Marine & Offshore Insulation Technical Guidelines

2nd edition

Introduction

Rockwool Marine & Offshore is part of the Rockwool International Group, the worlds largest producer of stone wool and has for several years been one of the leading suppliers of insulation for the marine and offshore sector world wide. We offer a wide range of tested and approved products and constructions specially developed for marine and offshore. We offer competitive solutions within e.g. fire, sound and thermal insulation and insulation of technical installations. A dedicated team of specialists is daily working to optimize our range of products and constructions. The development and sale are taking place in close cooperation with the local Rockwool companies and a world wide net of agents and dealers. One of our main tasks is to assist and guide our customers with the right information and advice about our products, constructions and the practical insulation work. This manual combines all relevant information on marine and offshore insulation and is designed to keep you updated on our knowledge within the field. We hope that you will nd the Technical Guidelines useful in your daily work and inspirational to your future work within marine and offshore insulation.

Guidelines to be used in your daily work In the Technical Guidelines you will nd: General information about standards and test methods within marine and offshore. Practical information and advice about insulation and installation procedures. Detailed information about our range of products and constructions, construction details for e.g. bulkhead, deck and junctions. Overall information about sound insulation and measurements of our products. Construction details within thermal and technical insulation. Overview of our product range and our certificates. The recommendations in this manual should be seen as guidelines only. It is of course important that the insulation work is done according to the IMO rules and regulations from national authorities and classification societies. Further support and information We hope that this manual will be useful in your daily work. The manual however forms only a part of our support and information to the market. You are always more than welcome to contact your local Rockwool representative or our marine specialists who are ready to assist you with information and advice. Further information can also be found in our marine & offshore brochures e.g. Products & Constructions and Acoustic Manual. To get the most updated information we recommend the use of our web-site, www.rockwool-marine.com

Content

Introduction ....................................................................2 Marine & Offshore Insulation - an overview ..................................................................4 Insulation in General .............................................6
Preparation .................................................................................6 Cutting ........................................................................................6 Installation ..................................................................................7 Securing product ......................................................................8 Pins .............................................................................................8 Washers ......................................................................................8 Vapour barrier ...........................................................................9 Storage and stacking ................................................................9 Calculation of materials ..........................................................10 Choosing the right product ....................................................11

Floating Floor ..............................................................63


Marine Slab 200 .......................................................................64 Marine Slab 140 .......................................................................65

Technical Insulation ............................................ 67


Technical insulation in general ..............................................68 Insulation with Pipe Section ...................................................69 Insulation with Marine Lamella Mat .......................................70 Insulation with Marine Wired Mat ..........................................71 Insulation with Marine Slabs/Batts .........................................72 Cladding ...................................................................................72

Sound .................................................................................. 73
Rules and regulations .............................................................74 Sound absorption ....................................................................75 Sound reduction ......................................................................76

Regulations for Fire Insulation ..................12 Symbol Guide ..............................................................14 A-constructions ..........................................................15
Steel bulkhead .........................................................................15 Steel deck .................................................................................25 Aluminium bulkhead ...............................................................33 Aluminium deck .......................................................................37

Thermal Insulation of Bulkhead and Deck ............................................... 77


Solutions for thermal insulation .............................................78 Lambda values .........................................................................79 Thermal calculations ...............................................................80

Certificates.....................................................................81 Product Guide .............................................................85


Product selector .......................................................................86 Products ...................................................................................87 Surfaces ...................................................................................93

H-constructions .........................................................41
Steel bulkhead .........................................................................41 Steel deck .................................................................................47

Aquaduct ..........................................................................95 Health & Safety ...........................................................96 About Rockwool Marine & Offshore ......97 Notes
...................................................................................98

Jet Fire & Blast Resistance ..............................51


Bulkhead and deck jet fire 30 min. .....................................52 Blast resistance ........................................................................53

Construction Details .............................................55


Stiffeners ...................................................................................56 Bulkhead and deck connections ............................................57 Installation of surface steel plate ...........................................58

Additional Fire Protection ...............................59


Draught stoppers ....................................................................60 Penetrations ..............................................................................61 B15 extension ...........................................................................62

Marine & Offshore Insulation - an overview

Marine & Offshore Insulation - an overview


Bridge
At the bridge it is important to secure a high level of fire protection and sound insulation. See page 15-40 for A-constructions See page 63-66 for oating oor See page 73-76 for sound insulation

Disco
The discothque, cinema and bar areas onboard cruise ships are big sources of noise. It is important to have the right sound insulation around these areas towards the neighbouring areas. See page 15-40 for A-constructions See page 63-66 oating oor See page 73-76 for sound insulation

Corridors
Corridors are part of the emergency escape routes on a vessel. The numbers of horizontal fire zones passed by the corridor determine the fire insulation class. See page 15-40 for A-constructions

Cabins
On board a passenger ship it is essential to have the right insulation between the cabins. It is crucial to have the needed fire protection and it is getting more and more important to have a high level of sound and thermal insulation. See page 15-40 for A-constructions See page 73-76 for sound insulation See page 77-80 for thermal insulation

Storage and tank rooms


In the boiler room, storage rooms and tank rooms it is often important to insulate surfaces, boilers and pipes. See page 61 for penetrations See page 67-72 for technical insulation

Offshore
On offshore applications you have more or less the same conditions as on a ship. Furthermore you have the risk of hydrocarbon fire and need to protect people and material from an HC fire. See page 41-50 for H-constructions See page 51-54 for Jet Fire and Blast Resistance

Public area
The public area is requiring all kinds of insulation, depending on the situation. See page 15-40 for A-constructions See page 60 for draught stoppers See page 73-76 for sound insulation See page 77-80 for thermal insulation See page 93 for surfaces

Stairways
The stairways are part of the emergency escape routes on a vessel. The numbers of vertical fire zones passed by the stairway determine the fire insulation class. See page 15-40 for A-constructions

Galley
In the galley you always have a risk of fire, as you have a mixture of heat and ammable materials. In this case it is also necessary to be aware of the facings as you have oil vapour in the air. See page 15-40 for A-constructions See page 67-72 for technical insulation See page 93 for surfaces

Control room Engine room


The engine room contains a lot of fire risks so fire protection is essential. The engine room is also source of high and often disturbing noise. It is often filled with pipes, tanks, containers and other equipment where technical insulation is required. It is important to have the insulation protected so oil vapour does not get into the insulation material. See page 15-40 for A-constructions See page 67-72 for technical insulation See page 73-76 for sound insulation See page 93 for surfaces In the control room fire is to be held out as long as possible as this is the last place where all the technical equipment can be controlled. The sound level needs to be low, as engine crew has to spend a lot of time here. It is moreover important that no vapour gets to the machines and computers and that the room has a reasonable sound level. See page 15-40 for A-constructions See page 73-76 for sound insulation See page 93 for surfaces

Marine & Offshore Insulation - an overview

Insulation in General

Insulation in General
PREPARATION

The installation of insulation material can be done in different ways. It is up to the insulation contractor to choose the best way for each application. For fire rated constructions the installation has to follow the official drawings according to the fire test. Drawings can be found on our website, www.rockwool-marine. com. In the following you will find a general description of the way the insulation work can be done:

Fig. 1. Welding of pins to the plate (bulkhead/deck). As first step the pins must be welded to the plate and stiffener. Distance between pins should not exceed 300 mm. For fire rated constructions the position of pins must follow the official drawings.

CUTTING

Fig. 2. Painting of the plate To avoid corrosion the plate can afterwards be painted with anti corrosion paint.

Fig.3A. Using an electrical saw to cut large amounts of Rockwool products When cutting large quantities of Rockwool insulation it is recommended to use an electrical saw. This will ensure a good and angular surface that is easy to tighten against the next Batts/Slabs. 2-5 mm oversize is recommended. The pieces of insulation should be min. 150x150 mm.

Fig. 3B. Using a Rockwool knife to cut Rockwool Insulation Rockwool insulation can easily be cut with a Rockwool knife or a similar sharp knife. When the Batts/Slabs are cut in 2-5 mm oversize (depending on density) the optimal tension and tightness can be obtained when fitting the wool. The pieces of insulation should be min. 150x150 mm

Fig. 3C. Using a shear to cut Wired Mats Wired Mats should be cut with a large shear. 2-5 mm oversize is recommended. The pieces of insulation should be min. 150x150 mm.

INSTALLATION

Alternative 1, fig. 4A. Insulation of stiffeners Depending on the construction it is recommended to start with the insulation of the stiffeners. First by filling out the space, behind the stiffener, with Rockwool insulation. The insulation should fit exactly to the profile structure. Afterwards insulate around the stiffener with the required thickness of Rockwool insulation.

Alternative 1, fig. 5A. Insulation between stiffeners Insulate the plate between stiffeners with Rockwool insulation. Joints must be tight and no air gaps must be found. In connection with solutions with more than one layer of insulation, the joints should be staggered by 150 mm to ensure that no joints go straight through both layers.

Alternative 2, fig. 4A. Insulation between stiffeners Depending on the construction it can be easier to start with insulation of the plate. Joints must be tight and no air gaps must be found. In connection with solutions with more than one layer of insulation, the joints should be staggered by min. 150 mm to ensure that no joints go straight through both layers.

Alternative 2, fig. 5A. Insulation of stiffeners Insulate with Rockwool insulation around the stiffener. Fill out the space behind the stiffener with Rockwool insulation, the insulation should fit exactly to the profile structure.

Fig. 6 Fixing the insulation Fix washers on the pins in order to secure fixing of the insulation.

Insulation in General

Insulation in General

SECURING THE PRODUCT

Securing the product When installing the insulation all pieces must be fit firmly with minimum one pin approx 10 mm longer than the nominal thickness of the insulation. On A-constructions the material has to be fastened with spring washers. PINS

Securing H-constructions On H-constructions it is recommended that the pins are approx 40 mm longer than the nominal thickness of the insulation and are bent in different directions to ensure that the wool is secured. In case of H-constructions use of wire mesh as a cover is recommended. On H-constructions the material has to be fastened with spring washers.

Different pins Steel pins are used for steel decks and bulkheads. The steel pins are coated with copper for corrosion protection. Stainless steel pins with aluminium tip are used for aluminium constructions. The pins are normally 3 mm in diameter and can be aquired in different lengths.

WASHERS

Washers The spring washers used to slide over the pins for securing the insulation should be 38 mm in diameter and of corrosion protected material.

Covering the steel washers The washer can be fit with a plastic cap to cover the steel tip and to create a nice looking surface.

VAPOUR BARRIER In rooms where vapour will enter the insulation as a reason of temperature/ pressure differences, a vapour barrier is often a demand. When water vapour is moving from the hot room towards colder surfaces, it will often lead to problems with corrosion. If it is oil vapour this will be collected in the wool and endanger the fire properties of the wool. To close the surface on the Rockwool products there are several options e.g. reinforced alu foil: All joints must be sealed with a tape width of 75-100 mm to ensure an air tight surface. Make sure that there is no grease, oil or dirt on the surface before the tape is applied. This will cause the tape to come loose. Make sure all holes in the surface are closed. The surface must have a low ame spread approval if it is used for marine applications.

Using tape to ensure an airtight surface between two batts All joints must be sealed with a tape width of 75-100 mm to ensure an air tight surface. Make sure that there is no grease on the surface before the tape is applied. Pins and washers should be taped.

STORAGE AND STACKING In order to secure the right conditions for storage of Rockwool Marine & Offshore products a special set of conditions have been prepared, e.g. the products: Must at all times be stored dry indoor in closed warehouse facilities. Must not be stacked in more than two layers when delivered on pallets. Must only be stored on the at side when delivered in packages and must not be stacked in heights of more than three metres. Must at all times during storage remain untouched and must not be affected by any kind of treading, sitting or any other similar kind of exposure. Must be transported in closed compartments, e.g. trailers, containers and other cargo holds in order to avoid exposure to weather elements and/or condensation etc.

Storage of Rockwool insulation The products must at all times be stored dry indoor in closed warehouse facilities.

Stacking of Rockwool products The products must not be stacked in more than two layers when delivered on pallets. They must only be stored on the at side when delivered in packages and must not be stacked in heights of more than three metres. It is recommended that roll products are stacked upright.

Do not sit on the Rockwool material The products must at all times during storage remain untouched and must not be affected by any kind og treading, sitting or any other similar kind of exposure.

