963 v3 Engineering Course

Course revision version 003

Introductions
In order that you may get to know other delegates on the course, and to enable the tutor to gather some relevant information about your own situation, we would like you to introduce yourself. It would be helpful if, in your introduction, you would address the following.

Your name Your company and nature of business Your position and duties within the company Your reasons for attending the course Previous Trend courses attended

Trend - 963 v3 Eng -Rev 03

Trend Control Systems Limited


Trend is one of the worlds leading Building Management Systems manufacturers, with a worldwide distribution and support network covering over 50 countries. Its fully integrated control solutions are able to meet the most complex requirements of modern buildings. Founded in 1980, Trend has undergone rapid and consistent growth, achieving turnover in excess of $90m in 2005 (product supply). Trend is a BSI registered company, complying with the requirements of BS EN ISO 9001: 2000. This quality assurance standard covers the sales, marketing, design, manufacture and support of Building Management Systems. Through close control and monitoring of heating, ventilation, air conditioning and other building services, Trend systems are able to minimise energy consumption and maintain consistently comfortable conditions as well as bringing other key benefits such as lower plant maintenance costs. Systems are to be found in virtually every type of non-residential building, from schools, hospitals and leisure centres to office blocks, shops and factories. Suitable for the largest building complexes and multisite applications, they are still cost-effective even in very small premises. Trend control systems are supplied, engineered and commissioned by approved systems integrators. A significant number of these specialist controls companies have qualified as Trend Technology Centres, a status they have achieved by demonstrating they can meet defined high standards of workmanship, contract management, documentation and quality control. All are subject to regular audit to ensure these standards are being maintained.

Trend - 963 v3 Eng -Rev 03

Trend Control Systems Limited


Trend understands that every business has unique requirements, so our philosophy of service in the UK is to offer flexibility and choice through a range of tailored Service Level Agreements (SLAs). Supported 24/7 by a nationwide network of skilled engineers, we offer a range of services which are available to both installers and end users and cover both Trend and other manufactured systems. Furthermore, the ongoing monitoring of energy consumption and environmental conditions optimizes plant operation and reduces associated energy costs whilst ensuring that comfort conditions are maintained. The Trend package of advanced products, specialist services and a tried and tested route to market, not only provides systems that are fit for purpose but also ensures lowest lifetime costs. For more information please visit www.trendcontrols.com

Trend - 963 v3 Eng -Rev 03

Copyright
Copyright: Trend Control Systems Limited, Horsham, W. Sussex All rights reserved. This presentation contains proprietary information which is protected by copyright. No part of this presentation may be reproduced, transcribed, stored in a retrieval system, translated into any language or computer language, or transmitted in any form whatsoever without the prior consent of the publisher. For information contact: Trend Control Systems Limited, P.O. Box 34, Horsham, W. Sussex, RH12 2YF NOTICE: Trend Control Systems Limited makes no representations or warranties of any kind whatsoever with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness for any particular purpose. Trend Control Systems Limited shall not be liable for any errors contained herein or for incidental or consequential damages in connection with the furnishing, performance or use of this material. Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes in the content hereof without obligation to notify any person of such revisions or changes.

Trend - 963 v3 Eng -Rev 03

Course Aims and Objectives


This course has been designed to :1. Demonstrate the main engineering features of 963. 2. Give an understanding of the need to plan a new 963 project. 3. Enable the delegate to build a 963 project using many of the 963 features.

Trend - 963 v3 Eng -Rev 03

Our Project.

Trend - 963 v3 Eng -Rev 03

Exercises

Trend - 963 v3 Eng -Rev 03

Section 1 Getting Started

Aims: To enable the Engineer to Describe the 963 Installation process. Describe the Information Centre and its use Describe the Crypkey Site Keys and Site Codes Describe the 963 directory structure.

Objectives: By the end of the section the Engineer should be able to Install Trend 963 Supervisor Software Locate various files within the 963 directory. Access the Information center for specific information. Locate and verify license details.

Trend - 963 v3 Eng -Rev 03

Section 1 963 Options


963 is available in a number of different options, with additional functionality that can be unlocked, dependant on the options that have been purchased.

963 Lite

Standard version Standalone Supervisor

963 Server

Server\Client function over Ethernet

963 SNMP

Specialist retransmission of alarms using Simple Network Management Protocol

963 SMS

Alarm retransmission and text messaging to GSM mobile phones using Short Message Service (requires 2nd com port on PC for SMS modem).

963 Secure

Extra security and auditing for compliance with 21 CFR (part 11) also Mean Kinetic Temperature sensors.
10

Trend - 963 v3 Eng -Rev 03

Section 1 Installing 963

For our course we are going to be using 963 Server, this has been pre-installed for you but well now have a look at the installation process.

The first thing to do is to place the 963 disc into the CD drive, the install will then start automatically.

Trend - 963 v3 Eng -Rev 03

11

Section 1 Installing 963


The First window that you see, lets you select your language. Make your selection, then click NEXT.

963 will begin to load the installation files, which may take a few minuets.

Trend - 963 v3 Eng -Rev 03

12

Section 1 Installing 963


Once all the install files are loaded, you are prompted to continue with the installation.

Click NEXT

You will then be presented with the Software Licence agreement and will be asked to confirm that you accept the terms of the agreement!

Click YES

Trend - 963 v3 Eng -Rev 03

13

Section 1 Installing 963


The next window, asks you to enter your customer information.

Fill in the first two fields, with your name and company details. The serial number can usually be found on the back of the CD case. Store the disc and case in a safe place when you have completed the installation.

Trend - 963 v3 Eng -Rev 03

14

Section 1 Installing 963


Now you can specify where you want 963 to install, we will use the default destination :C:\Program Files\Trend Control Systems\963

Click NEXT or browse to an alternative install location. The last window lets you make some changes with regard to program groups and shortcuts. We will accept the default settings, so click NEXT and 963 will complete the installation.

Trend - 963 v3 Eng -Rev 03

15

Section 1 Installing 963


Finally, you will need to restart your PC.

Click FINISH to restart the computer.

Trend - 963 v3 Eng -Rev 03

16

Section 1 Running 963


Once your PC has restarted, Log on to Windows.

From the Windows Start button, select Programs, then Trend Control Systems, then 963.

The Supervisor Software will load and you will need to complete the Licence details.

Trend - 963 v3 Eng -Rev 03

17

Section 1 Crypkey
A unique Site Key is required to unlock the Crypkey protection. The Site Key is generated by Trend Technical Services The 963 is unlocked for a specified length of time and number of users, also with any additional variants that have been purchased, e.g. 963 Sever or SMS

Trend - 963 v3 Eng -Rev 03

18

Section 1 Licensing 963


The licence details need to be sent to Trend Middle East, who will use the information to produce the unlock code or Site Key. Input the Site Key, then click the update button. If you have typed in the correct Site Key, the Status field will change to display the 963 variant that has been unlocked. The Crypkey can be accessed from the Information Center.

Trend - 963 v3 Eng -Rev 03

19

Section 1 The Information Center


The information Center starts running whenever 963 is started.

The Information Center can be accessed by pressing the F1 key or selecting it from View on the Menu bar. The Information Center is designed to let you see what 963 is doing e.g. Starting up, downloading time changes etc. Icons allow access to further system information and status, depending on user access levels.

963 Help

Crypkey

Comms. displays

Script controls

System Information

Trend - 963 v3 Eng -Rev 03

20

Section 1 Directory Structure

The files that 963 uses need to be stored within the 963 directory. 963 uses specific sub directories for specific types of files. Usefully, you can select graphic files from anywhere else on your computer and 963 will copy them into the appropriate sub directory for you.

Trend - 963 v3 Eng -Rev 03

21

Section 1 Folders and File Types

Animation files are stored here in individual sub directories. Each animation has a set of pictures and a control file. Backdrops holds the background pictures used in schematic pages. The size of these pictures determines the size of the schematic page bmp is used to store pictures used on the schematic pages, some supplied plant graphics are stored in the Samples sub directory

Trend - 963 v3 Eng -Rev 03

22

Section 1 Folders and File Types

Database holds the working copy of the SQL database file- i96x_data.mdf. Copies are made automatically when 963 starts up Pages is where the schematic page layouts are stored. Each page has a .tss file which contains references to all the objects that make up the page. Scripts are stored here, they are text files that can be used to combine 963 actions and text comms to change system settings.

Trend - 963 v3 Eng -Rev 03

23

Section 2 Security and Logging in


Aims: To introduce the Engineer to : Security and PINs in Trend controllers. The additional Security features of 963 Secure. Strong passwords. The 963 Database Password Objectives: By the end of the section the Engineer should be able to : Log in and Log out of 963. Describe how 963 is secured. Add a New System Administrator. Add and edit a workgroup within 963.

The following parts of 21 CFR Part 11 are covered in this section. 11.10(d),11.10(g),11.100(a), 11.200(a),11.300(a),11.300(b), 11.300(c),11.300(d)
24

Trend - 963 v3 Eng -Rev 03

Section 2 Installed Users

When 963 installs, 2 users are created. The System Administrator is a Super User, pre configured with all 963 Functionality and a PIN level of 99. The Default Password for the System Administrator is Trend, The Default User has no 963 functionality and a PIN level of -1. The Default user logs in automatically when every body else is logged out

Trend - 963 v3 Eng -Rev 03

25

Section 2 Security with PINs

Trend controllers can be configured with their own security protection by way of Personal Identification Numbers or PINs. If Security is configured in a controller, then the Supervisor must send a valid PIN any time an adjustment is sent. This PIN is then checked against the security that is assigned to Knobs and Switches etc in the controller, to see if the adjustment is allowed.

Trend - 963 v3 Eng -Rev 03

26

Section 2 Security, What happens with PINs ?


In the IQ2 controller, there are 6 Users that can be configured, if one or more User is configured in a controller then the Supervisor must send a valid PIN otherwise adjustments will be disallowed. Here we can see 2 users that have been configured in a controller.

User 1 has the highest possible Level of 99 so will have access to all settings. His PIN is 1234.

User 2 has a lower level, so has less access to adjustments. His PIN is 8000.

Trend - 963 v3 Eng -Rev 03

27

Section 2 Security, What happens with PINs ?


Here we can see Knob 7 in a controller, it has been set to have a PIN Level of 50. A User trying to adjust this Knob would need to have Level of 50 or higher.

When an adjustment is made to a Secured controller, the user must use a PIN Level equal to or greater than the PIN Level set on the module.

If we configure 963 with a Level 99 PIN, then ALL adjustments made using the 963 will be accepted by the controller
1234

Trend - 963 v3 Eng -Rev 03

28

Section 2 Security, PINs


To Configure 963 with a PIN In the Navigator right click on the required level at which to apply the PIN; Site, LAN or Device.

Select Set Pin from the popup menu. Type in a Level 99 PIN (as found in a Controller).

1234

Click OK

Trend - 963 v3 Eng -Rev 03

29

Section 2 Security, PINs

The 963 is now configured so that Secured controllers will accept all adjustments from the Supervisor.

So when we come to engineer the 963 project we need to think about who is going to be using the 963 and what they are allowed to do with it.

This will be become the method of providing the Security on the system and this is controlled by a structure of Workgroups and Users.

Trend - 963 v3 Eng -Rev 03

30

Section 2 - Workgroups and Users

PIN level 10

The Workgroups can have different PIN Levels, the PIN Level of the Workgroup, operates

PIN level 50

within 963 to define what objects the User can access. Some of the Workgroups other properties define which Modes of

PIN level 80

963 can be accessed, whether the operator can resize or

PIN level 99

shutdown the 963 and if the operator can engineer the 963.

Trend - 963 v3 Eng -Rev 03

31

Section 2 PINs Summery


The PIN levels applied to the Workgroups control which schematic objects are available to the users as well as which adjustments can be made in the controller. A user can only view/access schematic objects which have a PIN level equal to or lower than the PIN level of the Workgroup they are using. The 963 sends a valid Level 99 PIN with every adjustment, we control the access to the adjustment with PIN levels applied to Schematic objects

Trend - 963 v3 Eng -Rev 03

32

Section 2 - Overview of Security in 963

Users have only a name and a password.

In 963 Secure these passwords need to be Strong Passwords!

When Users log out or are timed out, 963 logs in as the Default User.

Trend - 963 v3 Eng -Rev 03

33

Section 2 - Strong Passwords!


When using 963 Secure, To comply with 21 CFR Part 11 Passwords must be :1) 2) 3) 4) Unique to each operator A large set of characters i.e. 7 or 8 Different from previous passwords Not identifiable to the particular individual i.e. not a telephone number or date of birth etc.

Other versions of 963 dont require Strong Passwords, but it always good practice to use them !

Trend - 963 v3 Eng -Rev 03

34

Section 2 - Passwords in 963 Secure


To comply with 21 CFR Part 11 :-

Passwords also need to have a fixed life span, so can be set to expire after a set time period e.g. 6 months. When a password is expired, the user will be notified when they login. They will then be forced to enter a new password before they can access 963.

Trend - 963 v3 Eng -Rev 03

35

Section 2 - System Administrators


A new level of Workgroup (System Administrators) has been added to 963, which was previously only part of 963 Secure. In 963 Secure, Security tasks can only be performed by a member of the System Administrator Workgroup. These are :-

Add, delete edit other users. Manually back up a database. Change a Workgroups access rights. Change a User password. Delete historic records. Expire a user. Unlock a User. Unlock a System Administrator.

Trend - 963 v3 Eng -Rev 03

36

Section 2 - Exercise Password Properties

1)

Log on as the System Administrator, password Trend2009 (remember passwords are case sensitive).

2)

Right click on the System Administrator Workgroup and select properties. This will display the Workgroup Information dialogue box.

3)

Click on the System Administrator tab.

