipment, and taken to earth. If the initial box is
very large and services physically enter the box at widely spaced distances, it may be
prudent to draw other boxes inside (or alongside) the first, around particular items of
sensitive equipment to be protected, and repeat the process.
Typically it will be necessary to consider the following points for SPDs:
(a) At the point-of-entry of external services e.g. electricity supply and
telecommunications.
(b) At the connection of the external services to the equipment.
(c) At the connection of long internal cabling to the equipment e.g. communications and
LAN.
The following two mechanisms can damage equipment:
(i) An excessive voltage/current enters the building via a service due to either a lack of
protection or incorrectly installed protection.
NOTE: When protection is correctly installed both the mains and telecommunications point-
of-entry SPDs are bonded to the main earth bar by conductors of 1.5 m or less.
(ii) An excessive voltage/current is induced into the internal wiring loop.
5.6.5.2 Protection procedure
The procedure for protecting equipment is as follows:
(a) Install secondary protection at the equipment when the risk of damage due to
induction into the external service conductors (electricity supply and
telecommunications) and the building conductors exceeds an acceptable level.
(b) Install point-of-entry protection when the risk of damage due to a direct strike to the
structure or the service conductors exceeds an acceptable level.
NOTES:
1 A prime role of the point-of-entry protection, apart from preventing dangerous discharges
and step and touch potentials, is to protect the secondary protection from damage.
2 Telecommunications SPDs on customer cabling should be installed in accordance with
AS/ACIF S009 (in Australia only). In Australia, a licensed cabler must do this
installation. The installation of SPDs in the main switchboard (MSB) and in electrical
distribution boards (DBs) should be in accordance with AS/NZS 3000 and AS 4070. A
licensed electrician must do this installation.
For DOD Internal Use ONLY
AS/NZS 1768:2007 84
COPYRIGHT
5.6.5.3 Protection examples
The following examples show these principles being implemented:
(a) A central PLC and remote sensor In this example it is determined that a particular
industrial process must be protected. It consists of a central controller (PLC), and
various sensors and controls. For simplicity, the example will show two sensors, one
at a considerable distance from the PLC, and another close to the PLC. The
arrangement is as shown in Figure 5.9.

LEGEND:
BB = Bonding bar
MDF = Main distribution frame
MEB = Main earth bar
MEB = Main earth bar
MSB = Main switchboard
PLC = Programmable logic controller
FIGURE 5.9 EXAMPLE OF CENTRAL PLC AND REMOTE SENSOR
The PLC has a operator console and a modem to allow remote communication, and
consequently has electrical and telephone services. The signal line is over 1 km in
length. The first box is drawn around the PLC and associated close by equipment.
Other close by sensors or controls would be included within this box. Three electrical
services are identified that cross this box the a.c. power, the telephone line, and the
signal line to the remote sensor. Since all three are long or otherwise prone to having
surges on them, they need SPDs. Since the operator console is close to the PLC there
is no reasonable likelihood of surges impinging on that connection. Likewise, any
sensors or controls close to the PLC would not normally require protection.
For DOD Internal Use ONLY
85 AS/NZS 1768:2007

COPYRIGHT
Having identified the SPDs required close to the PLC, their installation is important.
They should be installed close to the equipment they are to protect, and must have
their earths connected together, and connected to the PLC earth, and taken to earth. In
practice, this might be laid out as follows. The PLC and modem are mounted next to
each other on a rack. Immediately below them, the required SPDs are mounted in a
row, with an earthing busbar immediately below them, connected at each end to the
rack frame. Each SPD will have a short direct connection to the busbar not exceeding
100 mm, and the PLC will also have a direct connection to the busbar. In this manner,
excellent equipotential bonding will be achieved for this equipment and associated
SPDs.
The SPD on the signal line at the PLC end does not provide protection for the remote
sensor. Again, a box is drawn around the sensor. The only line here is the signal line,
and so an SPD is provided on it. This SPD is earthed with a direct short connection to
the sensor earth (and associated pipe or vessel), and taken to a local earth. There is no
point in trying to connect this very distant earth to the PLC earth via a bonding
conductor.
In addition to the secondary SPDs installed closed to the equipment, the prudent
provision of primary point-of-entry SPDs has also been shown. Depending on the
assessed exposure of the signal line, which would include such considerations as
whether it is run in metallic conduit or not, it may be prudent to include primary
point-of-entry protection on the PLC signal lines where they enter the building, in
addition to the secondary protection shown at the PLC.
(b) A video surveillance system This example is very similar to the case just described.
The central monitoring and recording equipment will have surge protection applied to
the long video camera feeds and to the a.c. power line. The video feeds that are
selected for protection will need all the associated signal lines protected, and this may
include the video feed, the power supply leads, and any pan and tilt control signals.
The earths of these SPDs will connect to each other and to the equipment earth. Video
cameras that are located nearby in the same building may not need surge protection
fitted. Those video cameras that are located a long distance from the central
monitoring and recording equipment will need the same type of protection fitted at
the remote end as was fitted at the central end. The earths of these SPDs must be
connected to the video camera earth, and then be taken to a local earth. Although all
earth connections should be as short as possible, it is particularly important to keep
the length of the SPD earths to video camera earth short.
(c) A multistorey building with PABX on upper floor In this example illustrated in
Figure 5.10 it has been determined that protection is required. This is a multistorey
building with services entering on ground floor, and PABX on an upper floor. A box
has been drawn around the PABX. Regardless of whether the point-of-entry location
of the telecoms and power services are co-located, there can be induction into the
internal wiring between the ground floor and the PABX. Therefore the electricity
supply, the exchange line and the outdoor extensions will require protection at the
PABX. The local handsets do not need protection (inside the inner box). To ensure
adequate protection of the PABX it may be necessary to have a DB and a telecoms
distributor (IDF) co-located with the PABX. SPDs are installed in the DB and the
IDF. In areas where direct strike protection is required SPDs need to be installed at
the point-of-entry (see AS 4262.1).
For DOD Internal Use ONLY
AS/NZS 1768:2007 86
COPYRIGHT

LEGEND:
BB = Bonding bar
DB = Distribution board
IDF = Intermediate distribution frame
MDF = Main distribution frame
MEB = Main earth bar
MSB = Main switchboard
PABX = Private automatic branch exchange
FIGURE 5.10 EXAMPLE OF MULTISTOREY BUILDING WITH PABX
(d) A domestic computer and ADSL modem In this example it has been determined that
protection is required. Figure 5.11 shows how this has been implemented. A box has
been drawn around the ADSL modem and all interconnected equipment. A box has
also been drawn around the fax machine. The simplest way to provide SPDs with
short bonding conductors to a common earth point is to use an MSPD so this has been
used, along with a power board to provide additional protected outlets. A Fax
machine at the same physical location has also been protected using a second MSPD.
For DOD Internal Use ONLY
87 AS/NZS 1768:2007

COPYRIGHT

LEGEND:
ADSL = Asynchronous digital subscriber line
MEB = Main earth bar
MSPD = Multi-service surge protection device
SB = Switchboard
FIGURE 5.11 EXAMPLE OF DOMESTIC COMPUTER AND ADSL MODEM
Although shown in Figure 5.11, point-of-entry protection would normally only be installed
in areas where direct strikes are likely.
(e) A rooftop cellular base station
In this example a cellular base station is located on the roof of a multistorey building.
Figure 5.12 shows an effective means of providing lightning, earthing and surge
protection.
For DOD Internal Use ONLY
AS/NZS 1768:2007 88
COPYRIGHT

LEGEND:
BB = Bonding bar
DB = Distribution board
MEB = Main earth bar
MSB = Main switchboard
FIGURE 5.12 EXAMPLE OF ROOFTOP CELLULAR BASE STATION
The tower, being all steel, is self protecting. It should be bonded to the building lightning
protection system. If there is no building LPS the tower and cabin should be earthed by a
minimum of two downconductors. Should lightning strike the tower or the building LPS the
potential of the tower and cabin will rise. Therefore the tower and cabin together must be
treated as a separate entity.
For DOD Internal Use ONLY
89 AS/NZS 1768:2007

COPYRIGHT
The a.c. power supply is fed to the base station distribution board from a main switchboard
located in the basement of the building. An SPD, normally a surge diverter, would be
installed at the MSB. A second SPD, a surge filter, is installed on the a.c. power feed to the
rooftop distribution board. All other metallic services, for example antenna feeders should
be bonded and fitted with SPDs. All equipment should be referenced to a common earth
bonding bar in the cabin and this in turn bonded to the tower and building LPS. There will
be a connection to the main a.c. earth via the earth conductor in the power cable to the roof.
Good practice would dictate that all metallic services should enter the cabin on the same
side and the common earth to the tower and LPS should exit the same side.
It should be noted that in the event of a lightning strike to the tower, conducted currents
will flow through the power earth conductor, and care should be taken to segregate cables if
possible.
Also, this description only considers the equipment inside the box (i.e. inside the cabin).
Antennas installed on the tower that contain electronics may require additional protection
measures.
For DOD Internal Use ONLY
AS/NZS 1768:2007 90
COPYRIGHT
S E C T I O N 6 P R O T E C T I O N O F
M I S C E L L A N E O U S S T R U C T U R E S A N D
P R O P E R T Y
6.1 SCOPE OF SECTION
This Section provides recommendations for the protection of a variety of structures and
property against lightning where such protection is deemed necessary (see Section 2). The
recommendations of Sections 4 and 5 should be observed except where otherwise indicated.
6.2 STRUCTURES WITH ANTENNAS
6.2.1 Indoor antenna system
Structures protected against lightning in accordance with the recommendations of this
Standard may be equipped with indoor radio and television receiving antennas without
further precautions, provided that the separation between the antenna system, including its
down leads or feeders, and the external LPS or any of its internal sections is in accordance
with the values in Clause 4.16.
6.2.2 Outdoor antennas on protected structures
Structures protected against lightning in accordance with the recommendations of this
Standard may be equipped with outdoor radio and television receiving antennas without
further precautions, provided that every part of the antenna system, including any
supporting metalwork, is within the zone of protection of the LPS (see Clause 4.4). Where
these conditions cannot be fulfilled, precautions should be taken to ensure that the lightning
current can be discharged to earth without damage to the structure or injury to its occupants
with an antenna system fitted
(a) directly onto a protected structure. This can be accomplished by connecting the
antenna bracket structure to the LPS at the nearest point accessible below the antenna
installation; or
(b) on a metallic support structure that projects above the LPS. This can be accomplished
by connecting the antenna support structure to the LPS at the nearest point accessible
below the antenna installation.
NOTE: Consideration should be given to the fitting of SPDs in the conductors connected to the
antenna system.
6.2.3 Antennas on unprotected structures
Before installing an antenna on an unprotected structure, the need to provide an LPS should
be assessed as described in Section 2.
6.2.4 Earthing of radio systems
The earthing electrode of the LPS may also be used for the purpose of earthing a radio
system.
6.3 STRUCTURES NEAR TREES
When a tree is struck by lightning, a voltage drop develops along its branches, trunk and
roots. The side-flash clearances between the tree and adjacent structures are set by taking
100 kV/m as the flashover strength of unseasoned wet timber and 500 kV/m as the
breakdown strength of air. If the tree does not exceed the height of the structure its presence
can be disregarded. If the tree is taller than the structure, the following clearances between
the structure and the tree may be considered as safe:
(a) For normal structures; one-third of the height of the structure.
For DOD Internal Use ONLY
91 AS/NZS 1768:2007

COPYRIGHT
(b) For structures with explosive or highly-flammable contents; the height of the
structure.
If the clearances cannot be met then the structure should be fitted with lightning protection
in such a manner that the side-flash always terminates on the protection system.
If the tree is fitted with an LPS, no further protection will be necessary for the structure
provided that the conditions for the zone of protection and separation are fulfilled.
6.4 PROTECTION OF TREES
The protection of trees against the effects of lightning needs to be considered only where
the preservation of the tree is desired for historical or other reasons. For such cases the
following recommendations are made:
(a) A main downconductor should be run from the topmost part of the main stem to the
earth termination and should be protected from mechanical damage near ground level.
(b) Large upper branches should be provided with branch conductors bonded to the main
conductor.
(c) In the fixing of the conductors, allowance should be made for swaying in the wind
and the natural growth of the tree.
(d) Test joints may be waived.
(e) The earth termination should consist of two rods driven into the ground on opposite
sides of, and close to, the trunk of the tree. A strip conductor should be buried to a
depth of 300 mm to encircle the roots of the tree at a minimum distance of 8 m radius
from the centre of the tree or at a distance equal to 1 m beyond the spread of the
foliage, whichever is the greater. This conductor should also be bonded to the rods by
two radial conductors. The earth terminations and resistance should comply with
Clause 4.15.
(f) Where two or more trees are so close together that their encircling earth conductors
would intersect, one conductor adequately connected to the earth rods should be
buried so as to surround the roots of all the trees.
NOTE: The recommended earth termination network is designed to protect the roots of the tree
and to reduce the potential gradient, in the event of a lightning discharge to the tree, to a safe
value within the area bounded by the outer buried strip conductor.
6.5 CHIMNEYS, METAL GUY-WIRES OR WIRE ROPES
6.5.1 General
Metal guy-wires or wire ropes attached to steel anchor rods set in earth or buried reinforced
concrete anchor blocks may be considered as sufficiently earthed. Other guy-wires or wire
ropes should be earthed e.g. where fixed above ground to structures.
For means of securing conductors to structures, see Clause 4.10.
Metal chimneys or flues need no protection against lightning other than that afforded by
their construction, except that they should be properly earthed. If the construction of the
foundation does not provide ample electrical connection with the earth, earth connections
should be provided similar to those recommended for chimneys made of materials other
than metal (see Clause 6.5.3).
6.5.2 Metal ladders and metal linings
Where chimneys have a metal ladder or lining they should be connected to the LPS at their
upper and lower ends.
For DOD Internal Use ONLY
AS/NZS 1768:2007 92
COPYRIGHT
6.5.3 Chimneys
Chimneys consisting partly or wholly of reinforced concrete should comply with the
recommendations of Clauses 4.5, 4.10, 4.12 and 4.16, and, in addition, the reinforcing metal
should be electrically connected together and electrically connected to the downconductors
at the top and bottom of the concrete.
Chimneys, other than those of reinforced concrete or metal construction, shall be protected
in accordance with the requirements of Section 4, when required by the risk assessment of
Section 2.
NOTE: In existing chimneys, the reinforcement of which may be electrically continuous, it is
recommended that additional connections be made at points where the reinforcing rods are
accessible.
6.6 PROTECTION OF MINES
6.6.1 Factors influencing need for protection
In mining operations, electric shocks, possible premature detonation of explosives, and
ignition of flammable gases from the effects of lightning are recognized additional hazards.
Because these hazards are associated with the effects of lightning at or below the ground
surface, factors additional to the risk assessment approach of Section 2 influence the need
to provide lightning protection. These additional factors are associated with earth
resistivity, depth of the mining operation, presence of persons and the presence of
flammable gas or explosives. The degree of hazard is regarded as greater the shallower the
depth of the operation and the higher the resistivity of the earth involved.
Generally, these additional factors will indicate that lightning protection should be provided
or precautionary work procedures adopted.
6.6.2 Object of recommendations
The following recommendations for lightning protection for mining operations are aimed at
reducing the risk of electric shock and premature detonation of explosives. While the
recommendations will also reduce the risk of ignition of flammable gases from the effects
of lightning, flammable gas ignition is best prevented by ensuring that flammable
concentrations of gases do not occur.
The intent of the recommended LPS is to reduce the possibility of substantial voltages
appearing between conducting structures and between conducting structures and earth in
their immediate vicinity. Absolute protection against the effects of lightning cannot,
however, be guaranteed with the recommended protection system alone. Consequently,
recommendations are also given for operational procedures for the use of explosives when
lightning occurs close to the mine site.
In surface workings, the premature detonation of explosives, both directly and through
electric detonators, are considered possible, while in underground operations, the premature
detonation of explosives is considered possible only through electric detonators.
6.6.3 Underground workings
6.6.3.1 General
The following recommendations apply particularly to underground workings where electric
detonators are used as the means of initiating explosives.
6.6.3.2 Electric detonators
Detonators specially designed to reduce the risk of ignition by electrical discharge across
the fuse head should be used.
For DOD Internal Use ONLY
93 AS/NZS 1768:2007

COPYRIGHT
6.6.3.3 Shot firing circuit
Requirements for circuit equipment and procedures to be adopted for firing explosives
electrically are set out in AS 2187.2 or NZS 4403. Additional to those requirements, where
fixed wiring is used as part of the firing circuit, the conductors should be enclosed in metal
screening, armouring or conduit. This metal screening, armouring or conduit should be
connected to the electrical system earthing and bonded to other metallic structures as
described in Clause 6.6.3.7.
6.6.3.4 Overhead electricity supply service lines
To minimize the magnitude of incoming lightning surges on overhead electricity supply
service lines, overhead earth wires should be provided on all overhead electricity supply
service lines within 1.5 km of the mine.
Additionally, SPDs should be installed at the termination of the overhead electricity supply
service line for protection of connected cables or equipment.
6.6.3.5 Surface structures
Lightning protection should be provided on all structures above underground openings,
such as winder head frames. With other structures and buildings, the need to protect or not
should be determined from Section 2. It must be remembered that a surface LPS will still
discharge current to underground workings.
Lightning protection of surface structures should be carried out in accordance with
Section 4 and, where these buildings have explosive or highly-flammable contents, the
additional recommendations of Section 7.
Where various conductive structures, such as metallic enclosures of air, water and
electricity services, or reinforcing steel in concrete foundations, are laid in or on the
ground, advantage should be taken of these to reduce the earthing resistance of the LPS by
interconnecting and bonding these structures together and to the LPS earth termination
network. Typical sizes of bonding conductors are given in Table 4.6.
6.6.3.6 Bonding of surface metalwork
All metal structures entering openings to underground workings of a mine should be bonded
together at the point-of-entry to the opening and connected to the LPS earth termination
network of structures above the opening. This includes any reinforcing steel in the shaft,
concrete lining, shaft steel work, guides and ladders, armouring and sheathing of electrical
cables, air, water and ventilating pipes, rails and bell rope attachments. Typical sizes of
bonding conductors are given in Table 4.6.
6.6.3.7 Bonding of underground metalwork
In addition to the bonding recommended in Clause 6.6.3.6, metal structures and services in
underground access shafts should also be bonded together at intervals of not more than
75 m. Rock-bolted support structures are deemed to provide an adequate earth for this
purpose.
Winding ropes, guide ropes and balance ropes cannot be bonded to other structures except
at fixing points and, possibly ineffectively, through conveyances. High voltages relative to
their surrounds could occur during lightning activity.
6.6.3.8 Further precautions
The degree of hazard in any mine, both from electric shock and initiation of electric
detonators, is related to the depth of the operations. This relationship is inadequately
defined at present.
For DOD Internal Use ONLY
AS/NZS 1768:2007 94
COPYRIGHT
Shaft sinking and drifting are particular operations where lightning is a recognized hazard.
With these operations all work associated with electrical blasting should be suspended and
persons withdrawn to a safe distance when an electrical storm is approaching.
A conservative approach would require that the precautions applied to shaft sinking and
drifting be applied to all underground operations.
6.6.4 Surface workings
6.6.4.1 General
The following recommendations apply to surface mining operations where any type of
explosive is used in the mining operation.
6.6.4.2 Equipment
For many surface workings involving blasting operations, action need only be taken in the
immediate vicinity of the area where blasting takes place. This is because no
interconnection by metallic structures, such as air/water/electricity services, exists with
distant structures or earth. Where these services exist the recommendations for underground
working, of Clauses 6.6.3.3 to 6.6.3.5 apply and, where practicable, the bonding
recommendations of Clause 6.6.3.7 should also apply. Where electric detonators are used,
electric detonators of the type described in Clause 6.6.3.2 should be used.
6.6.4.3 On-site precautions
All work associated with blasting operations should be suspended and persons should be
withdrawn to a safe distance from explosives when an electric storm is approaching.
High equipment, such as drilling rigs, shovels and draglines, that may increase lightning
locality concentration, should be moved to a safe distance from the area where blasting is to
take place prior to explosives being brought to the site.
6.6.5 Lightning detector
Specially designed lightning detectors should be provided to warn of approaching electrical
storms so that the precautions set out in Clauses 6.6.3.8 and 6.6.4.3 may be taken.
6.7 PROTECTION OF BOATS
6.7.1 General
A boat should be considered to be at risk both because of its method of construction (except
for metal-hulled boats) and because it forms a marked protrusion above the surrounding
water surfaces. Overseas statistics show that in excess of 10 percent of fatalities occurring
on cruising sailing boats are due to lightning.
While the principles to be applied will not differ from those for land-based structures, the
methods employed will depend on the form of construction and the type of boat to be
protected.
NOTE: For further detail on the protection of boats against lightning refer to ISO 10134 and
Paragraph G2, Ref 7.
6.7.2 Elements of the protection system
6.7.2.1 Air terminal
A metal mast or the metal fitting on a timber mast will act as an adequate air terminal.
6.7.2.2 Downconductors
The mast, if metallic or if provided with a metal track, and stays will both act as
downconductors and each should be connected to an earth termination.
Stays as small as 3 mm diameter steel wire will serve as effective downconductors, but may
be damaged under severe lightning discharges.
For DOD Internal Use ONLY
95 AS/NZS 1768:2007

COPYRIGHT
6.7.2.3 Earthing
Any metal surface that is normally submerged in the water will provide adequate earthing.
Propellers, metal rudder surfaces and metal keels may be used. The earth plate for the radio
transmitter may also be used, providing that it is constructed of solid material and not of the
porous type. A metal or a ferro-cement hull also constitutes an adequate earth.
6.7.2.4 Metallic objects
Metallic objects that are permanent parts of the boat and whose function would not
seriously be affected by earthing should be made part of the LPS by interconnection with it.
NOTE: The purpose of interconnecting the metal parts of a boat with a downconductor is to
prevent side-flashes to metal objects that could form part of an alternative path to earth or which
could bridge out a substantial length of the downconductor.
A general rule is, that if the non-conducting part of the alternative path through such object
is less than one-eighth of the length of downconductor bridged out, then that object should
be electrically interconnected with the downconductor.
6.7.2.5 Radio transceivers
A whip antenna consisting of a fine wire embedded in a glass fibre tube cannot be
considered a satisfactory lightning conductor and should be folded down during a lightning
storm.
All radio equipment or other navigational equipment with exposed transducers such as
radar, wind speed/direction indicators, and the like, should be fitted with effectively-earthed
spark gaps or SPDs. Alternatively, input cabling should be disconnected from the
equipment if there appears to be imminent danger of the boat being struck by lightning.
6.7.2.6 Corrosion
Care should be taken that the design of the LPS does not promote the occurrence of
electrolytic or galvanic corrosion. Bonding of dissimilar metals and interconnection of the
earth terminals of different pieces of electrical equipment should not be undertaken without
expert knowledge of the possible problems involved (see also Clause 4.7.2).
6.7.3 Installation recommendations
6.7.3.1 Protection of boats with masts
Sailing or power boats that have a mast or masts of sufficient height to give an adequate
zone of protection in accordance with Clause 4.4 may be protected by earthing the lower
ends of the standing rigging and the base of a metallic mast, or the lower end of a
continuous metal sail track on a timber mast.
Where the mast of a boat is stepped on deck, particular care should be taken to ensure that
the conductor from the base of the mast follows a direct route if it passes through the
accommodation section of the boat, otherwise a situation analogous to that shown in
Figure 4.8 may occur.
A typical small sailing boat with aluminium mast stepped on deck, glass fibre hull with the
metal ballast encapsulated in the glass fibre (or unballasted and with a non-metallic
centreboard) and with chainplates moulded into the hull provides something of a problem.
In such cases, it is suggested that some protection be sought when necessary by temporarily
connecting the mast and stays together at deck level by a length of chain or other flexible
conductor and allowing a short length of chain or the conductor to hang in the water at each
chainplate.
For DOD Internal Use ONLY
AS/NZS 1768:2007 96
COPYRIGHT
6.7.3.2 Protection of boats without masts
Boats without masts do not constitute as high a risk as boats with masts. However, where
the size of the boat is such as to cause a marked protrusion above the surrounding water
surfaces, such boats should be fitted with air terminals that will give at least the protection
recommended in Section 4 for land-based structures.
6.7.4 Precautions for persons and maintenance suggestions
To the extent consistent with safe handling and navigation of the boat during a lightning
storm, persons should remain inside a closed boat and avoid contact with metallic items
such as gear levers or spotlight control handles. Persons should stay as far as practicable
from any parts of the standing rigging or other items forming part of a downconductor. No
person should be in the water or dangle arms or legs in the water.
If a boat has been struck by lightning, compasses and navigation instruments should be
checked for calibration. Protective coatings on steel hulls and glass fibre sheathing over
ballast keels should also be checked for damage. All standing and running rigging and
associated fittings should be checked in detail.
6.7.5 Bonding the lightning protection system to the vessels electrical wiring system
earth
The interworking and bonding of the LPS on a boat should recognize that the electrical
wiring system on a boat is commonly only a final subcircuit. As such, the wiring will be
very light, and neither the live conductors (whether or not energized) nor the earthing
arrangements, are capable of carrying lightning discharge current. Even with a larger
vessel, where the wiring is for a submain or a complete installation with a generator, this
will often still be the case, though larger wire sizes would be in use.
As a consequence, the LPS should be designed initially as a self-contained unit, even as far
as selecting and arranging the most appropriate below water level earthing electrode, in
accordance with Clause 6.7.2.3.
The wiring systems likely to be encountered (see AS/NZS 3004) are
(a) a conventional AS/NZS 3000 arrangement with an inlet socket; or
(b) a conventional arrangement, but with the shore earth broken (for voltages less than
about 2 V) by a galvanic isolator. The galvanic isolator may be located either on
board, or on shore; or
(c) a system where the need for an onboard earthing system is removed by either an
onboard or a shore-mounted isolation transformer.
Items (b) and (c) above are to avoid galvanic or electrolytic corrosion of metallic skin
fittings below the water line from interaction with shore earthing. It should be noted that
Item (c) is not intended to give effect to the usual function of isolation transformers, which
is to avoid earth path electric shock. The ship installation may have common fed
accessories off the isolation transformer secondary, and all systems may incorporate RCD
protection. One side of the isolation transformer secondary may be a pseudo neutral with
ship earthing.
In such cases, a ship earth or ship bonding of one side of the isolation transformer
secondary would be expected to be provided. Ships wired to earlier standards or overseas
standards may vary from the above.
When the LPS is completed, the earthing conductor at its final point connection to its
chosen earth termination network should be bonded to the ship earth or ship bonding point
at its termination. Where the bonding conductor on the electrical wiring is not actually
terminated on earth, the bond from the LPS should be connected to its lowest (height)
control point by a conductor of not less than twice the cross-sectional area of the electrical
wiring system.
For DOD Internal Use ONLY
97 AS/NZS 1768:2007

COPYRIGHT
6.8 FENCES
If an extended length of metal fence is struck it is raised momentarily to a high potential
relative to earth. Persons or livestock in close proximity to, or in contact with, such fencing
at the time of a lightning discharge to the fencing may therefore be exposed to danger.
Fences that give rise to the most risk are those constructed with posts of poor conducting
material, such as wood or concrete. Fences built with metal posts set in earth are less
hazardous, especially if the electrical continuity is broken. Breaking the electrical
continuity prevents a lightning stroke from affecting the entire length of a fence, as it can if
the stroke is direct and the fence continuous, even though earthed.
Thus it is desirable to limit the length of fencing so affected by the provision of gaps, and
also to provide several earthing electrodes in each section so as to facilitate the discharge to
earth of the lightning current. In addition, persons or livestock can be endangered by
potential differences in the ground in the proximity of fences (see Figure 6.1). The risk is
greatest on rocky ground.
No value can be given for the earth termination resistance, since this must be largely
governed by the physical conditions encountered, but the lower the resistance to earth the
less risk will result to persons and livestock. In this connection, it should be borne in mind
that because of large body spans and bare contact areas many types of livestock are more
susceptible to electric shock than humans.