Insulation in General

Calculation of Materials

Calculation of Materials

Below you will find a rough guidance for estimated need of material. Check your drawings for more detailed calculations.
INSULATION

1
Based on a plate of X m2. The amount of Batts/Slabs for stiffeners can as guidance be calculated as X times 0.7 Example: 100 m2 of plate needs to be insulated. Calculation of material for stiffener: 100 m2 x 0.7 = 70 m2

2
Based on a total amount of insulation for plate + stiffeners: The plate equals 60%. The stiffeners equals 40%

PINS AND WASHERS

1
As guidance the use of pins and washers can be calculated as follows: Plate in m2 times min. 12. Stiffener in m2 times min. 10. Example: 100 m2 insulation of plate requires 100 m2 x 12 pins/m2 = 1200 pins 100 m2 insulation of stiffeners requires 100 m2 x 10 pins/m2 = 1000 pins

2
Alternatively the use of pins and washers can be calculated by the total area of plate and stiffener in m2 times min. 18. Example: A total quantity of 100 m2 plate needs to be insulated; also taking the insulation of stiffeners into consideration. Estimated need of pins and washers: 100 m2 x 18 pins/m2 = 1800 pins

TAPE

WASTE

1
As guidance the amount of tape for joints can be calculated by the insulated in m2 times 4 stated in running metres Example: Tape for 100 m2 of insulation; 100 m2 x 4 m/m2 = 400 metres

1
As guidance the following amount of waste has to be included: Insulation area < 100 m2 10 % waste Insulation area > 100 m2 5% waste

IN GENERAL THE CUSTOMER IS ALWAYS RESPONSIBLE FOR CALCULATIONS

10

To find the correct product it is necessary to know which application it has to be used for e.g.: Fire insulation Sound insulation Thermal insulation Insulation of technical installations Floating oor insulation Panels Insulation of sub-sea pipelines Combinations e.g. re and sound insulation When choosing a product it is necessary to choose a product that is approved by the classification company that has to approve the application/newbuilding in the end. Some customers prefer to work with constructions based on Batts, securing easy handling of small size and fixed products, others prefer to work with constructions based on Wired Mat. For some customers it is important to have the best and most safe solutions typically based on a two layer solution where other customers tend to focus on easy and fast installation. Finally, it is important to focus on the right documentation such as: Type approvals Type certicates When using Rockwool insulation onboard a vessel carrying an EEA flag make sure that the product has the MED approval symbol (wheelmark). Rockwool Marine & Offshore has a large number of certificates for the different products and applications from classification companies based on fire tests made at IMO approved fire institutes.

When the application is known, the requirements for product characteristics need to be evaluated e.g.: Fire properties Sound properties Thickness Thermal conductivity Mechanical strength In some applications the weight could be of importance. In such cases the lighter products can be chosen, but it is not always the lightest solution that gives the best result. The light products do not protect against noise in the same frequency band as the more heavy products, so here it is necessary to know what result is requested in the end. All Rockwool products have good fire properties, but when using the products on ships or offshore rigs it is necessary to choose the right product fulfi lling the needed fire rating. Furthermore it can be relevant to evaluate the different solutions with regard to the working and installation method. Depending on the experience, the labour cost and the prioritisation it might be relevant to include parameters as e.g.: Easy handling Less cutting Fast installation Labour intensity

0575/year

It is important to make sure that the products and constructions have the right approval needed in the specific project, e.g. construction approval, noncombustible approval and low flame spread approval. Remember to check if the certificate is valid at the time where the insulation plan is approved by the classification societies.
11

Choosing the Right Product

Choosing the Right Product

Requirements for Fire Insulation

Regulations for Fire Insulation According to SOLAS


The requirements for materials and constructions to meet specified standards of safety are normally prescribed by international or national laws related to shipping and offshore installations. In addition to these regulations classification societies such as Det Norske Veritas (DNV) and Lloyds Register of Shipping (LRS) may have additional requirements. Approvals and Certification Suppliers of materials and constructions to the marine and offshore industry must prove that their products, as a minimum, meet the statutory requirements. The MED directive (EC Council Directive 96/98/ EC - Marine Equipment Directive) has replaced the previous approvals from the maritime authorities within EEA countries. All products supplied to marine carrying EEA flag must be subject to the MED directive. MED-certificates are issued by notified bodies accredited by an EEA country. Approved products bear the mark of conformity. Classification societies issue type approval certificates stating the permission to use specific materials and constructions together with any relative restrictions. If there are special circumstances or requirements for special details, it may be required to obtain statements from other authorities. Approval Requirements To satisfy the national authorities and classification societies, materials and constructions must be proven to comply with the national and international requirements. Tests have to been done at internationally recognised test laboratories. The tests have to be performed so that the materials or products are exposed to a fire generated under controlled conditions that simulate as closely as possible a worst case scenario. Test Requirements There are several national and international requirements regarding the use of materials on ships and offshore installations. These classifications are required to prove combustibility characteristics and include ignition properties, heat release and development of toxic gases and smoke. To prove that materials meet the required fire technical classification, tests are carried out at recognised test institutions according to standardised test methods. Material Test Methods. Testing of materials fire resistance is done according to FTP code for non-combustibility and where a facing is applied for low flame spread. The most commonly accepted test methods are: Non-Combustibility: IMO A-799(19) ISO 1182 Low Flame Spread: IMO A-653(16) It is important to note that materials which meet the requirements for non-combustibility do not have to be tested for other fire technical properties. Construction Test Methods Testing of a constructions fire resistance (decks, bulkheads, structural steel, penetrations etc.) is normally carried out in a standardised test furnace, where the construction specimen is exposed to a fire according to a standardised time/temperature curve. The most common test methods are: Recommendation on Fire Test Procedures for A, B and F Class Divisions. IMO A-754 (18)

12

SOLAS, Chapter II-2, Regulation 5.3.1:

Use of non-combustible materials Insulating materials shall be non-combustible, except in cargo spaces, mail rooms, baggage rooms and refrigerated compartments of service spaces. Vapour barriers and adhesives used in conjunction with insulation, as well as the insulation of pipe ttings for cold service systems, need not be of non-combustible materials, but they shall be kept to the minimum quantity practicable and their exposed surfaces shall have low ame-spread characteristics.

Notified Body Rockwool Marine & Offshore is certified according to the MED directive. As notified body we have chosen Det Norske Veritas which also guaranties our quality by running audits.

Fire Classifications of Divisions


Class B Fire Divisions
Class B re divisions must be of non-combustible materials and must prevent the propagation of ames for at least 30 minutes during a standard fire test. The divisions must be insulated so that the average temperature on the unexposed side of the division does not exceed 140C above the initial temperature. Furthermore, the temperature at any single point on the unexposed side must not exceed 225C above the initial temperature within the time limits.

Class B-30 30 minutes

Class B-15 15 minutes

Class B-0 0 minutes

Class A Fire Divisions


Class A re divisions must be of non-combustible materials and insulation materials must be fire tested at a recognised institution. They must be sufficiently braced and must prevent the propagation of ames and smoke for a minimum of one hour during a standard fire test. The divisions must be insulated so that the average temperature on the unexposed side of the division does not exceed 140C above the initial temperature. Furthermore, the temperature at any single point on the unexposed side must not exceed 180C above the initial temperature within the time limits.

Class A-60 60 minutes

Class A-30 30 minutes

Class A-15 15 minutes

Class A-0 0 minutes

Class H Fire Divisions


Class H re divisions must be of non-combustible materials and insulation materials must be fire tested at a recognized institution. They must be sufficiently braced and must prevent the propagation of ames and smoke for a minimum of two hours during a standard fire test for a hydrocarbon fire. The divisions must be insulated so that the average temperature on the unexposed side of the division does not exceed 140C above the initial temperature. Furthermore, the temperature at any single point on the unexposed side must not exceed 180C above the initial temperature within the time limits.

2x

Class H-120 120 minutes

Class H-60 60 minutes

Class H-0 0 minutes

13

Requirements for Fire Insulation

Symbol Guide

Symbol Guide

Rockwool Marine & Offshore has made symbols for all fire rated applications explaining the advantages with each application:

SYMBOL GUIDE One layer solution The construction is based on a solution where the construction is made with one product in one layer. This leads to faster installation. Safe solution The construction is based on a multiple, typical two layer solution which results in more safe solutions especially due to staggered joints.

Low construction weight The construction is based on products with a low density and/or low thickness which lead to low total construction weight.

Optimal sound properties The construction is based on products with higher density and/or more thickness which result in better sound properties.

Fast installation The construction is based on Mats which reduce the cutting especially around stiffeners, and consequently faster installation time.

Easy handling The construction is based on Batts, where the small size and fixed structure of the products give an easy handling in respect to cutting and installation.

14

Steel - Bulkhead A-30 Marine Batts 45 A-30 Marine Wired Mat 90 A-60 Marine Firebatts 100 A-60 Marine Firebatts 130 A-60 Marine Wired Mat 90 A-60 Marine Wired Mat 105 A-60 Marine Firebatts 100 restricted A-60 Marine Firebatts 130 restricted page 16 page 17 page 18 page 19 page 20 page 21 page 22 page 23

Steel Bulkhead

15

Index of A-constructions - Steel Bulkhead

Index of A-constructions Steel Bulkhead

A-30 Steel Bulkhead

A-30 Steel Bulkhead

MED B-4134

Product: Density:

Rockwool Marine Batts 45 45 kg/m3

Thickness: Plate 50 mm insulation Stiffener 25 mm insulation

Construction: Plate between stiffeners insulated with one layer of 50 mm Rockwool Marine Batts 45 Stiffeners insulated with min. 25 mm Rockwool Marine Batts 45. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm.

Advantages: One layer solution Low construction weight Easy handling

Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. The pins should exceed the insulation by approx 10 mm. Insulation can be placed on either side of the steel plate.

Surfaces: Reinforced aluminium foil Glass cloth Sound: 600 Weigthed sound absorption Marine Batts 45, 50 mm w = 0.75

600

50 mm Rockwool Marine Batts 45 4.5 mm steel

480

Pinning

3 mm steel pin w. washer


TEST: G10148

25 mm Rockwool Marine Batts 45 3 mm steel pin w. washer 50 mm Rockwool Marine Batts 45 4.5 mm steel

300 mm 1000 300 mm

25 mm Rockwool Marine Batts 45 3 mm steel pin w. washer

16

MED B-4134

Product: Density:

Rockwool Marine Wired Mat 90 90 kg/m3

Thickness: Plate 50 mm insulation Stiffener 30 mm insulation

Construction: Plate between stiffeners insulated with one layer of 50 mm Rockwool Marine Wired Mat 90 Stiffeners insulated with min. 30 mm Rockwool Marine Wired Mat 90 (min. 340 mm width) Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm.

Advantages: Fast installation Optimal sound properties

Application notes: All the connections must be tight, no air gaps. The pins should exceed the insulation by approx 10 mm. Wire mesh must be twisted together at joints. Insulation can be placed on either side of the steel plate.

