You are on page 1of 34

FAULTLEVELCALCULATIONS

ACASESTUDY

STEP1:SINGLELINEDIAGRAM
TRANSFORMER
1600kVA

PCC

13

F
22 ) 1

12

350A

11
21

STANDBY GENERATOR
1250kVA

F2

)
23

24

300A

300A

MCC

BUSBAR
31

M1

50HP

F
3

U/G CABLE

M2

M3

M4

100HP

30HP

150HP

CB
SDF
STARTER

STEP2:SYSTEMDATA
i) TRANSFORMER :

11/0.433kV
1600kVA
%R = 0.94
%X = 5.46
%Z = 5.54

ii) STANDBY GENERATOR :


UrG = 415V
1250kVA
%xd = 20
Cos rG = 0.8
Un = 415V

STEP2:SYSTEMDATA
iii) CABLE :

R = 0.062 /kM
X = 0.079 /kM
LENGTH OF CABLE,
21 TO 31= 100M

iv) INDUCTION MOTORS : M1, IrM = 70A


M2, IrM = 135A
M3, IrM = 40A
M4, IrM = 200A
(UrM = 415V; ILR = 6 IrM)

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step3:Conversionof%RintoOhmic
values,toobtainRT.
10x(0.94)x(0.433)2
RT (in) =
1600
=0.001102

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step4:Conversionof%XintoOhmic
values,toobtainXT.
10x(5.46)x(0.433)2
XT (in)=
1600
=0.006398

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step5:Conversion%xd ofthegenerator
intoOhmic values,toobtainXG.
10x(20)x(0.415)2
XG (in)=
1250
=0.027556

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step6:Theresistanceofthegenerator,
RGis:
RG (in) =

0.15XG

0.15x0.027556

0.0041334

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step7:Calculatingthecorrectionfactor
KG.

KG

415
1.05

415
1+[(0.2)(0.6)]

0.9375

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step8:FindingouttheCorrected
GeneratorResistance(RGK)&the
CorrectedGeneratorReactance(XGK):
RGK =
XGK

0.9375x0.0041334
=
0.003875
=
0.9375x0.027556
=
0.025834

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step9:Findingoutthecableresistance
&reactancefortheactuallengthofcable
useduptothepointoffault:
RL

0.062x0.1

0.0062

XL

0.079x0.1=

0.0079

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step10(F1):AddingofallR&allX
values&findingoutZk(forFaultatF1):
Zk(F1) =
=
=
=
=

[(RT)2 +(XT)2]
[(0.001102)2 +(0.006398)2]
[(0.000001214)+(0.00004093)]
[(0.00004214)]
0.006492

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step11(F1):Findingouttheinitial
symmetricalshortcircuitcurrent,Ik (forFault
atF1):
Ik(F!) =
=

1.05x415

3x0.006492
38752Aor38.75kA

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step12(F1):DeterminingtheX/Rratio
uptothepointoffault(forFaultatF1):
(XT)/(RT)=(0.006398)/(0.001102)
=5.8058

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step13(F1):CalculatingtheAsymmetry
Factor(forFaultatF1):
(F1)

(1.02+0.98e3RT/XT)

1.6045

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step14(F1):Calculatingthepeakcurrent,
(forFaultatF1):

ip(F1)

1.6045x 2x38752

87932Aor87.93kA

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step10(F2):AddingofallR&allX
values&findingoutZk(forFaultatF2):
Zk(F2) =
=
=
=
=

[(RGK)2 +(XGK)2]
[(0.003875)2 +(0.025834)2]
[(0.00001502)+(0.0006674)]
[(0.0006824)]
0.026123

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step11(F2):Findingouttheinitial
symmetricalshortcircuitcurrent,Ik (for
FaultatF2):
Ik(F2)

1.05x415

3x0.026123

9631Aor9.63kA

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step12(F2):DeterminingtheX/Rratio
uptothepointoffault(forFaultatF2):
(XGK)/(RGK)