FIGURE 6.1 EQUIPOTENTIAL LINES NEAR METAL FENCE CAUSED
BY LIGHTNING DISCHARGE TO FENCE
6.9 MISCELLANEOUS STRUCTURES
6.9.1 Shelters, shade structures and rotundas in the public domain
Structures of this nature, which have metallic roofs supported on wood or other electrically
non-conductive materials, shall have the metallic roof earthed by a minimum of two
standard downconductors at intervals not exceeding 20 m of the roof perimeter. These
downconductors should be arranged outside the structure away from exits and entrances and
to reduce the hazard of touch potential, should be installed in a suitable heavy duty
electrical conduit to the AS/NZS 2053 series. Where the metallic roof is in contact with,
and supported by, metallic supports, no additional downconductors are required.
In the case of structures of this nature with a non-conductive roof, air terminations and
downconductors shall be installed as per Section 4, with earthing as described below.
For DOD Internal Use ONLY
AS/NZS 1768:2007 98
COPYRIGHT
Each specially provided downconductor shall be suitably earthed. Where doubt exists as to
the effective earthing of metallic supports being used as downconductors, they should also
be suitably earthed.
In addition to these minimum requirements, further protection may be afforded to the
occupants of the shelter by installation of a ring earth.
6.9.2 Large tents and marquees
Where large temporary structures of this type are used for such purposes as exhibitions and
entertainments involving large numbers of people, consideration should be given to their
protection against lightning. In general such structures are manufactured from non-metallic
materials and the simplest form of protection will usually consist of one or more horizontal
air terminals suspended above them and connected solidly to earth. A non-metallic
extension of the vertical supports provided for such structures may, if convenient and
practicable, be used for supporting a network of horizontal air terminals but a clearance of
not less than 1.5 m should be maintained between the conductor and the fabric of the
enclosure. Downconductors should be arranged outside the structure away from exits and
entrances and be connected to earthing rods that, in turn, should be connected to a ring
conductor in such a manner as to be inaccessible to the general public. Those types of
tented structure that have metal frameworks should have these efficiently bonded to earth at
intervals of not more than 20 m of perimeter.
6.9.3 Small tents
For small tents, no specific recommendations can be given.
6.9.4 Metal scaffolding and similar structures, including overbridges
Where metal scaffolding is readily accessible to the general public, particularly when it is
erected over and on part of the common highway or may be used in the construction of
public seating accommodation, it should be efficiently bonded to earth. A simple method of
bonding such structures consists of running a strip of metal other than aluminium, 20 mm
3 mm size, underneath and in contact with the base plates carrying the vertical members of
the scaffolding and earthing it at intervals not exceeding 20 m. With public seating
accommodation only the peripheral members of the structure need bonding to earth. Other
steel structures, such as those used for pedestrian bridges over main trunk roads, are
frequently sited in isolated situations where they may be prone to lightning strikes and
should therefore be bonded to earth, particularly at the approach points.
6.9.5 Tall metal masts, towers, cranes and revolving and travelling structures
Masts and their guy-wires, floodlighting towers and other similar structures of metallic
construction, particularly those to which the general public have access, should be earthed
in accordance with this Standard.
Cranes and other tall lifting appliances used for building construction purposes, shipyards
and port installations should also be bonded to earth. For cranes or revolving structures
mounted on rails, efficient earthing of the rails, preferably at more than one point, will
usually provide adequate lightning protection.
In special cases, where concern is felt regarding possible damage by lightning to bearings,
additional measures may be justified.
Mobile towers, portable cranes and similar structures mounted on vehicles with pneumatic
tyres can be given a limited degree of protection against lightning damage by drag chains or
tyres of conducting rubber such as are provided for dissipating static electricity.
For DOD Internal Use ONLY
99 AS/NZS 1768:2007

COPYRIGHT
6.10 PROTECTION OF HOUSES AND SMALL BUILDINGS
6.10.1 General considerations
The application of this Clause is intended to be restricted to relatively small buildings, such
as houses or similar buildings, of a smaller size than those envisaged in Section 4 of this
Standard.
Lightning protection for a house or small building in complete accordance with the
recommendations of Section 4 may be difficult to justify on economic grounds. However,
there may be a need to provide some degree of protection against lightning damage.
Houses and small buildings vary greatly in the degree to which their construction provides
inherent lightning protection. Small buildings with mainly non-metallic materials offer little
or no inherent protection against lightning, whereas a building with a metallic roof, metallic
gutters, and metallic downpipes leading into the ground has a high degree of inherent
protection, since the main elements of an LPS are already present.
If lightning strikes a house with little or no inherent lightning protection, the lightning is
likely to penetrate the roof and attach to electrical wiring in the roof area. This will usually
result in damage to electrical equipment in the house, and in some cases, may result in a
fire, or in hazard to persons within the house.
The objective in protecting small buildings should be to provide conductors to intercept the
lightning, to provide a low-resistance path to earth, and to provide at least two earth stakes
or equivalent earthing electrodes for conveying the lightning current into the earth.
6.10.2 Air terminal network for the building
If the building roof consists mainly of metallic materials, then it will serve as the air
terminal network. It is necessary to ensure that there is electrical continuity between the
various parts of the roof. Adequate continuity will often be provided by the way in which
the metallic parts are overlapped and fastened.
If the building roof consists mainly of non-metallic materials, then an air terminal network
should be provided. Suitable materials are listed in Clause 4.7. Copper wire and copper
strip are recommended for their durability. At least one conductor should be run along the
highest parts of the roof, for example, the highest ridge of the building. If the roof has a
complicated shape, it may be necessary to run additional conductors along the highest parts
of each section of the roof. All conductors should be joined together.
To be in accordance with this Standard, the cross-sectional area of the conductors should be
not less than 35 mm
2
, achieved, for example, by copper strip 25 mm 1.5 mm. However, it
should be realized that much thinner conductors are able to carry most lightning currents
without damage. Even if the conductor were to melt, it would have carried out its function
for that one strike, as the lightning current would flow through the path of the molten metal,
rather than penetrate below the roof of the house.
For a large, more-or-less flat roof of non-conducting material, the simplest form of air
terminal network may be a series of vertical metallic rods above the roof level, all
connected together. The zone of protection provided by a vertical rod may be estimated
using the information in Clause 4.4.
Metallic gutters may become a strike attachment point. If there are metallic gutters around
the roof, these should be connected to the air terminal network. With metallic roofs, these
connections may already exist in the fastenings of the guttering to the roof. With
non-metallic roofs, the guttering should be connected to the air terminal network at no less
than two points.
For DOD Internal Use ONLY
AS/NZS 1768:2007 100
COPYRIGHT
6.10.3 Provision of downconductors for the building
There should be at least two low-resistance paths to convey the current from any lightning
strike to the roof to earth. Metallic downpipes from metallic gutters may be used for this
purpose, provided that they afford a direct electrically continuous path for the lightning
current. In the absence of any low-resistance path from roof to earth, at least two
conductors should be provided to serve as downconductors. These may be continuations of
the conductors forming part of the air terminal network, and the same recommendations
apply as in Clause 6.10.2.
6.10.4 Provision of earthing electrodes
A path to earth for the lightning current should be provided at no less than two well
separated points, for example, at opposite ends of the house. Preference should be given to
areas that are usually damp, such as gardens. A metallic water pipe buried in the ground
would be a satisfactory earthing electrode provided that the water pipe is also connected to
the electricity supply service earth.
Each downconductor should be connected to an earthing electrode by the shortest possible
route, with the proviso that downconductors and earthing electrodes should not be placed
close to entry doors, or places where persons are likely to stay for long periods. For
example, earthing electrodes should not be placed close to swimming pools.
Earthing electrodes and their connected conductors should be examined periodically to
ensure that they are intact, and not suffering corrosion or mechanical damage.
6.11 PROTECTION OF METALLIC PIPELINES
Recommendations for the protection of metallic pipelines are given in AS/NZS 4853.
For DOD Internal Use ONLY
101 AS/NZS 1768:2007

COPYRIGHT
S E C T I O N 7 P R O T E C T I O N O F
S T R U C T U R E S W I T H E X P L O S I V E O R
H I G H L Y - F L A M M A B L E C O N T E N T S
7.1 SCOPE OF SECTION
This Section provides a guide to the protection of structures containing explosives, or
highly-flammable solids, liquids, gases, vapours or dusts, from lightning or induced
discharges, and indicates ways of protecting those structures that are not inherently
self-protecting. Reference should be made to the AS/NZS 2430 series for information on
areas that are likely to have an explosive atmosphere. Reference should also be made to
AS/NZS 1020 for information on the control of static discharges.
7.2 GENERAL CONSIDERATIONS
7.2.1 Risk assessment
The approach for the assessment and management of risk due to lightning detailed in
Section 2 may be applied to structures with explosive or highly-flammable contents.
In some cases, the risk to life and property may be so obvious that the provision of every
means possible for protection from the consequences of a lightning discharge is essential.
Similarly, the owner of such a facility may decide that there should be no avoidable risk
and specify that every means possible for protection from the consequences of a lightning
discharge be installed.
Alternatively, the risk may be assessed as acceptable where the quantity of dangerous
material is strictly limited, as in a laboratory or small store, or where the structure is
specifically designed and situated to restrict the effects of a catastrophe. Also, lightning
protection may not be necessary in some circumstances where the dangerous materials are
not exposed but are completely encased in metal of an adequate thickness.
7.2.2 Protection required
Unless the risk assessment considerations in Clause 7.2.1 indicate that protection is not
required, the recommendations in this section should be followed for structures in which
explosives or highly-flammable solids, liquids, gases, vapours or dusts may accumulate, i.e.
in those areas that may be classified as hazardous.
Due to the increased risk, protection level I as defined in Section 4 should be applied to
these structures (e.g. a rolling sphere of 20 m radius when using the RSM).
7.2.3 Electrostatic shielding
The electrostatic induced voltage on isolated objects in the field of a storm cloud may cause
sparks to earth when a lightning discharge occurs to some adjacent object. Isolated objects
within a structure that is adequately shielded will themselves be electrostatically shielded.
If the structure is not shielded or is only partly shielded, then the isolated objects should be
earthed to prevent electrostatic sparks. For further discussion on the earthing of isolated
internal objects, see Section 5.
For DOD Internal Use ONLY
AS/NZS 1768:2007 102
COPYRIGHT
7.3 AREAS OF APPLICATION
Protection should, in all cases, be provided for the following structures:
(a) Tanks and vessels containing flammable solids, liquids, vapours or gases, or
highly-flammable or explosive dusts.
(b) All metallic pipes and electricity supply and telecommunications service lines at the
point where they enter or leave a hazardous area.
Piping that is not in electrical contact with its associated tank or vessel, such as an
open discharge line into a water tank, should be bonded to the tank or vessel by a
flexible conductor, and earthed. Cathodic protection may justify the insertion of an
insulating flange that will interrupt the electrical continuity of the total length of line.
Cathodic protection usually has its converter and monitoring equipment outside the
hazardous area, with ELV d.c. leads feeding into the latter. This may require separate
protection to each part of the circuit.
Where flexible connections between pipelines and tanks do not incorporate an
earth-continuity conductor, a separate conductor for earthing should be provided. No
pipeline should be used for earth-continuity purposes as a substitute for the
recommended earthing conductor.
(c) Buildings that may contain explosive or large quantities of highly-flammable
materials, or nominated buildings that may, in an emergency, be used for the storage
of explosives.
(d) Buildings that may contain small quantities of highly-flammable material or a large
quantity of combustible material if sited within 50 m of a building specified in Item
(c).
(e) Any structure sited within 30 m of a building containing explosives, which thus
constitutes a projectile hazard to this building in the event of dislodgment of masonry
and the like by lightning.
(f) Any structure sited within 30 m of a building containing explosives that, if struck by
lightning, might constitute a subsequent fire hazard.
7.4 EQUIPMENT APPLICATION
7.4.1 Earth bonding points
Earth bonding points should be designed and installed to provide permanent, electrically
sound connections between the tank, plant or structure and the earthing system.
The bonding points can be bosses tapped to receive a bolt up to 50 mm long, a tag
(minimum 50 50 10 mm) or a 50 mm threaded stud. The points should be fabricated to
provide or accept a minimum of M10 (10 mm diameter) bolt, lug or fixing.
Earth bonding points should be fabricated from the same (or compatible) metal as the
structure it is being welded to. Pressure vessels should be provided by the manufacturer
with a suitable bonding point to take the earth connection.
In order to avoid corrosion, earth bonding points should be installed not less than 500 mm
above ground level. In addition, all earth connections to the points should be protected with
a suitable corrosion inhibiting compound or paint.
7.4.2 Bonding conductors
Where various items of process plant or a number of vessels are mounted on an extensive
concrete plinth that elevates the equipment above ground level, bonding conductors should
be provided to form a common earth connection for all the downconductors from the plant.
For DOD Internal Use ONLY
103 AS/NZS 1768:2007

COPYRIGHT
Copper strip should be installed along two opposite sides of the plinth, fastened to the walls
not less than 500 mm above ground level to avoid corrosion. Tee-joints may be used
between down and bonding conductor. Diagonally opposite ends of the base conductor
should be provided with a test link from which connection is made to the earth termination
network, preferably to earth busbars that provide alternative earth connections.
Where one bonding conductor only is installed, test links and earth connections should be
provided at each end.
7.4.3 Sizes of copper strips
Sizes of copper strips should be in accordance with Table 4.6. For common earthing
systems, larger sizes may be needed depending on the fault current. These should be
selected in accordance with AS/NZS 3000.
7.4.4 Downconductors (see Clause 4.12)
All high salient structures within a process area should be provided with at least two
downconductors unless they are of welded construction or electrically continuous down to
base level.
Wherever possible, downconductors should be installed remote from stairs and operational
walkways and ladders.
Downconductors should preferably be installed at diagonally opposite corners of the
structure in positions that provide the shortest possible path for connection to the earth
termination network. They should be installed on the outside of the structure and should not
pass through it.
Copper strip should be used for downconductors and while, wherever possible, it should be
in a continuous length, test links may be attached for connection of down or base
conductors at various levels.
Where structural steelwork or columns do not require the installation of an air terminal, the
downconductor should extend from above the highest point of the structure.
Provision should be made for thermal expansion of the earthing conductor and associated
structure.
A test link should be installed in the downconductor in accordance with Clause 4.13, not
less than 500 mm above ground level.
Each downconductor from the highest point or points within the process area should take
the shortest possible path direct to earth and should be equipped with its own set of earthing
electrodes to provide a path of minimum impedance for a lightning discharge. The earthing
electrodes should be interconnected below ground level with the bonding conductor(s)
belonging to other earthing systems.
7.4.5 Air terminals (see Clause 4.11)
All high salient structures that are not electrically continuous and that are not within the
zone of protection of an adjacent protected structure should be equipped with air terminals
in accordance with the recommendations of this Standard.
Where two or more air terminals are employed they should be interconnected by roof
conductors for connection to at least two downconductors as follows:
(a) Roof conductors Copper strips should take the shortest salient route between the
various air terminals, with fasteners spaced as for downconductors.
(b) Air terminal network Buildings that are protected by an air terminal network should
be provided with at least two downconductors, that should be directly connected to
the most widely-spaced parts of the air terminal network.
For DOD Internal Use ONLY
AS/NZS 1768:2007 104
COPYRIGHT
7.5 SPECIFIC OCCUPANCIES
7.5.1 Protection of steel tanks
7.5.1.1 General precautions
The following precautions should be taken to minimize the effects of lightning discharge on
tanks containing petroleum products, including tanks with fixed roofs and tanks with
floating roofs:
(a) The shells of all tanks intended for the storage of highly-flammable liquids that can
produce an explosive gas atmosphere should be permanently and effectively earthed.
Other tanks, such as water tanks, if located in a hazardous area should also be
permanently and effectively earthed.
The combined earth resistance of permanent earth connections to the tank should not
exceed 10 .
The recommended method of earthing is by means of earthing electrodes as detailed
in Clause 4.15, but in some installations soil conditions and the earth resistance of the
tank when isolated from associated pipelines may in themselves constitute permanent
and effective earthing. In such cases, the necessity for tank earthing electrodes should
be considered with particular reference to site measurements of earth resistance.
(b) The minimum number of individual earthing electrodes on storage tanks will depend
upon the diameter and soil condition, and should be in accordance with the following
schedule for single tanks:

Diameter of tank
m
Minimum number of
independent earthing
electrodes
30 2
> 30 3
For a group of small tanks, earthing electrodes common to the group may be installed,
provided that each tank has two independent paths to earth. One of these paths may
be through the pipeline earthing system.
NOTE: The reason for the minimum of two earthing electrodes is that during testing of one
electrode the tank will remain earthed by the other electrode.
Earthing electrodes for a tank may be interconnected around the periphery of the tank,
and where two or more connections are used they should be spaced symmetrically
round the tank.
(c) Each earthing conductor should be terminated and attached by means of a bolted
connection to a steel boss welded to the tank body. The steel boss should be tapped to
receive a bolt or stud, preferably 10 mm diameter. Lock washers should be used on
the connecting assembly. Soldered connections should be avoided. It is suggested that
the boss be welded on the tank at a minimum height of 500 mm above the bottom of
the tank.
(d) When a pipe or rod earthing electrode is driven into the ground, mechanical
protection should be given to the head of the electrode.
NOTE: It is the practice of some organizations to enclose all earth stake heads in a pit, where
they are associated with special earthing, such as lightning protection or static earthing.
For DOD Internal Use ONLY
105 AS/NZS 1768:2007

COPYRIGHT
(e) Steel tanks with floating roofs should be protected by one of the measures described
in Items (i) and (ii):
(i) Multiple parallel connections between the floating roof and the tank shell, in
particular those designs incorporating mechanical linkage in the seal assembly.
This is the most effective method of discharging induced static charges caused
by atmospheric conditions; under this arrangement it is not necessary to bond
across internal drainpipe joints or external moving stairway joints.
(ii) Overhead earth wires or other suitable forms of interception protection in
accordance with Clause 4.4 (see also Clause 7.2.2). This may be appropriate in
areas where there is a known high ground flash density.
7.5.1.2 Above-ground steel tanks containing flammable liquids at atmospheric pressure
The contents of steel tanks with steel roofs of riveted, bolted, or welded construction, with
or without supporting members, used for the storage of flammable liquids, are considered to
be reasonably well protected against lightning if the tanks comply with the following
recommendations:
(a) All joints between steel plates should be riveted, bolted, or welded.
(b) All pipes entering the tank should be metallically bonded to the tank at the point of
entrance.
(c) All vapour or gas openings should be closed.
(d) The metal tank and roof should have adequate thickness so that holes will not be
burned through by lightning discharges (5 mm sheet steel roofs on tanks are
considered adequate for this purpose*).
(e) The roof should be continuously welded to the shell, or bolted, or riveted and
caulked, to provide a gastight seam and electrical continuity.
7.5.1.3 Steel tanks with non-metallic roofs
Steel tanks with wooden or other non-metallic roofs are not considered to be
self-protecting, even if the roof is essentially gastight and sheathed with thin metal and with
all gas openings closed or flameproofed.
Such tanks should be provided with air terminals of sufficient height and number to receive
all discharges and keep them away from the roof. The air terminals should be thoroughly
bonded to each other, to the metallic sheathing, if any, and to the tank. Isolated metal parts
should be avoided, or else bonded to the tank. In lieu of air terminals any of the following
may be used:
(a) Conducting masts suitably spaced around the tank.
(b) Overhead earth wires.
(c) A combination of masts and overhead earth wires.
7.5.2 Installations handling crude oil and productsJetties for marine tankers and
barges
The following recommendations should be observed as applicable:
(a) General All pipelines to jetties and any structural steelwork, plant and bollards on
jetties together with associated dolphins, walkways, and shore bollards should be
bonded to the electrical installation earthing system.

* This value is based on a recommendation in ANSI/NFPA 780.
For DOD Internal Use ONLY
AS/NZS 1768:2007 106
COPYRIGHT
Electrical equipment on a jetty should be connected to an earthing system as specified
in AS/NZS 3004.
Dependent upon site and operating conditions, it may be possible to obtain overall
protection by using one earthing system. Where it is considered that one common
earthing system may be adapted to comply with all the requirements, it is necessary to
ensure that the value of earth resistance does not exceed 4 .
Where steel or steel box piles are not employed, an earthing conductor should be
installed to enter the water below low water mark to provide a direct path for
lightning discharge.
(b) Jetties with cathodic protection It is recommended that the following precautions be
taken where jetties are protected by either sacrificial anodes or power-impressed
systems to prevent sparking at the tanker manifold when loading lines are being
connected or disconnected:
(i) Install an insulating flange at the jetty end of each loading line between jetty
and vessel whereby all flanges shore-side of the insulating flange are earthed to
the jetty earthing system and all flanges to the seaward side are earthed via the
vessel.
(ii) Ensure that the insulating flange cannot inadvertently be short-circuited by the
electrical connection of exposed metallic flanges on the seaward side of the
insulating flange to the jetty structure either by direct contact or by hose-
handling equipment.
(iii) Where sacrificial anodes are installed, it may be necessary to use manila
mooring ropes or straps to extend the life of the anodes and minimize current
flow between jetty and vessel.
(c) Ship/shore bonding cables An independent cable bonding connection between ship
and jetty, with or without cathodic protection, is not considered as serving any useful
purpose in
(i) the dispersal of static electricity; or
(ii) minimizing possible current flow in conductive type loading hoses.
7.5.3 Aircraft fuelling and de-fuelling
Aircraft fuelling and de-fuelling should be suspended when electrical storms are in the
vicinity.
7.5.4 Structures with explosive or highly-flammable contents
7.5.4.1 Methods of protection
Structures with explosive or highly-flammable contents should be protected in one or more
of the ways detailed in Clauses 7.5.4.2 to 7.5.4.6 and in accordance with the
recommendations of Clauses 7.5.4.7 to 7.5.4.16, as appropriate.
7.5.4.2 Air terminal network
An air terminal network should be suspended at an adequate height above the area to be
protected (see Clause 4.4).
Where a suspended conductor crosses chimneys or vents that emit explosive dusts or gases
under forced draught, the suspended conductors should be not less than 5 m above the
chimney or vent.
For DOD Internal Use ONLY
107 AS/NZS 1768:2007

COPYRIGHT
7.5.4.3 Network of horizontal conductors
Where the expense of the method described in Clause 7.5.4.2 cannot be justified, and where
no risk is involved in discharging the lightning current over the surface of the structure to
be protected, a network of horizontal conductors with a mesh between 3 m and 8 m,
according to the risk, should be fixed to the roof of the structure.
Each separate structure protected as above should be equipped with twice the number of
downconductors recommended in Clause 4.12.
7.5.4.4 Strikes to the sides of buildings
Consideration should be given to providing an array of vertical conductors to protect the
sides of buildings. These conductors should be spaced every 10 m and be connected to the
air terminal network (top) and earth termination network (bottom) of the LPS.
7.5.4.5 Vertical conductors
A structure or a group of structures of small horizontal dimensions may be protected by one
or more vertical lightning conductors (see Clause 4.4).
7.5.4.6 Below-ground structures
A structure that is wholly below ground and not connected to any services above ground
can be protected by an air terminal network as described in Clause 7.5.4.2 by virtue of the
fact that soil has an impulse breakdown strength that can be taken into account when the
risk of flashover from the protection system to the structure to be protected, including its
services, is being determined. Where the depth of burying is adequate, the air terminal
network may be replaced by a network of earthing strips arranged on the surface.
Where the underground structure has a reinforced concrete roof at or immediately below
soil level, the reinforcement may be used as a protection system provided that the
reinforcement is welded so that rectangular electrical conducting paths are formed with
sides not exceeding 2 m in length.
Where the underground structure has a roof that is not reinforced or where the
reinforcement is not electrically continuous, a buried conductor network located above the
structure and buried not less than 500 mm below the soil level may be used.
Where the structure is such that protection cannot be provided by use of the reinforcement
and the depth of soil above the roof is less than 500 mm, air terminals may be mounted on
suitable bases above the structure at soil level and interconnected by a roof conduction
network of closed mesh of between 3 m and 8 m.
7.5.4.7 Interconnection of earth terminations
The earth terminations of the earth protective system should be interconnected by a ring
conductor. This ring conductor should preferably be buried to a depth of not less than
500 mm and be not less than 2 m from the walls of the structure unless other considerations,
such as the need for bonding other objects to it, testing or risks of corrosion, make it
desirable to leave it exposed. The resistance value of the earth termination network should
be maintained permanently at 10 or less. If this value proves to be unobtainable, the
methods recommended in Clause 4.14 should be adopted, or the ring conductor should be
connected to the ring conductor of one or more neighbouring structures until the above
value is obtained.
7.5.4.8 Bonding of structural metal
All major metal forming part of the structure, including continuous metal reinforcement and
services should be bonded together and connected to the LPS. Such connections should be
made in at least two places and should, as far as is possible, be equally spaced round the
perimeter of the structure at intervals not exceeding 15 m.
For DOD Internal Use ONLY
AS/NZS 1768:2007 108
COPYRIGHT
7.5.4.9 Bonding of internal metal
Major metalwork inside the structure should be bonded to the LPS.
7.5.4.10 Electrical conductors entering structure
Electrical conductors entering the structure should be enclosed in metal. The metal
enclosure should be electrically continuous within the structure; it should be earthed at the
point-of-entry outside the structure on the supply side of the service and bonded directly to
the LPS.
7.5.4.11 Electrical conductors connected to overhead electricity supply service line
Where the electrical conductors are connected to an overhead electricity supply service line,
a length of buried cable with metal sheath or armouring should be inserted between the
overhead line and the point-of-entry to the structure, and an SPD, e.g. of the type containing
voltage-dependent resistors, shall be provided at the termination of the overhead line. The
earth terminal of this SPD should be bonded directly to the cable sheath or armouring. The
spark overvoltage of the SPD should not exceed half the breakdown withstand voltage of
the electrical equipment in the structure. In this operation, the appropriate Standard and any
regulations that may apply should be observed.
7.5.4.12 Metal not continuously earthed
Metallic pipes, metallic electrical cable sheaths or metallic armouring, steel ropes, rails or
guides that enter the structure and are not in continuous electrical contact with the earth
should be bonded to the LPS. They should be earthed at the point-of-entry outside the
structure and at two points, one about 75 m away and one a further 75 m away.
7.5.4.13 Adit or shaft
For a buried structure or underground excavation to which access is obtained by an adit or
shaft, the recommendations in Clause 7.5.4.12 as regards extra earthing should be followed
for the adit or shaft at intervals not exceeding 75 m as well as outside the structure.
7.5.4.14 Fences and retaining walls
The metal uprights, components and wires of all fences, and of retaining walls in close
proximity to the structure, should be connected in such a way as to provide continuous
metallic connection between themselves and the LPS. Discontinuous metal wire fencing on
non-conducting supports or wire coated with insulating material should not be employed.
7.5.4.15 Avoidance of tall components
Structures with explosive or highly-flammable contents should not be equipped with tall
components such as spires and flagstaffs or radio antennas on the structure or within 15 m
of the structure. This clearance applies also to the planting of new trees, but structures near
existing trees should be treated in accordance with Clause 6.3.
7.5.4.16 Tests of system
Tests should be carried out in accordance with Clause 8.3 at intervals of not more than two
years. The test equipment used should be certified for use in the particular hazardous area.
In some cases, non-certified testing equipment may be used provided that the location
where the tests are to be conducted has been proven to be free of combustible gases or
vapours.
For DOD Internal Use ONLY
109 AS/NZS 1768:2007

COPYRIGHT
S E C T I O N 8 I N S T A L L A T I O N A N D
M A I N T E N A N C E P R A C T I C E
8.1 WORK ON SITE
Throughout the period of erection of a structure, all large and prominent masses of
metalwork, such as steel frameworks, scaffolding and cranes, should be effectively
connected to earth. Once work has commenced on the installation of an LPS, an earth
connection should be maintained at all times.
During the construction of overhead electricity supply service lines, overhead equipment
for railway electrification and the like, the danger to persons can be minimized by ensuring
that an earth termination network is installed and properly connected before any conductors
other than earth wires are run out. Once the conductors are run out and insulation installed,
they should not be left floating while persons are working on them, but should be
connected to earth in the same manner as when maintenance is being carried out after the
line is commissioned.
8.2 INSPECTION
All LPSs should be inspected after completion, alteration or extension, in order to verify
that they are in accordance with this Standard. A routine inspection should be made at least
every two years. More frequent inspections may be warranted in some circumstances. Such
circumstances include, but are not limited to
(a) areas subject to severe weather and lightning activity;
(b) structures located in areas where aggressive soil or other conditions may accelerate
corrosion or other aspects of system degradation;
(c) changes in technology use within the structure that may necessitate a review of the
protection means and their continued effectiveness; and
(d) any other time where it is deemed necessary to update the original risk assessment for
lightning damage.
8.3 TESTING
On the completion of the installation or of any modification to it, and at the time of any
maintenance inspection, the resistance to earth of the whole installation and of each earth
termination should be measured, and the electrical continuity of all conductors, bonds and
joints and their mechanical condition verified. The testing should be carried out in
accordance with Appendix B.
Where regular testing during maintenance reveals that the earthing resistance is
substantially unchanged, the frequency of maintenance testing may be reduced to each
alternate inspection.
If the resistance to earth of an LPS, when so determined, exceeds the specified value for the
particular applications the value should be reduced to be in accordance with the
recommendations of this Standard. If the resistance is less than the recommended value but
significantly higher than the previous reading, the cause should be investigated in
accordance with Appendix C.
The condition of the soil, the procedure adopted, details of salting or other soil treatment,
and the results obtained should all be recorded as listed in Clause 8.4.
For DOD Internal Use ONLY
AS/NZS 1768:2007 110
COPYRIGHT
8.4 RECORDS
The following records should be kept on site, or by the persons responsible for the upkeep
of the installation:
(a) Scale drawings showing the nature, dimensions and position of all component parts of
the LPS.
(b) The nature of the soil and any special earthing arrangements.
(c) Date and particulars of salting, if used.
(d) Test conditions, date and results in accordance with Clause 8.3.
(e) Alterations, additions or repairs to the system.
(f) The name and contact details of the persons responsible for the installation or for its
upkeep.
NOTE: Detection of the occurrence of lightning flashes to the structure and the magnitude of the
discharge current may be estimated by magnetic links, magnetic tape strips or other current
monitoring devices. While the use of instruments to count the number of strikes intercepted by
the protection system is highly recommended, in practice, this may be impractical to achieve on
multiple downconductor LPSs.
8.5 MAINTENANCE
The general recommendations of this Standard provide, as one of their objectives, LPSs that
do not require a lot of maintenance. Nevertheless, some system components will lose their
effectiveness over time because of weathering, corrosion, and stroke damage. Both physical
and electrical characteristics of the LPS must be maintained to ensure compliance with the
design requirements.
The periodic inspection and tests described in Clauses 8.2 and 8.3 will indicate what
maintenance, if any, should be undertaken. Particular attention should be paid to earthing,
to any evidence of corrosion and to any alterations or extensions to the structure that may
affect the LPS. Examples of such alterations or extensions are as follows:
(a) Changes in the use of a building.
(b) Installation of fuel oil storage tanks.
(c) The erection of radio and television antennas.
(d) Installation or alteration to the electrical, telecommunications or computing facilities
within, or closely connected to, the building.
A good maintenance program should also contain provision for the following:
(i) Inspection of all system components.
(ii) Tightening of all accessible clamps and splices.
(iii) Measurement of system resistance, including earth resistance of terminals.
(iv) Inspection or testing of SPDs.
For DOD Internal Use ONLY
111 AS/NZS 1768:2007

COPYRIGHT
APPENDIX A
EXAMPLES OF LIGHTNING RISK CALCULATIONS
(Informative)
A1 INTRODUCTION
A number of lightning risk calculations have been included in this Appendix to illustrate
different structures and risk categories.
The risk calculation examples are:
(a) Example 140 m office block.
(b) Example 2Darwin hotel.
(c) Example 3Historic church.
(d) Example 4Remote pump station.
(e) Example 5Two storey house.
The front page of the Microsoft

Excel spreadsheet file LIGHTNING RISK.XLS has been


reproduced in Paragraphs A2.1 to A2.5 for each of these examples.
In addition to this, all the workings of the 40 m office block example have been included in
Paragraph A3.
For DOD Internal Use ONLY


COPYRIGHT
112
AS/NZS 1768:2007
A
2



S
A
M
P
L
E

S
P
R
E
A
D
S
H
E
E
T

C
A
L
C
U
L
A
T
I
O
N
S

A
2
.
1



E
x
a
m
p
l
e

1

4
0

m
e
t
r
e

h
i
g
h

o
f
f
i
c
e

b
l
o
c
k

(
R
)
(
R
a
)
(
R
d
)
S
t
a
n
d
a
r
d
s

A
u
s
t
r
a
l
i
a
V
e
r
s
i
o
n

3
.
0
D
a
t
e
:

2
8
/
1
/
2
0
0
6
0
.
0
0
E
+
0
0
4
.
8
1
E
-
0
6
0
.
0
0
E
+
0
0
0
.
0
0
E
+
0
0
D
i
r
e
c
t