Surfaces: Reinforced aluminium foil Glass cloth Sound: Weigthed sound absorption Marine Wired Mat 90, 50 mm w = 0.90

50 mm Rockwool Marine Wired Mat 90 4.5 mm steel

Pinning

30 mm Rockwool Marine Wired Mat 90 3 mm steel pin w. washer minimum 340 mm

300 mm

TEST: GV95.33.1

50 mm Rockwool Marine Wired Mat 90 4.5 mm steel

3 mm steel pin w. washer


30 mm Rockwool Marine Wired Mat 90 3 mm steel pin w. washer

17

A-30 Steel Bulkhead

A-30 Steel Bulkhead

A-60 Steel Bulkhead

A-60 Steel Bulkhead

MED B-4188

Product: Density:

Rockwool Marine Firebatts 100 100 kg/m3

Thickness: Plate 60 mm insulation Stiffener 25 mm insulation

Construction: Plate between stiffeners insulated with one layer of 60 mm Rockwool Marine Firebatts 100 Stiffeners insulated with min. 25 mm Rockwool Marine Firebatts 100. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300/400 mm distance. Insulation secured with washers of 38 mm. Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. The pins should exceed the insulation by approx 10 mm. The long side of the insulation to be installed vertically. Insulation can be placed on either side of the steel plate.
60 mm Rockwool Marine Firebatts 100 4.5 mm steel

Advantages: One layer solution Low construction weight Easy handling Surfaces: Reinforced aluminium foil Glass cloth Sound: Weigthed sound absorption Marine Firebatts 100, 60 mm w = 0.90 Weigthed sound reduction of the A60 application Rw = 45 dB

Pinning

300 mm
TEST: 2004cs01428/3

3 mm steel pin w. washer 25 mm Rockwool Marine Firebatts 100

400 mm
60 mm Rockwool Marine Firebatts 100 4.5 mm steel

3 mm steel pin w. washer


25 mm Rockwool Marine Firebatts 100 3 mm steel pin w. washer

18

MED B-4188

Product: Density:

Rockwool Marine Firebatts 130 130 kg/m3

Thickness: Plate 2x30 mm insulation Stiffener 30 mm insulation

Construction: Plate between stiffeners insulated with two layers of 30 mm Rockwool Marine Firebatts 130. Stiffeners insulated with min. 30 mm Rockwool Marine Firebatts 130. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm. Application notes: All the connections must be tight, no air gaps. 600 Gap under the stiffener must be fi lled out completely. Joints to be staggered, 150 mm overlap is recommended. The pins should exceed the insulation by approx 10 mm. Insulation can be placed on either side of the steel plate

Advantages: Safe solution Optimal sound properties Easy handling Surfaces: Reinforced aluminium foil 600 Glass cloth Sound: Weigthed sound absorption Marine Firebatts 130, 2x30 mm w = 0.90 Weigthed sound reduction of the A-60 application Rw = 48 dB

600

480
2x30 mm Rockwool Marine Firebatts 130 4.5 mm steel

Pinning

3 mm steel pin w. washer 30 mm Rockwool Marine Firebatts 130


TEST: G10096

300 mm

2x30 mm Rockwool Marine Firebatts 130 1000 4.5 mm steel

300 mm 3 mm steel pin w. washer


30 mm Rockwool Marine Firebatts 130 3 mm steel pin w. washer

19

A-60 Steel Bulkhead

A-60 Steel Bulkhead

A-60 Steel Bulkhead

A-60 Steel Bulkhead

MED B-4188

Product: Density:

Rockwool Marine Wired Mat 90 90 kg/m3

Thickness: Plate 2x45 mm insulation Stiffener 45 mm insulation

Construction: Plate between stiffeners insulated with two layers of 45 mm Rockwool Marine Wired Mat 90 Stiffeners insulated in the same process with min. 45 mm Rockwool Marine Wired Mat 90. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm. Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out 600 completely. Joints to be staggered, 150 mm overlap is recommended. The pins should exceed the insulation by approx 10 mm. Wire mesh must be twisted together at joints. Insulation can be placed on either side of the steel plate.

Advantages: F Fast installation Safe solution Optimal sound properties Surfaces: Reinforced aluminium foil Glass cloth

600

600

Sound: Weigthed sound absorption Marine Wired Mat 90, 2x45 mm w = 0.95 Weigthed sound reduction of the A60 application Rw= 58 dB (with 1 mm steel sheet in front of the insulation)

480
45 mm Rockwool Marine Wired Mat 90 4.5 mm steel

Pinning

300 mm
45 mm Rockwool Marine Wired Mat 90 3 mm steel pin w. washer
TEST: 2006cs13889-1

45 mm Rockwool Marine Wired Mat 90 4.5 mm steel

1000

3 mm steel pin w. washer

45 mm Rockwool Marine Wired Mat 90

20

MED B-4188

Product: Density:

Rockwool Marine Wired Mat 105 105 kg/m3

Thickness: Plate 75 mm insulation Stiffener 30 mm insulation

Construction: Plate between stiffeners insulated with one layer of 75 mm Rockwool Marine Wired Mat 105. Stiffeners insulated with min. 30 mm Rockwool Marine Wired Mat 105. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm. Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out 600 completely. The pins should exceed the insulation by approx 10 mm. Wire mesh must be twisted together at joints. Insulation can be placed on either side of the steel plate.

Advantages: One layer solution Fast installation Optimal sound properties Surfaces: Reinforced aluminium foil 600 Glass cloth Sound: Weigthed sound absorption Marine Wired Mat 105, 75 mm w = 0.90

600

75 mm Rockwool Wired Mat 105 4.5 mm steel

480

Pinning

TEST: 2006CS013889-2

3 mm steel pin w. washer 30 mm Rockwool Marine Wired Mat 105 75 mm Rockwool Marine Wired Mat 105 4.5 mm steel

300 mm

300 mm 3 mm steel pin w. washer

1000

30 mm Rockwool Marine Wired Mat 105 3 mm steel pin w. washer

21

A-60 Steel Bulkhead

A-60 Steel Bulkhead

A-60 Steel Bulkhead restricted

A-60 Steel Bulkhead restricted


MED B-4188

Product: Density:

Rockwool Marine Firebatts 100 100 kg/m3

Thickness: Plate 40 mm insulation Stiffener 40 mm insulation

Construction: Plate between stiffeners insulated with one layer of 40 mm Rockwool Marine Firebatts 100 Stiffeners insulated with min. 40 mm Rockwool Marine Firebatts 100. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300/400 mm distance. Insulation secured with washers of 38 mm. Application notes: Restricted application (fire against insulated side) All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. The pins should exceed the insulation by approx 10 mm. Insulation can be placed on either side of the steel plate.

Advantages: One layer solution Low construction weight Easy handling Surfaces: Reinforced aluminium foil Glass cloth

600

600

Sound: Weigthed sound absorption Marine Firebatts 100, 40 mm w = 0.80

40 mm Rockwool Marine Firebatts 100 4.5 mm steel

480
Pinning

TEST: 2004cs014787

3 mm steel pin w. washer 40 mm Rockwool Marine Firebatts 100 40 mm Rockwool Marine Firebatts 100 4.5 mm steel

400 mm

300 mm

1000

3 mm steel pin w. washer


40 mm Rockwool Marine Firebatts 100 3 mm steel pin w. washer

22

MED B-4188

Product: Density:

Rockwool Marine Firebatts 130 130 kg/m3

Thickness: Plate 50 mm insulation Stiffener 50 mm insulation

Construction: Plate between stiffeners insulated with one layer of 50 mm Rockwool Marine Firebatts 130. Stiffeners insulated with min. 50 mm Rockwool Marine Firebatts 130. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm. Application notes: Restricted application (fire against insulated side) 600 All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. The pins should exceed the insulation by approx 10 mm. Insulation can be placed on either side of the steel plate.

Advantages: One layer solution Optimal sound properties Easy handling Surfaces: Reinforced aluminium foil 600 Glass cloth Sound: Weigthed sound absorption of Marine Firebatts 130, 50 mm w = 0.80

600

50 mm Rockwool Marine Firebatts 130 4.5 mm steel

480

Pinning

3 mm steel pin w. washer 50 mm Rockwool Marine Firebatts 130


TEST: G10095/5993

300 mm

50 mm Rockwool Marine Firebatts 130 1000 4.5 mm steel

300 mm 3 mm steel pin w. washer


50 mm Rockwool Marine Firebatts 130 3 mm steel pin w. washer

23

A-60 Steel Bulkhead restricted

A-60 Steel Bulkhead restricted

24

Steel - Deck A-30 Marine Batts 45 A-30 Marine Wired Mat 90 A-60 Marine Firebatts 100 A-60 Marine Firebatts 130 A-60 Marine Wired Mat 90 A-60 Floating Floor Marine Slab 200 A-60 Floating Floor Marine Slab 140 page 26 page 27 page 28 page 29 page 30 page 31 page 32

Steel Deck

25

Index of A-constructions - Steel Deck

Index of A-constructions Steel Deck

A-30 Steel Deck

A-30 Steel Deck

MED B-4186

Product: Density:

Rockwool Marine Batts 45 45 kg/m3

Thickness: Plate 50 mm insulation Stiffener 30 mm insulation

Construction: Plate between stiffeners insulated with one layer of 50 mm Rockwool Marine Batts 45. Stiffeners insulated with min. 30 mm Rockwool Marine Batts 45. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm. Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. The pins should exceed the insulation by approx 10 mm.

Advantages: One layer solution Low construction weight Easy handling

Surfaces: Reinforced aluminium foil Glass cloth Sound: Weigthed sound absorption Marine Batts 45, 50 mm w = 0.75

50 mm Rockwool Marine Batts 45 4.5 mm steel

Pinning

300 mm
30 mm Rockwool Marine Batts 45 3 mm steel pin w. washer

TEST: PG10985

300 mm

50 mm Rockwool Marine Batts 45 4.5 mm steel

400 mm

30 mm Rockwool Marine Batts 45 3 mm steel pin w. washer

3 mm steel pin w. washer

26

MED B-4186

Product: Density:

Rockwool Marine Wired Mat 90 90 kg/m3

Thickness: Plate 30 mm insulation Stiffener 30 mm insulation

Construction: Plate between stiffeners insulated with one layer of 30 mm Rockwool Marine Wired Mat 90. Stiffeners insulated with min. 30 mm Rockwool Marine Wired Mat 90. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm. Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. The pins should exceed the insulation by approx 10 mm. Wire mesh must be twisted or clamped together at joints.

Advantages: One layer solution Fast installation

Surfaces: Reinforced aluminium foil Glass cloth

600

600

30 mm Rockwool Marine Wired Mat 90 4.5 mm steel

480

Pinning

3 mm steel pin w. washer


TEST: GH95.15.1

30 mm Rockwool Marine Wired Mat 90

300 mm

30 mm Rockwool Marine Wired Mat 90 4.5 mm steel

1000

3 mm steel pin w. washer

30 mm Rockwool Marine Wired Mat 90 3 mm steel pin w. washer

27

A-30 Steel Deck

A-30 Steel Deck

A-60 Steel Deck

A-60 Steel Deck

MED B-4189

Product: Density:

Rockwool Marine Firebatts 100 100 kg/m3

Thickness: Plate 40 mm insulation Stiffener 25 mm insulation

Construction: Plate between stiffeners insulated with one layer of 40 mm Rockwool Marine Firebatts 100. Stiffeners insulated with min. 25 mm Rockwool Marine Firebatts 100. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 250 mm distance. Insulation secured with washers of 38 mm.

Advantages: One layer solution Low construction weight Easy handling

Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. The pins should exceed the insulation by approx 10 mm.

Surfaces: Reinforced aluminium foil Glass cloth Sound: Weigthed sound absorption Marine Firebatts 100, 40 mm w = 0.80

40 mm Rockwool Marine Firebatts 100 4.5 mm steel

Pinning

25 mm Rockwool Marine Firebatts 100 3 mm steel pin w. washer


TEST: 96-DG-348-TO

40 mm Rockwool Marine Firebatts 100 4.5 mm steel

3 mm steel pin w. washer

250 mm
25 mm Rockwool Marine Firebatts 100 3 mm steel pin w. washer

250 mm

28

MED B-4189

Product: Density:

Rockwool Marine Firebatts 130 130 kg/m3

Thickness: Plate 40 mm insulation Stiffener 40 mm insulation

Construction: Plate between stiffeners insulated with one layer of 40 mm Rockwool Marine Firebatts 130. Stiffeners insulated with min. 40 mm Rockwool Marine Firebatts 130. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm.

Advantages: One layer solution Optimal sound properties Easy handling Surfaces: Reinforced aluminium foil Glass cloth 600

Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. The pins should exceed the insulation by approx 10 mm..

600

Sound: Weigthed sound absorption Marine Firebatts 130, 40 mm w = 0.75 Weighted sound reduction of the A60 application Rw = 56 dB (with 1 mm steel sheet in front of the insulation)

480
4.5 mm steel

Pinning
40 mm Rockwool Marine Firebatts 130 3 mm steel pin w. washer

3 mm steel pin w. washer


TEST: G10141/6026

40 mm Rockwool Marine Firebatts 130 4.5 mm steel 1000

200 mm 300 mm 400 mm

40 mm Rockwool Marine Firebatts 130 3 mm steel pin w. washer

29

A-60 Steel Deck

A-60 Steel Deck

A-60 Steel Deck

A-60 Steel Deck

MED B-4189

Product: Density:

Rockwool Marine Wired Mat 90 90 kg/m3

Thickness: Plate 45 mm insulation Stiffener 45 mm insulation

Construction: Plate between stiffeners insulated with one layer of 45 mm Rockwool Marine Wired Mat 90. Stiffeners insulated in the same process with 45 mm Rockwool Marine Wired Mat 90. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured with washers of 38 mm. Application notes: All the connections must be tight, no air gaps. Wire mesh must be twisted together at joints The pins should exceed the insulation by approx 10 mm.

