1) HT PANEL 110 V DC LOAD (CONTINIOUS) :

TOTAL NO OF FEEDER 13 13 13 13 13 LOAD(VA) UNIT ITEM 2.5 10 20 10 5 TOTAL LOAD(VA) 80.5 130 260 130 65

S.NO

DESCRIPTION Indicating lamps for HV sw.bd (33kV) Numerical relay Aux.relay Anti pumping relay Timer Annunciation panel loads

QTY

1 2 3 4 5

6 per feeder 1 per feeder 2 per bkr feeder 1 per feeder 1 per feeder 1 no per transformer feeder

10

70

2) HT PANEL 110 V DC LOAD (INSTANTANIOUS,TRIP) :

S.NO

DESCRIPTION

QTY

TOTAL NO OF PANEL

LOAD(VA) UNIT ITEM

TOTAL LOAD(VA)

HV incomer bkr tripping coil

1 no. per feeder 1 no. per feeder 1 no. per feeder 1 no per incomer 1no per incomer 1no per incomer

13 150 13 40

1950

Lockout relay Trip ckt supervision relay Hooter

520

13

40

520

50

100

Under voltage relay

40

80

Over voltage relay

40

80

3) HT PANEL 110 V DC LOAD ( INSTANTANIOUS,CLOSE ) :

S.NO

DESCRIPTION Closing of main HV incomer bkr Breaker spring charging motor

QTY 1 no. per feeder 1 no. per feeder

TOTAL NO OF FEEDER 13

LOAD(VA) UNIT ITEM 150

TOTAL LOAD(VA) 1950

13

150

1950

1) Total continious load (110 V DC System) on HT Panel of 33 KV = 735.5 VA 2) Total instantaneous (tripping) load (110 V DC System) on HT Panel of 33 KV = ( Tripping coil load + Other than tripping coil load ) = ( 1950 + 1300 ) = 3250 VA 3) Total instantaneous (closing) load (110 V DC System) on HT Panel of 33 KV = 3900 VA

S.NO

DESCRIPTION Indicating lamps for HV sw.bd (33kV) Numerical relay Aux.relay Anti pumping relay Annunciation panel loads

QTY

TOTAL NO OF FEEDER 15 15 15 15

LOAD(VA) UNIT ITEM 2.5 10 20 10

TOTAL LOAD(VA) 150 150 300 150

1 2 3 4

4 per feeder 1 per feeder 2 per bkr feeder 1 per feeder 1 no per transformer feeder

10

50

1A) LT PANEL(415 V PCC) 110 V DC LOAD (CONTINIOUS) :

2A) LT PANEL(415 V PCC) 110 V DC LOAD (INSTANTANIOUS,TRIP) :


S.NO DESCRIPTION QTY TOTAL NO OF PANEL LOAD(VA) UNIT ITEM TOTAL LOAD(VA)

LV incomer bkr tripping coil

1 no. per feeder 1 no. per feeder 1 no. per feeder 1no per incomer

15 150 15 40

2250

Lockout relay Trip ckt supervision relay Under voltage relay

600

15

40

600

40

80

4) Total continious load (110 V DC System) on LT Panel (415 V PCC) = 800 VA 5) Total instantaneous (tripping) load (110 V DC System) on LT Panel (415 V PCC) = ( Tripping coil load + Other than tripping coil load ) = ( 2250 + 1280 ) = 3530 VA 1C) LT PANEL(415 V MCC INCOMER) 110 V DC LOAD (CONTINIOUS) :
DESCRIPTION Indicating lamps for LT (415 V) Numerical relay Aux.relay Anti pumping relay QTY TOTAL NO OF FEEDER 2 2 2 2 LOAD(VA) UNIT ITEM 2.5 10 20 10 TOTAL LOAD(VA) 20 20 40 20

S.NO

1 2 3 4

4 per feeder 1 per feeder 2 per bkr feeder 1 per feeder

2C) LT PANEL(415 V MCC) 110 V DC LOAD (INSTANTANIOUS,TRIP) :


TOTAL NO OF PANEL LOAD(VA) UNIT ITEM TOTAL LOAD(VA)

S.NO

DESCRIPTION

QTY

LV incomer bkr tripping coil

1 no. per feeder 1 no. per feeder 1 no. per feeder 1no per incomer

2 150 2 40

300

Lockout relay Trip ckt supervision relay Under voltage relay

80

40

80

40

80

6) Total continious load (110 V DC System) on LT Panel (415 V MCC) = 100 VA 7) Total instantaneous (tripping) load (110 V DC System) on LT Panel (415 V MCC) = ( Tripping coil load + Other than tripping coil load ) = ( 300 + 240 ) = 540 VA

a) Total continious load = ( 735.5 + 800 + 100 ) = 1635.5 VA b) It is assumed that maximum 13 breaker will trip at a time,so total wattage consumed for this is ( 13 x 150) or 1950 VA. So, total tripping load = ( Wattage consumed by 13 nos of tripping coil + other than tripping coil load liable for instantanious trip) = 1950 + ( 1300 + 1280 +240) = 4770 VA

Total load VA = Continious load + Total tripping load = (1635.5 + 4770) VA = 6405.5 VA Total load current = (6405.5 / 110) = 58.23 Amp Taking 10 % design margin load current = 58.23 + (58.23 x 0.10 ) = 64.05 Amp