S
t
r
i
k
e

R
i
s
k
N
o
T
r
a
n
s
f
o
r
m
e
r

a
t

S
t
r
u
c
t
u
r
e
1
.
0
7
E
-
0
5
O
v
e
r
a
l
l

R
i
s
k





L
o
s
s

o
f

H
u
m
a
n

L
i
f
e





L
o
s
s

o
f

E
s
s
e
n
t
i
a
l

S
e
r
v
i
c
e
s
0
.
0
0
E
+
0
0
4
.
8
1
E
-
0
6
0
.
0
0
E
+
0
0
I
n
d
i
r
e
c
t

S
t
r
i
k
e

R
i
s
k
(
R
i
)
0
.
0
0
E
+
0
0





L
o
s
s

o
f

C
u
l
t
u
r
a
l

H
e
r
i
t
a
g
e
A
c
c
e
p
t
a
b
l
e

R
i
s
k
1
.
0
E
-
0
5





E
c
o
n
o
m
i
c

L
o
s
s
1
.
0
E
-
0
3
1
.
0
E
-
0
3
C
a
l
c
u
l
a
t
e
d

R
i
s
k
0
.
0
0
E
+
0
0
3
.
1
6
E
-
0
5
1
.
0
E
-
0
3
4
0
m

O
f
f
i
c
e

B
l
o
c
k
S
t
r
u
c
t
u
r
e

I
d
e
n
t
i
f
i
c
a
t
i
o
n
0
A
c
c
e
p
t
a
b
l
e

R
i
s
k

o
f

E
c
o
n
o
m
i
c

L
o
s
s
e
s
S
e
r
v
i
c
e

L
i
n
e
s
P
o
w
e
r

L
i
n
e
C
a
t
e
g
o
r
y

1

-

L
o
s
s

o
f

H
u
m
a
n

L
i
f
e
U
n
d
e
r
g
r
o
u
n
d
L
o
s
s

C
a
t
e
g
o
r
i
e
s
0
S
t
e
p

&

T
o
u
c
h

P
o
t
e
n
t
i
a
l

D
a
m
a
g
e

F
a
c
t
o
r
s
S
u
r
g
e

P
r
o
t
e
c
t
i
o
n

o
n

A
l
l

E
q
u
i
p
m
e
n
t
0
U
n
s
c
r
e
e
n
e
d
0
.
3
C
a
t
e
g
o
r
y

3

-

L
o
s
s

o
f

C
u
l
t
u
r
a
l

H
e
r
i
t
a
g
e
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
S
e
r
v
i
c
e

L
i
n
e

D
e
n
s
i
t
y
N
u
m
b
e
r
C
a
b
l
e

T
y
p
e
E
n
v
i
r
o
n
m
e
n
t
a
l

F
a
c
t
o
r
R
i
s
k

o
f

D
a
n
g
e
r
o
u
s

D
i
s
c
h
a
r
g
e
I
n
t
e
r
n
a
l

W
i
r
i
n
g

T
y
p
e
P
r
o
t
e
c
t
i
o
n

M
e
a
s
u
r
e
s
U
r
b
a
n
0
.
8
N
o
n
e
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
S
p
e
c
i
a
l

H
a
z
a
r
d
S
e
r
v
i
c
e
C
a
t
e
g
o
r
y

2

-

L
o
s
s

o
f

E
s
s
e
n
t
i
a
l

S
e
r
v
i
c
e
s
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
0
.
0
5
1
0
E
f
f
i
c
i
e
n
c
y

o
f


B
u
i
l
d
i
n
g

P
r
o
t
e
c
t
i
o
n
Y
e
s
S
u
r
g
e

P
r
o
t
e
c
t
i
o
n

a
t

P
o
i
n
t

o
f

E
n
t
r
y
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
1
.
E
-
0
3
3
I
s
o
l
a
t
e
d
0
0
U
n
s
c
r
e
e
n
e
d
0
M
e
d
i
u
m
U
n
s
c
r
e
e
n
e
d
E
n
v
i
r
o
n
m
e
n
t
0
L
e
n
g
t
h

(
m
)
W
i
d
t
h

(
m
)
S
t
r
u
c
t
u
r
e

A
t
t
r
i
b
u
t
e
s
R
i
s
k

o
f

F
i
r
e

o
r

P
h
y
s
i
c
a
l

D
a
m
a
g
e
1
.
E
-
0
3
R
i
s
k

A
s
s
e
s
s
m
e
n
t

f
o
r

L
i
g
h
t
n
i
n
g

P
r
o
t
e
c
t
i
o
n
O
t
h
e
r

O
v
e
r
h
e
a
d

S
e
r
v
i
c
e
s
L
o
w
2
0
2
0
4
0
C
a
t
e
g
o
r
y

4

-

E
c
o
n
o
m
i
c

L
o
s
s
H
e
i
g
h
t

(
m
)
2
.
0
9
E
-
0
5
G
r
o
u
n
d

f
l
a
s
h

d
e
n
s
i
t
y
S
t
r
u
c
t
u
r
e

D
i
m
e
n
s
i
o
n
s
C
a
b
l
e

T
y
p
e
O
t
h
e
r

U
n
d
e
r
g
r
o
u
n
d

S
e
r
v
i
c
e
s
U
n
s
c
r
e
e
n
e
d
N
o

T
r
a
n
s
f
o
r
m
e
r
N
u
m
b
e
r
C
a
b
l
e

T
y
p
e
F
i
r
e

P
r
o
t
e
c
t
i
o
n

For DOD Internal Use ONLY


COPYRIGHT
113
AS/NZS 1768:2007
A
2
.
2



E
x
a
m
p
l
e

2

D
a
r
w
i
n

h
o
t
e
l


(
R
)
(
R
a
)
(
R
d
)
S
t
a
n
d
a
r
d
s

A
u
s
t
r
a
l
i
a
V
e
r
s
i
o
n

3
.
0
D
a
t
e
:

2
8
/
1
/
2
0
0
6
0
.
0
0
E
+
0
0
3
.
3
6
E
-
0
6
0
.
0
0
E
+
0
0
0
.
0
0
E
+
0
0
D
i
r
e
c
t

S
t
r
i
k
e

R
i
s
k
N
o
T
r
a
n
s
f
o
r
m
e
r

a
t

S
t
r
u
c
t
u
r
e
1
.
7
0
E
-
0
5
O
v
e
r
a
l
l

R
i
s
k





L
o
s
s

o
f

H
u
m
a
n

L
i
f
e





L
o
s
s

o
f

E
s
s
e
n
t
i
a
l

S
e
r
v
i
c
e
s
0
.
0
0
E
+
0
0
3
.
3
6
E
-
0
6
0
.
0
0
E
+
0
0
I
n
d
i
r
e
c
t

S
t
r
i
k
e

R
i
s
k
(
R
i
)
3
.
2
0
E
-
1
0





L
o
s
s

o
f

C
u
l
t
u
r
a
l

H
e
r
i
t
a
g
e
A
c
c
e
p
t
a
b
l
e

R
i
s
k
1
.
0
E
-
0
5





E
c
o
n
o
m
i
c

L
o
s
s
1
.
0
E
-
0
3
1
.
0
E
-
0
3
C
a
l
c
u
l
a
t
e
d

R
i
s
k
0
.
0
0
E
+
0
0
3
.
2
6
E
-
0
4
1
.
0
E
-
0
3
H
o
t
e
l

i
n

D
a
r
w
i
n
S
t
r
u
c
t
u
r
e

I
d
e
n
t
i
f
i
c
a
t
i
o
n
0
A
c
c
e
p
t
a
b
l
e

R
i
s
k

o
f

E
c
o
n
o
m
i
c

L
o
s
s
e
s
S
e
r
v
i
c
e

L
i
n
e
s
P
o
w
e
r

L
i
n
e
C
a
t
e
g
o
r
y

1

-

L
o
s
s

o
f

H
u
m
a
n

L
i
f
e
U
n
d
e
r
g
r
o
u
n
d
L
o
s
s

C
a
t
e
g
o
r
i
e
s
0
S
t
e
p

&

T
o
u
c
h

P
o
t
e
n
t
i
a
l

D
a
m
a
g
e

F
a
c
t
o
r
s
S
u
r
g
e

P
r
o
t
e
c
t
i
o
n

o
n

A
l
l

E
q
u
i
p
m
e
n
t
0
U
n
s
c
r
e
e
n
e
d
0
.
5
C
a
t
e
g
o
r
y

3

-

L
o
s
s

o
f

C
u
l
t
u
r
a
l

H
e
r
i
t
a
g
e
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
S
e
r
v
i
c
e

L
i
n
e

D
e
n
s
i
t
y
N
u
m
b
e
r
C
a
b
l
e

T
y
p
e
E
n
v
i
r
o
n
m
e
n
t
a
l

F
a
c
t
o
r
R
i
s
k

o
f

D
a
n
g
e
r
o
u
s

D
i
s
c
h
a
r
g
e
I
n
t
e
r
n
a
l

W
i
r
i
n
g

T
y
p
e
P
r
o
t
e
c
t
i
o
n

M
e
a
s
u
r
e
s
U
r
b
a
n
0
.
8
N
o
n
e
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
S
p
e
c
i
a
l

H
a
z
a
r
d
S
e
r
v
i
c
e
C
a
t
e
g
o
r
y

2

-

L
o
s
s

o
f

E
s
s
e
n
t
i
a
l

S
e
r
v
i
c
e
s
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
0
.
1
1
0
E
f
f
i
c
i
e
n
c
y

o
f


B
u
i
l
d
i
n
g

P
r
o
t
e
c
t
i
o
n
Y
e
s
S
u
r
g
e

P
r
o
t
e
c
t
i
o
n

a
t

P
o
i
n
t

o
f

E
n
t
r
y
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
5
.
E
-
0
3
8
S
i
m
i
l
a
r

H
e
i
g
h
t
0
0
U
n
s
c
r
e
e
n
e
d
0
M
e
d
i
u
m
U
n
s
c
r
e
e
n
e
d
E
n
v
i
r
o
n
m
e
n
t
0
L
e
n
g
t
h

(
m
)
W
i
d
t
h

(
m
)
S
t
r
u
c
t
u
r
e

A
t
t
r
i
b
u
t
e
s
R
i
s
k

o
f

F
i
r
e

o
r

P
h
y
s
i
c
a
l

D
a
m
a
g
e
1
.
E
-
0
3
R
i
s
k

A
s
s
e
s
s
m
e
n
t

f
o
r

L
i
g
h
t
n
i
n
g

P
r
o
t
e
c
t
i
o
n
O
t
h
e
r

O
v
e
r
h
e
a
d

S
e
r
v
i
c
e
s
L
o
w
1
5
1
5
3
0
C
a
t
e
g
o
r
y

4

-

E
c
o
n
o
m
i
c

L
o
s
s
H
e
i
g
h
t

(
m
)
3
.
0
9
E
-
0
4
G
r
o
u
n
d

f
l
a
s
h

d
e
n
s
i
t
y
S
t
r
u
c
t
u
r
e

D
i
m
e
n
s
i
o
n
s
C
a
b
l
e

T
y
p
e
O
t
h
e
r

U
n
d
e
r
g
r
o
u
n
d

S
e
r
v
i
c
e
s
U
n
s
c
r
e
e
n
e
d
N
o

T
r
a
n
s
f
o
r
m
e
r
N
u
m
b
e
r
C
a
b
l
e

T
y
p
e
F
i
r
e

P
r
o
t
e
c
t
i
o
n

For DOD Internal Use ONLY


COPYRIGHT
114
AS/NZS 1768:2007
A
2
.
3



E
x
a
m
p
l
e

3

H
i
s
t
o
r
i
c

c
h
u
r
c
h

(
R
)
(
R
a
)
(
R
d
)
S
t
a
n
d
a
r
d
s

A
u
s
t
r
a
l
i
a
V
e
r
s
i
o
n

3
.
0
D
a
t
e
:

2
8
/
1
/
2
0
0
6
0
.
0
0
E
+
0
0
4
.
1
3
E
-
0
6
0
.
0
0
E
+
0
0
1
.
4
2
E
-
0
5
D
i
r
e
c
t

S
t
r
i
k
e

R
i
s
k
N
o
T
r
a
n
s
f
o
r
m
e
r

a
t

S
t
r
u
c
t
u
r
e
3
.
1
3
E
-
0
6
O
v
e
r
a
l
l

R
i
s
k





L
o
s
s

o
f

H
u
m
a
n

L
i
f
e





L
o
s
s

o
f

E
s
s
e
n
t
i
a
l

S
e
r
v
i
c
e
s
0
.
0
0
E
+
0
0
4
.
1
3
E
-
0
6
0
.
0
0
E
+
0
0
I
n
d
i
r
e
c
t

S
t
r
i
k
e

R
i
s
k
(
R
i
)
0
.
0
0
E
+
0
0





L
o
s
s

o
f

C
u
l
t
u
r
a
l

H
e
r
i
t
a
g
e
A
c
c
e
p
t
a
b
l
e

R
i
s
k
1
.
0
E
-
0
5





E
c
o
n
o
m
i
c

L
o
s
s
1
.
0
E
-
0
3
1
.
0
E
-
0
3
C
a
l
c
u
l
a
t
e
d

R
i
s
k
1
.
4
2
E
-
0
5
3
.
1
3
E
-
0
6
1
.
0
E
-
0
3
H
i
s
t
o
r
i
c

C
h
u
r
c
h
S
t
r
u
c
t
u
r
e

I
d
e
n
t
i
f
i
c
a
t
i
o
n
0
.
5 A
c
c
e
p
t
a
b
l
e

R
i
s
k

o
f

E
c
o
n
o
m
i
c

L
o
s
s
e
s
S
e
r
v
i
c
e

L
i
n
e
s
P
o
w
e
r

L
i
n
e
C
a
t
e
g
o
r
y

1

-

L
o
s
s

o
f

H
u
m
a
n

L
i
f
e
U
n
d
e
r
g
r
o
u
n
d
L
o
s
s

C
a
t
e
g
o
r
i
e
s
0
S
t
e
p

&

T
o
u
c
h

P
o
t
e
n
t
i
a
l

D
a
m
a
g
e

F
a
c
t
o
r
s
S
u
r
g
e

P
r
o
t
e
c
t
i
o
n

o
n

A
l
l

E
q
u
i
p
m
e
n
t
0
U
n
s
c
r
e
e
n
e
d
0
.
1
C
a
t
e
g
o
r
y

3

-

L
o
s
s

o
f

C
u
l
t
u
r
a
l

H
e
r
i
t
a
g
e
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
S
e
r
v
i
c
e

L
i
n
e

D
e
n
s
i
t
y
N
u
m
b
e
r
C
a
b
l
e

T
y
p
e
E
n
v
i
r
o
n
m
e
n
t
a
l

F
a
c
t
o
r
R
i
s
k

o
f

D
a
n
g
e
r
o
u
s

D
i
s
c
h
a
r
g
e
I
n
t
e
r
n
a
l

W
i
r
i
n
g

T
y
p
e
P
r
o
t
e
c
t
i
o
n

M
e
a
s
u
r
e
s
U
r
b
a
n
0
.
8
N
o
n
e
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
S
p
e
c
i
a
l

H
a
z
a
r
d
S
e
r
v
i
c
e
C
a
t
e
g
o
r
y

2

-

L
o
s
s

o
f

E
s
s
e
n
t
i
a
l

S
e
r
v
i
c
e
s
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
0
.
0
0
5
1
0
E
f
f
i
c
i
e
n
c
y

o
f


B
u
i
l
d
i
n
g

P
r
o
t
e
c
t
i
o
n
Y
e
s
S
u
r
g
e

P
r
o
t
e
c
t
i
o
n

a
t

P
o
i
n
t

o
f

E
n
t
r
y
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
1
.
E
-
0
5
1
S
i
m
i
l
a
r

H
e
i
g
h
t
0
0
U
n
s
c
r
e
e
n
e
d
0
H
i
g
h
U
n
s
c
r
e
e
n
e
d
E
n
v
i
r
o
n
m
e
n
t
0
L
e
n
g
t
h

(
m
)
W
i
d
t
h

(
m
)
S
t
r
u
c
t
u
r
e

A
t
t
r
i
b
u
t
e
s
R
i
s
k

o
f

F
i
r
e

o
r

P
h
y
s
i
c
a
l

D
a
m
a
g
e
1
.
E
-
0
3
R
i
s
k

A
s
s
e
s
s
m
e
n
t

f
o
r

L
i
g
h
t
n
i
n
g

P
r
o
t
e
c
t
i
o
n
O
t
h
e
r

O
v
e
r
h
e
a
d

S
e
r
v
i
c
e
s
L
o
w
4
0
4
0
1
3
0
C
a
t
e
g
o
r
y

4

-

E
c
o
n
o
m
i
c

L
o
s
s
H
e
i
g
h
t

(
m
)
5
.
0
0
E
-
0
9
G
r
o
u
n
d

f
l
a
s
h

d
e
n
s
i
t
y
S
t
r
u
c
t
u
r
e

D
i
m
e
n
s
i
o
n
s
C
a
b
l
e

T
y
p
e
O
t
h
e
r

U
n
d
e
r
g
r
o
u
n
d

S
e
r
v
i
c
e
s
U
n
s
c
r
e
e
n
e
d
N
o

T
r
a
n
s
f
o
r
m
e
r
N
u
m
b
e
r
C
a
b
l
e

T
y
p
e
F
i
r
e

P
r
o
t
e
c
t
i
o
n

For DOD Internal Use ONLY


COPYRIGHT
115
AS/NZS 1768:2007
A
2
.
4



E
x
a
m
p
l
e

4

R
e
m
o
t
e

p
u
m
p

s
t
a
t
i
o
n

(
R
)
(
R
a
)
(
R
d
)
S
t
a
n
d
a
r
d
s

A
u
s
t
r
a
l
i
a
V
e
r
s
i
o
n

3
.
0
D
a
t
e
:

2
8
/
1
/
2
0
0
6
0
.
0
0
E
+
0
0
7
.
4
3
E
-
1
0
2
.
9
7
E
-
0
9
0
.
0
0
E
+
0
0
D
i
r
e
c
t

S
t
r
i
k
e

R
i
s
k
Y
e
s
T
r
a
n
s
f
o
r
m
e
r

a
t

S
t
r
u
c
t
u
r
e
2
.
9
9
E
-
0
9
O
v
e
r
a
l
l

R
i
s
k





L
o
s
s

o
f

H
u
m
a
n

L
i
f
e





L
o
s
s

o
f

E
s
s
e
n
t
i
a
l

S
e
r
v
i
c
e
s
2
.
0
6
E
-
0
5
7
.
4
4
E
-
1
0
2
.
0
6
E
-
0
5
I
n
d
i
r
e
c
t

S
t
r
i
k
e

R
i
s
k
(
R
i
)
8
.
3
2
E
-
1
3





L
o
s
s

o
f

C
u
l
t
u
r
a
l

H
e
r
i
t
a
g
e
A
c
c
e
p
t
a
b
l
e

R
i
s
k
1
.
0
E
-
0
5





E
c
o
n
o
m
i
c

L
o
s
s
1
.
0
E
-
0
3
1
.
0
E
-
0
3
C
a
l
c
u
l
a
t
e
d

R
i
s
k
0
.
0
0
E
+
0
0
3
.
7
4
E
-
0
7
1
.
0
E
-
0
3
R
e
m
o
t
e

P
u
m
p

S
t
a
t
i
o
n
S
t
r
u
c
t
u
r
e

I
d
e
n
t
i
f
i
c
a
t
i
o
n
0
A
c
c
e
p
t
a
b
l
e

R
i
s
k

o
f

E
c
o
n
o
m
i
c

L
o
s
s
e
s
S
e
r
v
i
c
e

L
i
n
e
s
P
o
w
e
r

L
i
n
e
C
a
t
e
g
o
r
y

1

-

L
o
s
s

o
f

H
u
m
a
n

L
i
f
e
O
v
e
r
h
e
a
d
L
o
s
s

C
a
t
e
g
o
r
i
e
s
0
S
t
e
p

&

T
o
u
c
h

P
o
t
e
n
t
i
a
l

D
a
m
a
g
e

F
a
c
t
o
r
s
S
u
r
g
e

P
r
o
t
e
c
t
i
o
n

o
n

A
l
l

E
q
u
i
p
m
e
n
t
0
U
n
s
c
r
e
e
n
e
d
0
.
2
C
a
t
e
g
o
r
y

3

-

L
o
s
s

o
f

C
u
l
t
u
r
a
l

H
e
r
i
t
a
g
e
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
S
e
r
v
i
c
e

L
i
n
e

D
e
n
s
i
t
y
N
u
m
b
e
r
C
a
b
l
e

T
y
p
e
E
n
v
i
r
o
n
m
e
n
t
a
l

F
a
c
t
o
r
R
i
s
k

o
f

D
a
n
g
e
r
o
u
s

D
i
s
c
h
a
r
g
e
I
n
t
e
r
n
a
l

W
i
r
i
n
g

T
y
p
e
P
r
o
t
e
c
t
i
o
n

M
e
a
s
u
r
e
s
R
u
r
a
l
0
N
o
n
e
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
S
p
e
c
i
a
l

H
a
z
a
r
d
S
e
r
v
i
c
e
C
a
t
e
g
o
r
y

2

-

L
o
s
s

o
f

E
s
s
e
n
t
i
a
l

S
e
r
v
i
c
e
s
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
0
1
E
f
f
i
c
i
e
n
c
y

o
f


B
u
i
l
d
i
n
g

P
r
o
t
e
c
t
i
o
n
Y
e
s
S
u
r
g
e

P
r
o
t
e
c
t
i
o
n

a
t

P
o
i
n
t

o
f

E
n
t
r
y
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
1
.
E
-
0
4
2
I
s
o
l
a
t
e
d
0
.
0
1
0
.
1
U
n
s
c
r
e
e
n
e
d
0
L
o
w
U
n
s
c
r
e
e
n
e
d
E
n
v
i
r
o
n
m
e
n
t
0
L
e
n
g
t
h

(
m
)
W
i
d
t
h

(
m
)
S
t
r
u
c
t
u
r
e

A
t
t
r
i
b
u
t
e
s
R
i
s
k

o
f

F
i
r
e

o
r

P
h
y
s
i
c
a
l

D
a
m
a
g
e
1
.
E
-
0
3
R
i
s
k

A
s
s
e
s
s
m
e
n
t

f
o
r

L
i
g
h
t
n
i
n
g

P
r
o
t
e
c
t
i
o
n
O
t
h
e
r

O
v
e
r
h
e
a
d

S
e
r
v
i
c
e
s
L
o
w
3 3 3
C
a
t
e
g
o
r
y

4

-

E
c
o
n
o
m
i
c

L
o
s
s
H
e
i
g
h
t

(
m
)
3
.
7
1
E
-
0
7
G
r
o
u
n
d

f
l
a
s
h

d
e
n
s
i
t
y
S
t
r
u
c
t
u
r
e

D
i
m
e
n
s
i
o
n
s
C
a
b
l
e

T
y
p
e
O
t
h
e
r

U
n
d
e
r
g
r
o
u
n
d

S
e
r
v
i
c
e
s
U
n
s
c
r
e
e
n
e
d
N
o

T
r
a
n
s
f
o
r
m
e
r
N
u
m
b
e
r
C
a
b
l
e

T
y
p
e
F
i
r
e

P
r
o
t
e
c
t
i
o
n

For DOD Internal Use ONLY


COPYRIGHT
116
AS/NZS 1768:2007
A
2
.
5



E
x
a
m
p
l
e

5

T
w
o

s
t
o
r
e
y

h
o
u
s
e

(
R
)
(
R
a
)
(
R
d
)
S
t
a
n
d
a
r
d
s

A
u
s
t
r
a
l
i
a
V
e
r
s
i
o
n

3
.
0
D
a
t
e
:

2
8
/
1
/
2
0
0
6
0
.
0
0
E
+
0
0
1
.
6
5
E
-
0
6
0
.
0
0
E
+
0
0
0
.
0
0
E
+
0
0
D
i
r
e
c
t

S
t
r
i
k
e

R
i
s
k
N
o
T
r
a
n
s
f
o
r
m
e
r

a
t

S
t
r
u
c
t
u
r
e
5
.
7
9
E
-
0
6
O
v
e
r
a
l
l

R
i
s
k





L
o
s
s

o
f

H
u
m
a
n

L
i
f
e





L
o
s
s

o
f

E
s
s
e
n
t
i
a
l

S
e
r
v
i
c
e
s
0
.
0
0
E
+
0
0
2
.
7
2
E
-
0
6
0
.
0
0
E
+
0
0
I
n
d
i
r
e
c
t

S
t
r
i
k
e

R
i
s
k
(
R
i
)
1
.
0
7
E
-
0
6





L
o
s
s

o
f

C
u
l
t
u
r
a
l

H
e
r
i
t
a
g
e
A
c
c
e
p
t
a
b
l
e

R
i
s
k
1
.
0
E
-
0
5





E
c
o
n
o
m
i
c

L
o
s
s
1
.
0
E
-
0
3
1
.
0
E
-
0
3
C
a
l
c
u
l
a
t
e
d

R
i
s
k
0
.
0
0
E
+
0
0
8
.
0
7
E
-
0
4
1
.
0
E
-
0
3
T
w
o

S
t
o
r
e
y

H
o
u
s
e
S
t
r
u
c
t
u
r
e

I
d
e
n
t
i
f
i
c
a
t
i
o
n
0
A
c
c
e
p
t
a
b
l
e

R
i
s
k

o
f

E
c
o
n
o
m
i
c

L
o
s
s
e
s
S
e
r
v
i
c
e

L
i
n
e
s
P
o
w
e
r

L
i
n
e
C
a
t
e
g
o
r
y

1

-

L
o
s
s

o
f

H
u
m
a
n

L
i
f
e
O
v
e
r
h
e
a
d
L
o
s
s

C
a
t
e
g
o
r
i
e
s
0
S
t
e
p

&

T
o
u
c
h

P
o
t
e
n
t
i
a
l

D
a
m
a
g
e

F
a
c
t
o
r
s
S
u
r
g
e

P
r
o
t
e
c
t
i
o
n

o
n

A
l
l

E
q
u
i
p
m
e
n
t
0
U
n
s
c
r
e
e
n
e
d
0
.
3
C
a
t
e
g
o
r
y

3

-

L
o
s
s

o
f

C
u
l
t
u
r
a
l

H
e
r
i
t
a
g
e
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
S
e
r
v
i
c
e

L
i
n
e

D
e
n
s
i
t
y
N
u
m
b
e
r
C
a
b
l
e

T
y
p
e
E
n
v
i
r
o
n
m
e
n
t
a
l

F
a
c
t
o
r
R
i
s
k

o
f

D
a
n
g
e
r
o
u
s

D
i
s
c
h
a
r
g
e
I
n
t
e
r
n
a
l

W
i
r
i
n
g

T
y
p
e
P
r
o
t
e
c
t
i
o
n

M
e
a
s
u
r
e
s
S
u
b
u
r
b
a
n
0
N
o
n
e
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
S
p
e
c
i
a
l

H
a
z
a
r
d
S
e
r
v
i
c
e
C
a
t
e
g
o
r
y

2

-

L
o
s
s

o
f

E
s
s
e
n
t
i
a
l

S
e
r
v
i
c
e
s
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
0
.
0
5
1
E
f
f
i
c
i
e
n
c
y

o
f


B
u
i
l
d
i
n
g

P
r
o
t
e
c
t
i
o
n
N
o
S
u
r
g
e

P
r
o
t
e
c
t
i
o
n

a
t

P
o
i
n
t

o
f

E
n
t
r
y
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
F
i
r
e

D
a
m
a
g
e

F
a
c
t
o
r
O
v
e
r
v
o
l
t
a
g
e

D
a
m
a
g
e

F
a
c
t
o
r
1
.
E
-
0
4
2
L
o
w
e
r

H
e
i
g
h
t
0
0
U
n
s
c
r
e
e
n
e
d
1
H
i
g
h
U
n
s
c
r
e
e
n
e
d
E
n
v
i
r
o
n
m
e
n
t
0
L
e
n
g
t
h

(
m
)
W
i
d
t
h

(
m
)
S
t
r
u
c
t
u
r
e

A
t
t
r
i
b
u
t
e
s
R
i
s
k

o
f

F
i
r
e

o
r

P
h
y
s
i
c
a
l

D
a
m
a
g
e
1
.
E
-
0
3
R
i
s
k

A
s
s
e
s
s
m
e
n
t

f
o
r

L
i
g
h
t
n
i
n
g

P
r
o
t
e
c
t
i
o
n
O
t
h
e
r

O
v
e
r
h
e
a
d

S
e
r
v
i
c
e
s
L
o
w
2
0
3
0
1
2
C
a
t
e
g
o
r
y

4

-

E
c
o
n
o
m
i
c

L
o
s
s
H
e
i
g
h
t

(
m
)
8
.
0
1
E
-
0
4
G
r
o
u
n
d

f
l
a
s
h

d
e
n
s
i
t
y
S
t
r
u
c
t
u
r
e

D
i
m
e
n
s
i
o
n
s
C
a
b
l
e

T
y
p
e
O
t
h
e
r

U
n
d
e
r
g
r
o
u
n
d

S
e
r
v
i
c
e
s
U
n
s
c
r
e
e
n
e
d
N
o

T
r
a
n
s
f
o
r
m
e
r
N
u
m
b
e
r
C
a
b
l
e

T
y
p
e
F
i
r
e

P
r
o
t
e
c
t
i
o
n

For DOD Internal Use ONLY
117 AS/NZS 1768:2007

COPYRIGHT
117
A3 SAMPLE BY-HAND CALCULATION40 METRE HIGH OFFICE BLOCK
The following calculates the risk of lightning damage to a structure and its equipment
outlined in initial work by IEC Committee TC 81. One power line and any number of
overhead and underground service lines are considered. Selectable parameters have been
tailored for Australian and New Zealand conditions.
Parameter Example value

Lightning activity
N
g
N
g
= 3 Ground strike density in ground strikes per km
2
per year
STRUCTURE
L L = 20 m Structure length in metres
W W = 20 m Structure width in metres
H H = 40 m Structure height in metres
C
d
C
d
= 1.0 Environmental factor for surrounding object height
(direct strikes to structure)
Structure in large area of structures or trees of the
same height or greater e.g. typical building in
CBD, or shed in an industrial area 0.25
Structure surrounded by smaller structures. e.g. tall
building in urban area 0.5
Isolated structure with no other structures or
objects within a distance of 3 height from the
structure. e.g. structure in a rural area 1
Isolated structure on hilltop or knoll. e.g.
communications site 2
D
m
D
m
= 250 m Distance from structure that a lightning strike to
ground creates a magnetic field which may be
great enough to induce an overvoltage exceeding
the impulse level of internal equipment.
Fixed factor 250 m
C
s
C
s
= 0.01 Correction factor for surrounding area. (Density
factor relating to service drops)
CBD 0
Urban 0.1
Suburban 0.5
Rural 1
P
h
P
h
= 0.01 Probability that lightning will cause a shock to
animals or human beings outside the structure due
to dangerous step and touch potentials.
Fixed factor 10
2

P
g
P
g
= 10
5
Probability that lightning will cause a shock to
animals or human beings inside the structure due to
dangerous step and touch potentials.
Fixed factor 10
5

For DOD Internal Use ONLY
AS/NZS 1768:2007 118

COPYRIGHT
118
Parameter Example value

P
f
P
f
= 0.001 Probability that a dangerous discharge will initiate
a fire, explosion, mechanical destruction or
chemical release.
Explosive high risk of explosion (petrochemical
plant) 1
High risk of mechanical and thermal effects (High
or significant risk of fire or mechanical damage,
roof of combustible material, e.g. thatched roof) 10
1

Medium risk of mechanical and thermal effects
(Significant use of combustible building material,
e.g. timber frame; OR risk of mechanical damage,
e.g. significant masonry dislodged) 10
2

Low risk of mechanical and thermal effects (eg.
modern reinforced concrete building) 10
3

Negligible risk of mechanical and thermal effects
(all metal structure) 0
P
s
P
s
= 0.2 Probability of a dangerous discharge based on
structure type
High
(Brick, masonry, flammable material, timber or
non-conducting material, unprotected roof
installations with electrical lines to inside, e.g.
antennae) 1
Medium
(Continuous reinforced concrete or steel columns
or downconductors. Maximum spacing 20 m) 0.2
Low
(all metal construction) 0.01
P
i
P
i
= 1 Probability of a dangerous discharge based on
internal wiring type
Unscreened wiring 1
Continuously screened wiring 0.1
EQUIPMENT
k
w
k
w
= 1
Correction factor for impulse level of equipment.