Advantages: One layer solution Low construction weight Fast installation Surfaces: Reinforced aluminium foil Glass cloth Sound: Weigthed sound absorption Marine Wired Mat 90, 45 mm w = 0.90

45 mm Rockwool Marine Wired Mat 90 4.5 mm steel

Pinning

TEST: PG10984/8384

3 mm steel pin w. washer 45 mm Rockwool Marine Wired Mat 90

300 mm 400 mm

45 mm Rockwool Marine Wired Mat 90 4.5 mm steel

3 mm steel pin w. washer

3 mm steel pin w. washer

30

MED B-4189

Product: Density:

Rockwool Marine Slab 200 200 kg/m3

Thickness: Plate 2x30 mm insulation Top plate min. 2 mm steel plate

Construction: Standard steel plate 4.5 mm ( 0.5 mm) thick. The floor insulated with two layers of 30 mm Rockwool Marine Slab 200. Insulation covered by a 2 mm steel plate spot welded at c/c 150 mm. Application notes: First layer insulation is with butted joints. Second layer with butted and staggered joints to avoid overlapping joints. Do not step directly on the wool during installation. Always use a board or similar when moving around on the wool. To avoid sound from travelling it is recommended to finish the construction with a rigid Rockwool product placed edgeways and sealed with a flexible sealant.

Advantages: Safe solution Optimal sound properties Easy handling

Surface: The wool must be covered by a minimum 2 mm thick steel plate. Top layer must be evaluated according to static calculations. Max. load on insulation material: 40 kN/m2

600
2x30 mm Rockwool Marine Slab 200 2 mm steel

600

600

480
4.5 mm steel

TEST: 103020,44

Flexible sealant Rockwool Marine Slab 200 2x30 mm Rockwool Marine Slab 200 2 mm steel

1000

31

A-60 Floating Floor

A-60 Floating Floor

A-60 Floating Floor

A-60 Floating Floor

MED B-4189

Product: Density:

Rockwool Marine Slab 140 140 kg/m3

Thickness: Plate 60 mm insulation Top plates 1.5 + 3 mm steel plate

Construction: Standard steel plate 4.5 mm ( 0.5 mm) thick. The floor insulated with Rockwool Marine Slab 140 in 60 mm thickness. Insulation covered by 1.5 mm + 3 mm steel plate. Application notes: Insulation installed with butted joints. Do not step directly on the wool during installation. Always use a board or similar when moving around on the wool. To avoid sound from travelling it is recommended to finish the construction with a rigid Rockwool product placed edgeways and sealed with a flexible sealant. This solution is not recommended in areas with load on the deck. The first layer of steel plate must be 1.5 mm thick, installed with 50 mm overlap and secured with pop rivets. The second layer (top layer) must be 3 mm steel plate with butted joints and spot welded at c/c 150 mm.
60 mm Rockwool Marine Slab 140 1.5 mm steel 3 mm steel

Advantages: Safe solution Optimal sound properties Easy handling

Surface: The wool must be covered by a minimum 1.5 + 3 mm thick steel plate. Max. load on insulation material: 12 kN/m2

600

600

600

480

4.5 mm steel

TEST: 22N002.07D

Flexible sealant Rockwool Marine Slab 140 60 mm Rockwool Marine Slab 140 1.5 mm steel 3 mm steel

1000

32

Aluminium - Bulkhead A-60 Marine Firebatts 130 A-60 Marine Firebatts 100 A-60 Restricted Marine Firebatts 130 page 34 page 35 page 36

Aluminium Bulkhead

33

Index of A-constructions - Aluminium Bulkhead

Index of A-constructions Aluminium Bulkhead

A-60 Aluminium Bulkhead

A-60 Aluminium Bulkhead

MED B-4190

Product: Density:

Rockwool Marine Firebatts 130 130 kg/m3

Thickness: Plate 2x30 insulation on both sides Stiffener 2x30 mm

Construction: Plate between stiffeners insulated with two layers of 30 mm Rockwool Marine Firebatts 130. Insulation on both sides of the alu plate. Stiffeners insulated with two layers of min. 30 mm Rockwool Marine Firebatts 130. 600 600 Standard alu plate min. 6 mm ( 0.5 mm) thick. Stiffeners 9 mm alu. 3 mm alu tipped stainless steel pins fixed with approx 300 mm distance. Insulation secured with stainless steel washers of 38 mm. Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. Joints must be staggered, 150 mm overlap is recommended

The pins should exceed the insulation by approx 10 mm. Advantages: Safe solution

600

Optimal sound properties Easy handling

480

Surfaces: Reinforced aluminium foil Glass cloth Sound: Weighted sound absorption Marine Firebatts 130, 2x30 mm w=0.90

6 mm alu

Pinning

2x30 mm Rockwool Marine Firebatts 130

1000
TEST: PG10699/7735

9 mm alu 3 mm alu tipped stainless steel pin w. washer 2x30 mm Rockwool Marine Firebatts 130

300 mm

300 mm

3 mm alu tipped stainless steel pin w. washer


2x30 mm Rockwool Marine Firebatts 130 3 mm alu tipped stainless steel pin w. washer

34

Product: Density:

Rockwool Marine Firebatts 100 100 kg/m3

Thickness: Plate 2x30 insulation on both sides Stiffener 2x30 mm

Construction: Plate between stiffeners insulated with two layers of 30 mm Rockwool Marine Firebatts 100. Insulation on both sides of the alu plate. Stiffeners insulated with two layers of min. 30 mm Rockwool Marine Firebatts 100. Standard alu plate min. 6 mm ( 0.5 mm) thick. Stiffeners 9 mm alu. 3 mm alu tipped stainless steel pins fixed with approx 300 mm distance. Insulation secured with stainless steel washers of 38 mm. Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. Joints must be staggered, 150 mm overlap is recommended

The pins should exceed the insulation by approx 10 mm. Advantages: Safe solution Low construction weight Easy handling

Surfaces: Reinforced aluminium foil Glass cloth Sound: Weighted sound absorption Marine Firebatts 100, 60 mm w=0.90

6 mm alu

Pinning
2x30 mm Rockwool Marine Firebatts 100 9 mm alu 2x30 mm Rockwool Marine Firebatts 100 3 mm alu tipped stainless steel pin w. washer

300 mm 400 mm

3 mm alu tipped stainless steel pin w. washer


2x30 mm Rockwool Marine Firebatts 100 3 mm alu tipped stainless steel pin w. washer

35

A-60 Aluminium Bulkhead

A-60 Aluminium Bulkhead

A-60 Aluminium Bulkhead restricted

A-60 Aluminium Bulkhead restricted


MED B-4190

Product: Density:

Rockwool Marine Firebatts 130 130 kg/m3

Thickness: Plate 2x30 mm insulation Stiffener 2x30 mm insulation

Construction: Plate between stiffeners insulated with two layers of 30 mm Rockwool Marine Firebatts 130. Stiffeners insulated with two layers of min. 30 mm Rockwool Marine Firebatts 130. 600 600 Standard alu plate min. 6 mm ( 0.5 mm) thick. Stiffeners 9 mm alu. 3 mm alu tipped stainless steel pins fixed with approx 300 mm distance. Insulation secured with stainless steel washers of 38 mm. Application notes: Restricted application (fire against insulated side) All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. Joints must be staggered, 150 mm overlap is recommended The pins should exceed the insulation by approx 10 mm.

Insulation can be placed on either side of the alu plate Advantages: Safe solution

600

Optimal sound properties Easy handling Surfaces: Reinforced aluminium foil Glass cloth Sound: Weighted sound absorption Marine Firebatts 130, 2x30 mm w=0.90

480

6 mm alu

Pinning

1000
9 mm alu 3 mm alu tipped stainless steel pin w. washer
TEST: PG10125/5996

300 mm

300 mm

2x30 mm Rockwool Marine Firebatts 130

3 mm alu tipped stainless steel pin w. washer


2x30 mm Rockwool Marine Firebatts 130 3 mm alu tipped stainless steel pin w. washer

36

Aluminium - Deck A-30 Marine Batts 45/Marine Wired Mat 90 A-60 Marine Firebatts 130 A-60 Marine Firebatts 100 page 38 page 39 page 40

Aluminium Deck

37

Index of A-constructions - Aluminium Deck

Index of A-constructions Aluminium Deck

A-30 Aluminium Deck

A-30 Aluminium Deck

MED B-4187

Product: Density:

Rockwool Marine Batts 45/ Rockwool Marine Wired Mat 90 45/90 kg/m3

Thickness: Plate 50 mm insulation Stiffener 45 mm insulation

Construction: Plate insulated with one layer of 50 mm Rockwool Marine Batts 45 Stiffeners insulated with min. 45 mm Rockwool Marine Wired Mat 90. Standard alu plate min. 6 mm ( 0.5 mm) thick. Stiffeners 9 mm alu. 3 mm alu tipped stainless steel pins fixed with approx 300 mm distance. Insulation secured with stainless steel washers 600 of 38 mm. Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. The pins should exceed the insulation by approx 10 mm.

Advantages: One layer solution Fast installation Optimal sound properties Easy handling Surfaces: Reinforced aluminium foil Glass cloth Sound: Weigthed sound absorption Marine Wired Mat 90, 45 mm w = 0.90 Marine Batts 45, 50 mm w = 0.75

600

600

480 50 mm Rockwool Marine Batts 45 6 mm alu


Pinning
9 mm alu

3 mm alu tipped stainless steel pin w. washer


TEST: PG11045

45 mm Rockwool Marine Wired Mat 90 50 mm Rockwool Marine Batts 45 6 mm alu

400 mm

300 mm

1000

3 mm alu tipped stainless steel pin w. washer


9 mm alu

45 mm Rockwool Marine Wired Mat 90 3 mm alu tipped stainless steel pin with washer

300 mm

38

MED B-4187

Product: Density:

Rockwool Marine Firebatts 130 130 kg/m3

Thickness: Plate 2x30 mm insulation Stiffener 2x30 mm insulation

Construction: Plate between stiffeners insulated with two layers of 30 mm Rockwool Marine Firebatts 130. Stiffeners insulated with two layers of min. 30 mm Rockwool Marine Firebatts 130. Standard alu plate min. 6 mm ( 0.5 mm) thick. Stiffeners 9 mm alu. 3 mm alu tipped stainless steel pins fixed with approx 300/400 mm distance. Insulation secured with stainless steel washers of 38 mm. Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out 600 completely. Joints must be staggered, 150 mm overlap is recommended The pins should exceed the insulation by approx 10 mm.

Advantages: Safe solution Optimal sound properties Easy handling Surfaces: Reinforced aluminium foil Glass cloth Sound: 600 Weigthed sound absorption Marine Firebatts 130, 2x30 mm w = 0.90

600

Pinning
3 mm alu tipped stainless steel pin with washer 6 mm alu 2x30 mm Rockwool Marine Firebatts 130 9 mm alu
TEST: PG10765

400 mm 300 mm

3 mm alu tipped stainless steel pin with washer


2x30 mm Rockwool Marine Firebatts 130 3 mm alu tipped stainless steel pin with washer

300 mm
39

A-60 Aluminium Deck

A-60 Aluminium Deck

A-60 Aluminium Deck

A-60 Aluminium Deck

Product: Density:

Rockwool Marine Firebatts 100 100 kg/m3

Thickness: Plate 2x30 mm insulation Stiffener 2x30 mm insulation

Construction: Plate between stiffeners insulated with two layers of 30 mm Rockwool Marine Firebatts 100. Stiffeners insulated with two layers of min. 30 mm Rockwool Marine Firebatts 100. Standard alu plate min. 6 mm ( 0.5 mm) thick. Stiffeners 9 mm alu. 3 mm alu tipped stainless steel pins fixed with approx 300/400 mm distance. Insulation secured with stainless steel washers of 38 mm. Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. Joints must be staggered, 150 mm overlap is recommended The pins should exceed the insulation by approx 10 mm.