Trend - 963 v3 Eng -Rev 03

37

Section 2 - Exercise - Password Properties

Set up Strength of the password as shown opposite:6

1) 2) 3) 4)

Number of password retries before password is disabled = 6. Minimum password length = 4. Force users to re-enter password when acknowledging alarms = off Set password life, in Days, Months and Years. = 1 year.

The properties configured here are cascaded down to all workgroups.

More than one user can and should be set up as a System Administrator.
Trend - 963 v3 Eng -Rev 03

38

Section 2 - 963 Users


When new users are created by a System Administrator, they are given a password, this password can only be used once. This is so that the System Administrator is not aware of any users password.

When the user logs in for the first time they will be prompted to change the password.

Users must be aware that they are responsible for keeping the passwords secure, if they think their password has been compromised then they must change it (Part 11.300 (c)).

Trend - 963 v3 Eng -Rev 03

39

Section 2 - To Unlock a User


If a user enters the password incorrectly x times then the following appears.

Locked users are indicated in 963 by this 1) Log in as a member of the System administrators workgroup. 2) 3)

user icon.

Right click on the user in the navigator. Select Unlock User, this will display a dialogue box asking for a new start up password to be entered.

4)

The user can then enter the new password only once, as 963 will force the user to change the password once they have logged on.

Trend - 963 v3 Eng -Rev 03

40

Section 2 - Expire a User


Sometimes you may be required to Expire a user. An Expired user remains on the system, as do all records of their interaction with the system.

To Expire a Users Password. 1) 2) 3) 4) Log in as a member of the System Administrators Workgroup. Right click on the desired user in the navigator. Select Expire User. A confirmation box appears.

Once a user has been expired that users icon is struck through

and the Username cannot be reissued. All the users data is retained for future auditing.

Trend - 963 v3 Eng -Rev 03

41

Important !!!
If the System Administrator locks themselves out of 963 Secure, the only option that they have is to use the database password.

This is the only other option, the System Administrator must be aware of the database password and it should be kept Secure (i.e. Record held in Fire safe). We would also advise that at least 2 System Administrator users are created.

Apart from the Database password there is no other route for the System Administrator being able to log back in.

Trend - 963 v3 Eng -Rev 03

42

Section 2 - Database Password


To prevent the 963 database being accessed by unauthorised users, password protection is employed.

1)

Log on as a member of the System Administrators workgroup. Right click on the System Administrator workgroup icon and select Properties. The Workgroup information dialogue box will appear, select the System Administrator tab. Click on Set Database Password

2) 3)

4)

Trend - 963 v3 Eng -Rev 03

43

Section 2 - Database Password


5) A Confirmation window appears, click Yes.

6)

In the Database Properties window, select the Security option to enable the Password protection of the Database. Click Set database password

7)

Trend - 963 v3 Eng -Rev 03

44

Section 2 - Database Password


8) A Confirmation window appears, click Yes.

9) 10) 11)

Type in your new Strong Database Password twice. Click OK Make a note of the password and keep it safe.

The default database password is Trend963


Trend - 963 v3 Eng -Rev 03

45

Section 3 963 Device Viewer and the Network

Aims: To introduce the Engineer to Learning and Adding site networks Using the Device Viewer

Objectives: By the end of the section the Engineer should be able to Describe how to display the site structure using device viewer. Use the Device Viewer to display dynamic data and graphs .

Trend - 963 v3 Eng -Rev 03

46

Section 3 The First Engineering task

Now that we have installed 963, the next task is to learn the Site, this is done from the Device Viewer Mode (if you are engineering off site, you can import a project file from SET). Learning the site establishes the communications between the 963 and the devices on the network and maps the devices into the Device Viewers Navigator. This learned information is stored in the i96x_data.mdf database file.

Trend - 963 v3 Eng -Rev 03

47

Section 3 Exercise Learning the Site

1)

In Device Viewer, pin out the Navigator and right click on the House icon thats labeled Local site not learned From the pop up menu, select Learn my local site Give the site a label of Trend University The Information Center will now be displayed whilst 963 learns the site. The result should look similar to the example opposite.

2)

3)

Trend - 963 v3 Eng -Rev 03

48

Section 3 Exercise Learning the Site

When the site has been learned, the Information Center will disappear. 4) Click on the + to the left of the Red House to reveal what has been learned. This will show the LANs that 963 has discovered. Click on the + next to Local LAN 0, this will show you the devices on the LAN. You will find the devices that are on your desk with the IQ3LAN at address 24, your 963 will also be shown. Each 963 in the Training room has a different Trend Address. The address is set on the Trend LNC card fitted in the PC but other connection methods can be used.

5)

Trend - 963 v3 Eng -Rev 03

49

Section 3 Device Icons

Over the last 25 years, Trend has manufactured a range of equipment, all of which can be mapped and accessed using the 963. Here we can see the icons that represent the various devices that you may come across in the field.

Local Site Local LAN 96x Supervisor IQ2 Series Controller Remote Site Remote LAN Network Display Panel Comms. Node Controller Unknown Device IQ1 Series Controller Fieldbus Node Controller Internetwork Node Controller Autodial Node Controller Internetwork Node Controller

Trend - 963 v3 Eng -Rev 03

50

Section 3 - Exercise - Changing and Collecting Labels

We can Edit the labels in the navigator, by right clicking and selecting Label from the menu. 1) Edit your local LAN so it is called Sports Complex We have Learned and Edited the site details, now we need to Collect Labels. Collecting Labels, retrieves the rest of the information from the devices on the network, and can be applied at Site, LAN or Controller level. Learning at Site level will obviously take longer and will produce heavy network traffic, so beware !

Trend - 963 v3 Eng -Rev 03

51

Section 3 - Exercise - Changing and Collecting Labels

Try collecting labels from the IQ3 on your desk.

2)

Right click on Controller 24 and then select Collect Labels from the menu. The Information Center appears to let you know the 963 is busy. When the data has been collected, it is stored in the i96x_data.mdf file. This stored data is used in the 963 displays, that way only the current values need to be requested from the controller, the rest of the data can come from database. This keeps network messages to a minimum.

Trend - 963 v3 Eng -Rev 03

52

Section 3 - Exercise - Changing and Collecting Labels

Check that the 963 can bring back data from the controller. 3) Select your IQ3 in the navigator then select one or more of the module icons from the top of the main data display.

Sensors, Digital Inputs, MKT Sensors, Critical Alarms, Knobs, Switches, Timezones, and Drivers

The labels, Units, PIN levels etc. are being supplied from the data base. Only the Values are live and being called from the controller.

Trend - 963 v3 Eng -Rev 03

53

Section 3 Get the most from Device Viewer


To get the best out of Device Viewer consider the following points ! How many Devices do you need data from ? Which Modules are you interested in ? Sort Columns by clicking on headings Auto refresh fixed at 30 seconds. Use Manual Refresh to update Now. Right click a Module for a menu to edit, graph, etc.

Trend - 963 v3 Eng -Rev 03

54

Section 3 - Exercise Engineering with Device Viewer

Engineering using the device viewer. Ensure you select the IQ3 and not the Directory.

1)

Adjust a setpoint Select Outstation 24 and Knobs Locate Changing Rooms Setpoint Right click on the label Adjust value to 23 deg C.

Trend - 963 v3 Eng -Rev 03

55

Section 3 - Exercise Engineering with Device Viewer

2)

Sort by Label - Add Sensors and Drivers to the points you are displaying. Click on the header of the Label Column. This will bring together points with similar labels, grouping points relating to a certain piece of plant.

Trend - 963 v3 Eng -Rev 03

56

Section 3 - Exercise Engineering with Device Viewer

3)

Edit a point Add the Label and Units for a Knob. Locate Knob 30, right click on it to get the menu. Right Click on Change Label. Set the Label to Global Heat-Cool rate. Set the Units to read Deg days.

Trend - 963 v3 Eng -Rev 03

57

Section 3 Editing points from Device Viewer


Right click on the device in the navigator and select Edit Item, from the pop up menu.

This will show the module parameters in a popup window.

From here you can adjust many of the parameters for the selected module.

The Parameters that are available for adjustment can be controlled by editing the appropriate file in the 963\templates directory.
58

Trend - 963 v3 Eng -Rev 03

Section 3 Editing points from Device Viewer


Select Adjust Point from the next popup menu. Enter new value in the dialogue box, (use capital I and O to adjust a Digital status) then click ok. Changes made here are logged in the Alarms database, against the log-in name.

For Secure sites configuration mode should be disabled and minor changes to strategy should be made using this method.

Trend - 963 v3 Eng -Rev 03

59

Section 3 Device Viewer Search


Using the Navigator select the required level to search, site/LAN/controller.

Select the modules you wish to view.

Enter the search string e.g. Boiler. The Search is not CaSe SeNsItIvE.

The * can be used as a wild card i.e. *Boiler* will return any point with Boiler in the label, such as HWS Boiler, Boiler Flow Setpoint etc. Click on the Search button. The 963 filters the displayed list to show only items that match the label. Search retains a list of past searches.

Trend - 963 v3 Eng -Rev 03

60

Section 3 Adding sites

To add a site to the 963, click on a blank part of the Navigator, in Device Viewer and select Add a new site from the menu.

Give the new site an appropriate label. Learn Network box, leave ticked if you want 963 to learn the site as soon as its connected . Select type of connection: Telephone via Trend modem IP via TCP/IP or via EINC or Local for mobile engineers with more than one site on their laptop.

Trend - 963 v3 Eng -Rev 03

61

Section 3 Adding sites (Autodialed)


Enter the telephone number of the remote Trend Modem. Select the Type of Trend modem to be used (if unsure select Any Dialler). Site Location (of Modem) and LAN number (if remote site is a single LAN) Click Finish. This will start the dial-out process and 963 will begin learning the remote site

Trend - 963 v3 Eng -Rev 03

62

Section 4 Schematic Objects Basics

Aims: To enable the Engineer to Add and Edit Static Objects. Assign 963 Actions to a Static Objects.

Objectives: By the end of the section the Engineer should be able to Toggle 963 into Engineering Mode Configure a User Logon Page. Modify Object properties.

Trend - 963 v3 Eng -Rev 03

63

Section 4 Engineering Schematic Pages


The Schematics pages in 963 can be configured to display many types of data, both from the Trend System and the PC. We can also add buttons to enable the users to interact with the Trend system in many ways.

In 963 we refer to these as Objects, there are two types. Dynamic objects display live data from the System and Static objects display text, pictures or other files and can be assigned with actions to carry out various actions. All these objects need to be configured and the next couple of sections will show you how to use many of the options that are available.

Trend - 963 v3 Eng -Rev 03

64

Section 4 Engineering Schematic Pages

To engineer pages within 963, we need to be logged on as a User who has engineering rights. Then from the Navigator select the page to be edited. Right click on the Schematic page and select Configure Page from the menu. This toggles the display into engineering mode (and enables the Schematic config. Tab, more later).

Trend - 963 v3 Eng -Rev 03

65

Section 4 - Configuration of pages

Right click on a schematic page again to pop up the basic engineering menu, shown opposite.

From here you can Add a new object Reset Object defaults Edit objects Enable a page grid to assist with layout. Change the Backdrop. Undo changes that you have made.

Trend - 963 v3 Eng -Rev 03

66

Section 4 - Exercise - Configuration of Log in Page


This exercise will guide you through engineering a User Logon page.

1)

Log in as System Administrator, display the System Administrator Login page (select from the Navigator in User mode).

2)

Right click on the schematic page, select Configure page from the menu. You are now in engineering mode, the Schematics Config. Tab is activated (more later).

Trend - 963 v3 Eng -Rev 03

67

Section 4 - Exercise - Configuration of Log in Page

We are going to edit the text that that says Name : to read Name : System Administrator.

3)

Double click on the piece of text or right click on the text and select Properties from the menu. The text will become hatched over, showing that it is selected and the Display Object Editor will open.

4)

In the Display Object Editor, change the To Display field so that it reads Name : System Administrator.

Trend - 963 v3 Eng -Rev 03

68

Section 4 - Exercise - Configuration of Log in Page

5)

The Text attributes, font, colour, size can be changed. Select the attribute you want to change by clicking in the appropriate field.

6)

Click the menu button to bring up the options menu for the attribute that you want to change. Change the attributes as required.

7)

When happy with the results Click OK.

Trend - 963 v3 Eng -Rev 03

69

Section 4 - Exercise - Configuration of Log in Page

8)

Next add a picture of the System Administrator to the Log in Page. Right click on the page where you want to place the picture.

9)

Select New Object, then New Static Object from the menu. In the Object Display Editor select the To Display field and click the menu button. This opens the Display dialogue, click Choose BMP.

Trend - 963 v3 Eng -Rev 03

70

Section 4 - Exercise - Configuration of Log in Page

10) A window opens, showing all the available files from the 963\BMP folder. Scroll to the bottom of the window to select the Sysadmin.bmp.

11) Click OK to place the picture on the page.

Trend - 963 v3 Eng -Rev 03

71

Section 4 - Exercise - Configuration of Log in Page

The next part of the exercise shows you how to create a button, i.e. an object that has an action assigned to it. This will be a button that will log in the System Administrator .

12) Add a New Static Object, set the To Display field to Log In. To make the object a button we have to assign a action in the Action field. 13) Click the menu button.

Trend - 963 v3 Eng -Rev 03

72

Section 4 - Exercise - Configuration of Log in Page

14) From the What Action dialogue, click on the LOGINAS.

, from the drop down menu choose

15) Then select the System Administrator from the list of users in the next window.

Trend - 963 v3 Eng -Rev 03

73

Section 4 - Exercise - Configuration of Log in Page

16) You could also edit the Tooltip to read Click here to Log In, this will appear when the cursor is placed over the object

17) Change the PIN level to 1. With the PIN level set at its lowest setting, the button will always be visible, even when the default user is logged in. 18) Position the button at suitable place on the page.