Fixed factor
1
(applies to
impulse level
of 1.5 kV)
CONDUCTIVE SERVICE LINES
Assumes one or no power line and it is either overhead or underground. The quantity of overhead
and underground service lines in separate routes must be selected. The length of service lines is
determined based on rural, urban, suburban or CBD situation. Assumes there is no adjacent
structure connected by a service line.
Power line
P
l
P
l
= 2 Power line type
Overhead 1
Underground 2
None 0
For DOD Internal Use ONLY
119 AS/NZS 1768:2007

COPYRIGHT
119
Parameter Example value

P
e0
P
e0
= 1 Probability of dangerous discharge based on
external wiring type
Unscreened wiring 1
Screened cable with screen earthed or wiring in
continuous metal conduit that is earthed 0.4
C
t0
C
t0
= 1 Correction factor for transformer
LV line, no transformer 1
MV line with HV/LV transformer or isolation
transformer 0.25
Overhead service line
n
oh
n
oh
= 0 Number of overhead service lines in separate
routes
P
e1
P
e1
= 1 Probability of dangerous discharge based on
external wiring type
Unscreened wiring 1
Screened cable with screen earthed or wiring in
continuous metal conduit that is earthed 0.4
Fibre optic lines without metal conductors 0

1

1
= 100 m Soil resistivity
Fixed factor 100 m
H
cl
H
cl
= 7 m Height of conductors above ground
Fixed value 7 m
L
1
L
1
= 100 m Length of line to the structure from the last
distribution node
CBD 0 m
Urban 100 m
Suburban 500 m
Rural 1000 m
Assume there is no adjacent structure
1
a1
1
a1
= 0 m Length of adjacent structure
w
a1
w
a1
= 0 m Width of adjacent structure
h
a1
h
a1
= 0 m Height of adjacent structure
C
t1
C
t1
= 1 Correction factor for transformer
Fixed factor 1
(no isolation
transformer)
Conductive underground servicesElectrical services e.g. Communication lines
n
ug
n
ug
= 0 Number of underground service lines in separate
routes
P
e2
P
e2
= 1 Probability of dangerous discharge based on
external service type
Unscreened wiring 1
Screened cable with screen earthed or wiring in
continuous metal conduit that is earthed 0.4

2

2
= 100 m Soil resistivity
Fixed factor 100 m
For DOD Internal Use ONLY
AS/NZS 1768:2007 120

COPYRIGHT
120
Parameter Example value

L
2
L
2
= 100 m Length of line to the structure from the last
distribution node
CBD 0 m
Urban 100 m
Suburban 500 m
Rural 1000 m
Assume there is no adjacent structure
1
a2
1
a2
= 0 m Length of adjacent structure
w
a2
w
a2
= 0 m Width of adjacent structure
h
a2
h
a2
= 0 m Height of adjacent structure
C
t2
C
t2
= 1 Correction factor for transformer
Fixed factor 1
(no isolation
transformer)
ACCEPTABLE RISK AND DAMAGE FACTORS
Damage category 1Loss of human life
R
a1
R
a1
= 10
5
Acceptable risk. Probability of loss of human life
per year
Fixed value for loss of human life 10
5

k
h1
k
h1
= 10 Increasing factor applied to damage factor for fire
and overvoltage when risk of loss of human life is
aggravated by special hazards
Low level of panic (building with less than three
floors and less than 100 people) 1
Difficulty of evacuation, immobilized people 5
Average level of panic (sport or cultural structure
with between 100 and 1000 people) 10
High level of panic (theatres, concert halls,
cultural and sport events with more than 1000
people) 100
Hazards for surroundings or environment 200
Contamination of surroundings or environment 500

h1

h1
= 0.01 Damage factor for step and touch potential outside
structure
Fixed value 0.01

g1

g1
= 0.0001 Damage factor for step and touch potential inside
structure
Fixed value 0.0001

f1

f1
= 0.05 Damage factor for fire
Loss of human life
Hospitals, hotels, public buildings 0.1
Industrial properties, properties for commercial
activities, schools, offices 0.05
Public entertainment buildings, churches,
museums, temporary structure 0.005
For DOD Internal Use ONLY
121 AS/NZS 1768:2007

COPYRIGHT
121
Parameter Example value

o1

o1
= 0 Damage factor for overvoltages
Loss of human life
Hospitals 0.0005
Industrial properties with risk of explosion 0.05
Other structures 0
Damage category 2Loss of essential service to the public
R
a2
R
a2
= 10
3
Acceptable risk. Probability of loss of essential
service to the public per year
Fixed value for loss of service to the public 10
3

f2

f2
= 0 Damage factor for fire
Unacceptable loss of service to the public
Gas supply 0.2
Water supply 0.1
Radio and television 0.08
Telecommunications 0.06
Power supply, railway 0.04
No essential service function associated with the
structure 0

o2

o2
= 0 Damage factor for overvoltages
Unacceptable loss of service to the public
Gas supply 0.02
Water supply 0.01
Radio and television 0.005
Telecommunications 0.003
Power supply, railway 0.001
No essential service function associated with the
structure 0
Damage category 3Loss of cultural heritage (it is assumed there are no electronic devices
inside)
R
a3
R
a3
= 10
3
Acceptable risk. Probability of loss of cultural
heritage per year
Fixed value for loss of cultural heritage 10
3

f3

f3
= 0 Damage factor for fire
Loss of irreplaceable cultural heritage
Typical value 0.5
No cultural heritage value 0
Damage category 4Economic loss
R
a4
R
a4
= 10
3
Acceptable risk for economic loss. Probability of
economic loss per year
Depends on structure owners requirement
Range available is 0.1, 0.01, 0.001, 0.0001,
0.00001 Suggest 0.001
For DOD Internal Use ONLY
AS/NZS 1768:2007 122

COPYRIGHT
122
Parameter Example value

k
h4
k
h4
= 1 Increasing factor applied to damage factor for fire
and overvoltage when risk of loss of human life is
aggravated by special hazards
Fixed value 1
(no special
hazard factor)

h4

h4
= 0 Damage factor for step and touch potential outside
structure
Fixed value for agricultural properties with
animals around the structure 0.01
Otherwise 0

g4

g4
= 0 Damage factor for step and touch potential inside
structure
Fixed value for agricultural properties with
animals inside the structure 0.0001
Otherwise 0

f4

f4
= 0.3 Damage factor for fire
Economic loss

f
= average value of possible loss/total value
structure, contents and activities
Typical values for economic loss:
Hospitals, hotels, industrial properties, museums 0.5
Properties for public use, agricultural properties 0.4
Offices, schools 0.3
Commercial activities, public entertainment 0.2
Prisons, churches 0.1
No economic loss 0

o4

o4
= 0.001 Damage factor for overvoltages
Economic loss

o
= average value of possible loss/total value
structure, contents and activities
Typical values for economic loss:
Hospitals, hotels, industrial properties, museums 0.005
Properties for public use, agricultural properties,
offices, schools 0.001
Commercial activities, public entertainment 0.0001
Prisons, churches 0.00001
No economic loss 0
For DOD Internal Use ONLY
123 AS/NZS 1768:2007

COPYRIGHT
123
Parameter Example value

LIGHTNING PROTECTION MEASURES
E E = 0.8 Efficiency of lightning protection system on the
structure. Takes into account interception and
sizing efficiencies
Level I 98%
Level II 95%
Level III 90%
Level IV 80%
No protection 0%
Assumes surge protection is applied to all OR
none of the internal equipment of the structure
k
2
k
2
= 1 Reduction factor for isolation equipment on
internal equipment
Fixed factor 1
(no isolation
transformer
on internal
equipment)
k
3
k
3
= 1 Reduction factor for surge protection device on
input of equipment
Surge protection device on input of equipment 0.01
No surge protection device on input of equipment 1.0
k
f
k
f
= 1 Reduction factor for fire protection measures
No protection measures 1.0
Extinguishers, hydrants, manual alarm
installations, fixed manually operated
extinguishing installations 0.8
Protection escape routes, fireproof compartments,
automatic alarms protected from overvoltage,
automatically operated extinguishers, operating
time of escape routes less than 10 minutes 0.6
Conductive service linesassumes surge protection must be applied to all OR none of the
service lines
k
4
k
4
= 1 Reduction factor for isolation equipment at
entry point of service line
Fixed factor 1
(no isolation
transformer on line
entry point)
k
5
k
5
= 0.01 Reduction factor for surge protection device
on entry point of service line
Surge protection device on entry point of line 0.01
No surge protection device on entry point of
line 1.0
For DOD Internal Use ONLY


COPYRIGHT
124
AS/NZS 1768:2007
C
A
L
C
U
L
A
T
I
O
N
S

P
a
r
a
m
e
t
e
r

E
x
a
m
p
l
e

v
a
l
u
e





D
i
r
e
c
t

s
t
r
i
k
e
s

t
o

s
t
r
u
c
t
u
r
e

A
d

=

L


W

+

6


(
L

+

W
)

+

9


H
2

A
d

=

0
.
0
5
5

k
m
2

C
o
l
l
e
c
t
i
o
n

a
r
e
a

i
n

s
q
u
a
r
e

m
e
t
r
e
s

f
o
r

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e
.

B
a
s
e
d

o
n

i
n
t
e
r
s
e
c
t
i
o
n

o
f

g
r
o
u
n
d

s
u
r
f
a
c
e

a
n
d

a

l
i
n
e

w
i
t
h

s
l
o
p
e

o
f

1
/
3

t
h
a
t

t
o
u
c
h
e
s

t
h
e

t
o
p

o
f

t
h
e

s
t
r
u
c
t
u
r
e

N
d

=

N
g


A
d


C
d

N
d

=

0
.
1
6
5
7

A
v
e
r
a
g
e

n
u
m
b
e
r

o
f

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

p
e
r

y
e
a
r

I
n
d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

s
t
r
u
c
t
u
r
e

A
m

=

L


W

+

2


D
m


(
L

+

W
)

+

D
m
2


A
d


A
r
e
a

o
f

i
n
f
l
u
e
n
c
e

f
o
r

g
e
n
e
r
a
t
i
o
n

o
f

o
v
e
r
v
o
l
t
a
g
e
s

A
m

=

i
f

(
A
m

<

0
,

0

k
m
2

,

A
m
)

A
m

=

0
.
1
6
2

k
m
2

L
i
m
i
t

m
i
n
i
m
u
m

v
a
l
u
e

t
o

z
e
r
o

i
f

h
e
i
g
h
t

o
f

s
t
r
u
c
t
u
r
e

i
s

t
o
o

l
a
r
g
e

N
m

=

N
g


A
m

N
m

=

0
.
4
8
4
5

A
v
e
r
a
g
e

n
u
m
b
e
r

o
f

s
t
r
i
k
e
s

d
i
r
e
c
t

t
o

g
r
o
u
n
d

o
r

t
o

g
r
o
u
n
d
e
d

o
b
j
e
c
t
s

n
e
a
r

t
h
e

s
t
r
u
c
t
u
r
e

p
e
r

y
e
a
r

c
a
u
s
i
n
g

o
v
e
r
v
o
l
t
a
g
e
s

O
V
E
R
H
E
A
D

S
E
R
V
I
C
E

L
I
N
E

n
o
h
p

=

i
f

(
P
l

=

1
,

1
,

0
)

n
o
h
p

=

0

C
a
l
c
u
l
a
t
e

n
u
m
b
e
r

o
f

o
v
e
r
h
e
a
d

p
o
w
e
r

s
e
r
v
i
c
e

l
i
n
e
s

D
i
r
e
c
t

s
t
r
i
k
e
s

t
o

o
v
e
r
h
e
a
d

l
i
n
e

D
c
1

=

3


H
c
1

D
c
1

=

2
1

m

L
a
t
e
r
a
l

d
i
s
t
a
n
c
e

f
o
r

o
v
e
r
h
e
a
d

l
i
n
e

L
c
1

=

L
1


h
a
1

L
c
1

=

2
0

m

E
f
f
e
c
t
i
v
e

l
e
n
g
t
h

f
o
r

o
v
e
r
h
e
a
d

l
i
n
e

L
c
1

=

i
f

(
L
c
1


0

m
,

L
c
1
,

0

m
)

L
c
1

=

0

m


A
c
1

=

2


D
c
1


L
c
1

A
c
1

=

0

k
m
2

C
o
l
l
e
c
t
i
o
n

a
r
e
a

f
o
r

o
v
e
r
h
e
a
d

l
i
n
e

A
a
1

=

1
a
1


w
a
l

+

6


h
a
l


(
1
a
1

+

w
a
1
)

+

9

h
a
l
2

A
a
1

=

0

k
m
2

C
o
l
l
e
c
t
i
o
n

a
r
e
a

f
o
r

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

a
d
j
a
c
e
n
t

s
t
r
u
c
t
u
r
e

For DOD Internal Use ONLY


COPYRIGHT
125
AS/NZS 1768:2007
C
A
L
C
U
L
A
T
I
O
N
S

P
a
r
a
m
e
t
e
r

E
x
a
m
p
l
e

v
a
l
u
e


N
c
1
p

=

N
g


(
A
c
1

+

A
a
1
)


C
t
0


C
s

N
c
1
p

=

0

A
v
e
r
a
g
e

n
u
m
b
e
r

o
f

s
t
r
i
k
e
s

d
i
r
e
c
t

t
o

t
h
e

o
v
e
r
h
e
a
d

p
o
w
e
r

l
i
n
e

p
e
r

y
e
a
r

t
h
a
t

a
r
e

p
o
t
e
n
t
i
a
l
l
y

d
a
n
g
e
r
o
u
s

N
c
1

=

N
g


(
A
c
1

+

A
a
1
)


C
t
1


C
s

N
c
1

=

0

A
v
e
r
a
g
e

n
u
m
b
e
r

o
f

s
t
r
i
k
e
s

d
i
r
e
c
t

t
o

o
t
h
e
r

c
o
n
d
u
c
t
i
v
e

o
v
e
r
h
e
a
d

l
i
n
e

p
e
r

y
e
a
r

t
h
a
t

a
r
e

p
o
t
e
n
t
i
a
l
l
y

d
a
n
g
e
r
o
u
s

I
n
d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

o
v
e
r
h
e
a
d

l
i
n
e

D
1
1

=

5
0
0


0
.
5
0
.
5
1
m
o
h
m


D
1
1

=

5
0
0
0

m

L
a
t
e
r
a
l

d
i
s
t
a
n
c
e

f
o
r

i
n
d
u
c
e
d

o
v
e
r
v
o
l
t
a
g
e
s

d
u
e

t
o

s
t
r
i
k
e
s

t
o

g
r
o
u
n
d

n
e
a
r

t
h
e

l
i
n
e

A
1
1

=

2


D
1
1


L
1

A
1
1

=

1

k
m
2

C
o
l
l
e
c
t
i
o
n

a
r
e
a

f
o
r

i
n
d
u
c
e
d

o
v
e
r
v
o
l
t
a
g
e
s

d
u
e

t
o

s
t
r
i
k
e
s

t
o

g
r
o
u
n
d

n
e
a
r

t
h
e

o
v
e
r
h
e
a
d

l
i
n
e

N
1
1
p

=

N
g


A
1
1


C
t
0


C
s

N
1
1
p

=

0
.
3
0

A
v
e
r
a
g
e

n
u
m
b
e
r

o
f

s
t
r
i
k
e
s

t
o

g
r
o
u
n
d

n
e
a
r

t
h
e

o
v
e
r
h
e
a
d

p
o
w
e
r

l
i
n
e

p
e
r

y
e
a
r

t
h
a
t

c
a
u
s
e

p
o
t
e
n
t
i
a
l
l
y

d
a
n
g
e
r
o
u
s

i
n
d
u
c
e
d

v
o
l
t
a
g
e
s

N
1
1

=

N
g


A
1
1


C
t
1


C
s

N
1
1

=

0
.
3
0

A
v
e
r
a
g
e

n
u
m
b
e
r

o
f

s
t
r
i
k
e
s

t
o

g
r
o
u
n
d

n
e
a
r

o
t
h
e
r

c
o
n
d
u
c
t
i
v
e

o
v
e
r
h
e
a
d

l
i
n
e

p
e
r

y
e
a
r

t
h
a
t

c
a
u
s
e

p
o
t
e
n
t
i
a
l
l
y

d
a
n
g
e
r
o
u
s

i
n
d
u
c
e
d

v
o
l
t
a
g
e
s

U
N
D
E
R
G
R
O
U
N
D

S
E
R
V
I
C
E

L
I
N
E

n
u
g
p

=

i
f

(
P
l

=

2
,

1
,

0
)

n
u
g
p

=

1

C
a
l
c
u
l
a
t
e

t
o
t
a
l

n
u
m
b
e
r

o
f

u
n
d
e
r
g
r
o
u
n
d


p
o
w
e
r

s
e
r
v
i
c
e

l
i
n
e
s

D
i
r
e
c
t

s
t
r
i
k
e
s

t
o

u
n
d
e
r
g
r
o
u
n
d

s
e
r
v
i
c
e

l
i
n
e

D
c
2

=

0
.
2


0
.
5
0
.
5
2
m
o
h
m


D
c
2

=

2

m

L
a
t
e
r
a
l

d
i
s
t
a
n
c
e

f
o
r

u
n
d
e
r
g
r
o
u
n
d

l
i
n
e

L
c
2

=

L
2


h
a
2

L
c
2

=

2
0

m

E
f
f
e
c
t
i
v
e

l
e
n
g
t
h

f
o
r

u
n
d
e
r
g
r
o
u
n
d

l
i
n
e

L
c
2

=

i
f

(
L
c
2


m
,

L
c
2
,

0


m
)

L
c
2

=

0

m


A
c
2

=

2


D
c
2


L
c
2

A
c
2

=

0

k
m
2

C
o
l
l
e
c
t
i
o
n

a
r
e
a

f
o
r

u
n
d
e
r
g
r
o
u
n
d

l
i
n
e

A
a
2

=

1
a
2


w
a
2

+

6


h
a
2


(
1
a
2

+

w
a
2
)

+

9


h
a
2
2

A
a
2

=

0

k
m
2

C
o
l
l
e
c
t
i
o
n

a
r
e
a

f
o
r

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

a
d
j
a
c
e
n
t

s
t
r
u
c
t
u
r
e

For DOD Internal Use ONLY


COPYRIGHT
126
AS/NZS 1768:2007
C
A
L
C
U
L
A
T
I
O
N
S

P
a
r
a
m
e
t
e
r

E
x
a
m
p
l
e

v
a
l
u
e


N
c
2
p

=

N
g


(
A
c
2

+

A
a
2
)


C
t
0


C
s

N
c
2
p

=

0

A
v
e
r
a
g
e

n
u
m
b
e
r

o
f

s
t
r
i
k
e
s

d
i
r
e
c
t

t
o

t
h
e

u
n
d
e
r
g
r
o
u
n
d

p
o
w
e
r

l
i
n
e

p
e
r

y
e
a
r

t
h
a
t

a
r
e

p
o
t
e
n
t
i
a
l
l
y

d
a
n
g
e
r
o
u
s

N
c
2

=

N
g


(
A
c
2

+

A
a
2
)


C
t
2


C
s

N
c
2

=

0

A
v
e
r
a
g
e

n
u
m
b
e
r

o
f

s
t
r
i
k
e
s

d
i
r
e
c
t

t
o

o
t
h
e
r

c
o
n
d
u
c
t
i
v
e

u
n
d
e
r
g
r
o
u
n
d


l
i
n
e

p
e
r

y
e
a
r

t
h
a
t

a
r
e

p
o
t
e
n
t
i
a
l
l
y

d
a
n
g
e
r
o
u
s

I
n
d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

u
n
d
e
r
g
r
o
u
n
d

s
e
r
v
i
c
e

l
i
n
e

D
1
2

=

2
5
0


0
.
5
0
.
5
2
m
o
h
m


D
1
2

=

2
5
0
0

m

L
a
t
e
r
a
l

d
i
s
t
a
n
c
e

f
o
r

i
n
d
u
c
e
d

o
v
e
r
v
o
l
t
a
g
e
s

d
u
e

t
o

s
t
r
i
k
e
s

t
o

g
r
o
u
n
d

n
e
a
r

t
h
e

u
n
d
e
r
g
r
o
u
n
d

c
a
b
l
e

A
1
2

=

2


D
1
2


L
2

A
1
2

=

0
.
5

k
m
2

C
o
l
l
e
c
t
i
o
n

a
r
e
a

f
o
r

i
n
d
u
c
e
d

o
v
e
r
v
o
l
t
a
g
e
s

d
u
e

t
o

s
t
r
i
k
e
s

t
o

g
r
o
u
n
d

n
e
a
r

t
h
e

u
n
d
e
r
g
r
o
u
n
d

c
a
b
l
e

N
1
2
p

=

N
g


A
1
2


C
t
0


C
s

N
1
2
p

=

0
.
1
5

A
v
e
r
a
g
e

n
u
m
b
e
r

o
f

s
t
r
i
k
e
s

t
o

g
r
o
u
n
d

n
e
a
r

t
h
e

u
n
d
e
r
g
r
o
u
n
d

p
o
w
e
r

c
a
b
l
e

p
e
r

y
e
a
r

t
h
a
t

c
a
u
s
e

p
o
t
e
n
t
i
a
l
l
y

d
a
n
g
e
r
o
u
s

i
n
d
u
c
e
d

v
o
l
t
a
g
e
s

N
1
2

=

N
g


A
1
2


C
t
2


C
s

N
1
2

=

0
.
1
5

A
v
e
r
a
g
e

n
u
m
b
e
r

o
f

s
t
r
i
k
e
s

t
o

g
r
o
u
n
d

n
e
a
r

o
t
h
e
r

u
n
d
e
r
g
r
o
u
n
d

c
a
b
l
e

p
e
r

y
e
a
r

t
h
a
t

c
a
u
s
e

p
o
t
e
n
t
i
a
l
l
y

d
a
n
g
e
r
o
u
s

i
n
d
u
c
e
d

v
o
l
t
a
g
e
s

R
I
S
K

C
A
L
C
U
L
A
T
I
O
N
S

F
O
R

D
A
M
A
G
E

C
A
T
E
G
O
R
Y

1


L
o
s
s

o
f

h
u
m
a
n

l
i
f
e

R
i
s
k

o
f

d
a
n
g
e
r
o
u
s

s
t
e
p

a
n
d

t
o
u
c
h

p
o
t
e
n
t
i
a
l

o
u
t
s
i
d
e

s
t
r
u
c
t
u
r
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

s
t
r
u
c
t
u
r
e

k
1

=

1


E


R
e
d
u
c
t
i
o
n

f
a
c
t
o
r

f
o
r

s
t
r
u
c
t
u
r
e

l
i
g
h
t
n
i
n
g

p
r
o
t
e
c
t
i
o
n

s
y
s
t
e
m

P
h
1

=

k
1


P
h


P
s

P
h
1

=

4


1
0
-
4

P
r
o
b
a
b
i
l
i
t
y

o
f

d
a
n
g
e
r
o
u
s

s
t
e
p

a
n
d

t
o
u
c
h

v
o
l
t
a
g
e
s

o
u
t
s
i
d
e

s
t
r
u
c
t
u
r
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

u
n
p
r
o
t
e
c
t
e
d

s
t
r
u
c
t
u
r
e

R
h
1

=

N
d


P
h
1

h
1

R
h
1

=

6
.
6
2
8


1
0
-
7

R
i
s
k

o
f

d
a
n
g
e
r
o
u
s

s
t
e
p

a
n
d

t
o
u
c
h

p
o
t
e
n
t
i
a
l

t
o

h
u
m
a
n
s

o
u
t
s
i
d
e

t
h
e

s
t
r
u
c
t
u
r
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

For DOD Internal Use ONLY


COPYRIGHT
127
AS/NZS 1768:2007
C
A
L
C
U
L
A
T
I
O
N
S

P
a
r
a
m
e
t
e
r

E
x
a
m
p
l
e

v
a
l
u
e


R
i
s
k

o
f

p
h
y
s
i
c
a
l

d
e
s
t
r
u
c
t
i
o
n

d
u
e

t
o

f
i
r
e
,

e
x
p
l
o
s
i
o
n
,

m
e
c
h
a
n
i
c
a
l

d
a
m
a
g
e

a
n
d

c
h
e
m
i
c
a
l

d
i
s
c
h
a
r
g
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

s
t
r
u
c
t
u
r
e

P
e
0

=

i
f

(
P
1

=

0
,

0
,

P
e
0
)

P
e
0

=

1

C
h
e
c
k

i
f

t
h
e
r
e

i
s

n
o

p
o
w
e
r

l
i
n
e
.

I
f

t
h
e
r
e

i
s

n
o

p
o
w
e
r

l
i
n
e

t
h
e
n

s
e
t

t
o

z
e
r
o

P
e
t

=

P
e
0

+

n
o
h


P
e
1

+

n
u
g


P
e
2

P
e
t

=

1

T
o
t
a
l

p
a
r
t
i
a
l

p
r
o
b
a
b
i
l
i
t
y

t
h
a
t

e
x
t
e
r
n
a
l

w
i
r
i
n
g

c
a
r
r
i
e
s

a

s
u
r
g
e

P
e
t
c

=

i
f

(
P
e
t

>

1
,
1
,

P
e
t
)

P
e
t
c

=

1

L
i
m
i
t

p
a
r
t
i
a
l

p
r
o
b
a
b
i
l
i
t
y

t
o

a

m
a
x
i
m
u
m

o
f

1

P
e
w
d

=

k
5


P
e
t
c

P
e
w
d

=

0
.
0
1

P
r
o
b
a
b
i
l
i
t
y

t
h
a
t

e
x
t
e
r
n
a
l

w
i
r
i
n
g

c
a
r
r
i
e
s

a

s
u
r
g
e

f
r
o
m

s
t
r
u
c
t
u
r
e

t
h
a
t

c
a
u
s
e
s

p
h
y
s
i
c
a
l

d
a
m
a
g
e

P
s

=

k
f


P
f


(
k
1


P
s

+

P
e
w
d
)

P
s

=

5


1
0
-
5

P
r
o
b
a
b
i
l
i
t
y

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

s
t
r
u
c
t
u
r
e

w
i
l
l

c
a
u
s
e

p
h
y
s
i
c
a
l

d
a
m
a
g
e

R
s
1

=

N
d


P
s

f
1


k
h
1

R
s
1

=

4
.
1
4
3


1
0
-
6

R
i
s
k

o
f

p
h
y
s
i
c
a
l

d
a
m
a
g
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
i
s
k

o
f

e
l
e
c
t
r
i
c
a
l
/
e
l
e
c
t
r
o
n
i
c

e
q
u
i
p
m
e
n
t

m
a
l
f
u
n
c
t
i
o
n

o
r

f
a
i
l
u
r
e

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

f
r
o
m

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

P
e
w
d
o

=

k
w


k
2


k
3


k
4


k
5


P
e
t
c

P
e
w
d
o

=

0
.
0
1

P
r
o
b
a
b
i
l
i
t
y

t
h
a
t

e
x
t
e
r
n
a
l

w
i
r
i
n
g

c
a
r
r
i
e
s

a

s
u
r
g
e

f
r
o
m

s
t
r
u
c
t
u
r
e

t
h
a
t

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

t
o

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

P
w

=

1


(
1


k
1


P
s


P
i


k
2


k
3


k
w
)


(
1


P
e
w
d
o
)