Advantages: Safe solution Low construction weight Easy handling Surfaces: Reinforced aluminium foil Glass cloth Sound: Weigthed sound absorption Marine Firebatts 100, 60 mm w = 0.90

Pinning
3 mm alu tipped stainless steel pin with washer 6 mm alu 2x30 mm Rockwool Marine Firebatts 100 9 mm alu

300 mm 400 mm

3 mm alu tipped stainless steel pin w. washer


2x30 mm Rockwool Marine Firebatts 100 3 mm alu tipped stainless steel pin with washer

40

Steel - Bulkhead restricted H-60 HC Firebatts 150/ HC Wired Mat 150 page 42 page 43

H-120 HC Firebatts 150/ HC Wired Mat 150 Corrugated Steel Bulkhead non-load bearing H-60 HC Firebatts 150/ HC Wired Mat 150

page 44 page 45

H-120 HC Firebatts 150/ HC Wired Mat 150

Steel Bulkhead

41

Index of H-constructions - Steel Deck

Index of H-constructions Steel Bulkhead

H-60 Steel Bulkhead restricted

H-60 Steel Bulkhead restricted

Product: Density:

Rockwool HC Firebatts 150 Rockwool HC Wired Mat 150 150 kg/m3

Thickness: Plate: 30 mm + 40 mm insulation Stiffener: 40 mm insulation

Construction: Plate insulated with one layer of 30 mm Rockwool HC Firebatts 150 and one layer of 40 mm Rockwool HC Wired Mat 150. Stiffeners insulated in the same process with min. 40 mm of Rockwool HC Wired Mat 150. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured by washers of 38mm. Application notes: Restricted application (fire against insulated side) All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. Joints between layers must be staggered, 150 mm overlap is recommended. The pins should exceed the insulation by approx 10 mm. Wire mesh must be twisted together at joints.

Insulation can be placed on either side of the steel plate. Advantages: Safe solution Optimal sound properties Fast installation

600
Surfaces: Reinforced aluminium foil

600

480

4.5 mm steel 30 mm Rockwool HC Firebatts 150 40 mm Rockwool HC Wired Mat 150

Pinning

290 mm 400 mm
3 mm steel pin with washer
30 mm Rockwool HC Firebatts 150 4.5 mm steel

1000

3 mm steel pin with washer

40 mm Rockwool HC Wired Mat 150

42

Product: Density:

Rockwool HC Firebatts 150 Rockwool HC Wired Mat 150 150 kg/m3

Thickness: Plate: 30 mm +40 mm insulation Stiffener: 2x40 mm insulation

Construction: Plate insulated with one layer of 30 mm HC Firebatts 150 and one layer of 40 mm HC Wired Mat 150 Stiffeners insulated with min. 2x40 mm Rockwool HC Wired Mat 150. Second layer in the same process as insulation of the plate. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 300 mm distance. Insulation secured by washers of 38 mm Application notes: Restricted application (fire against insulated side) All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. Joints between layers must be staggered, 150 mm overlap is recommended. The pins should exceed the insulation by approx 10 mm. Wire mesh must be twisted480 together at joints.

Insulation can be placed on either side of the steel plate. Advantages: Safe solution Optimal sound properties Fast installation

600
Surfaces: Reinforced aluminium foil

600

4.5 mm steel 30 mm Rockwool HC Firebatts 150 40 mm Rockwool HC Wired Mat 150

Pinning

250 mm 400 mm
3 mm steel pin with washer
30 mm Rockwool HC Firebatts 150 4.5 mm steel

1000

3 mm steel pin with washer

40 mm Rockwool HC Wired Mat 150

43

H-120 Steel Bulkhead restricted

H-120 Steel Bulkhead restricted

60

H-60 corrugated Steel Bulkhead

H-60 corrugated Steel Bulkhead


non-load bearing

Product: Density:

Rockwool HC Firebatts 150 Rockwool HC Wired Mat 150 150 kg/m3

Thickness: Plate 50 mm + 40 mm insulation

Construction: Corrugated steel plate insulated with 50 mm Rockwool HC Firebatts 150 and 40 mm Rockwool HC Wired Mat 150. Corrugated steel plate of min. 1.5 mm. 3 mm pins fixed with approx 300 mm distance. Pins fixed on top of corrugated steel plate by washers of 38 mm No fi ll of corrugation Application notes: All the connections must be tight, no air gaps. Joints must be staggered, 150 mm overlap is recommended. The pins should exceed the insulation by approx 10 mm Wire mesh twisted together of joints. Same solution as H-120.

Advantages: Safe solution Optimal sound properties Fast installation Surfaces: Reinforced aluminium foil

600

600

Pinning
1.5 mm steel

45 mm

3 mm steel pin w. washer 480

250 mm
3 mm steel pin w. washer 50 mm Rockwool HC Firebatts 150 40 mm Rockwool HC Wired Mat 150 250 mm

300 mm

1000

44

non-load bearing

Product: Density:

Rockwool HC Firebatts 150 Rockwool HC Wired Mat 150 150 kg/m3

Thickness: Plate 50 mm + 40 mm insulation

Construction: Corrugated steel plate insulated with 50 mm Rockwool HC Firebatts 150 and 40 mm Rockwool HC Wired Mat 150. Corrugated steel plate of min. 1.5 mm. 3 mm pins fixed with approx 300 mm distance. Pins fixed on top of corrugated steel plate by washers of 38 mm No fi ll of corrugation Application notes: All the connections must be tight, no air gaps. Joints must be staggered, 150 mm overlap is recommended. The pins should exceed the insulation by approx 10 mm Wire mesh twisted together of joints. Same solution as H-60.

Advantages: Safe solution Optimal sound properties Fast installation Surfaces: Reinforced aluminium foil

600

600

Pinning
1.5 mm steel

45 mm

3 mm steel pin w. washer 480

250 mm
3 mm steel pin w. washer 50 mm Rockwool HC Firebatts 150 40 mm Rockwool HC Wired Mat 150 250 mm

300 mm

1000

45

H-120 corrugated Steel Bulkhead

H-120 corrugated Steel Bulkhead

46

Steel - Deck H-60 H-120 HC Firebatts 150 HC Firebatts 150 page 48 page 49

Steel Deck

47

Index of H-constructions - Steel Deck

Index of H-constructions Steel Deck

H-60 Steel Deck

H-60 Steel Deck

Product: Density:

Rockwool HC Firebatts 150 150 kg/m3

Thickness: Plate 50 + 50 mm insulation Stiffener 50 + 50 mm insulation

Construction: Plate insulated with two layers of 50 mm Rockwool HC Firebatts 150. Stiffeners insulated with min. 2x50 mm Rockwool HC Firebatts 150. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm pins fixed with approx 100/400 mm distance.

Advantages: Safe solution Optimal sound properties Easy handling

Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. The pins should exceed the insulation by approx 10 mm. Joints to be staggered, 150 mm overlap is recommended.

Surfaces: Reinforced aluminium foil

Sound: Weigthed sound absorption HC Firebatts 150, 2x50 mm w = 0.90

Pinning

4.5 mm steel 2x50 mm Rockwool HC Firebatts 150 3 mm steel pin w. washer

400 mm

3 mm steel pin with washer


4.5 mm steel 2x50 mm Rockwool HC Firebatts 150 3 mm steel pin with washer

1000
48

Product: Density:

Rockwool HC Firebatts 150 150 kg/m3

Thickness: Plate 65 + 65 mm insulation Stiffener 65 + 65 mm insulation

Construction: Plate insulated with two layers of 65 mm Rockwool HC Firebatts 150. Stiffeners insulated with min. 2x65 mm Rockwool HC Firebatts 150. Standard steel plate 4.5 mm ( 0.5 mm) thick. 3 mm extra long pins fixed with approx 300 mm distance. Insulation secured with washers 38 mm Insulation covered with wire mesh. Application notes: All the connections must be tight, no air gaps. Gap under the stiffener must be fi lled out completely. The pins should exceed the insulation by approx 40 mm. Insulation secured by bending the 40 mm longer pins in different directions, after fixing the washers. Joints to be staggered, 150 mm overlap is recommended. Wire mesh must be twisted of joints.

Advantages: Safe solution Optimal sound properties Easy handling Surfaces: Reinforced aluminium foil

Sound: Weigthed sound absorption 600 HC Firebatts 150, 2x50 mm w = 0.90

600

Expires 2009.10.07 - will not be renewed. Contact Rockwool Marine & Offshore.

4.5 mm steel

480

Pinning

3 mm steel pin w. washer


2x65 mm Rockwool HC Firebatts 150 3 mm steel pin w. washer

300 mm 1000 300 mm


4.5 mm steel 2x65 mm Rockwool HC Firebatts 150 3 mm steel pin w. washer

49

H-120 Steel Deck

H-120 Steel Deck

50

Bulkhead and Deck Jet Fire 30 min. Blast Resistance

page 52 page 53

Jet Fire & Blast Resistance

51

Index of Jet Fire & Blast Restistance

Index of Jet Fire & Blast Resistance

Bulkhead and Deck Jet Fire 30 min.

Bulkhead and Deck Jet Fire 30 min.

Product: Density:

Rockwool HC Firebatts 150 150 kg/m3

Thickness: Plate: 85 mm (35+50 mm) insulation

Construction: Plate and stiffener must be insulated with 35 mm and 50 mm Rockwool HC Firebatts 150. First layer, 35 mm, with reinforced aluminium foil. The foil must be placed so it is between the two layers of insulation. Standard steel plate 5 mm. Standard pins or stainless steel pins 3 mm. Insulation secured with washers of 38 mm. Insulation secured with galvanised wire mesh. Wire mesh must be covered with reinforced aluminium foil. The construction must be covered with 0.8-1.0 mm stainless steel plate. All joints in the stainless steel plate must be against a back-up steel angle 40x20x4 mm, covered with ceramic paper. Stainless steel plate fixed with self-tapping screws at 150 mm c/c. For further details check official drawing.

Application notes: Joints between the two layers of Rockwool HC Firebatts 150 must be staggered, 150 mm overlap is recommended. Wire mesh clamped or twisted at joints Pins must be bent over the fixing washers Test duration 30 min. Advantages: Safe solution

Supports at 500 mm c/c 135

500 mm c/c 65 35 50

Aluminium foil 0.05 mm Support pl. 30x3 at 1000 mm c/c (vertically)

35 50 35 35 50 Support angle 50
L40x20x4 mm welded to support plate SS. screws at 150 mm c/c Ceramic paper Butt jointed stainless steel plate Galvanised wire mesh Reinforced aluminium foil 0.05 mm

Stainless steel plate

52

General arrangement prior to testing - blast resistance - class H The regulatory requirements for the blast behaviour of fire rated bulkheads are not normally well documented. It is considered a general requirement that all parts of fire divisions maintain the same fire and explosion resistance and proof of this must be documented through physical testing.

Rockwool, in association with SINTEF (NBL) in Norway, has performed extensive testing on H-rated Rockwool insulation systems, using controlled gas explosions. The test results below refer to the same insulation construction with various types of wire mesh. Test results on H-0 rated insulation
Test construction 50+35 mm Rockwool HC Firebatts 150 with: Heavy duty stainless steel mesh with pins bent over washers Heavy duty stainless steel mesh with pins bent over washers Galvanised wire mesh with pins bent over washers Galvanised wire mesh with pins bent over washers Galvanised wire mesh with standard pins and washers Load characteristics Pmax(bar) Uxx(m/s) ta(m) 0.34 0.68 0.33 0.58 0.37 240 300 240 300 270 54 33 50 35 49 None None None None None Critical damage

All the above tests were carried out without any significant damage to the insulation material. According to the Norwegian Fire Research Laboratory (SINTEF) a fire will not affect the fire integrity or stability of the insulation. Due to the test methods used, SINTEF has assessed the above results to be conservative.

General arrangement after testing - recommended design limits Rockwool HC Firebatts 150 with: Heavy duty stainless mesh and bent pins: Peak overpressure: 0.7 bar Duration (positive phase): 35 ms Explosion wind: 300 m/s Galvanised mesh and bent pins: Peak overpressure: 0.6 bar Duration (positive phase) 35 ms Explosion wind: 300 m/s Galvanised mesh and standard pins: Peak overpressure: 0.4 bar Duration (positive phase): 50 ms Explosion wind: 300 m/s
Strength of covering steel plate must be calculated by designer

53

Blast Resistance

Blast Resistance

54

Stiffeners Bulkhead and Deck Connections Installation of Surface Protections Steel Plate

page 56 page 57 page 58

Bulkhead and Deck Details

55

Index of Construction Details

Index of Construction Details

Stiffeners

Stiffeners

In most bulkhead and deck constructions stiffeners are used to secure the necessary strength in the construction. In order to prevent heat transmission it is important to secure the right insulation. In general insulation of the stiffeners must follow the official drawings as carried out in the fire tests.