Trend - 963 v3 Eng -Rev 03

74

Section 4 - Exercise - Configuration of Log in Page

19) Make another new object with the settings shown opposite. 20) When finished exit engineering mode by right clicking on the schematics page and deselecting Configure page. 21) Try the buttons that you have just made to make sure they work.

Note. It is important to remember to exit configuration mode when you have finished editing an individual page.

Trend - 963 v3 Eng -Rev 03

75

Section 5 Engineering Schematics


Aims: To enable the engineer to Engineer Schematic and Template pages. Describe Dynamic object properties. Describe Static object properties

Objectives: By the end of the section the engineer should be able to Follow the correct sequence for creating schematic pages. Engineer and edit both dynamic and static objects. Use 963 Simulation mode. Copy 963 Schematic pages.

Trend - 963 v3 Eng -Rev 03

76

Section 5 The 3 Steps of a Schematics Projects

1.

Engineer the the Template page. All new schematic pages are created as a copy of the template. Plan and Engineer the Schematics Navigator.Consider Security, How users move between pages and Logical groups e.g. Floor plans, Plant rooms etc. Engineer each individual schematic page. Consider a standard style and number of points per page (Max 30 dynamic points per page).

2.

3.

Trend - 963 v3 Eng -Rev 03

77

Section 5 Engineering the Template page(s)


The Template page is engineered in the same way as any other schematics page. All new schematic pages are created from the Template page. Therefore any graphics and dynamic points added to the template will be automatically added to every new page created. Engineering the template page correctly at the start of a project can save a lot of repetitive work and therefore time. e.g if a company logo or an outside air temperature is required on every page. To edit the Template, right click on an empty section of the Navigator and select Edit Template Page The Template page is saved as :C:\Program Files\Trend Control Systems\963\Template\pages.tss

Trend - 963 v3 Eng -Rev 03

78

Section 5 Engineering the Schematics Navigator

The Schematics Navigator has two purposes.

1. To provide a method of moving between the schematic pages 2. To provide security by displaying only the schematics that have been assigned to the current users workgroup. Pages in 963 can be either created in a folder or at the Root level i.e.not in a folder. There is no limit to the number of pages or folders that can be created. Folders have two functions. 1. To logically arrange pages. 2. To provide the security.
79

Trend - 963 v3 Eng -Rev 03

Section 5 Exercise - Schematics Navigator

This exercise will describe setting up the navigator for a set of schematic pages, make sure you are logged on as the System Administrator, then go to the schematics mode of 963. You will see that some schematics have already been created. You are going to make some additions to the existing Trend University project. You have been asked to add the Sports complex to the project and to provide different access for admin and engineering operators. We need to consider using folders for grouping the pages to apply security. The result should look like this.

Trend - 963 v3 Eng -Rev 03

80

Section 5 Exercise - Schematics Navigator

1)

To add a folder, right click on on pages and select Add Folder, you then give the folder a label.

2)

Add the folders highlighted on the previous page.

3)

Next, add the pages to the project. To add a page, right click on the folder that you want to add it to, then select Add Schematic from the menu.

Trend - 963 v3 Eng -Rev 03

81

Section 5 Exercise - Schematics Navigator

5)

Add the page shown opposite, to the Sports Complex folder.

6)

Add the pages shown opposite, to the Sports Complex Admin folder.

If a folder or page has been added in the wrong location, just click on it and drag it to the right place. Due to the Security that is applied to these folders within 963, you can not drag a page from a folder to the root.

Trend - 963 v3 Eng -Rev 03

82

Section 5 Copy Schematics

If schematics pages need to be backed up, copied or exported to another project this can be done from the 963 pages directory.

Start Windows Explorer and navigate to C:\Program Files\Trend Control Systems\963\Pages.

The Schematics are in the same folders that have been created in the navigator and are saved as .tss files.

Note, the .TSS file is not a graphics file, its a text file that lists the objects used on the page and the co-ordinates of where they are placed on the page. Therefore if you are copying pages you need to copy the Backdrop and BMP directories as well.

Trend - 963 v3 Eng -Rev 03

83

Section 5 Engineering Schematic pages

Once created, each new schematic page will need to be edited. The normal order for engineering each page would be:i. ii. iii. iv. v. Set the backdrop Add static objects e.g. text, graphics Set up actions for static objects Add dynamic objects Go live and test

All engineering is carried out in Configure Page mode. In this mode :Dynamic objects are frozen i.e. will show the last value or the point reference. The Schematics Config and Display Object Editor are available. Buttons and Actions do not work.

Trend - 963 v3 Eng -Rev 03

84

Section 5 The Display Object Editor


As we have already seen, this allows us to edit the parameters of an object on the page.

To Display, sets the text or graphic we want to display on the page. Action, allows us to make the object a button, go to another page, Log In to the system etc. Text, lets us alter the text properties font, size etc. Graphic, adjusts frame rate for animations and lets us change colors of text buttons Size and position, sets object size and whether the object is visible or hidden.

Trend - 963 v3 Eng -Rev 03

85

Section 5 The Schematics Config. Pane


This tool has 5 tabs and enables items to be dragged and dropped directly onto the schematics page.

Explorer tab lets you select any supported graphic file type from anywhere on your PC, the file is copied into the appropriate 963 directory and then referenced from that location. Device Viewer tab lets you select controller points and drop them on a page. Users tab, from here you can drag a users name onto a page, this creates a log in button for that user. Graphs tab creates buttons or embedded graphs from previously saved graph definitions (more later). Diary tab creates shortcut buttons that take you directly to Diary groups (more later).

Trend - 963 v3 Eng -Rev 03

86

Section 5 Creating the Sports Complex Home Page


This exercise will demonstrate how to engineer the Sports Complex Home page. We are going to add 3 objects to the page.

Static object Dynamic Object Backdrop

Trend - 963 v3 Eng -Rev 03

87

Section 5 Exercise - Sports Complex Home Page

1)

Log in as the System Administrator and display the Sports Complex Home page. Warning all the pages that you have created look the same, so check that you have the right page selected in the Navigator, also check the 963 Title bar, the current page name is displayed there.

2)

Right click on the schematics page and select Configure Page. The Schematics Config and Display Object Editor become available.

3)

Right Click on the Schematics page again and select Change Backdrop.

Trend - 963 v3 Eng -Rev 03

88

Section 5 Exercise - Sports Complex Home Page

4)

Now select the Sports Complex backdrop from the list of available backdrop pictures and click OK.

5)

Next add a Static object, right click on the page, select New Object, then New Static Object.

6)

Change the To Display text to read Welcome to the Sports Complex

7)

Modify the Text attributes, make the font bigger, change its color as required.

Trend - 963 v3 Eng -Rev 03

89

Section 5 Exercise - Sports Complex Home Page

8)

Finally were going to add the Dynamic Object for the Outside Air temp. Click on the Schematics Config Pane tab and pin it out.

9)

Select the Device Viewer Tab. This shows all the connected devices, select the Sports Complex controller (24) and click on the + to show the available modules within the controller.

Trend - 963 v3 Eng -Rev 03

90

Section 5 Exercise - Sports Complex Home Page

10) Select the Sensors. The lower half shows a list of all the sensors that are set up in the controller. Find the Outside Air Sensor (S11) and then drag it onto the page. If required, change the attributes using the Object editor.

11) When you are happy with the result, right click on a blank part of the schematic page and deselect Configure page to return to normal operating mode.

Trend - 963 v3 Eng -Rev 03

91

Section 5 Adding Objects Manually


There may be cases where it is not practical or possible to add an object to a page by dragging it from the Schematics Config Pane. Some Examples are:A piece of static text, like Welcome to the Sports Complex A dynamic point from a controller that has not yet been connected to the system.

These objects need to be added to the page manually. We did this in the previous exercise with a Static object, we can do the same with a Dynamic object but its a bit more complex.

Trend - 963 v3 Eng -Rev 03

92

Section 5 Editing Dynamic Objects


Lets look at the properties that make up a Dynamic object.

When a dynamic object is dragged and dropped onto a page, the LAN, Outstation, Label, Units and Item fields are all completed automatically. If the point is added manually, all these fields need to be completed by the engineer.

Trend - 963 v3 Eng -Rev 03

93

Section 5 Editing Dynamic Objects

The Refresh rate sets how often the dynamic value is updated from the controller, its set in seconds and the fastest setting is 5 seconds.

The PIN level works with the Workgroups to set which uses can access the point.

Trend - 963 v3 Eng -Rev 03

94

Section 5 Editing Dynamic Objects

The When On and When Off parameters are used for digital objects. They can be configured to display a different graphic for each state. E.g. Boiler on and Boiler off. Select the Menu button, then Choose from directory, then browse for the file you want to use.

Trend - 963 v3 Eng -Rev 03

95

Section 5 Editing Dynamic Objects


The When in Alarm field allows a different graphic to be displayed when the digital point is in an alarm condition. Change the setting to <FLASH> by clicking the + and selecting from the drop down menu.

The When Overridden On and When Overridden Off parameters are used for digital outputs where the IQ3 Hand/Off/Auto module is used. They enable use of different graphic representations if the output has been manually overridden on or off.

Trend - 963 v3 Eng -Rev 03

96

Section 5 Editing Dynamic Objects

Decimal places sets the number of decimal places of the displayed value. For analogue outputs, valves, dampers etc this is best set to 0 whist for sensors its generally set to 1. Display as determines what information is displayed from the point. A drop down menu gives a number of options. Display Analogue Graphic lets us display a series of graphics that represent a changing analogue value (more later).

Trend - 963 v3 Eng -Rev 03

97

Section 6 Engineering Dynamic Schematics

Aims: To enable the engineer to Engineer Dynamic Objects on a Schematic page.

Objectives: By the end of the section the engineer should be able to Add Dynamic points to a 963 Schematics page. Display a dynamic point as a graphic. Tidy up a schematic page.

Trend - 963 v3 Eng -Rev 03

98

Section 6 Engineering Dynamic Schematics


Dynamic Objects display data from the controller on Schematic pages. The data can be represented in a number of ways depending on the type of data to be displayed. For example, a Digital output could be represented by. a changing piece of text or alternating pictures or an animation

An analogue value could be represented by a changing text display or an analogue graphic.

Trend - 963 v3 Eng -Rev 03

99

Section 6 Changing dynamic object displays

A digital dynamic object, Switch, Driver etc can be configured to display extra text or Graphics. To add extra text we need to edit the default display which is just On or Off. Click on the menu button for the field that you want to change, then type the new text into the I shall display this field. If you want to display a graphic instead of text, make a choice from the option buttons.

Trend - 963 v3 Eng -Rev 03

100

Section 6 Engineering the Sports Hall

The next exercise will demonstrate how to engineer a schematic page, comprising a number of dynamic points. The exercise will also give you some useful tips on how to present the information.

Trend - 963 v3 Eng -Rev 03

101

Section 6 Engineering the Sports Hall - Exercise

1)

Select the Sports Hall Lighting page from the Sports Complex Admin folder. Go into Configure page mode and select the option to change the Backdrop, and select Sports Hall Lighting.

2)

Trend - 963 v3 Eng -Rev 03

102

Section 6 Engineering the Sports Hall - Exercise

3)

Open the Schematics Config. Tool, and select the Device Viewer Tab. From here you can drag and drop Dynamic points onto the page. The following points need to be added to the page :S1 Sports Hall temp K1 Sports Hall Setpoint K2 Sports Hall Un-Occ Setpoint W1 Single Court Lighting W2 Dual Court Lighting D5 Sports Hall Lighting Z3 Sports Hall Timezone

4)

Trend - 963 v3 Eng -Rev 03

103

Section 6 Engineering the Sports Hall - Exercise

5)

After placing the objects on the page you will need to edit them. Consider the following points :Font style, size and colour PIN levels for Knobs, Switches, Sensors and Timezones. Display options i.e. Label, Value and Units What to display if the point is in alarm. Refresh rate

You could also consider having different colours for different items.i.e. Red for sensors, Blue for adjustments (Knob, Switches and Tmezones), Black for outputs etc. Edit the dynamic points that you have just added to the page to display the following. Font - Ariel Size - 14

Trend - 963 v3 Eng -Rev 03

104

Section 6 Engineering the Sports Hall - Exercise

7) Go to each Dynamic object in turn and edit the following properties Refresh Rate = 5 seconds Display as = Label, Value and Units PIN level = 70 8) Test the page, Set the Timezone to be on all week, the Driver Value should change from 0 to 40 9) Select Single Court Button, the Value should change from 40 to 70 10) Select Dual Court Button and the Value should change from 70 to 100

Trend - 963 v3 Eng -Rev 03

105

Section 6 Moving Objects


It is possible, whilst in configuration mode to group select objects. To do this, 1) Left click and drag a box around a group of objects. or 2) Hold down the CTRL key and then single left click on any required object.

Groups of objects can be moved around the screen by:Dragging the group Using the 4 arrow keys on the keyboard, these will move the object at a rate of 5 pixels. Pressing the shift key at the same time as the arrow key will increase the rate to 15 pixels.

You can also swap the position of any two selected objects with CTRL+S
106

Trend - 963 v3 Eng -Rev 03

Section 6 Moving Objects


Groups of objects can be arranged by, Right clicking on the group then selecting Edit objects, then arrange objects. Select the number of rows and 963 calculates the number of columns. CTRL + R are the shortcut keys for this option.

Or you can use

CTRL + arrow keys to align the objects. e.g. CTRL + -> will align all selected objects to the right hand edge of the object furthest to the right.

Be careful, with this as its easy to place objects on top of each other. Remember you can use the undo CTRL+Z.
Trend - 963 v3 Eng -Rev 03

107

Section 6 Moving Objects

When new objects are added to a schematic page the default is set to use Auto size. i.e. the buttons will fit to accommodate the text.