P
w

=

0
.
0
5

P
r
o
b
a
b
i
l
i
t
y

o
f

e
l
e
c
t
r
o
n
i
c

f
a
i
l
u
r
e

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

f
r
o
m

d
i
r
e
c
t

s
t
r
i
k
e

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
w
1

=

N
d


P
w

o
1


k
h
1

R
w
1

=

0

R
i
s
k

d
u
e

t
o

f
a
i
l
u
r
e

o
r

m
a
l
f
u
n
c
t
i
o
n

o
f

e
l
e
c
t
r
i
c
a
l

a
n
d

e
l
e
c
t
r
o
n
i
c

e
q
u
i
p
m
e
n
t

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

f
r
o
m

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
i
s
k

o
f

e
l
e
c
t
r
i
c
a
l
/
e
l
e
c
t
r
o
n
i
c

e
q
u
i
p
m
e
n
t

m
a
l
f
u
n
c
t
i
o
n

o
r

f
a
i
l
u
r
e

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

f
r
o
m

i
n
d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

P
m

=

k
1


k
2


k
3


k
w


P
s


P
i

P
m

=

0
.
0
4

P
r
o
b
a
b
i
l
i
t
y

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

g
r
o
u
n
d

n
e
a
r

t
h
e

s
t
r
u
c
t
u
r
e

w
i
l
l

c
a
u
s
e

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

t
o

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

R
m
1

=

N
m


P
m

o
1


k
h
1

R
m
1

=

0

R
i
s
k

o
f

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

g
r
o
u
n
d

n
e
a
r

t
h
e

s
t
r
u
c
t
u
r
e

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

For DOD Internal Use ONLY


COPYRIGHT
128
AS/NZS 1768:2007
C
A
L
C
U
L
A
T
I
O
N
S

P
a
r
a
m
e
t
e
r

E
x
a
m
p
l
e

v
a
l
u
e


R
i
s
k

o
f

d
a
n
g
e
r
o
u
s

t
o
u
c
h

p
o
t
e
n
t
i
a
l

i
n
s
i
d
e

s
t
r
u
c
t
u
r
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

s
e
r
v
i
c
e

l
i
n
e
s

P
c
1
p

=

n
o
h
p


k
5


P
e
0

P
c
l
p

=

0

P
r
o
b
a
b
i
l
i
t
y

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

t
h
e

o
v
e
r
h
e
a
d

p
o
w
e
r

l
i
n
e

w
i
l
l

c
a
u
s
e

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

t
o

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

P
c
1

=

n
o
h


k
5


P
e
1

P
c
1

=

0

P
r
o
b
a
b
i
l
i
t
y

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

o
t
h
e
r

o
v
e
r
h
e
a
d

l
i
n
e

w
i
l
l

c
a
u
s
e

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

t
o

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

P
c
2
p

=

n
u
g
p


k
5


P
e
0

P
c
2
p

=

0
.
0
1

P
r
o
b
a
b
i
l
i
t
y

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

t
h
e

u
n
d
e
r
g
r
o
u
n
d

p
o
w
e
r

l
i
n
e

w
i
l
l

c
a
u
s
e

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

t
o

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

P
c
2

=

n
u
g


k
5


P
e
2

P
c
2

=

0

P
r
o
b
a
b
i
l
i
t
y

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

o
t
h
e
r

u
n
d
e
r
g
r
o
u
n
d

l
i
n
e

w
i
l
l

c
a
u
s
e

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

t
o

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

R
g
1

=

P
g


(
N
c
1


P
c
1

+

N
c
2


P
c
2

+

N
c
1
p


P
c
l
p

+

N
c
2
p


P
c
2
p
)

g
1

R
g
1

=

0

R
i
s
k

o
f

d
a
n
g
e
r
o
u
s

s
t
e
p

a
n
d

t
o
u
c
h

p
o
t
e
n
t
i
a
l

t
o

h
u
m
a
n
s

i
n
s
i
d
e

t
h
e

s
t
r
u
c
t
u
r
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
i
s
k

o
f

f
i
r
e
,

e
x
p
l
o
s
i
o
n
,

m
e
c
h
a
n
i
c
a
l

d
a
m
a
g
e

a
n
d

c
h
e
m
i
c
a
l

d
i
s
c
h
a
r
g
e

c
a
u
s
e
d

b
y

e
l
e
c
t
r
i
c
a
l
/
e
l
e
c
t
r
o
n
i
c

e
q
u
i
p
m
e
n
t

m
a
l
f
u
n
c
t
i
o
n

o
r

f
a
i
l
u
r
e

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

f
r
o
m

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

s
e
r
v
i
c
e

l
i
n
e
s

R
c
1

=

k
f


P
f


(
N
c
1


P
c
1

+

N
c
2


P
c
2

+

N
c
1
p


P
c
1
p

+

N
c
2
p


P
c
2
p
)

f
1


k
h
1

R
c
1

=

0

R
i
s
k

o
f

f
i
r
e
,

e
x
p
l
o
s
i
o
n
,

m
e
c
h
a
n
i
c
a
l

d
a
m
a
g
e

a
n
d

c
h
e
m
i
c
a
l

r
e
l
e
a
s
e

c
a
u
s
e
d

b
y

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

s
e
r
v
i
c
e

l
i
n
e
s

w
h
i
c
h

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

For DOD Internal Use ONLY


COPYRIGHT
129
AS/NZS 1768:2007
C
A
L
C
U
L
A
T
I
O
N
S

P
a
r
a
m
e
t
e
r

E
x
a
m
p
l
e

v
a
l
u
e


R
i
s
k

o
f

e
l
e
c
t
r
i
c
a
l
/
e
l
e
c
t
r
o
n
i
c

e
q
u
i
p
m
e
n
t

m
a
l
f
u
n
c
t
i
o
n

o
r

f
a
i
l
u
r
e

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

f
r
o
m

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

s
e
r
v
i
c
e

l
i
n
e
s

R
e
1

=

k
w


k
2


k
3


k
4


(
N
c
1


P
c
1

+

N
c
2


P
c
2

+

N
c
2
p


P
c
2
p
)

o
1


k
h
1

R
e
1

=

0

R
i
s
k

o
f

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

t
h
e

s
e
r
v
i
c
e

l
i
n
e
s

t
h
a
t

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

R
i
s
k

o
f

e
l
e
c
t
r
i
c
a
l
/
e
l
e
c
t
r
o
n
i
c

e
q
u
i
p
m
e
n
t

m
a
l
f
u
n
c
t
i
o
n

o
r

f
a
i
l
u
r
e

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

f
r
o
m

i
n
d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

s
e
r
v
i
c
e

l
i
n
e
s

P
i
1
p

=

n
o
h
p


k
w


k
2


k
3


k
4


k
5


P
e
o

P
i
1
p

=

0

P
r
o
b
a
b
i
l
i
t
y

a
n

i
n
d
i
r
e
c
t

s
t
r
i
k
e

n
e
a
r

t
h
e

o
v
e
r
h
e
a
d

p
o
w
e
r

l
i
n
e

w
i
l
l

c
a
u
s
e

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

t
o

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

P
i
l

=

n
o
h


k
w


k
2


k
3


k
4


k
5


P
e
l

P
i
1

=

0

P
r
o
b
a
b
i
l
i
t
y

a
n

i
n
d
i
r
e
c
t

s
t
r
i
k
e

n
e
a
r

o
t
h
e
r

o
v
e
r
h
e
a
d

l
i
n
e

w
i
l
l

c
a
u
s
e

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

t
o

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

P
i
2
p

=

n
u
g
p


k
w


k
2


k
3


k
4


k
5


P
e
0

P
i
2
p

=

0
.
0
1

P
r
o
b
a
b
i
l
i
t
y

a
n

i
n
d
i
r
e
c
t

s
t
r
i
k
e

n
e
a
r

t
h
e

u
n
d
e
r
g
r
o
u
n
d

p
o
w
e
r

c
a
b
l
e

l
i
n
e

w
i
l
l

c
a
u
s
e

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

t
o

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

P
i
2

=

n
u
g


k
w


k
2


k
3


k
4


k
5


P
e
2

P
i
2

=

0

P
r
o
b
a
b
i
l
i
t
y

a
n

i
n
d
i
r
e
c
t

s
t
r
i
k
e

n
e
a
r

o
t
h
e
r

u
n
d
e
r
g
r
o
u
n
d

c
a
b
l
e

w
i
l
l

c
a
u
s
e

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

t
o

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

R
1
1

=

(
N
1
1


P
i
1

+

N
1
2


P
i
2

+

N
1
1
p


P
i
1
p

+

N
1
2
p


P
i
2
p
)

o
1


k
h
1

R
1
1

=

0

R
i
s
k

o
f

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a
n

i
n
d
i
r
e
c
t

s
t
r
i
k
e

n
e
a
r

t
h
e

s
e
r
v
i
c
e

l
i
n
e
s

t
h
a
t

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

T
o
t
a
l

r
i
s
k

(
R
1
)



R
d
1

=

R
h
1

+

R
s
1

+

R
w
1

R
d
1

=

4
.
8
0
6


1
0
-
6

R
i
s
k

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
i
1

=

R
g
1

+

R
c
1

+

R
m
1

+

R
e
1

+

R
1
1

R
i
1

=

0

R
i
s
k

d
u
e

t
o

i
n
d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
1

=

R
i
1

+

R
d
1

R
1

=

4
.
8
0
6


1
0
-
6

T
o
t
a
l

r
i
s
k

f
o
r

a

s
t
r
u
c
t
u
r
e

d
u
e

t
o

l
i
g
h
t
n
i
n
g

s
t
r
i
k
e
s


R
a
1

=

1


1
0
-
5

A
c
c
e
p
t
a
b
l
e

r
i
s
k

C
o
m
p
a
r
e

t
o
t
a
l

r
i
s
k

t
o

a
c
c
e
p
t
a
b
l
e

r
i
s
k
.

I
f

t
o
t
a
l

r
i
s
k

e
x
c
e
e
d
s

a
c
c
e
p
t
a
b
l
e

r
i
s
k
,

i
n
c
r
e
a
s
e

t
h
e

l
e
v
e
l

o
f

p
r
o
t
e
c
t
i
o
n

m
e
a
s
u
r
e
s
.

For DOD Internal Use ONLY


COPYRIGHT
130
AS/NZS 1768:2007
C
A
L
C
U
L
A
T
I
O
N
S

P
a
r
a
m
e
t
e
r

E
x
a
m
p
l
e

v
a
l
u
e


R
i
s
k

f
a
c
t
o
r
s

p
r
e
s
e
n
t
e
d

i
n

d
i
f
f
e
r
e
n
t

f
o
r
m
a
t



R
t
1

=

R
h
1

+

R
g
1

R
t
1

=

6
.
6
3


1
0
-
7

R
i
s
k

o
f

s
t
e
p

a
n
d

t
o
u
c
h

v
o
l
t
a
g
e

R
f
1

=

R
s
1

+

R
c
1

R
f
1

=

4
.
1
4
3


1
0
-
6

R
i
s
k

d
u
e

t
o

f
i
r
e
,

e
x
p
l
o
s
i
o
n
,

m
e
c
h
a
n
i
c
a
l

d
a
m
a
g
e

a
n
d

c
h
e
m
i
c
a
l

r
e
l
e
a
s
e

R
o
1

=

R
w
1

+

R
m
1

+

R
e
1

+

R
1
1

R
o
1

=

0

R
i
s
k

d
u
e

t
o

f
a
i
l
u
r
e

o
f

i
n
t
e
r
n
a
l

e
l
e
c
t
r
i
c
a
l

a
n
d

e
l
e
c
t
r
o
n
i
c

e
q
u
i
p
m
e
n
t

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e

R
I
S
K

C
A
L
C
U
L
A
T
I
O
N
S

F
O
R

D
A
M
A
G
E

C
A
T
E
G
O
R
Y

2


L
o
s
s

o
f

e
s
s
e
n
t
i
a
l

s
e
r
v
i
c
e

t
o

t
h
e

p
u
b
l
i
c

R
s
2

=

N
d


P
s

f
2

R
s
2

=

0

R
i
s
k

o
f

p
h
y
s
i
c
a
l

d
a
m
a
g
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
c
2

=

k
f


P
f


(
N
c
1


P
c
1

+

N
c
2


P
c
2

+

N
c
1
p


P
c
1
p

+

N
c
2
p


P
c
2
p
)

f
2

R
c
2

=

0

R
i
s
k

o
f

f
i
r
e
,

e
x
p
l
o
s
i
o
n
,

m
e
c
h
a
n
i
c
a
l

d
a
m
a
g
e

a
n
d

c
h
e
m
i
c
a
l

r
e
l
e
a
s
e

c
a
u
s
e
d

b
y

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

s
e
r
v
i
c
e

l
i
n
e
s

w
h
i
c
h

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

R
w
2

=

N
d


P
w

o
2

R
w
2

=

0

R
i
s
k

d
u
e

t
o

f
a
i
l
u
r
e

o
r

m
a
l
f
u
n
c
t
i
o
n

o
f

e
l
e
c
t
r
i
c
a
l

a
n
d

e
l
e
c
t
r
o
n
i
c

e
q
u
i
p
m
e
n
t

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

f
r
o
m

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
m
2

=

N
m


P
m

o
2

R
m
2

=

0

R
i
s
k

o
f

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

g
r
o
u
n
d

n
e
a
r

t
h
e

s
t
r
u
c
t
u
r
e

t
h
a
t

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

R
e
2

=

k
w


k
2


k
3


k
4


(
N
c
1


P
c
1

+

N
c
2


P
c
2

+

N
c
1
p


P
c
1
p

+

N
c
2
p


P
c
2
p
)

o
2

R
e
2

=

0

R
i
s
k

o
f

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

t
h
e

s
e
r
v
i
c
e

l
i
n
e
s

t
h
a
t

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

R
1
2

=

(
N
1
1


P
i
1

+

N
1
2


P
i
2

+

N
1
1
p


P
i
1
p

+

N
1
2
p


P
i
2
p
)

o
2

R
1
2

=

0

R
i
s
k

o
f

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a

i
n
d
i
r
e
c
t

s
t
r
i
k
e

n
e
a
r

t
h
e

s
e
r
v
i
c
e

l
i
n
e
s

t
h
a
t

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

R
d
2

=

0

+

R
s
2

+

R
w
2

R
d
2

=

0

R
i
s
k

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
i
2

=

R
c
2

+

R
m
2

+

R
e
2

+

R
1
2

R
i
2

=

0

R
i
s
k

d
u
e

t
o

i
n
d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
2

=

R
i
2

+

R
d
2

R
2

=

0

T
o
t
a
l

r
i
s
k

f
o
r

a

s
t
r
u
c
t
u
r
e

d
u
e

t
o

l
i
g
h
t
n
i
n
g

s
t
r
i
k
e
s


R
a
2

=

1


1
0
-
3

A
c
c
e
p
t
a
b
l
e

r
i
s
k

C
o
m
p
a
r
e

t
o
t
a
l

r
i
s
k

t
o

a
c
c
e
p
t
a
b
l
e

r
i
s
k
.

I
f

t
o
t
a
l

r
i
s
k

e
x
c
e
e
d
s

a
c
c
e
p
t
a
b
l
e

r
i
s
k
,

i
n
c
r
e
a
s
e

t
h
e

l
e
v
e
l

o
f

p
r
o
t
e
c
t
i
o
n

m
e
a
s
u
r
e
s
.

For DOD Internal Use ONLY


COPYRIGHT
131
AS/NZS 1768:2007
C
A
L
C
U
L
A
T
I
O
N
S

P
a
r
a
m
e
t
e
r

E
x
a
m
p
l
e

v
a
l
u
e


R
I
S
K

C
A
L
C
U
L
A
T
I
O
N
S

F
O
R

D
A
M
A
G
E

C
A
T
E
G
O
R
Y

3


L
o
s
s

o
f

c
u
l
t
u
r
a
l

h
e
r
i
t
a
g
e

R
s
3

=

N
d


P
s

f
3

R
s
3

=

0

R
i
s
k

o
f

p
h
y
s
i
c
a
l

d
a
m
a
g
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
c
3

=

k
f


P
f


(
N
c
1


P
c
1

+

N
c
2


P
c
2

+

N
c
1
p


P
c
1
p

+

N
c
2
p


P
c
2
p
)

f
3

R
c
3

=

0

R
i
s
k

o
f

f
i
r
e
,

e
x
p
l
o
s
i
o
n
,

m
e
c
h
a
n
i
c
a
l

d
a
m
a
g
e

a
n
d

c
h
e
m
i
c
a
l

r
e
l
e
a
s
e

c
a
u
s
e
d

b
y

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

s
e
r
v
i
c
e

l
i
n
e
s

t
h
a
t

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

R
d
3

=

0

+

R
s
3

+

0

R
d
3

=

0

R
i
s
k

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
i
3

=

0

+

R
c
3

+

0

R
i
3

=

0

R
i
s
k

d
u
e

t
o

i
n
d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
3

=

R
i
3

+

R
d
3

R
3

=

0

T
o
t
a
l

r
i
s
k

f
o
r

a

s
t
r
u
c
t
u
r
e

d
u
e

t
o

l
i
g
h
t
n
i
n
g

s
t
r
i
k
e
s


R
a
3

=

1


1
0
-
3

A
c
c
e
p
t
a
b
l
e

r
i
s
k

C
o
m
p
a
r
e

t
o
t
a
l

r
i
s
k

t
o

a
c
c
e
p
t
a
b
l
e

r
i
s
k
.

I
f

t
o
t
a
l

r
i
s
k

e
x
c
e
e
d
s

a
c
c
e
p
t
a
b
l
e

r
i
s
k
,

i
n
c
r
e
a
s
e

t
h
e

l
e
v
e
l

o
f

p
r
o
t
e
c
t
i
o
n

m
e
a
s
u
r
e
s
.

R
I
S
K

C
A
L
C
U
L
A
T
I
O
N
S

F
O
R

D
A
M
A
G
E

C
A
T
E
G
O
R
Y

4


E
c
o
n
o
m
i
c

l
o
s
s

R
h
4

=

N
d


P
h

h
4

R
h
4

=

0

R
i
s
k

o
f

d
a
n
g
e
r
o
u
s

s
t
e
p

a
n
d

t
o
u
c
h

p
o
t
e
n
t
i
a
l

t
o

a
n
i
m
a
l
s

o
u
t
s
i
d
e

t
h
e

s
t
r
u
c
t
u
r
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
s
4

=

N
d


P
s

f
4


k
h
4

R
s
4

=

2
.
4
8
6


1
0
-
6

R
i
s
k

o
f

p
h
y
s
i
c
a
l

d
a
m
a
g
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
w
4

=

N
d


P
w

o
4


k
h
4

R
w
4

=

8
.
2
2


1
0
-
6

R
i
s
k

d
u
e

t
o

f
a
i
l
u
r
e

o
r

m
a
l
f
u
n
c
t
i
o
n

o
f

e
l
e
c
t
r
i
c
a
l

a
n
d

e
l
e
c
t
r
o
n
i
c

e
q
u
i
p
m
e
n
t

d
u
e

t
o

o
v
e
r
v
o
l
t
a
g
e
s

f
r
o
m

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
m
4

=

N
m


P
m

o
4


k
h
4

R
m
4

=

1
.
9
3
8


1
0
-
5

R
i
s
k

o
f

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

g
r
o
u
n
d

n
e
a
r

t
h
e

s
t
r
u
c
t
u
r
e

t
h
a
t

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

R
g
4

=

P
g


(
N
c
1


P
c
1

+

N
c
2


P
c
2

+

N
c
1
p


P
c
1
p

+

N
c
2
p


P
c
2
p
)

g
4

R
g
4

=

0

R
i
s
k

o
f

d
a
n
g
e
r
o
u
s

s
t
e
p

a
n
d

t
o
u
c
h

p
o
t
e
n
t
i
a
l

t
o

a
n
i
m
a
l
s

o
u
t
s
i
d
e

t
h
e

s
t
r
u
c
t
u
r
e

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

For DOD Internal Use ONLY


COPYRIGHT
132
AS/NZS 1768:2007
C
A
L
C
U
L
A
T
I
O
N
S

P
a
r
a
m
e
t
e
r

E
x
a
m
p
l
e

v
a
l
u
e


R
c
4

=

k
f


P
f


(
N
c
1


P
c
1

+

N
c
2


P
c
2

+

N
c
1
p


P
c
1
p

+

N
c
2
p


P
c
2
p
)

f
4


k
h
4

R
c
4

=

0

R
i
s
k

o
f

f
i
r
e
,

e
x
p
l
o
s
i
o
n
,

m
e
c
h
a
n
i
c
a
l

d
a
m
a
g
e

a
n
d

c
h
e
m
i
c
a
l

r
e
l
e
a
s
e

c
a
u
s
e
d

b
y

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

s
e
r
v
i
c
e

l
i
n
e
s

t
h
a
t

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

R
e
4

=

k
w


k
2


k
3


k
4


(
N
c
1


P
c
1

+

N
c
2


P
c
2

+

N
c
1
p


P
c
1
p

+

N
c
2
p


P
c
2
p
)

o
4


k
h
4

R
e
4

=

0

R
i
s
k

o
f

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a

d
i
r
e
c
t

s
t
r
i
k
e

t
o

t
h
e

s
e
r
v
i
c
e

l
i
n
e
s

t
h
a
t

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

R
1
4

=

(
N
1
1


P
i
1

+

N
1
2


P
i
2

+

N
1
1
p


P
i
1
p

+

N
1
2
p


P
i
2
p
)

o
4


k
h
4

R
1
4

=

1
.
5
0


1
0
-
6

R
i
s
k

o
f

i
n
t
e
r
n
a
l

e
q
u
i
p
m
e
n
t

f
a
i
l
u
r
e

d
u
e

t
o

a
n

i
n
d
i
r
e
c
t

s
t
r
i
k
e

n
e
a
r

t
h
e

s
e
r
v
i
c
e

l
i
n
e
s

t
h
a
t

c
a
u
s
e
s

a

d
a
m
a
g
i
n
g

o
v
e
r
v
o
l
t
a
g
e

R
d
4

=

R
h
4

+

R
s
4

+

R
w
4

R
d
4

=

1
.
0
7
0


1
0
-
5

R
i
s
k

d
u
e

t
o

d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
i
4

=

R
g
4

+

R
m
4

+

R
c
4

+

R
e
4

+

R
1
4

R
i
4

=

2
.
0
8
8


1
0
-
5

R
i
s
k

d
u
e

t
o

i
n
d
i
r
e
c
t

s
t
r
i
k
e
s

t
o

t
h
e

s
t
r
u
c
t
u
r
e

R
4

=

R
i
4

+

R
d
4

R
4

=

3
.
1
5
8


1
0
-
5

T
o
t
a
l

r
i
s
k

f
o
r

a

s
t
r
u
c
t
u
r
e

d
u
e

t
o

l
i
g
h
t
n
i
n
g

s
t
r
i
k
e
s


R
a
4

=

1


1
0
-
3

A
c
c
e
p
t
a
b
l
e

r
i
s
k

C
o
m
p
a
r
e

t
o
t
a
l

r
i
s
k

t
o

a
c
c
e
p
t
a
b
l
e

r
i
s
k
.

I
f

t
o
t
a
l

r
i
s
k

e
x
c
e
e
d
s

a
c
c
e
p
t
a
b
l
e

r
i
s
k
,

i
n
c
r
e
a
s
e

t
h
e

l
e
v
e
l

o
f

p
r
o
t
e
c
t
i
o
n

m
e
a
s
u
r
e
s
.

R
d

=

R
d
1

+

R
d
2

+

R
d
3

+

R
d
4

R
d

=

1
.
5
5
1


1
0
-
5


R
i

=

R
i
1

+

R
i
2

+

R
i
3

+

R
i
4

R
i

=

2
.
0
8
8


1
0
-
5


For DOD Internal Use ONLY
133 AS/NZS 1768:2007

COPYRIGHT
APPENDIX B
THE NATURE OF LIGHTNING AND THE PRINCIPLES OF LIGHTNING
PROTECTION
(Informative)
B1 SCOPE OF APPENDIX
This Appendix deals with the nature of the phenomena involved in a study of lightning
protection and the basic principles of designing such protection. A brief description of
various elements of an LPS and their function is also provided.
Recommendations for systems to protect against the direct or indirect effect of lightning are
given in the body of this Standard.
B2 THE NATURE OF LIGHTNING
B2.1 Nature of lightning
Thunderstorms occur under particular meteorological conditions, and partial separation of
electrical charges within the thundercloud usually results in regions with net negative
charge mainly in the lower parts of the thundercloud, and regions with net positive charge
mainly in the upper part. Lightning is an electrical discharge between differently charged
regions within the cloud (cloud flash) or between a charged region, nearly always the lower
negatively charged region, and earth (ground flash).
A complete ground flash consists of a sequence of one or more high amplitude short
duration current impulses, or strokes. Significant numbers (about 40%) of ground flashes
have more than one ground termination, usually separated by distances up to a few
kilometres (Paragraph G2, Ref. 8). In some ground flashes low amplitude long duration
currents (sometimes termed continuing currents) flow between the strokes or after a
sequence of strokes. The currents are unidirectional and usually negative, i.e. a negative
charge is injected into the object struck. For all practical purposes the stroke can be
considered to be generated by a current source whose waveshape and magnitude are
unaffected by the characteristics of the ground termination.
B2.2 The lightning attachment process
The first stroke of a ground flash is normally preceded by a downward-progressing
low-current leader discharge that commences in the negatively charged region of the cloud
and progresses towards the earth, depositing negative charges in the air surrounding the
leader discharge channel. When the lower end of the leader is roughly 100 m from the earth,
electrical discharges (streamers) are likely to be initiated at protruding earthed objects, and
to propagate upwards towards the leader discharge channel. Several streamers may start, but
usually only one is successful in reaching the downcoming leader. The high current phase
(return stroke) commences at the moment the upward moving streamer meets the
downcoming leader. The position in space of the lower portion of the lightning discharge
channel is therefore determined by the path of the successful streamer, i.e. the one that
succeeded in reaching the downcoming leader. The primary task in protecting a structure is
therefore to ensure a high probability that the successful streamer originates from the
lightning protection conductors, and not from a part of the structure that would be adversely
affected by the lightning current that subsequently flows.
For DOD Internal Use ONLY
AS/NZS 1768:2007 134

COPYRIGHT
As the path of the successful streamer may have a large horizontal component, e.g. many
tens of metres, as well as a vertical component, an elevated earthed conductor will provide
protection for objects spread out below it. It is therefore possible to provide protection for a
large volume with a relatively small number of correctly positioned conductors. This is the
basis for the concept of a zone of protection provided by an elevated earthed conductor, and
provides the basic principle underlying interception lightning protection. Thus the basic
protection system consists of air terminals to provide launching points for streamers, and
downconductors and earthing electrodes to deliver the lightning current into the earth.
B2.3 Thunderstorm and lightning occurrence
Thunderstorm occurrence at a particular location is usually expressed in terms of the
number of calendar days in a year when thunder was heard at the location, averaged over
several years. The resulting information is usually given as an average annual thunderday
map. The frequency of occurrence of thunderstorms varies significantly depending on
location. Moreover, the severity of lightning storms, as distinct from their frequency of
occurrence, is known to be much greater in some areas than in others. Hence, the need for
protection varies across the country, although not necessarily in direct proportion to
thunderstorm frequency. A few severe thunderstorms in a season may make the need for
protection greater than a relatively large number of storms of lesser activity. Therefore,
lightning ground flash density is a better measure of lightning activity in a particular
location.
Data on the geographical distributions of average ground flash density are given in
Section 2
(a) in Figure 2.3 for Australia; and
(b) in Figure 2.4 for New Zealand.
Earlier editions of AS/NZS 1768 provided Thunderday maps, and ground flash density (N
g
)
could be estimated from thunderdays (T
d
) using an equation of the form
N
g
= a T
d
b
. . .B2.3
in which a and b are empirically determined constants, with values of a = 0.012 and b = 1.4
appropriate for Australia (Paragraph G2, Ref. 9); the so called CIGRE formula adopted by
IEC has a = 0.04 and b = 1.25, and generally gives higher values for N
g
.
Local topographical features may cause variations in the occurrence of ground flashes. The
occurrence will be higher than the average on high ground, e.g. ridges, and lower than
average on nearby low ground. In some cases, a large topographical feature such as a high
mountain may interact with prevailing meteorological conditions to cause a concentration
of thunderstorms and ground flashes. Such effects may be identified by enquiry of local
telecommunications and electricity supply engineers or meteorological stations, and of local
residents. On a smaller scale, tall objects, e.g. roof of a building, tree top or overhead
conductor, tend to divert lightning flashes to themselves, as explained in Paragraph B2.2,
thus shielding a certain surrounding area from direct strikes.
There is a network of lightning flash counters (LFC) in Australia. The available count data
enable estimates to be made of ground flash density at the LFC sites, but these require
corrections for site and calibration errors and for response to nearby cloud flashes. Recently
lightning positioning systems have been installed in Australia and New Zealand and data
are available from the commercial providers. Earlier systems have been in operation in
central-east New South Wales and south-east Queensland for about twenty years, but their
data are not extensive and may not be reliable. Optical observations of lightning flashes
are made from satellites fitted with appropriate sensors. Considerable data on worldwide
lightning activity are now available from U.S. satellites which usually survey the earth from
near-polar orbits. Worldwide data and maps since April 1995 of recorded lightning flashes
are readily accessible on a NASA website (Paragraph G2, Ref. 10).
For DOD Internal Use ONLY
135 AS/NZS 1768:2007

COPYRIGHT
In Australia, the geographical distribution of lightning incidence is described by a map of
average annual lightning ground flash density, N
g
(Paragraph G2, Ref. 11). The map has
been derived using lightning data obtained by ground-based lightning detection instruments
such as CIGRE-500 and CGR3 and by NASA satellite-based instruments such as Optical
Transient Detector and Lighting Imaging Sensor. This map is contoured in units of flash
density (km
2
yr
1
). N
g
varies from over 6 km
2
yr
1
in the northern parts of Australia to
about 1 km
2
yr
1
and below in the southern parts. The map is recommended for estimating
N
g
values for lightning protection system design. The overall uncertainty in the flash
density values indicated on the Australian flash density map is estimated to be 30%.
The New Zealand N
g
map has been derived from ground flash density data obtained from
the Lightning Detection Network of New Zealand for the period 1 January 2001 through to
9 February 2006.
B3 EFFECTS OF LIGHTNING
The principal effects of a lightning discharge to an object are electrical, thermal and
mechanical. These effects are determined by the magnitude and waveshape of the current
discharged into the object and the nature of the object itself. Statistical distributions of
some characteristics of ground flashes are given in Table B1.
When the lightning current flows through the building or LPS, the electrical potential of the
building may rise to a high, usually negative, value with respect to remote earth.
The lightning current produces a high potential gradient around the earthing electrode that
can be dangerous to persons and to livestock.
The rate of rise of current in conjunction with inductance of the discharge path produces a
voltage drop that will vary in time depending upon the current waveshape; because of the
fast rate of rise of the lightning discharge current, the inductance of conductors assumes a
far greater importance in determining potential rise than does the resistance of conductors.
The voltage across an inductor is given by the expression V = L di/dt. Assuming an
approximate inductance of 1H/m for a typical conductor and a typical rate of rise of
current of 25 kA/s, the voltage developed across a 40 m length of 25 3 mm copper strap
is 1 MV, compared to just 770 V due to its resistance. As the point of strike on the LPS may
be raised to a high potential, there is also the risk of a flashover from the LPS to nearby
objects. This is called a side-flash. The risk of side-flash is increased at any deeply
re-entrant bend or loop in a downconductor due to the local increase in inductance. If such a
flashover occurred, part of the lightning current would be discharged through internal
installations with consequent risk to the occupants and the fabric of the building.
The amount of energy deposited in any object carrying lightning current may be calculated
by multiplying the action integral by the electrical resistance of the object. From this, the
temperature rise may be calculated. It should be noted however, that the resistance of most
objects other than metallic conductors, e.g. wood, masonry or earth, is very non-linear for
the large currents associated with lightning. It should also be noted that the passage of
lightning current through moist resistive materials such as masonry or wood can convert the
moisture to high-pressure steam, causing the material to explode or shatter.
The thermal effect of a lightning discharge is confined to the temperature rise of the
conductor through which the lightning current is discharged. Although the amplitude of a
lightning current may be high, its duration is so short that the thermal effect on an LPS, or
on the metallic parts of a structure where this is included in the LPS, is usually negligible.
This ignores the fusing or welding effects that occur locally consequent upon the rupture of
a conductor that was previously damaged or was of inadequate cross-section. In practice the
cross-sectional area of a normal lightning conductor is determined primarily by mechanical
and secondarily by thermal considerations.
For DOD Internal Use ONLY
AS/NZS 1768:2007 136

COPYRIGHT
At the point of attachment of a lightning discharge channel to a thin metal surface, a hole
may be melted in the surface. In the rare case where this occurs, some thermal energy will
be deposited directly in the metal from the hot plasma of the lightning discharge channel, as
well as the thermal energy caused by the passage of current through the metal. The size of
the hole melted in the sheet depends on the material, the thickness of the sheet, and the
charge delivered. For example, a moderately severe lightning flash delivering a charge of
70 C would melt a hole about 12 mm in diameter in a sheet of roofing iron.
For DOD Internal Use ONLY
137 AS/NZS 1768:2007

COPYRIGHT
TABLE B1
SUMMARY OF THE FREQUENCY DISTRIBUTIONS OF THE MAIN
CHARACTERISTICS OF THE LIGHTNING FLASH TO GROUND
Percentage of events having value of characteristic
greater than value shown below (see Note 1)
Item
No
Lightning characteristic
99 90 75 50 25 10 1
Unit
1 Number of common strokes 1 1 2 3 5 7 12
2
Time interval between
strokes
10 25 35 55 90 150 400 ms
3
First stroke peak current
I
max.

5 12 20 30 50 80 130 kA
4
Subsequent stroke peak
current I
max.