Solas requires that the stiffeners must be insulated*. One way is to insulate without filling the space behind the stiffeners.

450 mm

450 mm
Insulation of stiffener with Marine Wired Mat 105

Insulation of stiffener with Marine Firebatts 100

* acc. to SOLAS MSC/circ. 1120 annex reg. 9.3.4

In other situations the insulation can follow the shape of the stiffener or the void behind the stiffener can be filled out.

450 mm

450 mm

450 mm
Insulation of stiffener with Marine Wired Mat 90

Insulation of stiffener with Marine Batts 45

If the stiffener is more than 450 mm wide the insulation can be stopped at 450 mm.

450 mm

450 mm

450 mm

Insulation of stiffener with Marine Wired Mat 90

Insulation of stiffener with Marine Firebatts 100

56

When two plates are connected in a corner, the heat bridge should always be kept in mind when insulating. The structure must have insulation so that heat transfer can not occur from one unexposed surface through the structure and onto another unexposed surface. The heat must always go minimum 450 mm under the insulation before reaching an unexposed surface(acc. to SOLAS MSC/circ. 1120 annex reg. 9.3.4). Connections between A-60 and A-0 constructions should be insulated by adding a layer of A-60 insulation on the A-0 construction in a minimum width of 450 mm. This is to minimize the effect of the heat A0 bridge.
A60 Bulkhead or Deck Min. 450

Additional insulation Steel Bulkhead/Deck

Another alternative to insulate the heat bridge can be done by installing min. 450 mm* of insulation on the other side of the construction. This will reduce the transferred heat and thereby minimise the risk of self A0 Min. ignition inside the 450 Steel Bulkhead/Deck connecting room.
Additional insulation

* Rockwool recommends 900 mm to secure that the heat always go min. 450 mm under the insulation before reaching an unexposed surface.

Bulkhead and Deck - Construction details In connection with insulation it is important to pay special attention to the details related to junctions, corners etc. in order to avoid potential heat bridges. Below you will find examples of construction details: Corner example
A60 Steel Bulkhead/Deck Steel Bulkhead/Deck Additional insulation Min. 450 Additional insulation Min. 450

Junction example 1
A60

Junction example 2
A60 Bulkhead or Deck

A0
A0/ A60

Additional insulation A60 Steel Bulkhead or Deck A60 Steel Bulkhead or Deck Min. 450 Steel Bulkhead/Deck

Insulation on either side of Bulkhead/Deck

Insulation on the outside of Bulkhead/Deck

Insulation on the inside of Bulkhead/Deck

A60 Bulkhead or Deck

57

Bulkhead and Deck Connections

Bulkhead and Deck Connections

Installation of Surface Steel Plate

Installation of Surface Steel Plate

A surface protection of sheet metal can be installed in different ways, depending on the layout of the stiffeners and the amount of insulation. It is important to make the fixing in a way that minimises the heat bridges and structural noise transmitted via the hull.

Example 1

Example 2

40 mm 40 mm

40 mm 40 mm Max. Max. 150 mm 150 mm Max. Max. 150 mm 150 mm L- Steel L- Steel Flat steel Flat steel Surface steel Surface steel

Max. 500 mm Max. 500 mm L- Steel L- Steel Surface steel Surface steel

Max. 500 mm Max. 500 mm L- Steel L- Steel Surface steel Surface steel

L- Steel L- Steel Flat steel Flat steel Surface steel Surface steel

Fixing of surface steel where space is needed for pipes etc.

Fixing of surface steel as close to the steel plate as possible.

Example 3

Example 4

10 mm 10 mm Surface steel Surface steel Flat steel Flat steel 65 mm 65 mm L- Steel L- Steel Surface steel Surface steel Flat steel Flat steel L- Steel L- Steel Flat steel Flat steel

10 mm 10 mm

40 mm 40 mm 65 mm 65 mm L- Steel L- Steel

40 mm 40 mm

L- Steel L- Steel Flat steel Flat steel Surface steel Surface steel

Surface steel Surface steel

Fixing of surface steel taking large stiffeners into consideration.

Fixing of surface with no stiffeners or stiffeners on the other side of steel plate.

58

Draught Stoppers Penetrations B-15 Extension

page 60 page 61 page 62

B-15 Extension

Draught Stoppers

Penetration

59

Index of Additional Fire Protection

Index of Additional Fire Protection

Draught Stoppers

Draught Stoppers

Draught stoppers are used above ceilings to avoid the spread of smoke and flames in case of fire. Normally the classification companies request a B-0 fire insulation above the ceiling. This can be made from Rockwool Marine Wired Mat or Rockwool Marine Batts after request from the local surveyor or the customer. Construction Rockwool Marine Wired Mat 105, min. 50 mm, with reinforced aluminium foil or Rockwool Marine Firebatts 100, min. 60 mm, with reinforced aluminium foil. Marine Firebatts 100 must be covered with wire mesh. Insulation fixed with 3 mm pins and secured with 38 mm washers. Installation Step 1: First the pins are welded vertically to the underside of the deck in alignment with the required position of the Draught Stopper. Step 2: The pins are then bent 90 in a staggered pattern as shown. Step 3: The Rockwool and wire mesh are then pushed over the pins so that they protrude by a minimum of 25 mm. The insulation is secured by spring steel washers. Penetrations Penetrations through the Draught Stopper are simply made by cutting out the shape of the penetrating items in the Rockwool, for example, pipes, HVAC ducts and cable racks. The cut edge of the Wired Mat must fit tightly to the edge of the penetrating item and the slit in the Rockwool must be stitched/taped back together using steel wire/alu tape. This solution can be used for any type of penetration including multiple penetrations.

60

SOLAS, Part C, Chapter II-2, Regulation 8, sec 4 :

Air spaces enclosed behind ceilings, panelling or linings shall be divided by close-fitting Draught Stops spaced not more than 14 m apart. In the vertical direction, such enclosed air spaces, including those behind linings of stairways, trunks, etc., shall be closed at each deck.

The interpretation of the rules given by IMO in MSC/circ. 847 reg 35.

L1 + L 2 = min. 900 mm L1 L2 Rockwool Fire Insulation

Penetrations of fire protection When pipes, ducts or other go through a bulkhead or deck it is called a penetration. There are special rules regarding insulation when the decks or bulkheads with fire class are penetrated. The pipe going through a fire classed structure must be made of steel and must have a length of minimum 900 mm. IMO suggests to use min. 450 mm on each side of the construction. The min. 900 mm insulation must have the same insulation class weight as the structure that is penetrated.

Steel pipe

Steel min. 3 mm thick

A-60 insulation

SOLAS, Chapter II-2, Regulation 9, sec 3:

The duct spool must be insulated with A-rated fire insulation for a distance of either side of the bulkhead or deck (L1 + L2 = 900 mm)

61

Penetrations

Penetrations

B-15 Extension

B-15 Extension

B-15 extension is used as a B-15 wall extension above the ceiling. The B-15 extension prevents smoke and fire to spread above the ceiling. The B-15 extension solution has passed a B-15 fire test with Rockwool Marine Slab 180, 25 mm which fulfi ls the IMO demands. B-15 wall extension/separation of adjacent spaces Product: Density: Rockwool Marine Slab 180, 25 mm 180 kg/m3

Vessels have screen between the cabins with a fire class of B-0, B-15, A-15 or A30. When a B-0 or B-15 seperation is requested Rockwool recommends using a B-15 construction. 1 2
730 mm

This construction consists of a normal B-15 wall and above the ceiling a 25 mm Rockwool Marine Slab 180. Construction: B-15 Lining panel as wall between cabins. B-15 Screen made of 25 mm Rockwool Marine Slab 180 above the ceiling.

1
Steel angle bar 40x40x2 mm Spot welding for xing Steel angle bar 25x25x2 mm B-15 screen of Rockwool Marine Slab 180, 25 mm

3 2
Spot welding for xing Top steel intermediary prole with pins included Steel angle bar 25x25x2 mm Spot welding for xing B-15 screen Rockwool Marine Slab 180, 25 mm Top steel prole B-15 screen Rockwool Marine Slab 180, 25 mm Spring washer

20 mm 30 mm 50 mm

62

Rockwool Marine Slab 200 Rockwool Marine Slab 140

page 64 page 65

Floating Floor
63

Index of Floating Floor

Index of Floating Floor

Floating Floor Constructions

Floating Floor Constructions Class A-60


MED-B-2302 includes two different types of A-60 Deck class Floating Floor constructions. 1) Rockwool Marine Slab 200 This solution consists of two layers Rockwool Marine Slab 200, each of 30 mm thickness, covered by minimum 2 mm steel plate, spot welded at c/c 150 mm. This construction combines the excellent properties of fire protection, noise reduction, high compression strength and thermal insulation. The max free area recommended is 8 x 8 m. If larger free areas are to be made, division flat bars should be made. This allows the insulation to stay in position without the need of gluing. It is recommended to make full overlap of the two layers. All joints of the Marine Slabs have to be tight butted joints. Smaller weld marks, dents, etc. of an approx max diameter of 50 mm and 10 mm height will be absorbed. If the deck is undulating, an approved self levelling compound or floor screed will have to be used as first layer; a fire retardant PE compound, cement based fi ller or similar. If a water based floor screed or levelling compound is used, it must be given sufficient time to cure before the floating construction is installed. It is very important to ensure not to encapsulate water/moisture, as this will enhance corrosion and limit the expected life time of the construction.

The top layer has to be made of minimum one layer of 2 mm steel plate, according to the fire approvals. Final floor covering has to be decided based upon requirements for mechanical strength and floor finish. As flooring solution, this one is a safe solution, in the sense that a Rockwool Marine Slab of 200 kg/m3 is very ridged and strong, and combined with a medium thick steel plate this is normally adequate for all normal accommodation load.

64

Rockwool Marine & Offshore is preferred supplier for many marine ooring companies. These companies integrate the Rockwool products in their more sophisticated solutions.

Note: Deviations from the certified A-60 oating oor construction in any form, could require new approval by the Class Society or National Marine Authority.

2) Marine Slab 140 This solution consists of one layer of Rockwool Marine Slab 140, 60 mm thickness, covered by minimum 1.5 + 3 mm steel plate. The construction gives in addition to the excellent properties of fire protection, noise reduction and thermal insulation, also reduction of structural noise/vibrations in the steel deck. Rockwool Slab 140 has been designed with focus on the dynamic stiffness, i.e. best possible noise reduction. Please note that the compression strength of this solution is lower than the Marine Slab 200 solution. The first layer of steel plate must be 1.5 mm thick, installed with 50 mm overlap and secured with pop rivets. The second layer(top layer) must be 3 mm steel plate with butted joints and spot welded at c/c 150 mm. Top covering has to be decided based upon requirements for mechanical strength and finish.

Sealing of edges to prevent structural noise

Enclosing: For the perimeter of the construction it is recommended to finish the insulation with a rigid Rockwool product i.e. Rockwool Marine Slab 140 or 200 placed edgeways and sealed with a flexible sealant. Many of the flooring companies are using Rockwool Marine Slabs in densities of 140 - 200 kg/m3, in combination with more complex top layers. The max load for the complete flooring construction will depend entirely on the top layer. The load capacity of the specific construction is to be calculated and tested by the flooring company. Rockwool Marine & Offshore is preferred supplier for many dedicated marine flooring companies. These companies then create more sophisticated solutions for superb noise reduction in both high and low frequencies.
65

Floating Floor Constructions

66

Technical Insulation in General Insulation with Pipe Section Insulation with Marine Lamella Mat 32 Insulation with Marine Wired Mat Insulation with Marine Slabs/Batts Cladding

page 68 page 69 page 70 page 71 page 72 page 72

Technical Insulation
67

Index of Technical insulation

Index of Technical Insulation

Technical insulation

Technical Insulation
Technical Insulation in General
To guarantee a correct process cycle, the condition of the media within the pipes must remain within the set limitations (e.g. temperature, viscosity, pressure, etc.). In addition to the correct isometric construction and fastening of the piping, the piping insulation also has an important function. It must ensure that heat losses are effectively reduced and that the installation continues to operate economically and functionally on a permanent basis. This is the only way to guarantee the maximum efficiency of the process cycle throughout the design service life without losses as a result of faults.