The result may be that some of the buttons have widely different dimensions. Also remember, that the width of the button can change as the text changes e.g. Boiler OK changes to Boiler Fault.

To overcome this, change the Auto Size field to No. You will then be able to set the same fixed height and width for the objects, so that they look neat and tidy.

Trend - 963 v3 Eng -Rev 03

108

Section 6 Tidying up exercise

Arrange the dynamic objects for the Sports Hall page as shown. Disable the Auto size function and set all the objects to have the following dimensions. Width = 250 Height = 30

Try arranging the objects using CTRL + R Try swapping 2 objects using CTRL + S

Trend - 963 v3 Eng -Rev 03

109

Section 6 Analogue Graphics

An Analogue object can be configured to display a set of graphics instead of text. Set Display as = Value Set Display Analogue Graphic = Yes Click the menu button in the Analogue File field, then browse for the file. Note to use analogue graphics, they must be stored in the 963\analogue directory and there must be a separate folder for each set of analogue graphics. More on analogue graphics later.

Trend - 963 v3 Eng -Rev 03

110

Section 6 Analogue Graphics - Exercise

On the Sports Hall Lighting page.

1)

Add another Driver 5 (Sports Hall Lighting). Change the parameters to display the analogue file :analogue\Hall Lighting\Hall Lighting.analogue Exit page Configuration, make sure that the Timezone is on. Switch the Single Court Lighting on. Switch the Dual Court Lighting on. Go back in to page Configuration and reposition the graphic.

2)

3)

4) 5) 6)

Trend - 963 v3 Eng -Rev 03

111

Section 6 Copying Schematics


Copying pages is a very quick method of engineering many similar schematics pages The process is as follows :i. In the Navigator, select the page you wish to copy. ii. Right Click on the page and select Copy, from the menu. iii. Right Click on the destination for the copied page and select Paste. iv. If pasting into the same location, 963 will display a warning that the page already exists, you may continue but will be asked to rename the new page. You can now edit the new page and change the point references using the Display Object Editor or Find and replace (more on this later) tools.

Trend - 963 v3 Eng -Rev 03

112

Section 6 Copying Schematics - Exercise

This Exercise will guide you through copying the Sports Hall Lighting page and using it as a template for the New Sports Hall. Although the point references will be different all the rest of the engineering will have been done. 1) 2) 3) 4) 5) Copy the Sports Hall Lighting page, then paste it in the same Directory. Rename the Copy as New Sports Hall. You may need to refresh the navigator. You now have a duplicate page with all the objects already in place. The Final step would be to change the Controller references for each point. We will do this later as part of another exercise

Trend - 963 v3 Eng -Rev 03

113

Section 6 Schematics Summary


Important features of Schematics to remember: All editing is saved automatically. There is an undo feature of 20 back steps, select by right clicking on the page or use CTRL +Z. Changing Item labels on a schematic page only updates the .tss file, it does not change the label in the controller as it does from Device Viewer. Objects have PIN levels, these control whether a user can access the object, depending on the PIN level set in the Users Workgroup. The screen size used by 963 is set by the size of the Backdrop image. Select multiple objects by holding the CTRL key and left clicking on each in turn. Fine tune the position of objects using arrow keys, hold the Shift key at the same time to move objects 3 times faster. If only a file reference is displayed on the page, 963 has not been able to find the graphic

Trend - 963 v3 Eng -Rev 03

114

Section 7 Engineering Static Objects

Aims: To enable the engineer to Create buttons on a schematics page. Use 963 Actions

Objectives: By the end of the section the engineer should be able to Engineer a Graphic with an Action. Engineer a button with a GOTO action. Animate a button.

Trend - 963 v3 Eng -Rev 03

115

Section 7 963 actions


Static Objects on a schematic page can be engineered as Buttons. A button is a Static object that has a 963 action assigned to it, and when the Button is clicked the action is carried out.
There are 80 actions that can be selected, most of which can be assigned to a button. Some of the most commonly used are :-

GOTO LOGINAS LOGOUT PRINTGRAPH PRINTPAGE SEND

- Takes the user to a different page - Allows a specified user to log in. - Logs any user out of 963 - Prints a specified graph trace - Prints the current schematics page - Sends a text comms to a controller

Trend - 963 v3 Eng -Rev 03

116

Section 7 Setting up the action

Select the static object that you want to use as a button and edit its parameters. Click the menu button in the action field Select the action from the drop down menu or type in the action.

Some actions require more details so will display another widow to input the information e.g. a GOTO action needs to know what page you want it to go to.

Trend - 963 v3 Eng -Rev 03

117

Section 7 Graphic buttons - Exercise

This Exercise will guide you through setting up 2 buttons, one with a GOTO action and one with a VIEWGRAPH action. 1) 2) Go into page configuration on the Trend University Home page. Place the first graphic on the page, bmp\trend uni\map buttons\sports hall.bmp, position it over the sports complex on the map. Change the objects action to GOTO, then select the Sports Complex Home from the list.

3)

Trend - 963 v3 Eng -Rev 03

118

Section 7 Graphic buttons - Exercise

4) 5)

Place the second graphic on the page, gif\glass.gif. Set the action field to VIEWGRAPH, click yes as we do want to specify a particular graph. Specify the graph that you want to assign to the button in this case well use Total Gas. Exit page configuration mode and test your buttons.

6)

7)

Hint if you need a similar button on many pages, right click and select Edit then copy. Then just paste it onto the required pages using CTRL +V

Trend - 963 v3 Eng -Rev 03

119

Section 7 Animated Graphic buttons


Eyes.bmp When a graphic is used as a button it can be animated. 963 will look for 3 extra graphic files in the same directory, that start with the same name.

Eyes_o.bmp will display when the cursor is over the graphic

Eyes_h.bmp will display when the cursor has hovered over the button for 4 seconds.

Eyes_d.bmp will display when the button is clicked down.

Go to the Admin office page, look at the mouse and the penguin
Trend - 963 v3 Eng -Rev 03

120

Section 7 More buttons

The SEND action allows us to send a Trend Text Comm. to a controller to change a modules parameters. When we configure a SEND action we have to specify the LAN and O/s address for the target controller and then specify the Text Comm. that we want to send.

This example would SEND a Value of 21.5 to all Knobs in controller 24 on LAN 0

Trend - 963 v3 Eng -Rev 03

121

Section 7 More buttons

We can also build questions into the SEND action, to enable the user to input variables. e.g. the value for a setpoint or a status for a switch. This is achieved by including the 963 variable <?> at the point in the text comm. where the new value needs to be. For example SEND L0O24K1(V=<?Type the new value here>) Would pop up the dialogue box below, to prompt the user to Type the new value here for Knob 1 in Os 24 on LAN 0

Trend - 963 v3 Eng -Rev 03

122

Section 7 Login Action


We can set up 963 so that a user is taken to a particular page when they log in.

This uses the GOTO action and is set up in the Workgroups.

Specify the workgroups start page by clicking on Choose Startup page in the Workgroup properties.

Select the required page from the pop up list that we saw earlier.

Trend - 963 v3 Eng -Rev 03

123

Section 7 Login Action - Exercise

1) 2)

Go to Users mode Edit both the Default and Field Service Workgroups so that they have the Trend University Home as their Startup page.

3)

Remember we can restrict user access to certain schematics by selecting which folders they can see. We do this in the Folders tab.

4)

Check that the Field Service workgroup can access all schematics and that the Default Workgroup can access none.

Trend - 963 v3 Eng -Rev 03

124

Section 7 Navigating Schematics


When designing the schematics pages for the customer we need to decide how the users will navigate the system. Many sites will have dozens of schematic pages, Universities and military installations may consists of many individual buildings, all of which may need to be represented in the 963. There are 2 options for navigating the system :1) Navigation Buttons 2) The Schematics Navigator

The advantage of using engineered buttons is that they are direct, one click and you are at the required page. The buttons can also be given PIN protection, therefore restricting access only to authorized users. If buttons are used the schematics navigator can be hidden, giving more screen space for the schematic page.

Trend - 963 v3 Eng -Rev 03

125

Section 7 Moving between Schematics

Many 963 projects utilize a site plan or map as a central point from which to navigate around the system, with navigation buttons for each building or area. Access to various areas can be controlled by setting different PIN levels on the navigation buttons. The next exercise is to engineer a Navigation page for the Trend University Sports Complex.

Trend - 963 v3 Eng -Rev 03

126

Section 7 Moving between Schematics Exercise

Engineer the Sports Complex Home page as shown here. 1) Set the backdrop to Sports Complex 2

2)

Add and Edit the Static Objects. Edit the, action PIN level etc the settings for each static object are shown on the next few pages.

Trend - 963 v3 Eng -Rev 03

127

Section 7 Moving between Schematics Exercise

Once a schematic page has been created, you can Drag and Drop it from the Schematics Config. Pane on to a page where it becomes a automatically navigation button to that page.

Trend - 963 v3 Eng -Rev 03

128

Section 7 Moving between Schematics Exercise

For our project we need to create the buttons as show on this and the following two pages. We can create these from new. i.e. New Static Object or we can drag them onto the page from the Schematics Config Pane and then edit them as required.

Trend - 963 v3 Eng -Rev 03

129

Section 7 Moving between Schematics Exercise

Trend - 963 v3 Eng -Rev 03

130

Section 7 Moving between Schematics Exercise

Trend - 963 v3 Eng -Rev 03

131

Section 8 More Schematics

Aims: To enable the engineer to Use the 963 graphics library. Engineer Schematics for unfinished sites Use the Find and Replace function

Objectives: By the end of the section the engineer should be able to Create dynamic links on a schematic page for unlearned sites. Use the Find and Replace function to change links on 963 object attributes.

Trend - 963 v3 Eng -Rev 03

132

Section 8 Engineering an Plant Schematics.


Included as part of the 963 installation is a collection of basic plant graphics that can be used to create Plant schematics. You will find samples of both static graphics (.bmp), Animation and Analogue files in the appropriate 963 Sub directories.

Trend - 963 v3 Eng -Rev 03

133

Section 8 Engineering an Air Handling Unit


In the next exercise we are going to be using some of these sample graphics to create a schematics page for an Air Handling Unit. Although the AHU could be constructed directly on the schematics page using components from the library, better results are achieved if a backdrop is constructed first using a graphics package. This has a number of benefits:I. II. III. There are less objects for the 963 to load on to the page. You only have to build the Backdrop once but can use it for many AHUs You can keep a copy of the backdrop for use on other projects.

Trend - 963 v3 Eng -Rev 03

134

Section 8 Engineering an AHU - Exercise

This exercise will guide you through engineering the AHU page using a pre-engineered Backdrop and items from the 963 sample library. 1) Go to the Changing AHU page, in the Sports Complex Plant folder. 2) Add the following dynamic objects to the page as text . S1 - Sports Hall Space Temp S4 - AHU Supply Temp S5 - AHU Return Temp K1 - Sports Hall Setpoint K10 - Frost Setpoint D1 - AHU Heating Valve D2 Dampers D3 - Cooling Valve

Trend - 963 v3 Eng -Rev 03

135

Section 8 Engineering an AHU - Exercise

3) 4)

Place Driver 4 on to the page. Edit the objects properties to match the settings shown opposite. Copy and paste another Driver 4 onto the page For the new object change the When On field to display Fan left.animation.

5)

6)

Trend - 963 v3 Eng -Rev 03

136

Section 8 Engineering an AHU - Exercise

8)

Place a new Dynamic object on the page

9)

Edit the properties to match those shown. The Item field G10(D) is the common point in the control strategy that is on when either pump is enabled.

10) Copy and paste this object, then change the When On field to display Horiz Right hot.animation

Trend - 963 v3 Eng -Rev 03

137

Section 8 Engineering an AHU - Exercise

11)

Arrange the points to match the schematic page shown below.

Trend - 963 v3 Eng -Rev 03

138

Section 8 Find and Replace


Find and Replace is a very powerful tool and can be used at various levels within the project. To use Find and Replace, log on as a high level user. Open schematics navigator. Right click on Pages (root), a folder or a single page. Select Find and Replace from the popup menu. The Find and Replace wizard will open. When in page configuration, it can be used on the entire page or just on a, previously selected group of objects.

Trend - 963 v3 Eng -Rev 03

139

Section 8 Find and Replace


The Wizard can be used on most schematic object attributes. It is a very powerful way of editing many objects at once e.g. Refresh rates for all objects, on all pages within a folder can be changed in one go.

Select the attribute to modify.

Free text search, specify the old value and the new value.
Trend - 963 v3 Eng -Rev 03

140

Section 8 Find and Replace - Exercise

1)

Carry out a find and Replace on the New Sports Hall page. Replace the Os (Outstation) reference to 25 instead of 24. The wizard disappears and is replaced by a box indicating how many changes have been made.

2)

3)

Trend - 963 v3 Eng -Rev 03

141

Section 8 Find and Replace on Labels


If you have created schematic pages for controllers that were not yet connected to the system. Learn the new controller using device viewer. Use Find and Replace on the appropriate pages, using the Label field. 963 replaces all the labels on the page, with the labels stored in the database, so matching them with the controller.

Trend - 963 v3 Eng -Rev 03

142

Section 9 Other Display Options

Aims: To enable the engineer to Pre-engineer graph Buttons Create a Points window

Objectives: By the end of the section the engineer should be able to Engineer and display a multi-trace graph from a single schematics button. Engineer and display a limited points window from a schematic button or a dynamic point, using the VIEWPOINTS actions

Trend - 963 v3 Eng -Rev 03

143

Section 9 Other Display Options


The following actions may be used to create some alterative displays for users to access controller information. POPUP Displays a schematic page in a new window.

VIEWGRAPH

Opens a pre-engineered graph.

VIEWPOINTS

Displays a pre-engineered list of points in a new window.

GENERIC

A button can be added to a page that when selected will display a generic page, and specify the device from which the values are retrieved.