3 6 10 15 20 30 40 kA
5 First stroke (di/dt)
max.
6 10 15 25 30 40 70 kA/s
6 Subsequent stroke (di/dt)
max.
6 15 25 45 80 100 200 kA/s
7 Total charge 1 3 6 15 40 70 200 C
8 Continuing current charge 6 10 20 30 40 70 100 C
9 Continuing current I
max.
30 50 80 100 150 200 400 A
10 Overall duration of flash 50 100 250 400 600 900 1 500 ms
11 Action integral (see Note 2) 10
2
3 10
2
10
3
5 10
3
3 10
4
10
5
5 10
5
A
2
.s
NOTES:
1 The values shown in this table have been derived from a number of sources, and have been rounded in
accordance with the accuracy with which these data are known. Values at the 1 percent and 99 percent
levels are very uncertain, and are given only to indicate an order of magnitude.
2 The action integral, defined as t i d
2
for the whole flash, is equivalent to the energy deposited in a one-
ohm resistor by the passage of the entire current for the duration of the flash.
The passage of lightning current through a conductor causes a force on the conductor given
by the equation:
F = B l i . . . B3
where
F = the force on the conductor, in newtons (N)
B = the component of the magnetic flux density at right angles to the conductor, in
teslas (T)
l = the length of the conductor, in metres (m)
i = the current through the conductor, in amperes (A)
B4 POTENTIAL DIFFERENCES CAUSED BY LIGHTNING
B4.1 General
A lightning flash to a building or structure, or a flash to ground near a building or structure
will cause a potential rise in the vicinity of the strike attachment point, and may also cause
a potential rise of objects remote from the point of strike. For example, a lightning strike to
a service conductor (electricity supply, telecommunications, or other metallic service) can
cause current to be transmitted to the building, thus raising the potential of the building. A
lightning flash to ground can also induce voltages and currents in remote conductors by
electric and magnetic coupling (see also Section 5 and Appendix F).
For DOD Internal Use ONLY
AS/NZS 1768:2007 138

COPYRIGHT
B4.2 Earth currents
At the point where the lightning current enters the ground the current density is high.
Hazardous earth potential gradients may be generated. Earthing electrodes should be
distributed more or less symmetrically, preferably outside and around the circumference of
a structure, rather than be grouped on one side. This will help to minimize earth potential
gradients near the building, and tend to cause the lightning current to flow away from the
building rather than underneath it.
In addition, with earth connections properly distributed, the current from a lightning flash
to ground near the building will be concentrated at the outer extremities. Thus current flow
underneath the building, as well as earth potential gradients, will be minimized.
B4.3 Side-flash
If a lightning conductor system is placed on a building and there are unbonded metal
objects of considerable size nearby, there will be a tendency for side-flashing to occur
between the conductors of the LPS and the unbonded metal objects. To prevent damage
from side-flash, interconnecting conductors should be provided at all places where side-
flashes are likely to occur. This is referred to as equipotential bonding, although complete
equalization of potential is never achieved. As the currents required to equalize potentials
are considerably less than the full lightning current, conductors of relatively small
cross-section are adequate for this purpose (see also Clause 4.16.2).
B4.4 Potential (voltage) differences
The impedance of the earth termination network to the rapidly changing lightning current
influences the potential rise of the LPS. This in turn affects the risk both of side-flashing
within the structure to be protected, and of dangerous potential gradients in the ground
adjacent to the earth termination network. The potential gradient around the earth
termination network, on the other hand, depends on the physical arrangement of the
earthing electrodes and the soil resistivity. In Figure B1, a lightning flash is assumed to
occur to the LPS of a building. For the purposes of the illustration, no equipotential bonding
is shown although such bonding is required in accordance with this Standard. As the
lightning current is discharged through the downconductor and the earthing electrode, the
conductor system and the surrounding soil are raised, for the duration of the discharge, to a
potential with respect to the general mass of the earth. The resulting potential differences as
shown by step, touch and transferred potentials in Figure B1 may be lethal; hence the
importance of keeping the impedance of the earth termination network low, and of
preventing large local potential gradients by equipotential bonding, and by the manner in
which the earthing electrodes are arranged.
For DOD Internal Use ONLY
139 AS/NZS 1768:2007

COPYRIGHT

NOTES:
1 Person X is in contact with the ground at a and b: person Y is in contact with the ground at c and the
conductor at d; person Z is in contact with the conductor at e and a metallic handrail f shown earthed at g.
2 Person X is subject to step potential.
3 Person Y is subject to touch potential.
4 Person Z is subject to transferred potential.
5 The potential depends on the current magnitude and the impedance of the path of the lightning discharge.
6 Step potential increases with the size of the step a-b in the radial direction from the conductor and
decreases with the increase in the distance between person X and the conductor.
7 The transferred potential increases with increase in the radial distance between the downconductor and the
ground at g.
8 The diagram does not show equipotential bonding that may be necessary to protect persons from hazardous
potential differences of the type described in this diagram (see Sections 4 and 5).
FIGURE B1 INSTANTANEOUS POTENTIAL DIFFERENCES DURING A LIGHTNING
FLASH TO AN EARTHED CONDUCTOR
B5 PRINCIPLES OF LIGHTNING PROTECTION
B5.1 Purpose of protection
The purpose of lightning protection is to protect persons, buildings and their contents, or
structures in general, from the effects of lightning, there being no evidence for believing
that any form of protection can prevent lightning strikes.
For DOD Internal Use ONLY
AS/NZS 1768:2007 140

COPYRIGHT
B5.2 Interception of lightning
The function of an air terminal in an LPS is to divert to itself the lightning discharge that
might otherwise strike a vulnerable part of the object to be protected. It is generally
accepted that the range over which an air terminal can attract a lightning discharge is not
constant, but increases with the severity of the discharge.
The path of a lightning discharge near a structure is determined by the path of the
successful streamer (see Paragraph B2.2) that will usually be initiated from a conducting
part of the structure nearest to the downcoming leader. The initiation of streamers is also
influenced by the local electric field. The upper outer edges and corners of buildings or
structures, and especially protruding parts, are likely to have higher local electric fields
than elsewhere, and are therefore likely places for the initiation of streamers. When the
downcoming leader is within about 200 m of the building, the electric field at these
protruding parts and corners will exceed the breakdown field strength of air, resulting in
corona currents that cause these parts to be surrounded by ionized air. The resulting space
charges influence the electric field in such a manner that the field is limited to the
breakdown strength of air. However, these complicating factors do not alter the fact that the
most probable strike attachment point on a building is the edge, corner, or other protruding
part closest to the downcoming leader. This is the basic reason why the RSM gives a
reliable guide to the most probable strike attachment points.
Hence, if air terminals are placed at all locations where high electric fields and streamer
initiation are likely, there will be a high probability that the discharge will terminate on
some portion of the LPS.
B5.3 Determination of lightning strike attachment points to buildings
B5.3.1 The rolling sphere method
The procedure for determining lightning strike attachment points is based on the RSM
whereby a sphere of specified radius is imagined to be rolled across the ground towards the
building, up the side, and over the top of the building, and down the other side to ground.
This can be carried out in various orientations with respect to the building. Any point on the
building touched by the sphere is a possible lightning strike attachment point.
The physical basis for this method is as follows. As the lightning leader stroke approaches
the ground, the electric field at various salient points, such as the upper corners of
buildings, will help to launch electrical discharges, or streamers, that progress upwards
toward the tip of the downcoming leader stroke. The position in space of the lightning
discharge channel, and the location of the strike attachment point, is determined when the
leader and one of the upward streamers join to complete the lightning discharge path. The
upward streamer that determines the strike attachment point is generally that launched from
the salient point or earthed conductor closest to the downcoming leader. The rolling sphere
will tend to touch those salient points, and the method therefore provides a geometric means
of identifying such points.
B5.3.2 The striking distance
The striking distance, d
s
, is the distance between the leader tip and the eventual strike
attachment point at the moment when it has become inevitable that the gap, of dimension d
s
,
will be bridged by the lightning discharge channel.
The RSM is closely related to the electrogeometric method developed for predicting
lightning attachment to electricity supply service lines, whereby the lightning leader is
supposed to progress until it comes within the distance d
s
of an earthed object, when the
final discharge path is determined to that object.
There are theoretical and observational grounds for a relationship between d
s
and the i
max.
,
where i
max.
is the peak return stroke current. The following relationship has been proposed:
For DOD Internal Use ONLY
141 AS/NZS 1768:2007

COPYRIGHT
d
s
= 10 i
max.
0.65
. . . B5.3.2
where
d
s
= the striking distance, in metres (m)
i
max.
= the peak current of the return stroke, in kiloamperes (kA)
The advantage of the RSM is that it is relatively easy to apply, even to buildings of
complicated shape. The limitation of the method is that no account is taken of the influence
of electric fields in initiating return streamers, and the method therefore does not
distinguish between likely and unlikely lightning strike attachment points. In particular, the
enhancement of electric fields at the upper outer corners of a building makes these corners
the most probable strike attachment points, whereas return streamers are unlikely to be
initiated from a flat surface away from a corner or edge, even if on the roof and touched by
the sphere. Therefore, in Clause 4.4.2, an increased radius of the rolling sphere was
introduced for dealing with the protection of plane surfaces.
Some qualitative indication of the probability of strike attachment to any particular point
can be obtained if the sphere is supposed to be rolled over the building in such a manner
that its centre moves at constant speed. Then the length of time that the sphere dwells on
any point of the building gives a qualitative indication of the probability of that point being
struck. Thus for a simple rectangular building with a flat roof, the dwell time would be
large at the corners and edges, and small at any point on the flat part of the roof, correctly
indicating a high probability of the corners or edges being struck, and a low probability that
a point on the flat part of the roof will be struck.
The RSM with its modification of an increased radius for plane surfaces is now applied
with some account of electric field enhancement effects in mind, so that high priority is
given to providing air terminals at the more probable attachment points. For a building of
more or less rectangular shape with a flat roof, this means giving top priority to providing
air terminals around the periphery of the roof. This could take the form, for example, of a
metallic perimeter handrail.
B5.4 Protection of the sides of tall buildings
When the RSM is applied to a building of height greater than the selected sphere radius,
then the sphere touches the vertical edges on the sides of the building at all points above a
height equal to the sphere radius and a sphere of the corresponding increased sphere radius
touches all flat surfaces on the sides about a height equal to the increased radius. This
indicates the possibility of strikes to the sides of the building, and raises the question of the
need for an air terminal network on the sides of the building.
Practical experience indicates that strikes to vertical edges on the sides of tall buildings do
occur but are uncommon in that strikes rarely occur to the flat side surfaces. There are
theoretical reasons for believing that only flashes with low i
max.
and consequently low d
s

values are likely to be able to penetrate below the level of the roof of the building and strike
the sides. The consequences of a strike to the sides of a building may result in damage of a
minor nature. Unless there are specific reasons for side protection, as would be the case for
a structure containing explosives, it is considered that the cost of side protection would not
normally be justified.
If it is decided that some protection for the sides of a building is justified, then conductors
should be provided at the most probable lightning attachment points on the sides of the
building. The most probable attachment points are at protruding corners and vertical edges
of the sides of the building, including surfaces with changes greater than 20. The
conductors will generally serve both as air terminals and downconductors and will in
general be connected to the roof air terminal network at their upper ends, and to the
earthing termination network at their lower ends. The conductors may be made flush with
the surface, and should be placed as near as practicable to the vertical edge to be protected.
For DOD Internal Use ONLY
AS/NZS 1768:2007 142

COPYRIGHT
Where the building construction includes extensive metal objects on the vertical outer
surfaces, such as large metallic window frames, then such objects can form part of the
interception protection system. It is necessary to provide electrical connections between
adjacent metal objects both in the horizontal and vertical directions, and to provide periodic
connections between the surface metalwork and the reinforcing steel, or the
downconductors if separate from the reinforcing. This provides multiple paths for the
lightning current from any point on the surface metalwork to earth, and local potential
differences will be reduced to an acceptable level.
Return streamers are more likely to develop from a good conductor on the surface than from
a poor conductor in a similar position. Thus if a wall consists mainly of a poorly conducting
material, and there are isolated objects with earth connections made of a highly conductive
material distributed over the surface, then the return streamers will tend to originate
preferentially from the highly conducting objects with earth connections. A wall of poorly
conducting material can therefore be substantially protected by earthed metallic studs
placed on a grid pattern flush with the surface of the wall. Alternatively, protection can be
provided by a system of metallic strips flush with the surface. Even if the lightning happens
to strike a point on the non-conducting surface away from an earthed conducting point, it is
likely that it will track across the non-conducting surface and terminate on the earthed
conducting point.
B5.5 Safe discharge to earth
B5.5.1 General
If the air terminal network is adequately connected to earth, the current will pass to ground
without damage to the structure. Metallic parts of a building or structure may usefully be
made part of the LPS, provided that the passage of lightning current will not cause harm
(for bonding of metal in or on a structure, see Clause 4.16.2.2).
B5.5.2 Use of reinforcing steel as a downconductor
It is sometimes suggested that overlapped and tied reinforcing rods do not provide good
electrical connections, and are therefore not suitable for carrying lightning currents.
However, the situation differs greatly from that in which a conducting path for power
currents is required. Even if there are thin films of iron oxides and cement between the bars,
the voltage required to cause breakdown of these films would be less than 1000 V. Once
breakdown has occurred, there would be localized arcing between the steel bars, with a
voltage drop of a few tens of volts. The initial breakdown across the oxide and cement films
would occur during the first few microseconds of the first stroke when there is a large
inductive voltage drop from top to bottom of the building; this voltage would be very much
larger than the voltage required to break down the oxide and cement films between bars.
Thus there are good reasons for relying on the reinforcing bars to act as downconductors,
even when no special precautions have been taken (such as welding the bars together) to
ensure electrical continuity. The localized arcing referred to above would produce relatively
small amounts of energy in relation to the thermal capacity of typical reinforcing bars, so
heating effects should be negligible.
Where the structural steel reinforcement of the building is to be utilized as the
downconductor system, it is important that there be an effective electrical connection
between the air terminal network and the steel reinforcement. Such connections should be
made as close as practicable to the top of the building and preferably at a number of points
around the building perimeter.
Tall metal structures, such as chimneys, provide an adequate conducting path, but care must
be taken to ensure that they are also suitably earthed.
Special precautions are needed for the protection of structures containing explosives,
highly-flammable materials and gases. The principles involved in such protection systems
are given in Section 7.
For DOD Internal Use ONLY
143 AS/NZS 1768:2007

COPYRIGHT
B5.6 Potential equalization
As explained in Paragraph B4, lightning strikes may give rise to harmful potential
differences within a building. Of particular concern is the occurrence of potential
differences that may exist between local earth and incoming conductors such as metallic
water services, telecommunication systems, and electricity supply systems.
Reduction of these potential differences may be achieved by a system of coordinated
bonding of all affected conductors contained in the building. This includes all incoming
metallic services, protective earths associated with electricity supply and
telecommunications systems, and the building lightning protection earth termination
network (if provided). Potential equalization (understood to imply approximate potential
equalization) may be effected by including in the bonding scheme earthed building
metalwork such as reinforcement metals and metal framework, if any. In cases where the
presence of dissimilar metals may create corrosion problems or for other reasons, the
commoning path may be effected by using suitably rated SPDs.
B6 ELEMENTS OF A PROTECTION SYSTEM
The main parts of a typical LPS for a building or structure may be summarized as follows,
noting that not all parts will be present in all systems:
(a) Air terminals are placed so as to achieve interception lightning protection, ensuring a
high probability that lightning will attach to the air terminal network, and not to parts
of the protected object that could be damaged by lightning current. Existing
metalwork should be used as far as possible, supplemented by carefully positioned air
terminals giving priority to high probability attachment points. These are the upper
outer corners and edges of the building and any salient or protruding objects on the
roof. The form of air terminal should be chosen for simplicity and low cost consistent
with adequate mechanical strength, durability and aesthetic acceptability.
(b) Downconductors are used to convey lightning current towards the earth. Existing
building metalwork should be used as far as possible, especially steel frames and
reinforcing steel in reinforced concrete columns, supplemented where necessary by
external downconductors. If these downconductors are also to serve as part of the air
terminal network for the sides of a tall building, they should preferably follow the
outer vertical corners of the building. Where the number of downconductors required
exceeds the number of vertical corners, the remaining downconductors should be
placed uniformly between the ones at the corners.
(c) Test links may be required between the downconductors and the earthing electrodes
to facilitate the testing of the LPS.
(d) The earth termination network consisting of one or more earthing electrodes, and any
interconnecting conductors between earthing electrodes, serves the purpose of
delivering the lightning current into the general mass of the earth. The footings of
large reinforced concrete buildings will generally provide a better earth connection
than can be provided by driven earthing electrodes around the periphery. Where the
superficial layers of the earth have high resistivity, deep driven earthing electrodes
may be needed to reach low-resistivity regions, and achieve an acceptable earth
resistance.
(e) Equipotential bonding is used to reduce or prevent hazardous potential differences
between any pair of extended conducting objects in the building or structure.
Equipotential bonding becomes particularly important in buildings or structures
having a high earth resistance. In the extreme situation where an acceptable
connection to earth cannot be achieved, it would be necessary to rely entirely on
equipotential bonding to protect persons and equipment against hazardous potential
differences caused by lightning.
For DOD Internal Use ONLY
AS/NZS 1768:2007 144

COPYRIGHT
(f) Equipotential bonding may, in some situations, be achieved by means of SPDs, where
direct connection of the conducting parts results in an unwanted effect, for example,
corrosion of metals, degradation or loss of communications.
(g) Overvoltage protection is achieved by using various types of SPDs (e.g. spark gaps,
gas-filled surge arrestors or MOVs) to prevent hazardous potential differences being
applied to persons or equipment, while allowing correct operating potentials to exist
(see Section 5 and Appendix F).
For DOD Internal Use ONLY
145 AS/NZS 1768:2007

COPYRIGHT
APPENDIX C
NOTES ON EARTHING ELECTRODES AND MEASUREMENT OF EARTH
IMPEDANCE
(Informative)
C1 GENERAL
C1.1 Function of an earthing electrode
The function of an earthing electrode is to provide an electrical connection to the general
mass of earth. The characteristic primarily determining the effectiveness of an earthing
electrode or group of interconnected earthing electrodes (earth termination network) is the
impedance that it provides between the earth termination network and the general mass of
earth.
C1.2 Factors influencing earth impedance
The impedance of the earth termination network to lightning currents varies with time and
the magnitude of the current, and is dependent on
(a) the resistance and surge impedance of the earthing electrode and the connecting
conductors;
(b) the contact resistance between the earthing electrode and the surrounding soil;
(c) the resistivity of the soil surrounding the earthing electrode; and
(d) the degree of soil ionization.
The resistance of the metallic conductors in the earth termination network can generally be
neglected.
In addition there are often fortuitous paths to earth, e.g. via bonded electricity reticulation
low-voltage neutrals. These can mask the earthing electrode impedance by paralleling other
routes of high surge impedance but low d.c. or low-frequency impedance to earth. It is
essential to utilize measurement techniques, referred to later, to discriminate between these
conditions.
C1.3 Measures for reducing earth impedance
Lightning current is considered to be a high frequency phenomenon with current rise times
in the order of 10 kiloamperes per microsecond (10 kA/s). In these circumstances, an earth
termination network can best be regarded as a leaky transmission line. Each conductor has
resistance, inductance and capacitance to earth and leakage through non-insulated contact.
An examination of earthing conductors using transmission line equations will show that the
impedance of the earth termination network is lowered by the following:
(a) The use of flat strip rather than circular conductors. This increases surface area,
reduces high-frequency resistance due to skin effect, increases both capacitive
coupling and the earth contact area for a given cross-section of conductor.
(b) The use of a centre point feed to create the effect of two parallel connected
transmission lines is also effective. This concept can be further enhanced by using
several radial conductors emanating from the injection point.
(c) The use of short-length multiple conductors for example up to 30 m, is preferred over
long buried systems.
For DOD Internal Use ONLY
AS/NZS 1768:2007 146

COPYRIGHT
(d) The use of ground enhancing compound around the conductor can reduce the
impedance of the earth electrode (see Paragraph G2, Ref. 12). The reduction in
impedance is achieved by greatly increasing the effective surface area and capacitive
coupling of the conductor to the soil.
In areas of low to moderate soil resistivity, vertical earthing electrodes will, for an earthing
electrode of given dimensions, usually be more effective in providing a low surge
impedance.
When trench (horizontal) earthing electrodes are installed, the initial surge impedance of
two or more electrically paralleled wires or strips, radiating symmetrically from a central
connection point, will be less than the equivalent length laid as one single unit. However,
the multiped earthing electrode will be of higher d.c. or low-frequency resistance due to
electric field interaction between the individual earthing electrode segments near the central
connection point. The optimum surge performance for a single horizontal earthing electrode
will usually be achieved when the downconductor attaches to its midpoint.
The contact resistance between the earthing electrode and the soil can be up to about 10
percent of the total resistance of the earth termination network. This resistance may be
reduced by ionization and arc-over in the soil in contact with the earthing electrode. The
major part of the earth resistance of an earthing electrode arises from the resistance of the
earth in the immediate vicinity of the earthing electrode. The value of this resistance
depends upon the shape, size, and position of the earthing electrode and the resistivity,
moisture content and degree of ionization of the soil in the vicinity of the earthing
electrode. The ratio of resistance at peak impulse current to resistance at low current
depends on the number and arrangement of the electrodes, the peak current and soil
resistivity. Examples are given in Table C1.
C2 RESISTIVITY OF SOIL
C2.1 General
Soil resistivity is another term for the specific resistance of soil. It is usually expressed in
ohm metres (symbol .m), i.e. the resistance in ohms between opposite faces of a cube of
soil having sides 1 m long.
The resistivity of the soil depends on its chemical and mechanical composition, moisture
content and temperature. In view of this there is a very large variation in resistivity between
different types of soils and with different moisture contents. This is illustrated in Tables C2,
C3 and C4.
NOTE: Earthing electrodes should not be located near brick kilns or other installations where the
soil can be dried out by the operating temperatures involved.
For DOD Internal Use ONLY
147 AS/NZS 1768:2007

COPYRIGHT
TABLE C1
EXAMPLES OF REDUCTION OF RESISTANCE OF EARTH CONNECTION
UNDER IMPULSE CONDITIONS
Soil resistance characteristic No. of rods and arrangement
One isolated rod
Four rods at corners of square,
3.05 m sides
Soil resistivity, .m 10
2
10
3
10
2
10
3

Resistance at low currents, 30 300 10.5 105
Resistance at current peak, 11.3 54 6.8 37
Ratio of resistance at current
peak/resistance at low current
0.38 0.18 0.65 0.35
NOTE: The table depends on the following earthing dimensions and conditions:
Diameter of rods = 10 mm Depth in earth = 3.05 m
Peak current injected = 80 kA Time to current crest = 4 s

For DOD Internal Use ONLY
AS/NZS 1768:2007 148

COPYRIGHT
TABLE C2
RESISTIVITY VALUES FOR VARIOUS MATERIALS
Material Resistivity, .m
Typical Usual limits
Salt sea water 0.2 0.15 to 0.25
Estuarine water 0.5 0.2 to 5
Artesian water 4 2 to 12
Damp black inland soil (see Note 1) 8 5 to 100
Damp clay 10 2 to 12
Inland lake water, reservoirs 20 10 to 500
River banks, alluvium 25 10 to 100
Clay/sand mixture (see Note 2) 30 20 to 200
River water (upstream) 40 30 to 200
Concrete (see Note 3) 100 40 to 1000
Dry inland soil (see Note 1) 100 20 to 1000
Moraine gravel 2000 1000 to 10000
Coal 2000 1000 to 5000
Secondary rock 3000 1000 to 50000
Sand (see Note 2) 3000 1000 to 10000
Solid volcanic rock (see Note 4) 20000 10000 to 50000
Ice (see Note 5) 100000 10000 to 100000
NOTES:
1 Black soil is a non-specific term applicable to vast areas of Queensland and New South Wales. The soil
is characterized by a high level of dissolved salts, and undergoes considerable contraction on drying out,
thus causing a significant increase in volume resistivity when dry.
2 Resistivity values for a clay/sand mixture and for sand are based on measurements of a number of sites in
Queensland. The resistivity of dry sand is intrinsically very high and it will serve to increase the
resistivity of any material in which it may be interspersed.
3 Values of resistivity for concrete apply to the cast material and do not include the effect of any
reinforcing bars. The values given will assist in determining the discharge resistance from steel
reinforcement to the general body of earth.
4 Solid volcanic rock is often subject to fissures and faults the contents of which substantially reduce the
resistivity, though not to a very satisfactory level for earthing electrode performance for lightning
protection.
5 Ice is included for reference. It is not anticipated that ice will be of significance in design for the normal
range of conditions.
For DOD Internal Use ONLY
149 AS/NZS 1768:2007

COPYRIGHT
TABLE C3
VARIATION OF SOIL RESISTIVITY WITH MOISTURE CONTENT
Moisture content
(percent by weight)
Typical value of resistivity
.m
Clay mixed with sand Sand
0 10000000
2.5 1500 3000000
5 430 50000
10 185 2100
15 105 630
20 63 290
30 42
TABLE C4
VARIATION OF RESISTIVITY WITH
TEMPERATURE IN A MIXTURE OF SAND
AND CLAY WITH A MOISTURE CONTENT
OF ABOUT 15 PERCENT BY WEIGHT
Temperature Typical value of resistivity
C .m
20
10
0 (water)
72
99
138
0 (ice)
5
15
300
790
3300
C2.2 Artificial reduction of soil resistivity
Chemical additives can be used to reduce soil resistivity. These additives generally take the
form of fully ionizable salts such as sulphates, chlorides or nitrates. Such chemical
additives should not be used indiscriminately as
(a) the benefit that they provide will lessen with time due to leaching through the soil;
and
(b) they may increase the rate of corrosion of the earthing electrode material.
Some of the chemical additives are also objectionable from an environmental viewpoint.
A bland backfill material such as calcium or sodium bentonite clay, or montmorillonite with
finely ground gypsum will reduce resistivity for a considerable period in high resistivity
soils, maintain some moisture adjacent to the earth termination network, and provide a
uniform and non-corrosive environment for the earthing electrodes. For further information
see the recommendations in AS 2239 relating to the backfilling of galvanic anodes.
C2.3 Determining soil resistivity by test
It is fairly easy and useful to determine soil resistivity by test before commencing to install
earthing electrodes. Testing procedures are given in Paragraph C10.1.
For DOD Internal Use ONLY
AS/NZS 1768:2007 150

COPYRIGHT
C3 CALCULATION OF EARTH RESISTANCE OF AN EARTHING ELECTRODE
If the soil resistivity is known (see Paragraph C2.3), the earth resistance R in ohms can be
calculated as follows:
(a) Single vertical rod of length L and diameter d metres, top of rod level with surface:
R =
8
ln 1
2
L

L d

|

|

\ .
]
. . . C3(1)
where
R = resistance, in ohms
= soil resistivity, in ohm metres
L = buried length of earthing electrode, in metres
d = diameter of earthing electrode, in metres
NOTE: Equation C3(1) is commonly referred to as the modified Dwight formula.
(b) As above, but top of rod h metres below surface:
R =
L + h
L + h

d
L

L 4
2
1
8
ln
2

]

|
.
|

. . . C3(2)
(c) Thin circular plate, diameter D metres, on surface:
R =
D 2

. . . C3(3)
(d) Thin circular plate, diameter D metres, buried h metres below surface:
R =


h
D

D

4
+ 0.5
2
. . . C3(4)
For a vertical plate, h is measured from the centre of the plate. In the case of a square
plate, the diameter can be replaced with 1.13 times the side of the square.
(e) Straight horizontal wire of length L and diameter d metres, on surface:
R =

|
.
|

1
4
ln
d
L

L

. . . C3(5)
For a thin strip earthing electrode, the diameter can be replaced with a half-width of
the strip.
(f) As for Item (e), but buried h metres below surface:
R =

|
|
|
.
|

1
4
ln
2
1

) (dh
L

L

. . . C3(6)
(g) Radial wires, number of wires n, on surface:
R =
(

'
|
) ( 1
4
ln n N +
d
L

L n


. . . C3(7)
where
N(n) =
n m sin
n m sin + 1
ln
1 n m
1 m
/
/

- =
=


. . . C3(8)
For DOD Internal Use ONLY
151 AS/NZS 1768:2007

COPYRIGHT
or for
n = 2 3 4 6 8 12 100
N(n) = 0.7 1.53 2.45 4.42 6.5 11.0 116
When the wires are buried at a depth of h metres then the diameter of the wire should
be replaced by the equivalent diameter
d =
2
1
) (dh
. . . C3(9)
(h) Ring of wire, radius of ring r metres:
R =
d
r

r
16
ln
4
2

. . . C3(10)
or in terms of the circumference l
R =
d
l

l 2
8
ln . . . C3(11)
When the wire is buried at a depth h, the diameter of the wire should be replaced by
the equivalent diameter determined from Equation C3(9).
NOTES:
1 The above equations assume that the longitudinal resistance of the earthing electrodes can
be neglected. The resistance for an earth termination network, of such dimensions that the
voltage drop along the earthing electrodes or buried conductors must be considered, may
be obtained as follows:
2
1
2
1
o o
coth

=
R
R
R
R
R R
. . . C3(12)
= R when R
o
/R 0.4
=
2
1
) (
o
RR when R
o
/R 2

where R is the resistance calculated from the relevant equation and R
o
is the
longitudinal resistance of the total length of wire.
2 The above equations also assume that the earthing electrodes on the surface are buried to
half their thickness or diameters; the lengths of rods and wires are much greater than their
diameters; the thickness of the plates is much smaller than the plate diameters and the
diameter smaller than the depth of burial; and that the angles between the radial wires are
equal.
3 Because of interaction, the obtainable earth resistance of two or more radial earthing
electrodes is higher than that for a single wire of the same length. The increase in
resistance is approximately as follows:
For two wires at right angles, energized at the joint, the earthing resistance is:
100
3R
R +

where R is the resistance of a single straight wire of the same total length and
energized at one end. For a three-point star it is:
100
6R
R +

and for four, six and eight-point stars, all energized at the centre, the resistances are:
. ly respective
100
65
+ and
100
42
+ ,
100
12

R
R
R
R
R
R +

For DOD Internal Use ONLY
AS/NZS 1768:2007 152

COPYRIGHT
4 The equations apply to direct current or power-frequency alternating current energization.
For all practical purposes the resistance to a lightning surge of a typical structure LPS
earth termination network discussed in this Standard can be considered as being
somewhat lower than its direct current or power-frequency alternating current value.
C4 USE OF EARTHING ELECTRODES IN PARALLEL
In situations where a desired earthing resistance cannot be achieved with one earthing
electrode, a number of earthing electrodes may be used in parallel.
The combined resistance of parallel earthing electrodes is a complex function of a number
of factors, some of the more important being the number of earthing electrodes, their
dimensions, the separation between the earthing electrodes, the soil resistivity and the
configuration of the earthing electrodes.
Where the desired resistance can be achieved with only a few additional earthing electrodes
and if the separation between the earthing electrodes is greater than their lengths (see Note),
then the resultant resistance may be calculated by using the ordinary equation for
resistances in parallel. In other situations the combined resistance owing to the mutual
interaction between the earthing electrodes, will be always higher than given by this
equation.
NOTE: For practical purposes, the separation between vertical earthing electrodes can be taken as
twice the length of the earthing electrode.
For example, the combined resistance of two parallel earthing electrodes of diameter d
separated by a distance s, which is small compared with the earthing electrodes length L, is
given by the following equation:
R =
(

'
|


a
L

L
1
2
n l


. . . C4(1)
where
R = resistance, in ohms
= soil resistivity, in ohm metres
L = buried length of earthing electrode, in metres
a = equivalent radius of the earthing electrode at the surface, in metres,
determined from the equation:
a =
4
1
2
1
2
1
2
1
] [ = ] ) ( ) ( [ s dhs s s dh
. . . C4(2)
where
d = diameter of earthing electrodes, in metres
h = buried depth of earthing electrode, in metres
s = distance between two parallel earthing electrodes, in metres
s = distance from one earthing electrode to the image of the other earthing
electrode, in metres
NOTE: The term
2
1
) ( s s is the effective separation, and
2
1
) ( s
2 2
4 s h + = . An equation for
radial conductors is given in Paragraph C3(g).
For DOD Internal Use ONLY
153 AS/NZS 1768:2007

COPYRIGHT
C5 DRIVEN OR DRILLED EARTHING ELECTRODES
C5.1 General
The use of driven or drilled earthing electrodes combines economy of surface space with
efficiency of performance, and accesses clays and other conductive layers at depth. In
consequence, it is a preferred method of earthing electrode installation.
C5.2 Safety
The indiscriminate driving of earthing electrodes or drilling for their placement can lead to
damage of other services and, in the case of electricity supply cables, to the creation of a
significant hazard to the operator. As normally the drilled or driven rod will not be earthed
to a low impedance system, it will usually remain live and dangerous if it contacts a live
conductor. High pressure gas or hydrocarbon pipes also create a significant hazard, quite
apart from service failure aspects. Consequently, appropriate searches for such services
should be made before drilling or driving.
C5.3 Installation
The extent of the earthing electrode installation needed will depend on the variation in soil
resistivity with depth, and the resistance to be achieved. Earthing electrodes may be driven
directly into the ground or fitted into pre-drilled holes. In the latter case a bentonite/gypsum
slurry or other drilling mud would normally be used as a permanent resistance and soil
contact medium.
C5.4 Materials for earthing electrodes
Earthing electrodes should be made of metals not liable to be materially affected by
corrosion. Clause 4.7.2 describes the considerations involved in selecting earthing electrode
materials to minimize corrosion in service.
C5.5 Earthing electrode diameter
Although the resistance between the earth and the earthing electrode depends to a certain
extent on the area of the earthing electrode in contact with the soil, a large earthing
electrode of, say, 50 mm diameter does not decrease the resistance materially compared
with earthing electrodes of 13 mm or 20 mm diameter, which need to be only slightly larger
to achieve the same resistance.
For a driven earthing electrode, provided the required current-carrying capacity is met, the
minimum diameter will usually be determined by mechanical rather than electrical
considerations. The usual practice is to select a diameter that will give enough strength to
enable the earthing electrode to be driven into the soil of a particular location without
bending or splitting. Large diameter earthing electrodes are more difficult to drive than
small diameter earthing electrodes. For deep drilled earthing electrodes the size is selected
in the light of available drill diameters, requirements for connections (if any) and economy.
Strip earthing electrodes are commonly used.
C5.6 Depth of installation
The depth to which an earthing electrode is installed is usually the most important factor
affecting its earth resistance, first because the area of soil contacted increases directly with
the length of earthing electrode below the surface, and secondly because the soil resistivity
usually decreases with depth.
For DOD Internal Use ONLY
AS/NZS 1768:2007 154

COPYRIGHT
This is shown by the measurements plotted in Figure C1 for a number of sites. For curves 1
and 2 it was known, by tests, that the soil down to a depth of between 6 m and 9 m
consisted of ballast, sand and gravel, below which was clay. The rapid reduction in
resistance when the earthing electrode penetrated the latter is very marked. The mean
resistivity up to a depth of 7 m in one case was 150 .m, at 10 m the mean value for the
whole depth was 20 .m due to the low resistivity of the clay stratum. Similarly for curve
4, the transition from gravelly soil to clay at a depth of about 1.5 m is very effective. For
curve 3, however, no such marked effect occurred although there is a gradual reduction in
average resistivity with increase in depth, as can be seen by comparison with the dotted
curves, which are calculated on the assumption of uniform resistivity.