Principally, a thermal insulation structure for piping consists of an appropriate insulating material, usually covered by sheet metal cladding. This protects the pipe and the insulation from external influences such as weather or mechanical loads. Spacers are also essential with insulation material such as wired mats, which do not offer sufficient resistance to pressure to hold the weight of the cladding and other external loads. These spacers transfer the loads from the cladding directly onto the pipe to be insulated. In case of vertical piping, support structures are fitted to take on the loads of the insulation and the cladding. In general, support structures and spacers form thermal bridges. HVAC Insulation - Pipes For the HVAC (Heat Ventilation Air Condition) applications onboard a ship it is most common to use Pipe Sections or Marine Lamella Mats to insulate the pipes. The aim is to prevent heat loss in heating systems and warm water supply. It is necessary to supply heating and warm water also in the last cabin away from the source.
68

The benefits of correct thermal insulation for piping include: Reduction of heat losses Cost savings Reduction of CO2 emissions Frost protection Process control:
ensuring the stability of the process temperature

Noise reduction Condensation prevention (Personal) Protection against high temperatures Airducts Today, many requirements are made on air ducts. Most important is that the comfort on board the vessels or platform living quarters is considered and that no compromises are made to the demands on fire safety. In connection with ventilation of cabins and other rooms it must furthermore be ensured that no condensation is formed and that the required temperature is maintained all the time. This is obtained by using one of the Rockwool Marine & Offshore products in the correct thickness. Thickness calculation program can be found on our webpage.

Insulation with Pipe Section


Generally, the best insulation is achieved by using Rockwool Pipe Section. The Pipe Sections can be used up to max. service temperatures of 620C acc. to EN 14707. Facing max. 80C. The Pipe Sections are supplied ready split and hinged for quick and easy snap-on assembly and are suitable for thermal and acoustical insulation of pipe work. Their excellent fit and high compression resistance mean that Pipe Sections can be applied in a single layer without any additional spacers. Consequently the number of thermal bridges, which have a negative influence on the insulation, is greatly reduced.

Banding Rockwool recommends that the Pipe Section is secured to the pipe by applying three steel bands per section length, with the end bands approximately 100mm from the lateral joints. If wire ties or spiral binding are to be used, they should only be considered on pipe sections with an outer surface diameter of 200 mm or less. In those cases, there should be: At least three wires tie per section. Spiral binding must be per section (i.e. tied off at each end of each pipe section).

Multiple Layers Where there is a requirement for more than one layer of Pipe Section, it is recommended that both layers should be banded to ensure a consistently tight fit of the insulation. The outer layer(s) of the section should be applied with staggered joints, both laterally and longitudinally.

69

Technical insulation

Technical insulation

Elbows/Bends To form insulated elbows with Pipe Section, the section is cut at angles to form segments. The amount of segments depends on the size of the pipe and the angle of the elbow. When the pipe section segments are fit around the pipe, they are secured with steel banding or wire ties per section. Any minor gaps between segments can be fi lled with pieces of Rockwool insulation.

Insulation with Marine Lamella Mat


Marine Lamella Mat 32 consists of stone wool lamellas placed edgewise, the majority of the fibres being perpendicular to the facing. The Marine Lamella Mats can be used up to max. service temperatures of 250C. Facing max. 80C. Due to the alignment of the Rockwool fibres in Marine Lamella Mats, they have a high resistance to compression. They are suitable for applications where there is a requirement for: Compression resistance Possible mechanical impact Operational vibration loads The surface finish on the Marine Lamella Mats, should be taped at all joints. The mats are secured with steel banding.

70

Insulation with Marine Wired Mat


Marine Wired Mat is a lightly bonded stone wool mat faced with a galvanised wire mesh. The Wired Mats can be used up to max. service temperatures of 680C acc. to EN 14706. Facing 80C. Due to their flexibility and high temperature resistance, Marine Wired Mats can easily be cut and fixed onto the piping. Marine Wired Mats have a relatively low resistance to pressure and from a practical point of view should only be installed in combination with spacers. Due to the thermal bridges of this combination the better insulation performances are often achieved in the lower and middle temperature range with Marine Pipe Sections rather than with Marine Wired Mats.

These wired mats are ideal for application in situations where the use of Pipe Sections is difficult or impossible: Temperatures above 300C Pipe diameters 350 mm Piping with a high number of shaped pieces such as elbows or T-joints.

Fixing Any gaps created by the type of support ring installed, must be fi lled with loose Rockwool. The Marine Wired Mats are secured to the pipe by stitching the edges of the wire mesh together with binding wire or by clipping the mesh together with C-Hooks. On pipes with a diameter greater than 350 mm, steel straps or additional pins and spring washers are applied on the underside of the pipe, it may be necessary to prevent sagging. On vertical pipes, the wire mesh of each mat must be tied to the support ring above.

Multiple Layers Where there is a requirement for more than one layer of Marine Wired Mat, it is recommended that all layers are stitched or clipped to ensure a consistently tight fit of the insulation. The outer layer(s) of mat should be applied with longitudinally staggered joints and where applicable, with staggered joints laterally.
71

Technical insulation

Technical insulation

Insulation with Marine Slabs/Batts


Tanks and vessels can be insulated with Rockwool Marine Slabs/Batts min. density 45 kg/m3 if there are no requirements for high operational temperatures. The products can be used up to max. service temperatures of 250C. The Marine Slabs/Batts are installed over metal strap ties. These ties are bent over the edge of the outer layer of Marine Slabs/Batts to retain them against the tank wall. Where the insulation extends more than 4 m in height, intermediate support profi les must be installed onto the tank wall. Special S-profi les can be used to ensure vertically staggered joints, while supporting the Marine Slabs/Batts above and retaining the Marine Slabs/Batts below. When more than one layer of Marine Slabs/Batts is required, all joints must be staggered and tightly butted together to avoid thermal bridges. The Marine Slabs/Batts must be covered with a flat or profi led external cladding to protect them from the weather and mechanical damage.

Cladding
Suitable cladding should be applied to protect the insulation from weather influences, mechanical loads and (potentially corrosive) pollution. Selecting the appropriate cladding depends on various factors, such as working loads, wind loads, ambient temperatures and conditions. When selecting the appropriate cladding, take the following points into account: As a general rule, galvanised steel more than aluminium is used indoors due to its mechanical strength, fire resistance and low surface temperature (in comparison to an aluminium cladding). In corrosive environments like outdoors on deck where salty water leads to corrision, aluminised steel, stainless steel or glass reinforced polyester (e.g. Rocktight) is used as cladding. Stainless steel is recommended for use in environments with a fire risk.
72

The surface temperature of the cladding is influenced by the material type. The following applies as a general rule: the shinier the surface, the higher the surface temperature. To exclude the risk of galvanic corrosion, only use combinations of metals that do not tend to corrode due to their electrochemical potentials. For acoustic insulation, a noise absorbent material (Lead layer, polyethyten foil) is installed on the insulation or inside the cladding. To reduce the risk of fire, limit the surface temperatures of the cladding to the maximum operating temperature of the noise absorbent material.

Rules and Regulations Sound Absorption Sound Reduction

page 74 page 75 page 76

73

Index of Sound

Index of Sound

Sound

Sound

Rules and Regulations


In general for commercial vessels the rules concerning noise levels onboard are quite simple and few. It is basically a set of dB(A) levels given for a range of different positions onboard. These settings are given in the IMO res. A.468(XII). Limits for noise levels are specified for various maximum spaces as follows:
Work spaces Machinery spaces (continuously manned) Machinery spaces (not continuously manned) Machinery control rooms Workshops Non-specified work spaces dB(A) 90 110 75 85 90

When the sound hits a wall, the sound is reflected - some will be absorbed and a small part will be transmitted. The sound insulating property of the construction, its reduction power called R, is measured in dB and is a measurement of the power of the construction to prevent the passage of the sound. High R = good sound insulation = good sound reduction. In porous absorbers like Rockwool materials the sound absorption takes place by the sound energy being converted into frictional heat between the Rockwool fibres. The sound absorption depends on the thickness of the material. The values at the low frequencies are improved with increased thickness. The same tendency can be obtained by moving the absorbers away from the base. Protection of the absorber by a cover plate does not change the absorption as long as the plate has a sufficient number of openings. A perforation of 15% could be sufficient for a 1 mm thick cover plate of steel. Thicker covers require a larger number of small holes.

Navigation spaces Navigating bridge and chart rooms Listening posts, including navigating bridge wings and windows Radio rooms (with radio equipment operating but not producing audio signals) Radar rooms

dB(A) 65 70 60 65

Accommodation spaces Cabins and hospitals Mess rooms Recreation rooms Open recreation areas Offices

dB(A) 60 65 65 75 65

Service spaces Galleys, without food processing equipment operating Service and pantries

dB(A) 75 75

Normally unoccupied spaces Spaces not specified 74

dB(A) 90

Sound Absorption

Overview - absorption measurements


No 1 2 3 4 5 6 Rockwool products Marine Batts 45, 50 mm Marine Slab 60, 50 mm Marine Slab 80, 50 mm Marine Slab 80, 50 mm + 1 mm perf. steel suspended 10 mm Marine Slab 80, 2 x 50 mm Marine Slab 80, 2 x 50 mm + glass net + 1 mm perf. steel Marine Slab 80, 2 x 50 mm + glass net + 1 mm perf. steel suspended 10 mm Marine Slab 140, 50 mm Marine Slab 150, 50 mm Marine Slab 200, 30 mm Marine Slab 200, 50 mm Marine Slab 200, 2 x 30 mm Marine Firebatts 100, 40 mm Marine Firebatts 100, 40 mm + alu foil Marine Firebatts 100, 60 mm incl. pins and washers Marine Firebatts 100, 60 mm incl. pins and washers, covered by 19 foil Marine Firebatts 130, 30 mm Marine Firebatts 130, 50 mm Marine Firebatts 130, 2 x 30 mm Marine Firebatts 130, 30 mm + 30 mm alu + 1 mm perf. steel suspended 10 mm Marine Firebatts 150, 2 x 50 mm Marine Wired Mat 80, 50 mm Marine Wired Mat 80, 50 mm incl. alu foil Marine Wired Mat 80, 100 mm Marine Wired Mat 80, 100 mm incl. alu foil Marine Wired Mat 90, 45 mm Marine Wired Mat 90, 2 x 45 mm Marine Wired Mat 90, 45 mm with 400 g/m2 glass cloth Marine Wired Mat 105, 30 mm Marine Wired Mat 105, 75 mm Marine Wired Mat 105, 100 mm
Weighted absorption

w = 0.75 w = 0.85 w = 0.90 w = 0.90 w = 0.95 w = 0.95 w = 0.95 w = 0.85 w = 0.75 w = 0.75 w = 0.75 w = 0.80 w = 0.80 w = 0.50 w = 0.90 w = 0.90 w = 0.70 w = 0.80 w = 0.90 w = 0.30 w = 0.90 w = 0.90 w = 0.75 w = 0.95 w = 0.75 w = 0.90 w = 0.95 w = 0.75 w = 0.80 w = 0.90 w = 0.90

Sound absorption is a material property which describes how well sound waves are absorbed in a material. When a sound wave is absorbed, it simply means that the sound wave is transferred into another kind of energy i.e. heat. On this page you will find the sound absorption coefficient, w for the most common Rockwool Marine & Offshore products.

7 8 9 10 11 12 13 14 15 16 17 18 19 20

21 22 23 24 25 26 27 28 29 For more information about sound insulation, please read the Rockwool Marine & Offshore Acoustic Manual or visit our webpage www.rockwool-marine.com 30 31

75

Sound

Sound

Sound Reduction

Overview - reduction measurements


No Rockwool products Marine Slab 80, 2 x 50 mm with 5 - 10 mm air gap Marine Firebatts 130, 2 x 30 mm / 30 mm Marine Firebatts 130, 2 x 30 mm / 30 mm with 19 foil perforated plate Marine Firebatts 130, 40 mm with 1 mm steel sheet Marine Wired Mat 90, 2 x 45 mm with 1 mm steel sheet Marine Firebatts 100, 60 mm + 25 mm strips on L-profiles Marine Firebatts 100, 60 mm GW 200 plus tape Marine Firebatts 100 Alu, 60 / 25 mm Marine Batts 45, 50 / 25 mm strips on L-profiles and 25 mm panel Weighted reduction Rw = 49 dB Rw = 48 dB Rw = 47 dB Rw = 56 dB Rw = 58 dB Rw = 45 dB Rw = 45 dB Rw = 46 dB Rw = 62 dB

Sound reduction is an impression rating the reduction of sound through a wall or a building element from one room to the other. Since the sound reduction may be different at different frequencies, test measurements are subjected to a standard procedure which yields a single number that is about equal to the average sound reduction in the middle of the human hearing range. The weighting procedure is standardized in ISO 717-1 for the sound reduction of airborne noise. Rw , Rw: weighted sound reduction index, dB Rw (dB) is the weighted apparent sound reduction index in a building, including flanking sound transmission. Rw is the laboratory value for the weighted sound reduction without flanking transmission.