Trend - 963 v3 Eng -Rev 03

144

Section 9 The POPUP action


The POPUP action is very simple to set up and is virtually the same as the GOTO action except that it displays the selected schematic page in a new window, this can be useful if the user need to view more than one schematic page at a time. 1) 2) 3) Select POPUP as the action. Select the Schematic page. Set the size and position of the new window using the Pop up dialogue box.

Trend - 963 v3 Eng -Rev 03

145

Section 9 The VIEWGRAPH action


Graphs can be viewed in a number of ways from 963 schematics pages. 1) 2) 3) Clicking a sensor button. Embedded in a page. Using a button with the action VIEWGRAPH.

If we want to embed a graph or use the VIEWGRAPH action, first we need decide what the graph is going to display, what traces, the scaling etc. This is called a graph definition and these are set up in the graph manager, which is accessed from the menu bar.

Trend - 963 v3 Eng -Rev 03

146

Section 9 Exercise - The Graph Manager

We are going to set up a Graph Definition for the Outside Air Sensor. 1) Make sure you are logged in as the System Administrator. 2) Open the Graph manager from the menu bar and select New. 3) Give the Definition a label My OAT sensor. We can now set up what we want the definition to display.

Trend - 963 v3 Eng -Rev 03

147

Section 9 Exercise - The Graph Manager

5)

Click Add Trace, we can then select the sensor that we want to use in the definition.

6)

Navigate your way to the OAT sensor by selecting the Site, LAN and Outstation that its connected to.

7)

Click on Find matching points to find all the Sensors in the controller.

8)

Then pick a point to use in the definition.

Trend - 963 v3 Eng -Rev 03

148

Section 9 Exercise - The Graph Manager

9)

Next choose a logging interval, there maybe one or more depending what has been configured in the controller.

10) Finally decide if you want to use the left or right axis for the value.

Trend - 963 v3 Eng -Rev 03

149

Section 9 Exercise - The Graph Manager

When youve finished you can preview the graph, or add further traces if you need a multi-trace graph.

At the bottom is the list of sensors that make up the graph.

If you need to fix the scaling, use precision graphs or apply a grid, this can be done by using the general options, dont forget to click the save when you have finished your configuration.

Trend - 963 v3 Eng -Rev 03

150

Section 9 Exercise - The Graph Manager

A quicker way of creating a Graph definition, especially for multi trace graphs.

Use this procedure and the sensors highlighted here, for the next part of the exercise. 1) In device viewer, group select the sensors that you wish to graph (963 supports graphs with up to 10 traces). Right click on one of the group and select, Graph Points from the menu. This will open a graph of the selected sensors.

2)

3)

Trend - 963 v3 Eng -Rev 03

151

Section 9 Exercise - The Graph Manager

4)

From the File menu, Save the Graph as VT Graph

5)

Go to the Sports HWS schematic page and configure the page with a new button labeled View VT Graph.

6)

Set the action to VIEWGRAPH and specify the VT Graph to be displayed.

7)

Exit page Configuration and test the button.

Trend - 963 v3 Eng -Rev 03

152

Section 9 Exercise - Embedded Graph

1)

To embed a graph on the page, go back into page Config. mode, open the Schematics Config. Pane and select the Graphs tab.

2)

Drag the VT Graph on to the page. Click Yes, to create the graph as a child window (embed).

3)

Position and resize as required (Warning the bigger the embedded graph the more memory used).

4)

Exit Page Config. and test.

Trend - 963 v3 Eng -Rev 03

153

Section 9 The VIEWPOINTS action

The VIEWPOINTS action displays a popup window listing specific controller points (from a single Controller), similar to the presentation we see in Device Viewer.

A viewpoints window can be initiated from a schematic object or as an Alarm action.

Trend - 963 v3 Eng -Rev 03

154

Section 9 The VIEWPOINTS action


There are 4 options for the VIEWPOINTS action.

VIEWPOINTS - This option displays all the dynamic points on a particular schematics page.

VIEWPOINTS + Item - This option can be linked with a specific item or module code e.g. S (Sensors) and will then show details of only the sensors of the schematics page.

Trend - 963 v3 Eng -Rev 03

155

Section 9 The VIEWPOINTS action


VIEWPOINTS + Display and Directory. This option displays all the dynamic points that have been setup in a Directory module within a controller. You need to specify the LAN O/s and Directory Module. The Code for Directory Module is @ followed by the number of the directory module e.g. VIEWPOINTS L0O24@2

VIEWPOINTS ++ Template - This is the more selective version so needs some set up. Use the 963 Help and Engineering manual to learn more about these 2 versions of the VIEWPOINT action.

Trend - 963 v3 Eng -Rev 03

156

Section 9 Exercise VIEWPOINTS action

1)

Go to the Changing AHU page. Configure the page to have a new static object labeled Points List. Set the action for the button to VIEWPOINTS.

2) 3)

Exit page Config. And test the button. Change the action on the button to VIEWPOINTS + Item, select S for Sensors, as the item. The action string should be VIEWPOINTS S. (Note the space!) Test the button.

Trend - 963 v3 Eng -Rev 03

157

Section 9 Create a template from Device Viewer

For Viewpoints ++ Template 1) Go to Device Viewer mode and display the desired points 2) Right click on a point or group of points, that is to be added to the template. 3) The Default file name is New.txt, this can be changed but the files do need to be saved in the Template Directory. 4) The default action is to add items to the file, use the check box if you wish to overwrite the existing file with new points.

Trend - 963 v3 Eng -Rev 03

158

Section 9 Create a template from Device Viewer

5)

Click on the Label Tab to add a title for the points window When all the points have been added for the template, a text file is created in the template directory. The 1st Line of the text file contains the title for the points window, subsequent lines list the point reference, Label, Units and PIN level etc. It is also possible to create these templates directly, using Notepad

Trend - 963 v3 Eng -Rev 03

159

Section 9 Creating Template Text Files


The text files used for the templates are a list of IQ points. This list can then be applied to any number of controllers that share the same strategy e.g. Trend IQL range. The syntax of the VIEWPOINTS ++ actions is: VIEWPOINTS (tele)(LAN address)(IQ address),template\filename.txt

VIEWPOINTS L20O43,template\FCU. txt

VIEWPOINTS L20O44,template\FCU. Txt

Trend - 963 v3 Eng -Rev 03

160

Section 9 - Creating a Generic Schematic Page


Generic schematics are a very easy way of dealing with a large number of controllers that have the same control strategy. e.g. Fan Coil Units.
FCU 1 O/s 24 LAN 0 2 25

FCU 1

FCU 2

FCU 3

FCU 4

Map page Generic page


Selecting any button on the map page, always displays the Generic page, but the data comes from a targeted controller.

Trend - 963 v3 Eng -Rev 03

161

Section 9 - Creating a Generic Schematic Page


The Dynamic Objects that are displayed on a Generic page need to have the Item reference configured e.g. D1, S1 etc. But they are then set to USE GENERIC, this disables the controller reference fields for the object, the controller is then targeted by the button on the map page. So at this stage the 963 knows what points to display, but not which controller to get the values from.

On our Map page, we would then need to create a new Static object for each Fan Coil Unit, with a action like GOTO pages\Generic\fcu.tss GENERIC=L0O25 This GOTO part of the action causes the 963 to display the FCU page and the GENERIC part selects where to retrieve the data from.

Trend - 963 v3 Eng -Rev 03

162

Section 9 - Creating a Generic Schematic Page


To create Generic schematic pages follow these steps 1. On The Generic page, add the Dynamic points and set the Use Generic field to Yes for all of them. It is important to identify which controller the page is returning values from, so add some dynamic objects from the controllers Address module. These objects also need to Use Generic.

2.

Controllers iDentifier - R(D)

Controllers address - R(L)

Controllers laN - R(N)

Trend - 963 v3 Eng -Rev 03

163

Section 9 - Creating a Generic Schematic Page

3.

Add buttons to target the controller from which to display values. This may be done by either of the following methods:i. On a map page, create buttons using a combination of GOTO and GENERIC actions. On the generic page, create a button with an action of SETGENERIC.
FCU 3 FCU 1

FCU 2

ii.

Trend - 963 v3 Eng -Rev 03

164

Section 9 - Generic Pages Exercise

This exercise is designed to demonstrate Generic schematics. For this exercise you will need to do some prep work with your neighbour. Join your LAN with a neighbour to build a single LAN comprising 2 x IQ3s and 2 x 963s. Set the address of one of the IQ3s to 25.

You will then both need to re-learn your site and collect labels.

Trend - 963 v3 Eng -Rev 03

165

Section 9 - Generic Pages Exercise

Engineering the Generic schematic 1. 2. In the Sports Complex Changing folder you will find a page called Generic Add the following Dynamic points to the page :- S20, K11, D12, D13, D4. Set the all the points to Use Generic and set the properties (Label, Value and Unit etc) as shown below.

Trend - 963 v3 Eng -Rev 03

166

Section 9 - Generic Pages Exercise continued

3.

Remember ! On any generic page it is important to display where the dynamic data is coming from, so create 3 new dynamic objects - set them to Use Generic. The Items needed are :R(D), R(L), R(N)

4.

Also set up a button with an GOTO action to return the user to the Sports Changing page.

Trend - 963 v3 Eng -Rev 03

167

Section 9 - Generic Pages Exercise continued

5.

On the Sports Changing schematic page, create a new button labeled FCU24 and set the action up as follows :GOTO Pages\Sports Complex Offices\Generic.tss GENERIC=L0O24 On the same schematic page create a new button labeled FCU25 and set the action up as follows GOTO Pages\Sports Complex Offices\Generic.tss GENERIC=L0O25 You can select the GOTO from the dropdown menu, but will have to add the rest by typing.

6.

Test your buttons, are you able to tell which controller you are displaying values from?

Trend - 963 v3 Eng -Rev 03

168

Section 9 - The SETGENERIC Action


A SETGENERIC button may be created by adding a new static object on the Generic schematic page and setting the action to SETGENERIC. When the button is clicked, a popup is shown allowing the operator to select a controller from which the generic page will get its dynamic values. Benefits of this method Easy to engineer. Drawbacks of this method The operator has to navigate to the desired controller, which could take a while on a large site. The popup shows all devices that have been learnt in the Device Viewer, therefore operators could select the wrong or even non controller devices.

Trend - 963 v3 Eng -Rev 03

169

Section 10 Animation and Analogue files

Aims: To enable the operator to Use Animations Use Analogue graphics

Objectives: By the end of the section the operator should be able to Describe how to link a animation file to a dynamic object Link analogue graphics to an analogue value at different levels

Trend - 963 v3 Eng -Rev 03

170

Section 10 Animations
Animations are a series of graphic files that are played in a sequence. All the files that make up an animation must be grouped together in a sub directory. A text file that lists that sequence of the graphics is saved as <filename>.animation This .animation file is referenced in the What to display field for that dynamic object.

963 animations support the following file types:- bmp, jpg, gif, wmf and emf

Trend - 963 v3 Eng -Rev 03

171

Section 10 Animations Exercise

This Exercise will guide you through creating and displaying an animation that will represent the status of a digital output.

1) 2)

Open Notepad and create the animation file shown here. Save the file as burner fire.animation in the following directory.

C:\Program files\Trend Control Systems\963\Animation\Trend uni\burner fire

Trend - 963 v3 Eng -Rev 03

172

Section 10 Animations Exercise

3)

The graphic files (fire 0 to fire 11) are already saved in the sub directory. Display the Sports Boilers page and add a new dynamic object for Boiler 1 (D7). Edit the objects properties to match those shown.

4)

Place the animation over the boilers sight glass. (Remember Simulation mode)

5) 6)

Repeat the above for Boiler 2 (D8). Exit page Config. and check your work.

Trend - 963 v3 Eng -Rev 03

173

Section 10 Analogue Graphics


Analogue graphics are similar to animations. Each set of graphics needs to be stored in its own sub directory.

A text file that lists that sequence of the graphics is saved as <filename>.analogue

This .analogue file is referenced in the Analogue File field for the dynamic object.

Each graphic is displayed as the analogue value is reached, and is held until the next or previous value is reached.

Trend - 963 v3 Eng -Rev 03

174

Section 10 Analogue Exercise

This Exercise will guide you through creating and displaying an analogue graphic that represents the status of an analogue input.

1) 2)

Open Notepad and create the animation file shown opposite. Save the file as Thermometer.analogue in the following directory.

C:\Program files\Trend Control Systems\963\analogue\Thermometer\

Trend - 963 v3 Eng -Rev 03

175

Section 10 Analogue Exercise

3)

The graphic files (0 to 27) are already saved in the sub directory. Display the Admin Office page and add a new dynamic object for Room Temperature Sensor (S2). Edit the objects properties to match those shown.

4)

Place the analogue graphic over the broken thermometer on the wall. Exit page Config. and check your work.

5)

Hold the sensor that is connected to input channel 4 (Sensor 2) of your controller. The graphic changes as the temperature rises.

Trend - 963 v3 Eng -Rev 03

176

Section 11 963 Scripts

Aims: To enable the operator to Use understand the concept of 963 scripts

Objectives: By the end of the section the operator should be able to Describe how to engineer a 963 script

Trend - 963 v3 Eng -Rev 03

177

Section 11 Script Files


Script files are a series of actions that have been created within a text document i.e. notepad and then saved as a .TXT file. The script file is a list of 963 actions and Trend text comms, which are then run in sequence.

This example displays a series of schematic pages. The SLEEP action is a pause counted in milliseconds. An Static object could be configured with the following action :SCRIPT scripts\Lightingtour.txt

Trend - 963 v3 Eng -Rev 03

178

Section 11 Scripts
It is possible to add a simple question to a script file thus giving the Operator a choice of what to do next. The question will appear as a simple box on screen with Yes or No buttons. To set the question up in a script file 963 looks for a line starting with a ? E.g. ?Do you wish to look at the AHU. If the operator clicks on the Yes then the next line in the script is executed. If No then the 2nd line after is executed and the Script is ended.