FIGURE C1 CALCULATED AND MEASURED CURVES OF RESISTANCE
OF 13 mm DIAMETER DRIVEN ROD EARTHING ELECTRODES
C5.7 Sleeving of exposed part of vertical earthing electrode
Where side-flashing or step and touch potentials are a design problem on a driven earthing
electrode, it is good practice to sleeve the upper part of the earthing electrode with a
non-conducting pipe or heat shrink tubing of adequate weather resistance and electrical
insulation properties. For example, this could take the form of 2 mm thickness of
polyethylene or 4 mm thickness of PVC covering the upper 2 m to 3 m of the earthing
electrode.
For DOD Internal Use ONLY
155 AS/NZS 1768:2007

COPYRIGHT
C5.8 Comparison with other earthing electrode types
The simplicity of driving an earthing electrode compared with making excavations for the
burying of plates or strips is obvious. The problem of the adequate packing of the soil
around the earthing electrode does not arise. The space occupied is small and, unlike plate
earthing electrodes, connections may be above ground. Moreover, where the permanent
moisture level or layer of low resistivity soil is available only at considerable depth below
the surface, earthing electrodes may be driven to depths that would be far beyond that
which would be practicable or economical for buried plate earthing electrodes.
However, where soil resistivity increases with depth, there is no point in driving an earthing
electrode any deeper as better results may be obtained by connecting a number of earthing
electrodes in parallel or by using a buried strip earthing electrode.
C6 BURIED STRIP EARTHING ELECTRODES
Buried strip earthing electrodes provide a solution to the problem of obtaining a low
resistance earth connection in locations where soil resistivity is high, particularly where
there is a superficial layer of soil over a stratum of rock and it is impracticable to drive an
earthing electrode. For a given cross-section, strip earthing electrodes have the advantage of
a greater surface area in contact with the soil.
The material for such earthing electrodes should be selected having regard to corrosion
compatibility with the protected structure (see Clause 4.7.2). For example, for a galvanized
steel tower, a 50 mm 3 mm galvanized steel strip would be preferred. Where the earthing
electrode is totally isolated from other metals, e.g. on an isolated stone or timber structure,
any one of a variety of materials may be used. These include copper, galvanized iron, steel,
stainless steel, Ni-resist. The last two materials offer some additional corrosion resistance
in aerated soils, but with the disadvantage of higher electrical resistance and cost.
Backfilling and compacting the trench will enhance the early resistance performance of the
earthing electrode. The cross-section of the conductor has very little effect on the resistance
of the earth connection so that the strip or cable size is not important provided it affords
reasonable protection against mechanical damage and corrosion, and is of adequate current
surge capacity. (see Table 4.6 for typical dimensions).
The economics of depth of burial versus resistance performance do not warrant laying strip
earthing electrodes below 500 mm, unless the risk of mechanical damage requires this
additional protection.
The optimum resistance for a given amount of earthing electrode material is achieved if the
earthing electrode is buried in a straight single trench or in several trenches radiating from a
point. If laid in parallel lines, the trenches should be widely separated (see Paragraph C1
and the Notes to Paragraph C3).
C7 BURIED PLATE EARTHING ELECTRODES
This form of earthing electrode is now mainly restricted to tower footings or the like where
the civil works for the structure to be protected provide the facilities for the laying of the
earthing electrode. The performance/cost relationship does not support other than
such specific applications.
C8 CONCRETE FOOTING EARTHING ELECTRODES
This form of earthing electrode is one of the most effective both in cost and electrical
performance of currently available earth termination networks. For a given site it provides a
permanent, distributed, low resistance earthing electrode at very little cost above the
structural civil work.
For DOD Internal Use ONLY
AS/NZS 1768:2007 156

COPYRIGHT
The vital part of the exercise is the planning, design and supervision of the construction, as
after concrete is poured it is impractical to address design deficiencies. If a sectional
measurement of earth resistance is desired, this will only be feasible at the appropriate stage
of construction.
As this earthing electrode is likely to be bonded deliberately or fortuitously to the
electricity supply service earthing system, and perhaps to other earthing systems, it is
important to consider the possibility of corrosion arising from contact with dissimilar
metals (see Clause 4.7.2). It may be necessary to address corrosion problems of rock
anchors by cathodic protection (see AS 2832.2).
The deliberate or fortuitous bonding of on-site fuel tanks, now relatively common adjacent
to building foundations, should also be taken into account in the design of LPS earthing
electrodes to ensure the earth discharge is from the earth termination network, i.e. the fuel
tanks are electrically screened.
C9 INSPECTION AND MAINTENANCE OF EARTHING ELECTRODES
The scheduling of earthing electrode maintenance inspections is the prerogative of the
system owner. However, the frequency of testing and the associated considerations are
listed below as a guide to good engineering practice. Data on the layout, materials of
construction data and electrical measurements pertaining to the original design should be
prepared and preserved as a guide to later performance. Soil resistivity data are likewise
useful for future comparison. The following practices are recommended:
(a) Inspections should be both physical and electrical.
(b) The inspections should be carried out at intervals of not less than two years.
Examples of the need for more frequent action would be if the earth termination
network is in a marine environment, subject to a high rate of corrosion. Such
installations may require inspection at intervals as frequent as once per year.
(c) The physical inspections should address corrosion or mechanical damage to visible
parts of the whole system, structural alterations that may have prejudiced the design
or operation of the system, or changes in the usage of the structure, e.g. fuel storage
added.
(d) Electrical tests should cover the continuity of the downconductors, the integrity of
bonding arrangements, and the resistance to earth of the earthing electrodes,
preferably individually as well as collectively. Methods of testing resistance to earth
are discussed in Paragraph C10. The continuity of downconductors should preferably
be checked by a high-current testing system (approximately 10 A) in order to detect
reduced current-carrying capacity resulting from fractures or other damage that may
be obscured from view.
(e) The enhancement or replacement of earthing electrodes to achieve a specified
resistance may be necessary, and if this is done it should be recorded along with other
test results. Restoration records of clamps, joints and fittings on downconductors or
earthing electrode terminations should also be kept as a future maintenance guide.
(f) Where uncertainty exists about the validity of inspection test results, comparison with
original design figures and data, together with the historical test records, will often
serve to indicate the extent of deterioration of the earthing electrodes. The change in
soil resistivity with rainfall can at times be particularly misleading, and test results
should be viewed with some suspicion if a significant reduction is observed in
resistance figures.
For DOD Internal Use ONLY
157 AS/NZS 1768:2007

COPYRIGHT
C10 MEASUREMENT OF SOIL RESISTIVITY, EARTHING ELECTRODE
RESISTANCE AND EARTH TERMINATION NETWORK IMPEDANCE
C10.1 Determination of soil resistivity by test
C10.1.1 Four-pin method
The Wenner or four-pin method of soil resistivity measurement is commonly used. It
involves the use of four test pins (test electrodes) equally spaced in a straight line and
driven to the same depth d, not exceeding 5 percent of their separation s and not more than
1 m in any case (see Figure C2).

LEGEND:
s = test pin separation
d = depth of test pin: this must be small in relation to s.
i.e. not greater than
20
s
and not in any case greater than 1 m
NOTES:
1 The above configuration will give a reading for , by calculation, that is equivalent to the resistivity at
depth 0.75s.
2 If it is required to determine average resistivity to various depths at a given point O, the centre point O of
the test configuration is kept fixed and the test pin separation s increased outward from that point.
3 As the effects of d.c. polarization on the test pins would give a superimposed error on V, of the same order
as the small voltage being recorded, it is necessary to use an alternating electricity supply source, or if d.c.,
a cyclically-reversed source. The latter would also require a synchronous reversal of the indicating system.
FIGURE C2 FOUR-PIN METHOD OF SOIL RESISTIVITY MEASUREMENT
If a known current I is passed between the outer test pins, and the voltage drop V between
the inner test pins is measured, the ratio V/I gives a resistance R. If the earth were perfectly
homogeneous, i.e. of a constant resistivity , then:
= 2sR
. . . C10.1.1
where
s = test pin separation, in metres
= average soil resistivity to a depth of s metres, in ohm metres
The soil is rarely homogeneous and the value calculated from Equation C10.1.1 (called
the apparent resistivity) will be found to vary with the test pin separation s. It is from these
variations that deductions can be made as to the variation in the nature of the underlying
soil.
For DOD Internal Use ONLY
AS/NZS 1768:2007 158

COPYRIGHT
Account should also be taken of seasonal variations of the soil, primarily because of
changing moisture content. By repeating the measurements with different values of test pin
separation, the average resistivity to various depths can be found and the results will
indicate whether an advantage is to be gained by installing deep-driven earthing electrodes
to reach strata of low resistivity.
In practice an indicating ohmmeter or null-reading bridge is used to measure the resistance
R from which soil resistivity is calculated by using Equation C10.1.1.
C10.1.2 Instrumentation for soil resistivity measurement
Measurement of soil resistivity by the Wenner method (Paragraph C10.1.1) requires a four-
pin earth resistance tester. There are two main types, the traditional null-reading analogue
or the later microprocessor based digital. Originally the analogue types were powered by a
hand wound generator but these have been largely superseded by battery-powered models.
The majority of four-pin earth testers currently available are battery-powered digital
instruments providing a square wave output. Test frequencies are usually around 128 Hz for
the basic models. More capable models offer variable test frequencies to avoid possible
errors from interference frequencies present on the earth system. These instruments can also
provide automatic frequency selection which detects interference frequencies and
automatically selects the optimum test frequency to avoid measurement errors.
The output voltage of earth testers usually ranges from 20 to 50 V. Test current is governed
by the resistance of the load and instruments are usually rated on their short circuit current.
That is the current the instrument can generate with the terminals shorted. Typically the
short circuit current ranges from 10 mA for basic models to 250 mA for more capable
instruments.
The connections for a four-pin measurement of soil resistivity is shown in Figure C3.

LEGEND:
s = test pin separation
d = depth of test pin: this must be small in relation to s.
i.e. not greater than
20
s
and not in any case greater than 1 m
C1 = Current terminal 1 on instrument (marked E on some instruments)
P1 = Potential terminal 1 on instrument (marked ES on some instruments)
C2 = Current terminal 2 on instrument (marked H on some instruments)
P2 = Potential terminal 2 on instrument (marked S on some instruments)
FIGURE C3 CONNECTIONS FOR EARTH RESISTIVITY TEST USING AN
INDICATING OHM METER OR NULL BALANCE BRIDGE FIGURE
For DOD Internal Use ONLY
159 AS/NZS 1768:2007

COPYRIGHT
C10.2 Earth resistance
C10.2.1 General procedure
Earth resistance is measured by applying a voltage to the earth electrode and measuring the
current passing through the electrode to earth. Resistance is calculated by the earth tester
using Ohms Law R=V/A. This is often referred to as the fall of potential method as shown
in Figure C4.
To create a path for the test current and to measure the voltage, a current is passed in a
potential test stake, which is placed in the soil outside the potential gradient area of the
electrode being measured.
The conduction of current through the soil is non-linear. Consequently, earth resistance
measurements will vary with different test voltages, currents and frequencies. Interference
voltage and frequency can be picked up by the test stakes. An earth resistance tester ideally
should provide variable test frequencies to avoid measurement errors from interference.
Earth resistance can be measured by a three-pin or four-pin measurement. The difference
between three-pin and four-pin testing is the number of connections to the electrode under
test. A three-pin test makes one connection to the earth electrode while a four-pin test
makes two. By making two connections to the electrode under test, the voltage is measured
at the earth electrode and not at the instrument. This eliminates any error caused by
resistance in the connecting lead and is generally regarded as the preferred method.

LEGEND:
C1 = Current terminal 1 on instrument (marked E on some instruments)
P1 = Potential terminal 1 on instrument (marked ES on some instruments)
C2 = Current terminal 2 on instrument (marked H on some instruments)
P2 = Potential terminal 2 on instrument (marked S on some instruments)
E = Earth electrode under test
P = Potential pin or stake
C = Current pin or stake (sometimes referred to as auxiliary stake)
RE = Resistance of earth electrode to ground
Rp = Resistance of potential pin to ground (sometimes referred to as Rs)
Rc = Resistance of current pin to ground (sometimes referred to as Rh)
V = Test voltage applied by instrument
I = Test current path
G = a.c. generator in instrument
NOTE: For three-pin measurement terminals C
1
and P
1
are bridged at the instrument
FIGURE C4 PRINCIPLE OF FOUR-PIN EARTH RESISTANCE MEASUREMENT
The fall of potential follows the relationship:
D =
2
I
V

. . .C10.2.1
For DOD Internal Use ONLY
AS/NZS 1768:2007 160

COPYRIGHT
where
D = the distance from the test stake in metres
I = the test current in Amps
= the soil resistivity in ohm-metres
V = the voltage at distance D from the test stake in Volts.
Consequently it is important that P be situated on the flat part of the curve as in Figures
C5 and C6. If C is not sufficiently distant from E, there will be no flat part of the curve.
This can be established by moving P and retesting. If it varies, then C is too close to E.
As a general rule, C should be separated from E by not less than 10 times the length of E,
for homogenous ground, and P about half the distance from E to C.

FIGURE C5 FALL OF POTENTIAL AROUND AN EARTH ELECTRODE AND TEST
STAKES

FIGURE C6 EFFECT OF THE FALL OF POTENTIAL ON THE MEASUREMENT OF
EARTH RESISTANCE
For DOD Internal Use ONLY
161 AS/NZS 1768:2007

COPYRIGHT
C10.2.2 Test lead considerations
Because of the inhomogeneity or layering of the soil it is prudent practice to use as long a
lead from E to C as practical. In fact, for extreme conditions, such as a mountain top, where
the site may be on a volcanic core, it is not uncommon practice to use a 500 m or 1000 m
test lead of physically substantial construction. Testing with short leads merely gives a test
pin resistance to that small volume of ground encompassed by the electric field between E
and C, in a roughly hemispherical volume.
With very long leads a significant hazard arises. EPR from power fault currents or lightning
pulse can give rise to dangerous voltages between different parts of the earths surface. The
handling of leads of 500 m or greater should be accompanied by the careful use of
insulating gloves suitable for working at voltages of up to 500 V a.c. Test instruments may
require fitting with radiofrequency suppression devices to prevent the pickup of
high-frequency radio communication signals damaging the electronic detection equipment,
or producing erroneous readings.
Another condition requiring very long leads is the situation of an earthing electrode of
considerable dimensions, e.g. a 500 m strip earthing electrode, especially in high resistivity
ground such as a mountain top or sandy plain. In this case, the concept of resistance to the
body of earth encompassed by the electric field above, requires a lead to C of the order of
500 m, at right angles to the run of the earthing electrode. The same safety considerations
apply.
C10.2.3 Instruments for earth resistance measurement
C10.2.3.1 General
The earth resistance of an earth electrode or group of electrodes can be measured by several
methods using various types of earth testers. It cannot be assumed that each method or each
type of instrument is suitable for every situation.
A four-pin earth tester (see Figure C7) as used for soil resistivity can also be used for
measuring earth resistance. Lower cost three-pin earth testers are also suitable for
measuring earth resistance but cannot be used to measure soil resistivity. Users must be
aware that measurements made with the three-pin method are susceptible to error from test
lead resistance.
Both three-pin and four-pin earth testers require the earth being measured to be
disconnection during measurement. This poses a major safety hazard should there be a
lightning strike or a fault current present during test. The use of a second downconductor
and consequent earth electrode will ensure that the LPS is always earthed during system
testing. (Refer to Clause 4.3.3(a)).
To eliminate the hazard and inconvenience of disconnecting the earth to be measured, the
selective method has been developed.
Another alternative is the stakeless method. This has the advantages of not requiring the
isolation of the earth electrode or the use of test stakes. This does however require the earth
system to have a secondary reliable solid bond to earth, such as a bond to the electrical
earth and/or metal water service. Users must be fully conversant with the earth circuitry,
otherwise measurements by this method can be misleading.
Each method has advantages and will produce reliable measurements if used in the
appropriate situations. There is no one method which can be used for every situation. This
has given rise to multi-method earth testers which combine all three methods into a single
instrument.
For DOD Internal Use ONLY
AS/NZS 1768:2007 162

COPYRIGHT
C10.2.3.2 The three and four-pin method

FIGURE C7 THE THREE-PIN AND FOUR-PIN METHOD OF MEASURING EARTH
ELECTRODE RESISTANCE
C10.2.3.3 Selective method
To address the hazard of isolating electrodes under test and the inconvenience of
disconnecting and reconnecting, the selective method of measuring earth resistance was
developed (see Figure C8).
The principle of the selective method is the use of a clip-on current transformer (CT) to
measure the test current flowing in the earth electrode under test. Resistance is computed
from the actual current flowing to earth via the electrode. Current flowing to earth through
the remainder of the earth network is not measured and has no effect on the result.

FIGURE C8 SELECTIVE EARTH RESISTANCE MEASUREMENT
Both the three-/four-pin and selective methods of measuring earth resistance rely on test
stakes being placed, typically 50 to 100 m, or even further from the earth system being
tested. This is generally of no consequence in rural areas but it is seldom possible in cities
and towns where buildings are surrounded by pavement or the electrodes are in basements.
C10.2.3.4 Stakeless or clamp-on method
Stakeless testing provides benefits in developed areas as it is no longer necessary to find
suitable soil to place test stakes or to need to run out long test leads and wind them up at the
completion of tests. It provides a convenient method of measuring earth resistance in
locations which were previously difficult or impossible to measure by other methods. No
direct connection is made to the earthing system and maximim safety is achieved.
For DOD Internal Use ONLY
163 AS/NZS 1768:2007

COPYRIGHT
Stakeless earth resistance testing requires a solidly earthed network in parallel with the
electrode to be tested to provide a path of negligible resistance to earth for the test current
(see Figures C9 and C10). For a valid reading, it is necessary that the resistance being
measured (R
x
) is large compared to the parallel combination of the other interconnected
paths to earth (R
1
to R
n
). More specifically, the actual value measured is given by
R
measured
= R
x
+ (parallel combination of R
1
to R
n
)
Two clip-on CTs are used for this method. The test voltage is applied to one CT which is
used in reverse to induce a test current to flow in the earth network, the other CT is used as
before to measure the component of test current flowing through the electrode under test.
Earth resistance is computed in the same manner as for the selective method.

FIGURE C9 PRINCIPLE OF STAKELESS MEASUREMENT
Stakeless earth testing can be as an adaptation of the selective method by adding a second
CT or as a specially designed clamp-on tester where the two coils are incorporated into a
single jaw. Clamp-on earth testers can only function in this mode and cannot test by any
other method.

FIGURE C10 MEASUREMENT OF EARTH RESISTANCE OF A LIGHTNING SYSTEM
WHICH IS BONDED TO THE ELECTRICAL EARTH USING THE STAKELESS METHOD
C10.3 Isolation of surge impedance of an earth termination network from other
fortuitous earth paths
The measurement of electrode surge impedance in an LPS earth termination network
requires that the electrical condition specific to a lightning pulse be addressed. Typically
the rise time of a substantially unmodified lightning pulse is around 1 s. This means that
fortuitously-bonded path lengths of more than a few tens of metres will present a reactive
component that prejudices the ability of such paths to divert a significant portion of the
total earth path current. This in turn requires the measuring system to reject such paths and
to measure the residual pathusually that to immediately adjacent earthing electrodes or
earth features.
For DOD Internal Use ONLY
AS/NZS 1768:2007 164

COPYRIGHT
This can be achieved fairly simply but at some cost by utilizing a relatively high frequency
source of power for the three-pin test. Several excellent commercial instruments are
available that operate in the 25 kHz to 50 kHz range.
These are used in the same manner as other three-pin (and four-pin) test sets. The difference
in readings between these and the low-frequency test sets will often be quite spectacular
and will point out obvious reasons for observed catastrophic failure from lightning in
systems thought to be adequately earthed. In particular, the electricity supply service
neutral/earth connection bonded for 50 Hz equipotential protection to LPS earth termination
network can give a grossly misleading sense of security if it is read with a 108 Hz test set.
Typically, a one ohm reading can in reality be 100 surge impedance, as measured by a
high frequency test set.
If a high frequency test set is unavailable, an alternative method with reasonable accuracy
may be used, based on the fall of potential curve around the electrode (see
Paragraph C10.2.1), similar to that used for testing substation earth mats.
Alternating current is applied between the earthing electrode (or its downconductor) and an
auxiliary test pin (see Figure C11). The portion of the current passing to earth via the
earthing electrode under test is measured by a clamp ammeter placed between the current
injection point and the earthing electrode entry to ground. The voltage to which this drives
the earthing electrode is measured by a flying lead voltmeter to a test pin sited in the flat
portion of the fall of potential curve. The resistance of the earthing electrode is a simple
R = V/I relationship, and is a good approximation to the surge impedance.
A skilled operator may elect to measure approximate lightning surge impedance at a site on
a long buried strip electrode by reduction of the length to the C2 electrode, using a
conventional 3 terminal test set. This requires both experience with the set and its
performance in various soil resistivities.

NOTE: No connections to bonding conductors should exist on the earth side of the current injection point.
FIGURE C11 MEASUREMENT OF EARTHING ELECTRODE SURGE IMPEDANCE
For DOD Internal Use ONLY
165 AS/NZS 1768:2007

COPYRIGHT
APPENDIX D
THE CALCULATION OF LIGHTNING DISCHARGE VOLTAGES AND
REQUISITE SEPARATION DISTANCES FOR ISOLATION OF A LIGHTNING
PROTECTION SYSTEM
(Informative)
D1 GENERAL
In the first one or two microseconds of a lightning discharge, transient voltages occur on
the air terminal network and on the downconductors, which may be far greater than the
discharge voltages that apply during the remainder of the discharge. This is because the
discharge energy injected into the air terminal network at any instant is initially stored as
thermal energy in the conductors of the protection system prior to discharging into the
general mass of earth via the earth termination network. This transient voltage frequently
determines the separation distance required for isolation of the LPS, if it is desired to
isolate in accordance with Clause 4.16.2.3 as the preferred method of protection against
side-flash (see Clause 4.16.2.1).
The peak values of the transient voltages appearing at various points of the protection
system differ according to location, and increase with distance from the earth termination
measured along the route of the discharge through the protection system. At points very
near to a concentrated earth termination, the transient voltages are suppressed by the
discharge to earth and minimum values of discharge voltage and required clearance can be
readily calculated (see Note 1). These lower limits apply only at the base of the structure
and are given by the equations:
V
e
= 150R . . . D1(1)
D
e
= 0.3R . . . D1(2)
where
V
e
= the discharge voltage at the base of the structure due to local EPR, in
kilovolts
R = the combined earth termination resistance, in ohms
D
e
= the required clearance in air at the base of the structure, in metres
The complete transient voltage waveshape at all points of the protection system can be
calculated using travelling wave techniques and a computer, however substantial
simplifications allowing helpful easily-calculated estimates can frequently be made (see
Paragraph D2).
An estimate of the transient voltage at any one point of an LPS can often be made using a
conventional circuit theory approach (see Paragraph D3). This is possible because the
transient voltages can often be neglected due to the high insulation strength of air to
extremely brief voltage stresses.
Transient voltages at points remote from the earth termination depend both on the lightning
stroke current waveshape and the characteristics of the protection system. As indicated in
Paragraph B2.2 and Table B1 of Appendix B, lightning flashes generally have a number of
component strokes with differing waveshapes. The critical voltage may correspond to the
highest peak current of a first stroke or to the steepest wavefront (di/dt)
max.
of a subsequent
stroke.
For DOD Internal Use ONLY
AS/NZS 1768:2007 166

COPYRIGHT
The design first and subsequent strokes used in this Standard are shown in Figure D1 (see
Note 2). The more severe of these cases was adopted in arriving at the required clearances
in Clause 4.16.2.3.

FIGURE D1 IDEALIZED LIGHTNING STROKE CURRENTS ADOPTED FOR DESIGN
PURPOSES
The electrical breakdown strength of air depends on the polarity of the applied voltage and
on the duration and shape of the voltage surge. In the studies conducted for this Standard,
the required clearances were estimated using the breakdown strength of air, shown in
Figure D2, which neglects some of these variables and should only be regarded as
approximate.

FIGURE D2 TIME DEPENDENCE OF THE ELECTRICAL BREAKDOWN STRENGTH OF
AIR
(approximation for the purpose of this Standard only)
For DOD Internal Use ONLY
167 AS/NZS 1768:2007

COPYRIGHT
In some cases where the transient voltage surges differed significantly from the waveshapes
(chopped and triangular waves) upon which the graph is based, a further adjustment was
made.
NOTES:
1 The lower limit of design discharge voltage is based on the assumed peak lightning current of
150 kA. The corresponding required clearance is based on a minimum electrical breakdown
strength of 500 kV/m in air.
2 The lightning flash is assumed to have a first stroke with I
max.
of 150 kA and (di/dt)
max.
of
32.6 kA/s and a steepest subsequent stroke with I
max.
of 40 kA and (di/dt)
max.
of 200 kA/s.
A more severe case would occur not more than once in each hundred lightning strikes to the
building, that is about once in a thousand years for a single 60 m high structure in a locality
with a moderate level of lightning activity (one strike per square kilometre per year).
D2 TRANSIENT VOLTAGE CALCULATIONS BY TRAVELLING WAVE
ANALYSIS
D2.1 Simplified travelling wave characteristics
An electric charge injected into one end of a conductor propagates along the conductor as a
travelling wave with velocity v given by:
v =
) (
1
1 1
C L

. . . D2.1(1)
where
v = velocity, in metres per second
L
1
= the inductance per unit length, in henries per metre
C
1
= the capacitance per unit length, in farads per metre
For a single bare conductor of radius r at a distance h above a perfect ground in free space,
L
1
and C
1
are given by:
L
1
=
r
h
o
2
1n
2

. . . D2.1(2)
C
1
=
r
h
o
2
1n
2

. . . D2.1(3)
where
o
and
o
are the permeability and permittivity of free space and the conductor is
assumed to be non-magnetic, i.e.

o
= 4 10
-7
H/m, and
o
= 8.85 10
-12
F/m
In air, and differ only slightly from
o
and
o
, and the velocity of the travelling wave
becomes the velocity of light, c, in metres per second:
v =
)
o o
(
1
= c = 3 10
8

. . . D2.1(4)
(In an insulated cable with continuously earthed sheath and dielectric or relative
permittivity k (where k is typically 3 to 6), the velocity is reduced by the factor 1/ k and is
typically 0.5 c.)
For DOD Internal Use ONLY
AS/NZS 1768:2007 168

COPYRIGHT
For lossless surge propagation, the voltage e generated by a travelling wave with current i is
given by:
e = iZ . . . D2.1(5)
where
Z =

1
1
C
L
is called the surge impedance of the conductor, and in free space
is given by:
Z = 60 1n
r
h 2

. . . D2.1(6)
where Z is in ohms.
When a travelling voltage wave in a conductor arrives at an electrical discontinuity, such as
an intersection of downconductors or the connection of a downconductor to an earth
termination, part of the travelling wave is transmitted and part is reflected.
If Z
1
is the surge impedance of the conductor on which the wave is travelling prior to
reaching the discontinuity, and Z
2
is impedance seen at the termination or combined parallel
surge impedance of conductors continuing beyond the junction or other discontinuity, then
the reflected surge v, i is related to the incoming surge by the equations:
v = bv = v

1 2
1 2
Z Z
Z Z

. . . D2.1(7)
i = bi = i

2 1
21 1
Z Z
Z Z

. . . D2.1(8)
and the combined transmitted wave v, i beyond the discontinuity or at the termination is
given by:
v = av = v

+
1 2
2
Z Z
2Z
= v(1 + b)
. . . D2.1(9)
i = i

+
1 2
1
Z Z
2Z
= i(1b)
. . . D2.1(10)
where
b = the reflection coefficient
a = the transmission coefficient
D2.2 Surge voltage calculation by lattice diagram
The LPS is represented by a simplified model in the form of nodes and branches. The nodes
are placed at junctions or impedance discontinuities. Each branch has a surge impedance,
and a travel time determined from its length and the surge velocity.
The earthing resistance at each earth termination is treated as a branch with surge
impedance equal to the earthing resistance in ohms and of infinite travel time.
Lattice diagram calculations are usually carried out by computer. Generally the program
calculates the response of the system to a unit step function current and the response to any
given input current wave is calculated as the superposition of the responses to the
succession of such step functions of various magnitudes, polarities and input times whose
sum closely approximates the desired input waveshape.
For DOD Internal Use ONLY
169 AS/NZS 1768:2007

COPYRIGHT
For manual calculations only very simple models can be handled but triangular waveshapes
can be readily used. It is therefore necessary to consider whether parallel downconductors
can be represented by a single downconductor.
Example D1
A building 35 m high is protected by four vertical air terminals placed at each corner of the
flat roof and interconnected around the perimeter of the roof to four downconductors of
surge impedance 480 that run vertically to earth at each corner. Each earth termination
has two to four driven earth stakes 3 m deep and 6 m apart to achieve a test resistance of
9 to 10 and a combined earthing resistance of 2.5 .
Calculate the first voltage peaks of the response to stroke currents i
a
(t) and i
b
(t) having
waveshapes A and B of Figure D1, respectively.
The system may be modelled as shown in Figure D3. The four air terminals and
downconductors are represented by a single branch of surge impedance 120 and length
40 m (say) terminated in a resistance (or reflectionless infinite branch) of impedance 2.5 .
Nodes 1 and 2 lie at the top and the base of the building respectively.
For convenience of representation take i(t) as positive and adopt units of kiloamperes (kA),
kilovolts (kV), and microseconds (s). Then the surge velocity C may be taken as 300 m/s
and the branch (1, 2) travel time is T = 0.133 s. The reflection coefficient b for surges
arriving at node 2 is evaluated as 0.95 so that 5 percent of the incident surge current at
node 2 leaks to earth with the remainder initially trapped on the protection system. The
reflection coefficient for surges returning to node 1 from 2 is evaluated as unity (the surge
impedance of the lightning discharge channel is neglected for this example). The lattice
diagram is developed as indicated in Figure D3(b).

