You are on page 1of 10

Power Distribution Unit PDU Model TAB-DC

Power Distribution Unit PDU Model TAB-DC

2012-04-24

HUAWEI Confidential

Page1, Total10

Power Distribution Unit PDU Model TAB-DC

Prepare d by Reviewe d by Reviewe d by Approve d by:

Wireless Technical Sales Department

Date Date Date Date

2009-03-17

2012-04-24

HUAWEI Confidential

Page2, Total10

Power Distribution Unit PDU Model TAB-DC

Contents

5.1 Engineering Specifications of the PDU...9 5.2 Electrical Specifications of the PDU...9 5.3 Surge Protection Specifications of the PDU..10

2012-04-24

HUAWEI Confidential

Page3, Total10

Power Distribution Unit PDU Model TAB-DC

Figures

2012-04-24

HUAWEI Confidential

Page4, Total10

Power Distribution Unit PDU Model TAB-DC

Tables

1. User Guide
2012-04-24 HUAWEI Confidential Page5, Total10

Power Distribution Unit PDU Model TAB-DC

1.1 Purpose This document describes the Power Distribution Unit (PDU) Model TAB-DC in terms of its functions, structure, and technical specifications.

2. Functions of Power Distribution Unit PDU


The Power Distribution Unit provides power supply solutions to Huawei Wireless products, and it also provides DC power distribution and surge protection functions. The Power Distribution Unit (PDU) provides the following functions: Providing twelve -48 V DC outputs divided into two banks to meet multiple power distribution requirements in scenarios of distributed and separated base stations Providing twelve 10 Amp outputs (BTicino Mod F/B 10) divided into two banks to meet power distributions requirements in scenarios of distributed and separated base stations Providing surge protection through the DC surge protection unit (Atlantic Scientific Mod MA15) connected to bank A. Providing four free spaces for additional breakers units.

3. Appearance of Power Distribution Unit PDU


The

2012-04-24

HUAWEI Confidential

Page6, Total10

Power Distribution Unit PDU Model TAB-DC

PDU is a 19 inch / 3U device 250A 16 way.

Figure 1 Appearance of the PDU

PDU Board.pdf

4. Principles of the PDU Model TAB-DC


This describes the power distribution principles and surge protection principles of the PDU Model TAB-DC. 4.1 Internal Structure of the PDU

Figure 2 Internal Structure of the PDU

(1) Positive copper bar (2) DC input power wiring terminal (3) DC output MCB (Breakers)
2012-04-24 HUAWEI Confidential Page7, Total10

Power Distribution Unit PDU Model TAB-DC

(4) DC Surge protector (5) Bank A (6) Bank B (7) Ground Terminal (8) Cable organizer (9) Stoppers for breakers

4.2 Power Distribution Principles of the PDU Model TAB-DC The power distribution principles of the PDU are as follows: The input (+) power is led into the PDU Model TAB-DC through the input terminal 35mm and then divided into 12 outputs through the copper bar to supply power to power consumption devices. The input (-) power is led into the PDU Model TAB-DC directly through the breakers The grounding of the PDU Model TAB-DC is implemented through the XXX grounding screw. For further information about breakers:

IT B icino M T btdin..pdf

4.3 Surge Protection Principle of the PDU Model TAB-DC The surge protector principle of the PDU is as follow: The surge protector unit provides protection to Bank A where NodeB and RRU are connected. For further information about surge protector:

ASC-MA15.pdf

5. Technical Specifications of the PDU Model TAB-DC


2012-04-24 HUAWEI Confidential Page8, Total10

Power Distribution Unit PDU Model TAB-DC

The technical specifications of the PDU consist of the engineering specifications, electrical specifications and surge protection specifications. 5.1 Engineering Specifications of the PDU This describes the engineering specifications of the PDU in terms of the weight, dimensions, and installation modes.

Table 1 Engineering specifications of the DCDU-03 Item Weight Dimensions (width x height x depth) Installation mode Specification 2.2 kg 483 mm 133 mm 140 mm Remarks -

In a 19-inch rack The PDU Model TAB-DC is installed in a space 19-inch space; the space for the two mounting ears is included into the board. The panel of the PDU occupies 3 unit racks.

Protection class Working temperature

IP20 -40C to +70C

5.2 Electrical Specifications of the PDU The electrical specifications of the PDU consists of the DC input characteristics and DC output characteristics.

Table 2 Electrical specifications of the DPU Item DC Sub-Item Rated input voltage -48 V DC
HUAWEI Confidential

Specification

Remarks Page9, Total10

2012-04-24

Power Distribution Unit PDU Model TAB-DC

Item input

Sub-Item

Specification

Remarks -

Input voltage range -38.4 V DC to -57 V DC Maximum input current 250 A -48 V DC -38.4 V DC to -57 V DC 10 A Over current protection and short-circuiting protection enabled for the Bank A outputs

DC output

Rated output voltage Output voltage range Output MCB configurations Output protection

5.3 Surge Protection Specifications of the PDU The PDU provides surge protection for the DC input power. Table 3 Surge protection specifications of the DCDU-03 Item Surge protection class Specification Protection requirement (8/20 s): 18 KA Maximum leakage current: <0.3 mA Maximum continuous operating current: 15A Maximum attenuation (typical): -55dB@100MHz Weight: 100gr Dimensions (w,d,h): 79mm x 25mm x 93mm