Trend - 963 v3 Eng -Rev 03

179

Section 11 Scripts Exercise

It is possible to run a script file from within a script file by using the following action SCRIPT scripts 1) 2) Create a new script file with the Actions below. Save the file as Lightingtour.txt into the same location

Trend - 963 v3 Eng -Rev 03

180

Section 11 Scripts Exercise

3)

Enter Configure Page mode on the Meters page.

4)

Drag the Lightingtour.txt script onto the page.

5) 6) 7)

Edit the button, Give it meaningful label. Set the PIN level to 10 Exit page Config. Mode and test.

Trend - 963 v3 Eng -Rev 03

181

Section 11 The Script Controls


When a script file is initiated all other 963 actions are held up, therefore at some stage a script file may need to be interrupted. This is done using the script controller

The Script controller allows you to; Pause Scripts Resume Scripts and Cancel and prevent all scripts from starting !

To hide the Script Control F1 to display the Information Centre and then click on the button labeled Show Script Control or just press the Esc key

Trend - 963 v3 Eng -Rev 03

182

Section 12 Extra System Schematics

Aims: To introduce and demonstrate:


The 963 Variable actions. Displaying an IQ controller status. 963 Lan Map.

Objectives: By the end of the section you will be able to Engineer buttons to synchronize the PC and controller clocks. Engineer on a schematic, data from a non standard dynamic source. Engineer and produce a numeric map of the local Trend LAN

Trend - 963 v3 Eng -Rev 03

183

Section 12 963 System Variables


963 can use System Variables, these allow us to use information from the 963 and its database. The System Variable <MODBY> will tell us who last engineered a schematic page. <TIMEON> will display how long 963 has been running. These System variables can be used in the To Display field of a Static object, mixed with Trend Text Comms in Scripts or as part of a SEND action. System variables need to be written between <.> Take a look at the 963 Variables Pamphlet that is included with your notes.

Trend - 963 v3 Eng -Rev 03

184

Section 12 963 System Variables


In addition to the previous examples the following can be used to return data from the PC clock <PCHOUR> <PCMIN> <PCDAY> <PCSEC> <PCMONTH> <PCYEAR> 2 digit year <PCWKDAY> Trend weekday (1=mon, 7=sun) <TIME>

These variables could be used to send the PC time to an controller using the SEND action E.g. SEND L0O24T(H=<PCHOUR>, N=<PCMIN>)

This SEND action could be launched every day by the event scheduler to synchronise the IQ Clock with the PC Clock.

Trend - 963 v3 Eng -Rev 03

185

Section 12 Questions with 963 Variables

It is possible to set up more flexibility with some of the 963 Actions, by asking the user questions when they click on a button.

Here are some examples :LOGINAS <?Enter your name> Careful with this one, it needs a space between the S and the < SEND L0O24W14(S=<?Enter I to turn on or O to turn off>)

SEND L0O24K<?Enter Knob number to be adjusted>(V=<?Enter new value>)

Trend - 963 v3 Eng -Rev 03

186

Section 12 The SEND action


The SEND action allows Text comm messages to be sent to Trend devices. Create a new static object with the SEND action followed by the required text comm

Examples of the SEND action. SEND L0O24R(A=<CNC>,R=<LAN>) - Would configure the alarm destination of outstation 24 to the address of the 963 supervisor.

SEND L0O24K1(V=<?Enter a value>) - Would set Knob 1 on Outstation 24 to a value specified by the operator. SEND L0O24W1(S=I) - Would set Switch 1 in Outstation 24 to be ON (I and O not 1 and 0 when
sending digital states).

SEND L0O24K/*OccSet*(V=19) - Would set a value of 19 in any Knob with OccSet in its label.

Trend - 963 v3 Eng -Rev 03

187

Section 12 - Exercise - 963 Variables and Lan Map

We have been asked by the client to set up a new schematics page displaying some useful system information. The page needs to be secured, so should only be accessible by users with a PIN >90. The Users need access to the page from the Sports Complex Home page. They will also need a button to get back there. Create the new System Info page in the Controller Folder that already exists.

Trend - 963 v3 Eng -Rev 03

188

Section 12 - Exercise - 963 Variable and Lan Map

1)

Place 4 new static objects on the page with the following in the to display field
Current IP address<IP> Current Trend address<CNC>on LAN <LAN> 963 has been running for <TIMEON> We are using <VER>

Trend - 963 v3 Eng -Rev 03

189

Section 12 LAN Mapping with 963

2)

Create a New Dynamic Object, with the properties shown opposite. For the item reference type in lowercase l (l for Lima). Set up any valid Trend network address for the node address Standard LAN addressing rules apply i.e. to map the Internetwork set the LAN address to 126. To map a remote or autodialed LAN set the appropriate LAN number. Set the Decimal Places to -1

Trend - 963 v3 Eng -Rev 03

190

Section 12 - Exercise - 963 Variable and Lan Map

3)

Place three new Dynamic objects on to the page, with the following in the Item fields. R(D) Controller Identifier. T(H) Controller Hours T(N) Controller Minutes

4)

Modify and arrange the objects to give a useful display, consider the use of Label, Value and Units. Dont forget a button to take the user back to Home page !

5)

Trend - 963 v3 Eng -Rev 03

191

Section 13 Managing Workgroups and Users

Aims: To enable the engineer to


Manage Workgroups and users Assign suitable workgroup parameters

Objectives: By the end of the section the engineer should be able to Describe how to enable and control access for users Engineer a universal Login page for all users.

Trend - 963 v3 Eng -Rev 03

192

Section 13 - Adding a Workgroup


Before adding a Workgroup to 963 we need to consider the following questions :Who, is going to use the 963 ? What, do they want to do with it ? Where, do they want to do it ?

For example, Who, Mechanical Engineer. What, look at the boilers. Where, via schematics.

This should give you some idea of what this user will want to do when they log in. e.g. login action of GOTO pages\Sports Complex Plant\Sports Boilers.tss Or put simply, take them to the relevant area of interest.

Trend - 963 v3 Eng -Rev 03

193

Section 13 - Deciding on a Log in Action


To help decide who, what and where the users are going to go when logging in to 963 it may be useful to produce a sketch or flow chart, indicating how the pages may be linked. (An example is on the next page). It may be beneficial to have a universal login route for all users, for example set up a schematic page that has buttons engineered for each individual or group of users. This could be the default schematic page, so the users would have to login before they can browse around 963. Other Items to consider are: Pin Levels Time Out Periods Access to Config, Device Viewer, Alarms Enable Engineering rights Client/Server Access Being able to close/minimise 963

Trend - 963 v3 Eng -Rev 03

194

Section 13 - Deciding on a Log in Action

The Button action GOTO<page> allows the uses to navigate to other pages.

The Login action GOTO<page> takes the users to their pertinent start page.

Trend - 963 v3 Eng -Rev 03

195

Section 13 - Workgroups and Users


Workgroups hold the access rights and the Users.

Users hold only a name and password.

Select the Users mode from the mode buttons or menu bar.

To add a Workgroup, right click on an empty part of the navigator window and select add a workgroup from the menu.

To add a User right click on a workgroup and select Add User from the menu.

Trend - 963 v3 Eng -Rev 03

196

Section 13 - Adding Workgroups Exercise


1) Add the following Workgroups and Users to your Project.

2)

Set the Workgroup name as Facilities Co-ordinators.

3)

Set the other parameters as follows :PIN Level = 10 Inactivity time = 5 Login action = (leave blank)

4)

Start up page, Click choose Start up page and select the Admin Office page from the list.

Trend - 963 v3 Eng -Rev 03

197

Section 13 - Adding Workgroups Exercise

5)

Click on the View Tab, Select only Diary and Scheduler for these users to access. Note, the left hand pane is a list of all available access rights, the right hand pane contains those that the workgroup will have access to. This principal is continued through the remaining Tabs.

Trend - 963 v3 Eng -Rev 03

198

Section 13 - Adding Workgroups Exercise

6)

Click on the Configuration Tab this is a list of engineering tasks that the workgroup can perform.

Use the settings shown opposite.

Trend - 963 v3 Eng -Rev 03

199

Section 13 - Adding Workgroups Exercise

7)

Click on the folders Tab this is a list of the schematic folders that the workgroup can access. Use the settings shown opposite. When finished, click OK Next we need to add a user to the workgroup that we have just created.

8)

Trend - 963 v3 Eng -Rev 03

200

Section 13 - Adding Workgroups Exercise

9)

Right click on the Facilities Co-ordinators workgroup that you have just created and select Add User from the menu.

10) Name the User as Early Shift and give them a password of Early1 Your new user is now set up and you may access their login page by clicking on their name in the navigator in user mode.

Trend - 963 v3 Eng -Rev 03

201

Section 13 - Adding Workgroups Exercise

To Edit the Early Shifts user login page 1) Unfold the navigator and select the Users Icon 2) Right click on page to enter page config mode. 3) Edit the Static objects to match those shown opposite The ID photos can be found in 963\bmp\trend uni\People Add a button with the action CHANGEPASSWORD

Trend - 963 v3 Eng -Rev 03

202

Section 13 - Adding Workgroups Exercise

4)

Add the following Workgroup to your Project.

5)

Set the Workgroup name as Energy Management.

6)

Set the other parameters as follows :PIN Level = 10 Inactivity time = 5 Login action = (leave blank)

7)

Start up page, Click choose Start up page and select the Meters page from the list.

Trend - 963 v3 Eng -Rev 03

203

Section 13 - Adding Workgroups Exercise

Energy Management View settings

8)

Use the settings shown opposite and on the following page for this workgroups rights. The Energy manager has access only to User and Schematics modes of 963

9)

Trend - 963 v3 Eng -Rev 03

204

Section 13 - Adding Workgroups Exercise

Energy Management Configuration settings

Energy Management Folder settings

Trend - 963 v3 Eng -Rev 03

205

Section 13 - Adding Workgroups Exercise

10) Right click on the Energy Management workgroup that you have just created and select Add User from the menu. 11) Name the User as Energy Manager and give them a password of Energy1 .

Trend - 963 v3 Eng -Rev 03

206

Section 13 - Adding Workgroups Exercise

12) Edit the Energy Managers user login page Edit the Static objects to match those shown opposite The ID photos can be found in 963\bmp\trend uni\People Add a button with the action CHANGEPASSWORD

Trend - 963 v3 Eng -Rev 03

207

Section 13 - Adding Workgroups Exercise

Add the following Workgroup to your Project. Set the Workgroup name as Site Supervisor Set the other parameters as follows :PIN Level = 90 Inactivity time = 10 Login action = (leave blank)

Start up page, Click choose Start up page and select the Trend University Home page from the list.

Trend - 963 v3 Eng -Rev 03

208

Section 13 - Adding Workgroups Exercise

Site Supervisor View settings

Use the settings shown opposite and on the following page for this workgroups rights. The Site Supervisor has access to all modes of 963 except IQ configuration

Trend - 963 v3 Eng -Rev 03

209

Section 13 - Adding Workgroups Exercise

Site Supervisor Configuration settings

Site Supervisor Folder settings

Trend - 963 v3 Eng -Rev 03

210

Section 13 - Adding Workgroups Exercise

Right click on the Site Supervisor workgroup that you have just created and select Add User from the menu. Name the User as Supervisor and give them a password of Supervisor1 .

Trend - 963 v3 Eng -Rev 03

211

Section 13 - Adding Workgroups Exercise

Edit the Supervisors user login page Edit the Static objects to match those shown opposite The ID photos can be found in 963\bmp\trend uni\People Add a button with the action CHANGEPASSWORD

Trend - 963 v3 Eng -Rev 03

212

Section 13 - Adding Workgroups Exercise

Add the following Workgroup to your Project. Set the Workgroup name as Plant Engineers Set the other parameters as follows :PIN Level = 50 Inactivity time = 10 Login action = (leave blank)

Start up page, Click choose Start up page and select the Plant Control Panel page from the list.

Trend - 963 v3 Eng -Rev 03

213

Section 13 - Adding Workgroups Exercise

Plant Engineers View settings

Use the settings shown opposite and on the following page for this workgroups rights. The Plant Engineers have access to Alarm Viewer as well as the basic Users and Schematic modes

Trend - 963 v3 Eng -Rev 03

214

Section 13 - Adding Workgroups Exercise

Plant Engineers Configuration settings

Plant Engineers Folder settings

Trend - 963 v3 Eng -Rev 03

215

Section 13 - Adding Workgroups Exercise

Right click on the Plant Engineers workgroup that you have just created and select Add User from the menu. Name the User as Mechanical Engineer and give them a password of Mech1 .

Trend - 963 v3 Eng -Rev 03

216

Section 13 - Adding Workgroups Exercise

To Edit the Mechanical Engineers user login page Edit the Static objects to match those shown opposite The ID photos can be found in 963\bmp\trend uni\People Add a button with the action CHANGEPASSWORD

When you have finished setting up all the workgroups and users, try logging in as each of them in turn. Notice the different Modes, Folders, buttons etc. available to each group.

Trend - 963 v3 Eng -Rev 03

217

Section 13 - Universal Login Page Exercise

Create the Log in buttons as shown below, also add a Log out button to complete the page.

If you wanted a single button for all users to Login with, use the action LOGINAS <?Please enter your user name to Log in>

Trend - 963 v3 Eng -Rev 03

218

Section 14 The Scheduler

Aims: To enable the engineer to


Explain the function of the Scheduler

Objectives: By the end of the section the engineer should be able to Use the scheduler to Auto launch 963 Actions

Trend - 963 v3 Eng -Rev 03

219

Section 14 The Scheduler


We can use the 963 to carry out certain actions automatically sometime in the future and repeat the action if required. Data recording, synchronising clocks and database backups are some examples of how the scheduler can be used. When we configure these actions, they are stored and handled by the 963 Scheduler.