FIGURE D3 CALCULATION OF SURGE VOLTAGE BY LATTICE DIAGRAM
The surge voltage v(t) at node 1 depends simply on the incident current i(t) until the first
reflection wave arrives at 0.266 s(2T) and is given by
v(t) = Zi(t), for 0 t 2T . . . D2. 2(1)
Because b is negative (0.95) the first reflected voltage wave bv is negative and is doubled
on arrival at the open-circuited node 1, i.e. from the instant 2T, the first reflected wave bv is
again reflected as bv. The voltage at node 1 is varied by 2bv, and is given by
v(t) = Zi(t) + 2bZi(t 2T), for 2T < t 4T
= 120[i(t) 1.9 i(t 2T)], for 2T < t 4T . . . D2. 2(2)
For DOD Internal Use ONLY
AS/NZS 1768:2007 170

COPYRIGHT
For the first stroke current i
a
(t), (where i
a
is in kiloamperes and t is in microseconds) the
current waveshape in the period 0 < t 4T is a ramp of uniform slope:
i
a
(t) = 32.6t . . . D2. 2(3)
The response is a triangular wave given by
v
a
(t) = 120 [32.6t 61.9(t 2T)] . . . D2. 2(4)
for which the peak value occurs at t = 2T as shown in Figure D3(c).
For the subsequent stroke current i
b
(t), the current waveshape reaches its crest value at
t = 0.2 s, which is prior to the arrival of the first reflection wave at t = T. The peak value
occurs at t = 0.2 s, and as the waveshape to this time is a ramp of uniform slope
(i
b
(t) = 200t, t 0.2), the peak value is 4800 kV and the response takes the form shown in
Figure D3(c).
It should be noted that the transient oscillatory response is damped by the discharge to earth
occurring at node 2.
A travelling wave analysis for each stroke current was carried out by computer for a
10-metre structure with combined earthing resistance of 5 , and for a case similar to the
above. The downconductor surge impedance was arbitrarily reduced to 40 to allow for
corona and a lightning discharge channel surge impedance of 1500 (a minimum value)
was used, increasing the damping of the transient oscillations. The response up to 6 s is
shown in Figure D4.
The travelling wave analysis permits calculation of the voltage response at any point on the
LPS because of the distributed constant representation of the system.
D3 SURGE VOLTAGE CALCULATIONS BY LUMPED CIRCUIT
APPROXIMATIONS
The lumped circuit approximation precludes any assessment of the transient voltage
oscillations associated with travelling waves generated on the protection system, however,
elementary calculations generate the base lines about which any transient oscillations occur.
Example D2
A building 35 m high is protected in a similar manner to that of the example in
Paragraph D2.2. Each of four downconductors is assessed as having a length of 40 m and
the inductance in microhenries per metre is given by:
L
1
= 0.2 1n
r
h 2
= 1.5 . . . D3(1)
where
h = the average height above ground of the four downconductors, in metres
r = typical radius of the four downconductors, in metres
For DOD Internal Use ONLY
171 AS/NZS 1768:2007

COPYRIGHT

Curves A: Response to design first stroke waveshape A of Figure D1
Curves B: Response to design subsequent stroke waveshape B of Figure D1
FIGURE D4 VOLTAGES ON LPSsILLUSTRATIVE CASES CALCULATED BY
SIMPLIFIED TRAVELLING WAVE ANALYSIS
For DOD Internal Use ONLY
AS/NZS 1768:2007 172

COPYRIGHT
The total inductance of the protection system is given by:
L =
n
H
L
1
. . . D3(2)
where
H = the average length of downconductors from the point struck to earth, in
metres (this differs from the definition in Clause 4.15.2.3 because the
voltage at intermediate points cannot be calculated for multiple
downconductors using lumped circuit approximations)
n = the number of downconductors connected to a common air terminal
network (spacing of downconductors is assumed large enough for
mutual effects to be neglected)
The capacitance of the system is also neglected.
The equivalent circuit for calculating the voltage at roof level (node 1) and ground level
(node 2) is shown in Figure D5.

FIGURE D5 SIMPLIFIED LUMPED EQUIVALENT CIRCUIT
The voltage at node 1 with respect to remote earth is given by:
v
1
(t) = i(t) R + L
t
t i
d
) ( d
. . . D3(3)
The response to the idealized design stroke currents i
a
(t) and i
b
(t), calculated from this
equation, is shown in Figure D6.
It can be seen by comparison with Figure D4 that the simplified lumped circuit method is an
extremely useful tool in estimating system responses to the various lightning stroke
currents. In the case of first strokes, for which the transient oscillations have effectively
been damped by the time of the current peak, the voltage waveform calculated by this
method is also an adequate basis for estimating the required clearances for isolation.
For DOD Internal Use ONLY
173 AS/NZS 1768:2007

COPYRIGHT

Curves A: Response to design first stroke waveshape A of Figure D1
Curves B: Response to design subsequent stroke waveshape B of Figure D1
FIGURE D6 VOLTAGES ON LPSsILLUSTRATIVE CASES CALCULATED BY
SIMPLIFIED LUMPED CIRCUIT ANALYSIS
For DOD Internal Use ONLY
AS/NZS 1768:2007 174

COPYRIGHT
APPENDIX E
EARTHING AND BONDING
(Informative)
E1 GENERAL
This Appendix provides additional information to Clause 5.5.2 on acceptable methods of
equipotential bonding. It is aimed at providing effective equipotential bonding between
services and the electrical installation earth/local earth.
E2 DEFINITIONS
For the purposes of this Appendix, the following definitions apply, in addition to those of
Clause 1.5.
E2.1 Common bonding network (CBN)
A common bonding network is formed by the interconnection of building steel and the
reinforcing steel in concrete etc. A CBN is an effective method to provide earthing and
bonding.
E2.2 Common utilities enclosure
A common utilities enclosure may contain, in separate compartments, the cabling and
equipment associated with the provision of service for example, electricity,
telecommunications, cable TV and water.
E2.3 Earth potential rise (EPR)
A rise in voltage of an earthing system and the surrounding soil with respect to a distant
earth.
NOTE: EPR is caused primarily when an earth fault on a HV power system produces a current
flow through the earthing system of a HV site.
E2.4 EPR hazard zone
The area around an earthing system bounded by a contour joining all points of EPR equal to
the maximum acceptable voltage below which no special precautions need to be taken to
protect telecommunication services, cabling providers and end-users.
E2.5 Main earthing bar (MEB)
Installed in the main switchboard (MSB), it provides a termination point for the main
earthing conductor, equipotential bonding conductors and protective earthing conductors.
E2.6 Main earthing conductor
The conductor connecting from the MEB to the electricity supply service earthing
electrode.
E2.7 Main switchboard (MSB)
Associated with the electricity supply service to the building. Contains the main earthing
bar (MEB), main neutral earth link and has a connection to the electricity supply service
earthing electrode. Where the multiple earthed neutral (MEN) system of earthing is
employed, a link exists between the MEB and the main neutral link (MEN link).
E2.8 Main distribution frame (MDF)
A distributor that provides, or is intended to provide, an electrical termination point for a
carriers lead-in cabling.
For DOD Internal Use ONLY
175 AS/NZS 1768:2007

COPYRIGHT
E3 HAZARDOUS CONDITIONS ASSOCIATED WITH HV POWER EPR
E3.1 General
Placement of equipment, telecommunications plant and a connection to the structure
earthing system shall not take place where a hazardous EPR exists.
If a building is only supplied by 230 V a.c. single phase power or 400 V a.c. three phase
power , there will be no need to consider EPR unless the proposed installation is within the
EPR hazard zone of a HV site, as determined by AS/NZS 3835, Parts 1 and 2.
E3.2 HV sites of particular concern
A hazardous EPR may occur in the following sites:
(a) In or near a power generating station or power substation.
(b) Near a HV transformer or SWER transformer.
(c) In or near electrical traction systems.
(d) In or near any HV site located in an area of high soil resistivity (e.g. rocky or dry,
sandy terrain).
For requirements for safety in these situations refer to AS/NZS 3835, Parts 1 and 2.
E4 METHODS OF EQUIPOTENTIAL BONDING
E4.1 General
As stated in Clause 5.6.2, the objective of equipotential bonding is to reduce the potential
difference between various parts of the structure and the main earth bar (MEB). To
coordinate with the equipment insulation as specified in IEC 60950.1, the requirement is to
limit the potential difference to less than or equal to 1.5 kV under direct strike conditions.
It is particularly necessary for telecommunication line SPD bonding to ensure coordination
with the requirements of IEC 60950.1. To achieve less than or equal to 1.5 kV, based on the
assumed U = 1 kV per m length for direct lightning strikes, the total length of bonding
conductor between the part being bonded and the MEB should be equal to or less than
1.5 m. This length is easy to achieve if all services enter at the same point in a small
structure.
In Australia, AS 4262.1 allows bonding conductors up to 10 m length, for safety of persons
using a telephone during a lightning storm, to coordinate with the handset breakdown
voltage of 7 kV required by AS/NZS 60950.1. Therefore in a poorly designed new small
structure, or in larger structures, bond wires up to 10 m may be used. However every
attempt should be made to achieve as short a bond wire as possible to ensure maximum
protection of people and equipment. In those exceptional cases where the total bonding
conductor length would to be greater than 10 m, an engineered solution should be applied.
E4.2 Using a bonding bar
To aid in the bonding of the various utility services it is preferable to use a bonding bar.
This bonding bar can be the MEB in the MSB but, for easy access, preferably a separate bar
provided in a common utilities enclosure or mounted as close as possible to the MSB.
Figure E1 shows the bonding bar and the connection of the various bonding conductors.
The bonding conductor requirements are
(a) the bonding bar should be bonded to the MEB in the MSB with a short bonding
conductor, preferably less than 0.5 m long, via a disconnect link;
(b) the MEB should be bonded directly to the electrical installation earth electrode with
as short a conductor as possible and in accordance with AS/NZS 3000; and
For DOD Internal Use ONLY
AS/NZS 1768:2007 176

COPYRIGHT
(c) all other bonding conductors should be kept short, preferably less than 1 m long, and
be bonded to the bonding bar.
NOTE: To achieve a high level of protection for telecommunications services, the total
bonding conductor length, between the telecommunication SPD and the MEB, should be no
more than 1.5 m. Where due to practical reasons, this 1.5 m requirement cannot be met, a
total bonding conductor length of no more than 10 m will provide a reasonable level of
protection for people using a telephone. In those exceptional cases where the total bonding
conductor length would be greater than 10 m, a risk assessment according to AS 4262.1
should be performed.
Where the risk according to AS 4262.1 is considered particularly high, an engineered solution
should be applied which will give protection equivalent to that using short bond wires. Some
examples of engineering solutions which could be applied in these particularly high risk
situations are given in Paragraphs E4.3 and E4.4.
The LPS, antennas and other earthed objects likely to be struck by lightning should be
bonded so as to comply with the requirements of Clause 4.16.2.2. This LPS earth
termination network should be directly bonded to the electrical installation earth electrode
electrode. All bonding conductors should be labelled at the point of connection to the
bonding bar, the main earthing conductor or the electricity supply service earthing
electrode. Bonded joints should be accessible for maintenance.
For DOD Internal Use ONLY
177 AS/NZS 1768:2007

COPYRIGHT

FIGURE E1 BONDING OF SERVICES
NOTES:
1 Refer to Paragraph E4.2 for bonding conductor lengths and other requirements.
2 Refer to AS/NZS 3000 for connection of the MEB to the electricity supply service earthing electrode.
The preferred method for new small buildings, e.g. domestic premises, is to co-locate the
entry of services next to the MSB or to use a combined utilities enclosure, see Figures E2
and E3.
For larger buildings an MDF will normally be installed and it may not be practicable to
achieve a short bonding conductor to the main earthing bar. Ideally, the MDF should be
installed as close as possible to the MSB. However, when the MDF is installed on a
different follor to the MSB, a bond to the nearest switchboard earthing system shall be
installed.
For DOD Internal Use ONLY
AS/NZS 1768:2007 178

COPYRIGHT

NOTE: An LPS earthing system would be bonded to the electricity supply service earthing electrode.
FIGURE E2 CO-LOCATION OF SERVICES NEXT TO A SWITCHBOARD
See AS/ACIF S009 for further methods of connecting the telecommunications SPD to the
MEB.
For DOD Internal Use ONLY
179 AS/NZS 1768:2007

COPYRIGHT

NOTE: An LPS earthing system would be bonded to the electricity supply service earthing electrode.
FIGURE E3 COMBINED UTILITIES ENCLOSURE
E4.3 Use of a common bonding network
A building with a properly bonded reinforced concrete floor effectively provides a common
bonding network (CBN). In this case, bonding can be achieved by bonding the various
services and SPDs directly to the CBN. This connection must be made by connecting
directly to the reinforcing mesh by a suitable method. The mesh must be electrically
continuous between the points of attachment. See Figure E4 which is an example showing a
building with a reinforced concrete floor. In a new building the reinforcing sheets should be
tied together with wire in accordance with Clause 4.5.2.4. In an existing building an attempt
should be made to measure the resistance of the reinforcing steel from one side of the slab
to the other. If continuity of the reinforcing steel is in doubt, e.g. the measurement was
made with the soil wet, a ring earth should be installed and bonded to the slab at every
earthing electrode.
For DOD Internal Use ONLY
AS/NZS 1768:2007 180

COPYRIGHT

NOTE: An LPS earthing system would be bonded to the electricity supply service earthing electrode.
FIGURE E4 COMMON BONDING NETWORK (CBN)
E4.4 Use of a ring earth
A ring earth system may need to be installed for one or more reasons as follows:
(a) To interconnect an LPS electrode system when installed.
(b) To provide effective bonding of services to the MEB/local earth when this cannot be
achieved by one of the preferred methods shown in Figures E2 and E3.
The same ring earth system can be used for multiple purposes. When used as an LPS the
resistance to ground should be 10 or less. When used only to bond incoming services,
there is no maximum resistance specified.
A ring earth, when required, should be provided by installing a bare conductor below
ground, see Figure E5. This conductor should encircle the building(s) and additional
earthing electrodes should be installed at each bonding point to the ring earth.
Where an LPS is installed, a ring earth should be used to interconnect all downconductors
unless the LPS is an integral part of the building. When a ring earth is installed as part of an
LPS system, equipotential bonding of services can be achieved by any one of the methods
shown in Figures E2 to E5 providing the conditions of the chosen method are achieved and
it complies with the requirements of AS/NZS 3000.
For DOD Internal Use ONLY
181 AS/NZS 1768:2007

COPYRIGHT

NOTE: Where an LPS is installed the LPS downconductors would be bonded to this ring earth system. In this
case the 10 resistance requirement applies.
FIGURE E5 RING EARTH
The method in Figure E5 is not as effective as the methods in Figures E2 to E4 but is an
attempt to minimize the potential difference between the telecommunications service SPD,
the MEB and ground.
Other valid engineered options can be used providing they reduce the potential difference to
an acceptable level.
For DOD Internal Use ONLY
AS/NZS 1768:2007 182

COPYRIGHT
APPENDIX F
WAVESHAPES FOR ASSESSING THE SUSCEPTIBILITY OF EQUIPMENT TO
TRANSIENT OVERVOLTAGES DUE TO LIGHTNING
(Informative)
Due to the random nature of lightning disturbances and the variable characteristics of the
transmission media (such as electricity supply and telecommunications service lines) these
transients exhibit wide waveshape variations. However, field and laboratory measurements,
confirmed by theoretical calculations, have led to the selection of a small number of
waveshapes that are representative of the majority of transients encountered in practice. The
value of these standard waveshapes lies in the uniform specification of transient protection
equipment. By using the same waveshapes and conditions to test the equipment,
manufacturers can quote results that may be directly compared between brands, enabling
the user to select an appropriate device.
The most common waveshapes used to represent transients on electricity supply service
lines are the 1.2/50 s voltage waveform and the 8/20 s current waveform. These two
waveshapes are shown in Figure F1, and Table F1 indicates their recommended applications
and magnitudes. Guidance on the use of these waveshapes in the testing of equipment is
given in AS 1931.1.
It is important to note that these waveshapes represent line input conditions expected under
practical conditions. Purchasers of protection equipment should ensure that equipment side
output voltages are reduced to be within the input tolerance envelope of the specified
equipment.
Tests have shown that the tolerable input voltage variations to electronic equipment can be
both time and magnitude dependent. Figure F2 shows two magnitude/time curves derived
for computing equipment. Long period variations can generally be corrected by line
conditioners while fast transients due to lightning need special devices. These usually
comprise non-linear devices to clamp overvoltages and subsequent filtering stages to
modify the residual waveshape. The purpose of such devices is to bring the residual
voltages from a lightning surge to within the safe operating zone.
The test voltage of Figure F1(a) can represent input levels to protection devices. The
residual voltage level is that seen at the output, or equipment side of the protection device,
when the impulse is applied at the crest of the a.c. voltage. This voltage level will be a
function of both the input pulse characteristics and the technical performance of the
protection device under test.
For DOD Internal Use ONLY
183 AS/NZS 1768:2007

COPYRIGHT

FIGURE F1 STANDARD UNIDIRECTIONAL WAVESHAPES

FIGURE F2 TYPICAL VOLTAGE/TIME TOLERANCE OF COMPUTING EQUIPMENT
* See Paragraph G2, Ref 13.
For DOD Internal Use ONLY
AS/NZS 1768:2007 184

COPYRIGHT
TABLE F1
RECOMMENDED APPLICATION FOR WAVESHAPES OF FIGURE F1
Location (see Figure F3)
Category Description
Waveshape
Medium
exposure peak
amplitude
Type of load
Figure F1(a) 6 kV high impedance A Long final subcircuits and
electricity supply outlets
Figure F1(b) 500 A low impedance
Figure F1(a) 6 kV high impedance B Major submains, short final
subcircuits and load centres
Figure F1(b) 3 kA low impedance
Figure F1(a) 6 kV* high impedance C1 Service entrance, other than
below
Figure F1(b) 10 kA low impedance
C2 Service entrance, building fed
by long overhead service lines,
or is a large industrial or
commercial premises
Figure F1(b) 20 kA low impedance
C3 Service entrance, building in a
high lightning area, or fitted
with a LPS
Figure F1(b) 50 kA low impedance
* The 6 kV amplitude shown here is a minimum value. Higher amplitudes may be used depending on generator
construction.
NOTES:
1 These test waveshape amplitudes were considered when formulating the recommended SPD surge ratings
of Table 5.1. In general, an SPD selected in accordance with Table 5.1 will handle a considerable number
of the corresponding test impulse amplitudes listed above.
2 Categories C2 and C3 do not show a voltage waveshape, as this large value current impulse is intended to
provide a measure of the SPD robustness, rather than allow a precise measurement of the let-through
voltage. See discussion of U
p
in Clause 5.6.3.5.
3 For testing the performance of SPDs on long, twisted pair telecommunications lines, a standard 10/700 s
voltage surge waveform is often used. The standard 10/700 s voltage surge generator is defined in ITU-
T-Recommendation K.44 (Figure A.3-1).
For DOD Internal Use ONLY
185 AS/NZS 1768:2007

COPYRIGHT

FIGURE F3 LOCATION CATEGORIES FOR APPLICATION
OF THE WAVESHAPES IN TABLE F1
For DOD Internal Use ONLY
AS/NZS 1768:2007 186

COPYRIGHT
APPENDIX G
REFERENCED DOCUMENTS
(Informative)
G1 REFERENCED STANDARDS AND REGULATORY DOCUMENTS
AS
1074 Steel tubes and tubulars for ordinary service
1214 Hot-dip galvanized coatings on threaded fasteners (ISO metric coarse
thread series)
1222 Steel conductors and staysBare overhead
1222.1 Part 1: Galvanized (SC/GZ)
1397 Steel sheet and stripHot-dipped zinc-coated or aluminium/zinc-coated
1432 Copper tubes for plumbing, gas fitting and drainage applications
1531 ConductorsBare overheadAluminium and aluminium alloy
1565 Copper and copper alloysIngots and castings
1566 Copper and copper alloysRolled flat products
1746 ConductorsBare overheadHard-drawn copper
1874 Aluminium and aluminium alloysIngots and castings
1931 High voltage testing techniques
1931.1 Part 1: General definitions and test requirements
2187 ExplosivesStorage, transport and use
2187.2 Part 2: Use of explosives
2239 Galvanic (sacrificial) anodes for cathodic protection
2738 Copper and copper alloysCompositions and designations of refinery
products, wrought products, ingots and castings
2832 Cathodic protection of metals
2832.1 Part 1: Pipes and cables
2832.2 Part 2: Compact buried structures
4070 Recommended practices for protection of low-voltage electrical
installations and equipment in MEN systems from transient overvoltages
4262 Telecommunication overvoltages
4262.1 Part 1: Protection of persons
4262.2 Part 2: Protection of equipment
AS/NZS
1020 The control of undesirable static electricity
1567 Copper and copper alloysWrought rods, bars and sections
1866 Aluminium and aluminium alloysExtruded rod, bar, solid and hollow
shapes
2053 Conduits and fittings for electrical installations (all Parts)
2430 Classification of hazardous areas (all Parts)
3000 Electrical installations (known as the Australian/New Zealand Wiring
Rules)
3004 Electrical installationsMarinas and pleasure craft at low-voltage
For DOD Internal Use ONLY
187 AS/NZS 1768:2007

COPYRIGHT
AS/NZS
3100 Approval and test specificationGeneral requirements for electrical
equipment
3191 Electric flexible cords
3835 Earth potential riseProtection of telecommunications network users,
personnel and plant
3835.1 Part 1: Code of practice
3835.2 Part 2: Application guide
4853 Electrical hazards on metallic pipelines
5000 Electric cablesPolymeric insulated
5000.1 Part 1: For working voltages up to and including 0.6/1 (1.2) kV
60950 Information technology equipmentSafety
60950.1 Part 1: General requirements
NZS
3501 Specification for copper tubes for water, gas, and sanitation
4403 Code of practice for the storage, handling, and use of explosives
(Explosives Code)
IEC
60950 Information technology equipmentSafety
60950.1 Part 1: General requirements
61643 Low-voltage surge protective devices
61643-1 Part 1: Surge protective devices connected to low-voltage power
distribution systemsRequirements and tests
61643-12 Part 12: Surge protective devices connected to low-voltage power
distribution systemsSelection and application principles
62305 Protection against lightning
62305.1 Part 1: General principles
62305.2 Part 2: Risk management
62305.3 Part 3: Physical damage to structures and life hazard
62305.4 Part 4: Electrical and electronic systems within structures
ISO
10134 Small craftElectrical devicesLightning-protection systems
BS
1473 Specification for wrought aluminium and aluminium alloys for general
engineering purposesRivet, bolt and screw stock
6651 Code of practice for protection of structures against lightning
ANSI/NFPA
780 Standard for the installation of lightning protection systems
ASTM
A240M Standard specification for chromium and chromium-nickel stainless steel
plate, sheet and strip for pressure vessels and for general applications
AUSTEL
AS/ACIF S009 Installation requirements for customer cabling (Wiring Rules)
ITU-T
K.44 Resistibility tests for telecommunication equipment exposed to
overvoltages and overcurrentsBasic recommendation
K.66 Protection of customer premises from overvoltages
For DOD Internal Use ONLY
AS/NZS 1768:2007 188

COPYRIGHT
UL
1449 Standard for Transient Voltage Surge Suppressors
G2 REFERENCED TECHNICAL PAPERS AND PUBLICATIONS
1 HOLLE, R., LOPEZ, R.E. and ZIMMERMANS, D. Updated recommendations for
lightning safety1998. Bulletin of the American Meteorological Society. 1999, vol 80,
1999, pp 2035-2041; see also HOLLE. R et al. Distances and times between flashes in
a storm. Proc. Int. Conf. on Lightning and Static Electricty (ICOLSE). Blackpool Set
2003. pp. 8.
2 ANDREWS, C.J., COOPER, M.A., DARVENIZA, M. and MACKERRAS, D. (Eds),
Lightning injury: Electrical, medical and legal aspects. Baton Rouge, Florida: CRC
Press, 1992. pp. 32.
3 HARTANO, Z.A. and ROBIAH, I. The collection surface concept as a reliable
method for predicting lightning strike location. Proc. 25th ICLP, Rhodes, Greece,
2000. pp. 328-333.
4 HARTANO, Z.A., ROBIAH, I. and DARVENIZA, M. A database of lightning
damage caused by bypasses of air terminals on buildings in Kuala Lumpur. Proc. 6th
SIDPA, Santos, Brazil, 2001. pp. 211-216.
5 DALESSANDRO, F. Improved placement of protective lightning rods on structures.
International Conference on Grounding and Earthing and 1st International Conference
on Lightning Physics and Effects. Brazil. 2004.
6 DARVENIZA, M. A modification to the rolling sphere method for positioning air
terminals for lightning protection of buildings. Proc. 25th ICLP, Rhodes, Greece,
2000. pp. 904-908.
7 THOMSON, E.M. A critical assessment of the U.S. code for lightning protection of
boats. IEEE Transactions on Electromagnetic Compatibility. Vol 33, No. 2. 1991, pp
132-138.
8 RAKOV, V.A. and UMAN, M.A. Lightning: Physics and Effects. Cambridge
University Press. Cambridge USA. 2003 (Chapter 4.2).
9 KULESHOV, Y. and JAYARATNE, E.R. Estimates of lightning ground flash density
in Australia and its relationship to thunder-days. Aust. Met. Mag. 53, 2004. pp 189-
196.
10 NASA website, http://thunder.msfc.nasa.gov/data/OTDsummaries/
11 KULESHOV, Y., MACKERRAS, D. and DARVENIZA, M. Spatial distribution and
frequency of lightning activity and lightning flash density maps for Australia. Journal
of Geophysical Research. Vol 111, D19105, doi:10.1029/2005JD006982. 2006.
12 DALESSANDRO, F., JUDSON, W. AND HAVELKA, M. Long-term study of a
ground enhancing material. International Conference on Grounding and Earthing and
1st International Conference on Lightning Physics and Effects. Brazil. 2004.
13 KEY, T.S. Diagnosing power quality-related computer problems. IEEE Transactions
on Industry Applications. Vol 1A-15, No. 4, July/August 1979, pp. 381-384.
For DOD Internal Use ONLY


Standards Australia
Standards Australia is an independent company, limited by guarantee, which prepares and publishes
most of the voluntary technical and commercial standards used in Australia. These standards are
developed through an open process of consultation and consensus, in which all interested parties are
invited to participate. Through a Memorandum of Understanding with the Commonwealth
government, Standards Australia is recognized as Australias peak national standards body.
Standards New Zealand
The first national Standards organization was created in New Zealand in 1932. The Standards
Council of New Zealand is the national authority responsible for the production of Standards.
Standards New Zealand is the trading arm of the Standards Council established under the Standards
Act 1988.
Australian/New Zealand Standards
Under a Memorandum of Understanding between Standards Australia and Standards New Zealand,
Australian/New Zealand Standards are prepared by committees of experts from industry,
governments, consumers and other sectors. The requirements or recommendations contained
in published Standards are a consensus of the views of representative interests and also take
account of comments received from other sources. They reflect the latest scientific and industry
experience. Australian/New Zealand Standards are kept under continuous review after publication
and are updated regularly to take account of changing technology.
International Involvement
Standards Australia and Standards New Zealand are responsible for ensuring that the Australian
and New Zealand viewpoints are considered in the formulation of international Standards and that
the latest international experience is incorporated in national and Joint Standards. This role is vital
in assisting local industry to compete in international markets. Both organizations are the national
members of ISO (the International Organization for Standardization) and IEC (the International
Electrotechnical Commission).
Visit our web sites
www.standards.org.au www.standards.co.nz
www.standards.com.au
For DOD Internal Use ONLY




GPO Box 476 Sydney NSW 2001
Administration
Phone (02) 8206 6000
Fax (02) 8206 6001
Email mail@standards.com.au
Customer Service
Phone 1300 65 46 46
Fax 1300 65 49 49
Email sales@standards.com.au
Internet www.standards.org.au
Level 10 Radio New Zealand House
155 The Terrace Wellington 6001
(Private Bag 2439 Wellington 6020)
Phone (04) 498 5990
Fax (04) 498 5994
Customer Services (04) 498 5991
Information Service (04) 498 5992
Email snz@standards.co.nz
Internet www.standards.co.nz
ISBN 0 7337 7967 0 Printed in Australia