=(0.025834)/(0.003875)
=6.6668

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step13(F2):CalculatingtheAsymmetry
Factor(forFaultatF2):
(F2)

(1.02+0.98e3RGK /XGK)

1.6449

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step14(F2):Calculatingthepeakcurrent,
(forFaultatF2):

ip(F2)

1.6449x 2x9631

22404A or22.40kA

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step10(F3):AddingofallR&allX
values&findingoutZk(forFaultatF3):
Zk(F3) =
=
=
=
=

[(RT+ RL)2 +(XT+ XL)2]


[(0.007302)2 +(0.014298)2]
[(0.00005332)+(0.00020443)]
[(0.0002576)]
0.0160546

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step11(F3):Findingouttheinitial
symmetricalshortcircuitcurrent,Ik (for
FaultatF3):
Ik(F3)

1.05x415

3x0.0160546

15670Aor15.67kA

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step12(F3):DeterminingtheX/Rratio
uptothepointoffault(forFaultatF3):
=

(XT+ XL)/(RT+ RL)

(0.014298)/(0.007302)

1.9581

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step13(F3):CalculatingtheAsymmetry
Factor(forFaultatF3):
(F3)

(1.02+0.98e3(RT +RL) /(XT +XL)

1.2318

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step14(F3):Calculatingthepeakcurrent,
(forFaultatF3):

ip(F3)

1.2318x 2x15670

27298Aor27.30kA

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step15:Calculatingtheaggregateofthe
ratedfullloadcurrentsofallthemotors
(IrM):
70+135+40+200=445A

FaultLevelCalculations DirectMethod
Astepbystepapproach
Step16:This(445A)isdefinitelymore
than1%ofthecontributionat:
F1:
F2:
F3:

38752x0.01
9631x0.01
15670x0.01

=387.52A
=96.31A
=156.70A

So,motorscontributiontofaultshastobe
considered.

FaultLevelCalculations DirectMethod Astep


bystepapproach
Step17:TheR.M.S.Currentcontributionto
theshortcircuit,fromthisgroupofmotors
willbe:
IkM

1.05x5x445

2336A

(Ascablesareinvolved)

FaultLevelCalculations DirectMethod A
stepbystepapproach
Step18:And,thepeakcurrentcontributionfromthis
motorgroupwouldbe:
ipM

M 2IkM =1.2980x1.414x2336

4288A

where,
M =

1.2980foranR/Xratioof0.42,asinthe
caseofLVInductionmotors

FaultLevelCalculations DirectMethod A
stepbystepapproach
Step19(F1):Now,calculatethetotalfaultlevel,
bothR.M.S.(IKT)andthePeak(ipT)atthefault
Location(ForFaultatF1):
IKT(F1)

38752+2336=41088A
=
41.09kA

and
ipT(F1)

=
=

87932+4288=92220A
92.22kA

FaultLevelCalculations DirectMethod A
stepbystepapproach
Step19(F2):Now,calculatethetotalfaultlevel,
bothR.M.S.(IKT)andthePeak(ipT)atthefault
Location(ForFaultatF2):
IKT(F2)

9631+2336=11967A
=
11.97kA

and
ipT(F2)

=
=

22404+4288=26692A
26.69kA

FaultLevelCalculations DirectMethod A
stepbystepapproach
Step19(F3):Now,calculatethetotalfaultlevel,
bothR.M.S.(IKT)andthePeak(ipT)atthefault
Location(ForFaultatF3):
IKT(F3)

15670+2336=18006A
=
18.01kA

and
ipT(F3)

=
=

27298+4288=31586A
31.59kA

TotalFaultLevel
Fault Location

IkT

ipT

F1

41.09 kA
(R.M.S.)

92.22 kA
(peak)

F2

11.97 kA
(R.M.S.)

26.69 kA
(peak)

F3

18.01 kA
(R.M.S.)

31.59 kA
(peak)

You might also like