Trend - 963 v3 Eng -Rev 03

220

Section 14 The Scheduler


To configure auto data recording for a sensor.
Display a graph of the sensor, then from the menu bar select Data recording, then Configure automatic data recording or right click on a sensor in Device Viewer and select the above option from the menu.

After selecting the plotting interval and the graph type, you will be presented with the Scheduling options.

Trend - 963 v3 Eng -Rev 03

221

Section 14 Recording a Graph Automatically


A dialogue box is shown, it is used to configure when and how many times 963 will record the graph Set the time and date of the 1st recording (ensure set to the future) Choose the recording interval options are: 5,10, 15, 30, 60 minutes 12, 24 hour, Weekly, Monthly, Yearly Choose how many times the recording is to occur Set the weekdays for recording Click Next when finished

Trend - 963 v3 Eng -Rev 03

222

Section 14 Recording a Graph Automatically


The last step is a dialogue window giving details about how the recording is configured

Check the recording is set up correctly then click Finish

Trend - 963 v3 Eng -Rev 03

223

Section 14 Recording a Graph Automatically


The programmed recording can be viewed in the Scheduler. The navigator has filters for selecting which type of actions you want to view. A New button allows you to configure a new Scheduled event.

Refresh List to view newly created events in the Schedule list. View and edit scheduled events.

Trend - 963 v3 Eng -Rev 03

224

Section 15 Alarms and Audits

Aims: To enable the operator to Describe the different alarms/events. Describe the various ways that Alarms are announced.

Objectives: By the end of the section the operator should be able to Use the Alarm Panel to acknowledge and Silence an Alarm. Interpret Alarm information. Perform an Alarm action.

Trend - 963 v3 Eng -Rev 03

225

Section 15 Alarms and Audits


963 version 3 maintains an audit trail of changes that are made which effect system performance; it records who made the change, what the change was and when it occurred. The changes, or events, can be configured to generate an alarm action to ensure that an attempt to breach security does not go undetected. The auditing cannot be turned off. Note that changes made in the IQ configuration through 963 are not logged. Configuration mode can and should be disabled by the System Administrator. The controllers themselves can be adjusted to raise alarms when any user makes a change. To ensure maximum security, it is recommended that the PC running 963 be configured prevent unauthorised access both to the PC, and files on it using standard Windows security features.

Trend - 963 v3 Eng -Rev 03

226

Section 15 Alarms and Audits


To perform an Audit on an item right click on the object in the navigator and select Show audit info for item.

This opens the list of events associated with the selected Item.

Trend - 963 v3 Eng -Rev 03

227

Section 15 Alarms and Audits


Area Alarm Filters Alarm Groups Automatic data recording Diary Downloads Exceptions IQ parameters Normal times Program Retransmission Scheduled action Security Site, LAN, Controller or Item. Diary groups Users Workgroups Event Logged Adding, removing and editing. Adding, removing and editing. Any automatic data recording function also raises events on success and failure. Automatic downloads. Adding, removing and editing. Changes through the 963-user interface. Adding, removing and editing. Start up, and shutdown. Adding, removing and editing. Adding, removing and editing Logging in, logging out, when a user is locked out an alarm is reported. Deleting and editing. Adding, removing and editing. Adding, removing and changing the password. Adding, removing and editing.

Trend - 963 v3 Eng -Rev 03

228

Section 15 Alarms Configuration


Before Alarms can be received at the 963, the rest of the system must be set up to deliver them ! Modules capable of sending alarms need have their alarms enabled. This allows the alarms to be sent to the controllers Alarm log. Using 963 in Config. Mode, we can enable alarms points in IQ1 and IQ2 controllers, for IQ3 controllers this will open the Web pages. When connected to the IQ3 LAN via 20mA LAN, we can only make these changes using Device Viewer Mode.

Trend - 963 v3 Eng -Rev 03

229

Section 15 Alarms Configuration - Exercise


Check that the alarms are enabled within the following modules : S1 to S6 and I1 to I4. 1) Go to the Device Viewer, right click on the module and select Edit Item from the Menu. This will display the Adjustment template for the module. 2) Right click on the module you want to enable and select Adjust Point 3) You will be prompted to enter a new value, I = On and O = Off

Trend - 963 v3 Eng -Rev 03

230

Section 15 Alarms Configuration


You may find that some parameters are missing from the Adjustment Module Template, not all parameters are included in all versions of 963 ! You can change what is displayed in these windows by editing the Template file, using Notepad. Using Windows Explorer, Navigate to the 963 Template folder, the Adjustment Module Templates are listed by Module Letter i.e. S = Sensors K= Knobs etc. There are two sets of templates, the folder labelled q holds the templates for IQ3s

Trend - 963 v3 Eng -Rev 03

231

Section 15 Alarms Configuration

You can add or remove parameters that are displayed in the Adjustment Modules. The syntax used is as show here.

Trend - 963 v3 Eng -Rev 03

232

Section 15 Alarms Configuration


We have now enabled Alarms for the Sensors and Digital inputs but they will only go as far as the controllers Alarm buffer. We still need to configure the Alarm Address in the controller, this tells the controller where to send alarms, in this case the 963 on our desk. In the Trend University project we have setup a button with a Script to do this for us. Go to the Alarm Destination Schematic page (in the Controller folder)

?
233

Trend - 963 v3 Eng -Rev 03

Section 15 Alarms Configuration

We have a Script attached to a button, which will send the 963 address to the controller. SEND L0O24e1(A=<CNC>) Click on the button to set the alarm address for your controller. The Alarms can now reach the 963. You can see, from the data on this page, that there is a mismatch between the alarm address in the controller and the address of the 963.

Congratulations, you have just setup the alarm handling for your network !

Trend - 963 v3 Eng -Rev 03

234

Section 15 Alarms Overview


The alarm is received at the 963, from the controllers via the network.

The 963 has optional Alarm Panels with Filters to catch various alarms.

The incoming Alarm is checked against each filter, until it finds a match, the panel is then displayed.

Alarms are.. Logged to the SQL database. i96x_data.mdf

and can also trigger other actions in 963 and be retransmitted to a printer, mobile phone, e-mail address or another 963

Trend - 963 v3 Eng -Rev 03

235

Section 15 Setting up Alarm Notification


To Configure Alarm handling in 963 the process consists of 3 steps.

Engineer Filters to catch particular Alarms

Engineer Alarm Groups with required Alarm Actions and Alarm Panel options

Link Filters to Alarm Groups

Trend - 963 v3 Eng -Rev 03

236

Section 15 Creating Filters


Right click on Alarm Filters in the Navigator, then select Create a new Filter, from the Menu.

The Filter editor is where the Filter criteria are set up, LAN, OS, Alarm Codes etc.

Clicking in a criteria field will show all options available, in the Suggested Items pane.

You can test your filter for matching points and matching alarms.

Trend - 963 v3 Eng -Rev 03

237

Section 15 Filter Criteria Options


Tele - Site Telephone numbers or IP address LAN - Specify LAN numbers OS - Specify device addresses Alarm code - Specify unique four letter alarm codes associated with each different type of alarm e.g. HIGH, CHIH, OUTL Module code or Item Label - Specify module configuration code e.g. S1, D1 or S1, alternatively specify a matching label used by IQ modules e.g. AHU Supply Temp or *Supply Temp* Text of alarm description - Specify unique alarm text associated with each different type of alarm e.g. Sensor Fail, Digin On Occurred Alarm priority - New alarm priority levels associated with new Alarm Strategy modules in ver3 firmware. Range 255 to 0 255 = High 0=Low

Trend - 963 v3 Eng -Rev 03

238

Section 15 Creating Filters, 963 Help


1) Use the 963 Help to find lists of alarm codes that can be filtered by the 963. 2) Click Help on the menu bar, select the Engineering Manual. 3) Use the Search feature to look for Alarm codes. 4) There are 2 types of Alarm code that we can filter, External and Internal. 5) Read each of the help sections for an explanation of the various alarms.

Trend - 963 v3 Eng -Rev 03

239

Section 15 Filter Examples


This Filter will catch alarms from all parts of the system because the * wildcard has been used in these fields. The Alarm code CONL has been used in this field so only Controller On Line alarms will be caught.

Trend - 963 v3 Eng -Rev 03

240

Section 15 Filter Examples


This Filter will catch alarms only from Outstations addressed as 24. The Alarm codes ADJU and ADJF are internal 963 alarms, the K* specifies any Knob. So this Filter will catch only adjustments made to Knobs on outstations addressed as 24.

Trend - 963 v3 Eng -Rev 03

241

Section 15 Filter Examples


This Filter will catch all Readback alarms from drivers with pump in the label. The alarm code SDGT and CDGT catch the Readback alarms. The *pump* item label refines the filter so that only items with pump in the label are filtered Dont forget label matching needs to be in and is case sensitive.

Trend - 963 v3 Eng -Rev 03

242

Section 15 Creating Filters Paper Exercise

1)

Set up a filter that will catch Sensor failed alarms from Room Temperature sensors anywhere on the system.

2)

Set up a filter that will catch Driver Maintenance alarms for any Boiler controlled by outstations 15 and 16 on LAN 11

Trend - 963 v3 Eng -Rev 03

243

Section 15 Filter Exercise

We are now going to create some filters for the Sports complex project. Try creating the following filters :1) Alarm Filter 1 to catch any Alarm from digital input 1 on your controller, Label the Filter Emergency Call Alarms. 2) Alarm Filter 2 to catch any Alarm from a Pressurisation unit, Label the Filter Digital Plant Alarms. 3) Alarm Filter 3 to catch any Alarms from Space temperature sensors, give the filter a suitable label. 4) Alarm Filter 4 to catch any Alarms from Plant temperature sensors, give the filter a suitable label.

Trend - 963 v3 Eng -Rev 03

244

Section 15 Creating Alarm Groups


Right click on Alarm groups in the Navigator, then select add Group, from the Menu.

The Alarm Group editor is where the group properties are set up. The first tab sets the properties for the Alarm Panel and for any action that we want to trigger when the group catches an alarm.

Trend - 963 v3 Eng -Rev 03

245

Section 15 Creating Alarm Groups

Give the Group a pertinent name.

Set up a 963 server action, this can be any of the standard actions. This action can also be linked into a diary group, so that a different out of occupation action could be engineered.

Enable the Alarm Panel, set colour, beep and set a action for the action button.

Trend - 963 v3 Eng -Rev 03

246

Section 15 Alarm Groups


The Alarm to Workgroup Set up allows an alarm action in addition to the alarm panel to be carried out if certain operators are logged in as either 963 Clients or to the 963 Server.

Specify the logged in Workgroups to be informed.

Set up an additional alarm Action (will only be performed if a specified workgroup is logged in).

Choose a specific colour to attach a coloured flag to the Client Alarm.

Trend - 963 v3 Eng -Rev 03

247

Section 15 Alarm Groups


The Print Options Tab allows alarm Printing to be configured.

Enable or Disable Alarm printing for each alarm group.

Specify what needs printing by editing the contents, i.e. add your own text or the 963 alarm variables e.g. <LABEL>

Define a specified printer for this alarm group (select the printer from. a list that have been configured on the PC Windows Settings - Printers

Trend - 963 v3 Eng -Rev 03

248

Section 15 Alarm Groups

The Filters Tab allows you to select which Alarm Filters will trigger this Alarm Group.

The list of all available Alarm Filters that have been configured.

The Alarm Filters that have been selected to trigger this Alarm Group.

Trend - 963 v3 Eng -Rev 03

249

Section 15 Alarm Groups Exercise

Create the Emergency Call Alarm Group with the settings shown on this and the next page.

Trend - 963 v3 Eng -Rev 03

250

Section 15 Alarm Groups Exercise

Trend - 963 v3 Eng -Rev 03

251

Section 15 Alarm Groups Exercise

Create the Plant Alarms Group with the settings shown on this and the next page.

Trend - 963 v3 Eng -Rev 03

252

Section 15 Alarm Groups Exercise

Trend - 963 v3 Eng -Rev 03

253

Section 15 Alarm Groups Exercise

Create the Space Temperature Alarms Group with the settings shown on this and the next page.

Trend - 963 v3 Eng -Rev 03

254

Section 15 Alarm Groups Exercise

Trend - 963 v3 Eng -Rev 03

255

Section 15 Alarm Lookup Table


963 Can be set to auto action alarms by editing the Alarm Codes table. Go to the Alarm Viewer. Click on the Setup tab. Click on the button labelled Alarm Codes, this will display the Alarm Codes lookup table. Identify the alarm you wish 963 to Auto Action and set the alarmRequiresAction value to a T(rue) or F(alse).

If the S2.ini file is edited and the following is added, [ALARMS] HideAutoAction=1 The alarms that are then set up to be Auto Actioned are also hidden in 963 (they do not appear in Incoming Alarms etc... however they are still logged as historical alarms in the Alarm Viewer)
Trend - 963 v3 Eng -Rev 03

256

Section 15 Writing Alarms to a Separate Log.


If you need to store alarms or any data or comments in a separate file in addition to the i96x_data.mdf file. Use the WRITETOTEXTFILE action, this can be used to write messages to a .TXT file. To use the WRITETOTEXTFILE action can be used with: Schematic Actions Event Scheduler Script Files The action needs to be set up in the following format: WRITETOTEXTFILE C: \Alarms\boiler house.txt, <ALLLABELS>

The above example will write all labels for an alarm or alarms into a text file labelled boiler house.txt located in the C:\Alarms directory. Note the directory must exist first. By default any new alarms will be added to the file. To overwrite the file each time add ||1 to the end of the action. Example WRITETOTEXTFILE C: \Alarms\boiler house.txt, <ALLLABELS>||1

Trend - 963 v3 Eng -Rev 03

257

Section 15 Alarm Variables <.......>


The print field can be comprised of text or part of the alarm message, the actions on the following page, can be used to extract information from the alarm: E.g. An alarm has occurred from <LABEL> at <TIME> from device <OS> <LAN> Note these Alarm Variables can also be used in other 963 actions e.g. WRITETOTEXTFILE, MESSAGE, SEND etc....
<ALARMDESC> <LABEL> <MODULE> <ALARMCODE> <LAN> <OS> <OSLABEL> <TIME> <ALL> <ALLLABELS> <SITE> <NEWLINE> <TAB> <LANLABEL> Alarm description e.g. SENSOR FAIL OCCURRED Item label e.g. Outside Air Temp Module code Standard Trend code e.g. OUTL LAN number Outstation number Outstation Label - from device view Time of occurred alarm Displays all the above data Displays only labels from the alarm Label of site Adds a new line to the message Puts a tab break in the message Label of LAN from 963 Device Viewer

<ALARMGROUP> Inserts the label of the alarm group that the alarm matches.

Trend - 963 v3 Eng -Rev 03

258

Section 16- Alarm Retransmission

Aims: To enable the engineer to Retransmit an alarm to a second 963 over the Trend LAN, Notify an operator that a retransmitted alarm has arrived. Use the REMOTE action.

Objectives: By the end of the section the engineer should be able to Retransmit an alarm to a 963 supervisor. Send a message or display a schematic page on a remote 963 using the REMOTE action.

Trend - 963 v3 Eng -Rev 03

259

Section 16- How do I Retransmit an Alarm ?


When setting up alarm retransmission the following needs to be decided 1) WHERE to retransmit the alarm. 2) WHICH alarms need to be retransmitted. 3) WHAT details of the alarm need to be retransmitted.

963 has two stages that need to be set up when alarm retransmission is engineered. Step 1 (WHERE) Set up all the Retransmission Destinations, i.e. Set up details for each target (e-mail, mobile phone, printer etc...) that alarms are going to be sent to. Step 2 (WHICH and WHAT) Edit the alarm groups and set them up with a RETRANSMISSION action and a Retransmission Destination

Trend - 963 v3 Eng -Rev 03

260

Section 16- Retransmit Destination


Right click on All retransmission destinations icon, then select Create a new retransmission destination.

This displays the retransmission editor.

Trend - 963 v3 Eng -Rev 03

261

Section 16- Retransmit Destination


Give the retransmission group a pertinent label, this is important for linking the Alarm Destination Details to the appropriate Alarm Group (more later) Click on the dropdown button and select the type of retransmission.

Retry interval time (minutes)

Set the number of retries as required. Set an alternative retransmission destination (the alarm would be retransmitted here after the number of retry attempts has been exceeded).

Trend - 963 v3 Eng -Rev 03

262

Section 16- Batching Alarms for Retransmission


Wait until the hours defined in this diary group before sending any pending alarms - This is used for grouping together non urgent alarms and retransmitting them later during a certain time period when the network is not so busy

Maximum Batch is used where alarm retransmission is used for multiple target destinations. It is designed to be used if a continued stream of alarms arrive, by setting a batch size e.g. 10 it will retransmit ten alarms to the first site then the same ten to a second site and so on, then retransmit the next batch.

Trend - 963 v3 Eng -Rev 03

263

Section 16- Retransmission to a 945,962 or 963

Set the type of destination to Free format.

Set the target retransmission address and LAN number and Telephone number (if retransmitting to a 963 on Ethernet then set this up to the Virtual CNC address of the EINC).

Extra text field for appended message. Leave this empty as it causes the information on the receiving Supervisor to be displaced.

Timeout must be set to at least 2000 (milliseconds)

Trend - 963 v3 Eng -Rev 03

264

Section 16 Exercise - Alarm Retransmission

1)

Use the device Viewer to find the addresses of the 963 Supervisors. Work as a pair using one 963 to send the alarms and one to receive.

2)

On the 963 that is going to send the alarms return to the Alarm View and create a new Retransmission Destination labelled Darkside 963 Type of retransmission Number of retries - 3 Interval between retries - 1 minute - Free format

3) 4)

Set the alarms to go to the other 963 supervisor address and LAN. Dont add any additional text (as we are going retransmit all the information we need in the main message field).

5)

Timeout set to

- 5000 milliseconds.

Trend - 963 v3 Eng -Rev 03

265

Section 16- Alarm Retransmission Exercise

It is possible to Send a test message to check that the destination details are configured correctly.

6)

Click on the Send Test Message button .

7)

Go to the Alarm View on the receiving 963 Supervisor and check the Incoming Alarms window.

8)

If the test message has been received, Click on OK to save. If not ask your tutor.

Trend - 963 v3 Eng -Rev 03

266

Section 16- Retransmit Destination

Right click on the appropriate alarm group,. Select Edit

This displays the alarm group editor, Click to choose an action of RETRANSMIT , you will be given a list of possible destinations for the retransmission.

Trend - 963 v3 Eng -Rev 03

267

Section 16- Retransmit Destination


Make your selection from the list. In this case we are have only one destination, but you need to select it.

Any text within the <

> (message field)

will be replaced with data from the system e.g. <CNC> <LAN>

Trend - 963 v3 Eng -Rev 03

268

Section 16 Exercise - Alarm Retransmission

This exercise will demonstrate retransmission of Sensor alarms using the <ALL> variable and the I1 alarms using the <963CODED> variable. The main objective of this exercise is to demonstrate the difference in how the alarm information is formatted using the 2 different variables. Still working in the same pairs, check that the alarm destinations are set up. 1) Edit the Space Temperature Alarms Group and set the Server action to retransmit to your partners PC. The message field is important because what is set up here will be sent to the other 963. Set the alarm up to send <ALL> 2) 3) Test, that the Alarms are retransmitted OK. Set up the Emergency Call Alarm to be retransmitted using the <963CODED> variable. Note the difference in how the information is presented on the receiving 963. 4) On the Darkside 963, engineer an alarm panel to catch the incoming retransmissions.

Trend - 963 v3 Eng -Rev 03

269

Section 16- Retransmit to SMTP e-mail


Select E-mail via SMTP (Simple Mail Transport Protocol). This then allows specific parameters to be set up for this type of retransmission.

Set up target e-mail addresses and e-mail address for the 963 (so that the recipient knows where the E-Mail has come from).

Enter the name of the server for the buildings e-mail network. Also specify the SMTP server port umber - normally this is set to 25 Text for the subject and message fields. These are then sent as the subject and the e-mail message.

Trend - 963 v3 Eng -Rev 03

270

Section 16- Retransmission to a Printer


Set the type of destination to Trend text message (PNC...) Set the target retransmission autodial number, address and LAN number.

Set up any retry or retransmission failure actions.

Extra text field for appended message.

Trend - 963 v3 Eng -Rev 03

271

Section 16- Retransmission to a Printer


To retransmit alarm information to a PNC the message format needs to be <FORPNC>. E.g. RETRANSMIT 3,(Alarm printer),<FORPNC>

This will automatically configure your alarms to be printed in the following format: -

<LABEL><TAB><ALARMDESC><TAB><TIME> Site: <SITE><TAB>LAN: <LANLABEL><TAB>OS: <OSLABEL> <TELE>L<LAN>O<OS> <MODULE> <ALARMCODE>

Trend - 963 v3 Eng -Rev 03

272

Section 16- Retransmission to Multiple Addresses


Set up your Alarm Retransmission Destination details for each target destination. E.g. Bureau 963

Duty Engineer Mobile Security Printer

Create an Alarm Group for each target destination with a Retransmit Action.

Link the required alarm filters to each alarm group (use the same filters in each Alarm Group).

Trend - 963 v3 Eng -Rev 03

273

Section 16- The REMOTE action


The REMOTE action can be used to send messages and actions to other 963s. Set up a New Static Object with the REMOTE action, Some examples are :REMOTE L0O67 GOTO Pages\Sports Complex Plant\Sports Boilers.tss This would action the 963 at address 7 to display the Sports Boilers page.

REMOTE L0O4 MSG Hello, can you reset AHU frost trip! This would display an popup message box on the remote 963, it can also be used for instant messaging between 963s by using the example overleaf.

Note: The MSG action message is limited to a maximum of 80 characters.

Trend - 963 v3 Eng -Rev 03

274

Section 18 Projects and Backing Up

Aims: To introduce the engineer to Configuring 963 to run with numerous projects Using 963 to Archive and Backup the database file.

Objectives: By the end of the section the engineer should be able to Describe how to set up 963 to engineer several projects on a PC with one 963 License. Describe the ARCHIVEDATA and BACKUPDB actions.

Trend - 963 v3 Eng -Rev 03

275

Section 18 Several Projects on one 963 License


It is Possible to work with a number of 963 projects on one PC. This is particularly useful for service and project work. To enable project handling, edit the following setting in the S2.INI file.

With this option configured, 963 will access the S2.exe file, then display a standard windows browser allowing you to navigate to the desired project.

Trend - 963 v3 Eng -Rev 03

276

Section 18 Projects Mode Exercise

1) 2)

Shut down 963 and using Windows explorer, navigate to the 963 directory. Locate the S2.INI file and open it with Notepad.

3)

Locate the [EXTRA] section of the file and ensure there is a line that reads exactly as follows :- SelectProjectDir=1

Trend - 963 v3 Eng -Rev 03

277

Section 18 Projects Mode Exercise

4) 5) 6) 7)

Restart 963. You will be presented with a browser window. Navigate to the require 963 project, then click OK. Your 963 will now open with the selected project.

Trend - 963 v3 Eng -Rev 03

278

Section 18 The 963 Project Backup


If using Project mode or taking Site backups, which folders and files do you need?

All the supporting folders (i.e. pictures, animations, pages, scripts, etc). The i96x_data.mdf & i96x_log.ldf from the database folder The tcommsrv.ini & s2.ini from the main 963 folder.

If the databases have been archived & the archives are still needed, there are usually 3 files for each archive in the main 963 folder, xxxxxx.ldf, xxxxxx.mdf xxxxxx.ndf

Trend - 963 v3 Eng -Rev 03

279

Section 18 The 963 Database


In versions of 963 prior to version 2.0, there were 5 different databases that were used to store information: S2.MDB S2Actionscheduler.MDB S2Alarms.MDB S2Comms.MDB S2DataLogger.MDB These files used the Microsoft Access database format. Since version 2.0, 963 uses Microsoft SQL Server based technology. The database server provided with the 963 installation is SQL Server operating in Mixed (SQL) mode and supports database sizes up to 6 GB. Four of the five database files of earlier versions have now been merged into one single database (i96x_data.mdf) containing all 963 data, while one is now obsolete (S2Comms.mdb).

Trend - 963 v3 Eng -Rev 03

280

Section 18 The 963 Database

Archive

Backup

Trend - 963 v3 Eng -Rev 03

281

Section 18 Archiving the Database


The ARCHIVEDATA action allows historic data (graph data, recorded schematics and alarms) within the supervisor to be archived to an internal or external file location. The data that you archive can either be deleted from the 963s database (Cut) or kept in the database (Copied). Any archived graph data can be played back using the Load recorded data option in the Graph Window. Any archived schematic data can be played back using the View recorded data option on the Data Recording menu. The archived file is saved with a .mdf file extension and by default is time and date stamped. The ARCHIVEDATA action can be used in :Schematic Actions Event Scheduler Script Files

Trend - 963 v3 Eng -Rev 03

282

Section 18 Exercise Archiving the Database

To Archive the database. 1) From the Database menu, select Archive Data. This will open the Save as dialogue. The default for the file name uses some of the 963 variables that have been covered in the course. <DATA> finds where 963 is installed, <PCDATE> adds a date stamp and <PCTIME> adds a time stamp. There are options to choose a different file location and to restore the default file name. 2) Click Next

Trend - 963 v3 Eng -Rev 03

283

Section 18 Archiving the Database

3)

You can now choose a date range for the archived data.

4)

Finally decide whether you want to delete the archived data from the working database or not.

Put simply, this meansClick Yes if you want to CUT the data from the database, Click No if you want to COPY the data from the database.

Trend - 963 v3 Eng -Rev 03

284

Section 18 Backing up the Database


The BACKUPDB action creates a copy of the database for use in the event of system failure. The Backup file is saved with a .dat file extension and by default, is time and date stamped in the same way as the Archive file. Note that the database can only be backed up to a local drive unless 963 has been correctly configured to backup to a network location, and the PC running 963 must be logged on to the network using the network user name specified during that configuration process. An alternative to this is to backup the files locally, and then copy the files created to the required remote location using Windows explorer. The BACKUPDB action can be used in :Schematic Actions Event Scheduler Script Files

X
Trend - 963 v3 Eng -Rev 03

285

Section 18 Backing up the Database

To Create a backup. 1) From the Database menu, select Properties.

2)

This will open the Database Properties window. Click Back up database.

Trend - 963 v3 Eng -Rev 03

286

Section 18 Backing up the Database

3)

The Backup Database dialogue box is displayed, read the message and then click Next. The dialogue box changes to

4)

The location of the file can be specified by clicking Choose file location The default is to back up the file to the directory in which 963 is installed, the filename is trend96X and it includes the date and time. To return to the default settings click Generate default file name

5) 6)

Click Finish. When the backup is complete the 963 dialogue box is displayed.

Trend - 963 v3 Eng -Rev 03

287

Section 18 Backing up the Database


The Backup that is created is for use in disaster recovery. It can be used to re-create a 963 database following a pc crash. To re-create a 963 database, 1) 2) 3) 4) From the Database menu, select Properties. This will open the Database Properties window. Tick the Restore database.. Option You will then be prompted to restart 963 and select the backup that you wish to use for the re-creation of the database.

Trend - 963 v3 Eng -Rev 03

288