All measurements carried out on 4.5 mm steel plate

76

Solutions for Thermal Insulation Lambda Values () Thermal Calculations

page 78 page 79 page 80

77

Index of Thermal insulation of Bulkhead & Deck

Index of Thermal Insulation of Bulkhead and Deck

Thermal Insulation

Thermal Insulation

The requirements of the indoor climate and comfort have become more stringent during the recent years. The insulation constitutes an important factor of this, as it ensures that the correct temperature is obtained. The most common way of expressing thermal properties is by using the following nomenclature: Coefcient of the Thermal Transmission (U-value) Thermal Resistance (R) Thermal Conductivity () It is important to note that the -value for any given material varies with temperature. Specification of the -value should therefore be referred to as mean temperature and, if possible, to a standardised method for measurement and calculation.

Solutions for Thermal Insulation


1: Thermal insulation can be used alone where there is no other demand for the deck and bulkhead. 2: Thermal insulation can also be used together with fire insulation or sound insulation. When the minimum insulation thickness has been found for protecting against sound or fire, the thermal transmission (U-value) of this material can be calculated from the -value. If a higher insulation level is requested the construction can be improved by adding an extra layer of a lower density product. In all cases of insulating towards cold temperatures the wool must always be covered by a vapour tight surface. This surface can be aluminium foil or another kind of vapour barrier. The gaps should be tightly sealed with alu tape. When adding additional insulation to a fire construction it should be documented and approved by the local surveyor.
78

Floor connection When making a surface towards the exterior it is necessary to end the insulation 50 mm above the floor. This to make sure that condensate from the bulkhead can be drained away.

In front of the gab, a piece of at iron can be fit to guide the condensate to a drain.

Lambda value ( ) measurements on Rockwool products (EN12667):

Product [W/mK ] Marine Batts 32 Marine Batts 45 Marine Slab 60 Marine Slab 80 Marine Slab 140 Marine Slab 150 Marine Slab 200 Marine Firebatts 100 Marine Firebatts 110 Marine Firebatts 130 Marine Lamella Mat 32 Marine Wired Mat 80 Marine Wired Mat 90 Marine Wired Mat 105 HC Firebatts 150 Pipe Section 850/864 Universal Pipe Section

10 0.036 0.034 0.034 0.034 0.035 0.035 0.037 0.035 0.035 0.035 0.039 0.033 0.034 0.034 0.035 0.035 0.036
79

All Rockwool Marine & Offshore products fulfil the IMO rules of noncombustibility and low ame spread. Besides this the products have excellent water repellent properties which are also important as thermal insulation is often placed directly up against the outer construction with changing temperatures.

Thermal Insulation

Thermal Calculations

Thermal Calculations

Lambda value/ thermal conductivity () The lambda() value, also referred to as thermal
conductivity, is a value indicating how well a material conducts heat. It indicates the quantity of heat (W), which is conducted through 1 m2 wall, in a thickness of 1 m, when the difference in temperature between the opposite surfaces of this wall equals 1 K (or 1C). In practice is a numerical value expressed in terms of W/(mK). The lower the value, the better the insulation property of the material. Examples at 10C Steel: = 50 W/mK Concrete: = 1.6 W/mK Glass: = 1.1 W/mK Wood: = 0.12 W/mK Rockwool: = 0.033W/mK
Most materials will increase in at rising temperatures.

= W/mK

U value U = W/m2K Thickness


The transport of thermal energy through a structure is expressed by a coefficient, U (Thermal transmittance coefficient). It represents the flow of heat (in W) through 1 m2 of a structure, when the difference between the two surrounding temperatures is 1 K (or 1C). The thermal transmittance coefficient is expressed in W/(m2K). The lower the coefficient, the better the structure insulates.

U=

R value 1 Thickness(m) R = U or R = ( W/mK)


Thermal resistance, R, is a measure used in a construction. The R value is the reciprocal value U-value. Increasing the thickness of an insulating layer increases the R value.

Examples
The steel plate is not taken into consideration due to the low added value. Marine Batts 45, 50 mm (10 = 0.034 W/mK) R = 0.05/0.034 = 1.47[m2K/W] U = 0.68[W/m2K] Marine Batts 45, 100 mm (10 = 0.034 W/mK) R = 0.1/0.034 = 2.94[m2K/W] U= 0.34[W/m2K]

Marine Firebatts 100, 60 mm (10 = 0.035 W/mK) R = 0.06/0.035 = 1.714[m2K/W] U = 0.57[W/m2K] Marine Firebatts 100, 60 mm + Marine Batts 45, 50 mm (10 = 0.035 W/mK 10 = 0.034 W/mK ) R = (0.06/0.035) + (0.05/0.034) = 3.18[m2K/W] U = 0.31[W/m2K] Marine Firebatts 100, 60mm + Marine Batts 45, 100mm (10 = 0.035 W/mK 10 = 0.034 W/mK ) R = (0.06/0.035) + (0.1/0.034) = 4.65[m2K/W] U = 0.21[W/m2K]

80

Rockwool Marine & Offshore holds a large number of certificates and the products and constructions are certified according to the latest IMO regulations. Rockwool Marine & Offshore is continuously renewing and getting new certificates, to get the newest information please visit our website, www.rockwoolmarine.com

On the following pages you will find an overview of the certificates Rockwool Marine & Offshore holds.

81

Certificates

Certificates

Certificates

American Bureau of Shipping (ABS)

MED 96/98/EC - USCG (DNV)

Russian Maritime Register of Shipping (RMRS)

China Classification Society (CCS)

Nippon Kaiji Kyokai (NKK)

Certificates

Classification Societies

Local authorities

Det Norske Vertitas (DNV)

Germanischer Lloyd (GL)

Lloyds Register (LR)

Indian Register (IR)

Bureau Veritas (BV)

Canada

Bulkhead
Steel A-30 A-30 A-60 A-60 A-60 A-60 A-60 restricted A-60 restricted Alu A-60 A-60 * A-60 restricted Marine Firebatts 130 Marine Firebatts 100 Marine Firebatts 130 Marine Batts 45 Marine Wired Mat 90 Marine Firebatts 100 Marine Firebatts 130 Marine Wired Mat 90 Marine Wired Mat 105 Marine Firebatts 100 Marine Firebatts 130

Density
kg/m3 45 90 100 130 90 105 100 130 kg/m 130 100 130
3

Thickness
Plate 50 50 60 2x30 2x45 75 40 50 Plate 2x30 ** 2x30 ** 2x30 Stiffener 25 30 25 30 45 30 40 50 Stiffener 2x30 2x30 2x30

Japan

A-constructions

* New construction - applied for certificates

** Insulation on both sides of alu plate

Deck
Steel A-30 A-30 A-60 A-60 A-60 A-60 Floating Floor A-60 Floating Floor Alu A-30 A-60 * A-60 Marine Batts 45/ Marine Wired Mat 90 Marine Firebatts 100 Marine Firebatts 130 Marine Batts 45 Marine Wired Mat 90 Marine Firebatts 100 Marine Firebatts 130 Marine Wired Mat 90 Marine Slab 200 (2 mm steel top plate) Marine Slab 140 (1.5 mm + 3 mm top steel plates)

Density
kg/m3 45 90 100 130 90 200

Thickness
Plate 50 30 40 40 45 2x30 Stiffener 30 30 25 40 45

140 kg/m3 90 100 130

60 Plate 50 2x30 2x30 Stiffener 45 2x30 2x30

* New construction - applied for certificates

H-constructions Bulkhead
Steel H-60 * restricted H-120 * restricted H-60 cor. Non Load Bearing * H-120 cor. Non Load Bearing * HC Firebatts 150 HC Wired Mat 150 HC Firebatts 150 HC Wired Mat 150 HC Firebatts 150 HC Wired Mat 150 HC Firebatts 150 HC Wired Mat 150

Density
kg/m 150 150 150
3

Thickness
Plate 30+40 30+40 50+40 Stiffener 40 2x40

150

50+40

* New construction - applied for certificates

Deck
Steel H-60 * H-120 ** HC Firebatts 150

Density
kg/m 150
3

Thickness
Plate 2x50 Stiffener 2x50

* New construction - applied for certificates ** Expires 2009.10.07. Will not be renewed. Contact Rockwool Marine & Offshore

82

Taiwan

American Bureau of Shipping (ABS)

MED 96/98/EC - USCG (DNV)

Russian Maritime Register of Shipping (RMRS)

China Classification Society (CCS)

Nippon Kaiji Kyokai (NKK)

Det Norske Vertitas (DNV)

Germanischer Lloyd (GL)

Lloyds Register (LR)

Indian Register (IR)

Bureau Veritas (BV)

Canada

Marine Batts
27-55 kg/m3 30-45 kg/m3 32-45 kg/m3 45 kg/m3

Marine Slab
55-300 kg/m3 60-200 kg/m3 60-240 kg/m3 60-250 kg/m3

Marine Firebatts
100-150 kg/m3 130 kg/m3

Japan

Non Combustible Products

Marine Lamella Mat


32-45 kg/m3

Marine Wired Mat


35-150 kg/m3 80-105 kg/m3 35-135 kg/m3 105 kg/m3

Pipe Sections
Marine Universal Pipe Sections Pipe Sections 850/864

Glass Cloth
Glass Cloth

Low Flame Spread


Reinforced aluminium foil with glass net/aluminium foil Glass cloth (200-400 gr/m2) Glass vlies Marine Rocktight

Please check www.rockwool-marine.com for latest update!


83

Taiwan

CAD drawings Certificates

Classification Societies

Local authorities

84

Product Selector Products Surfaces

page 86 page 87 page 93

85

Index of Product Guide

Index of Product Guide

Product Selector

Product Selector

Rockwool Marine & Offshore markets a range of specially developed and dedicated products within marine and offshore insulation. The table below gives an overview of our standard product range and applications

Products

Marine Wired Mat 80, 90, 105

Marine Batts 45*, 45 RL

Marine Lamella Mat 32

Universal Pipe Section

Pipe Sections 850/864

Marine Batts 32, 32 RL

Marine Slab 150, 200

Marine Slab 140, 200

Marine Firebatts 100

Marine Firebatts 130

Marine Firebatts 110

HC Wired Mat 150

HC Firebatts 150

Marine Slab 60

Marine Slab 80

Fields of application
Bulkhead and Deck A constructions H constructions Comfort Floating floors Pipes <250C >250C Tanks Air ducts <250C >250C Fire Comfort insulation Exhaust pipes Sub-sea pipelines Thermal insulation Fire Fire


* Fire, only Marine Batts 45

86

Aquaduct

Rockwool Marine Batts 32


Product description Rockwool Marine Batts 32 is a soft, resilient slab made of stone wool. The product can be supplied with reinforced alu foil. Application Marine Batts 32 is used for comfort insulation.

Rockwool Marine Batts 32 RL - reinforced alu foil


Product description Rockwool Marine Batts 32 RL is a soft, resilient roll made of stone wool. Marine Batts 32 RL is supplied as a highly compressed roll. The product is as standard supplied with reinforced alu foil. Application Marine Batts 32 RL is used for comfort insulation. The high compression reduces the transportation cost significantly.

Rockwool Marine Batts 45


Product description Rockwool Marine Batts 45 is a semi-regid, resilient slab made of stone wool. The product can be supplied with reinforced alu foil or glass fabric. Application Marine Batts 45 is used for comfort insulation and form part of approved A-30 Deck and A-30 Bulkhead constructions.

Rockwool Marine Batts 45 RL - reinforced alu foil


Product description Rockwool Marine Batts 45 RL is made of stone wool. The product can be supplied with reinforced alu foil. Application Marine Batts 45 RL is primarily used for comfort insulation 87

Products

Products

Products

Rockwool Marine Slab 60


Product description Rockwool Marine Slab 60 is a semi-rigid slab of stone wool. Excellent properties for easy handling and installation. Application Marine Slab 60 is primarily used for sound insulation. Perfect as thermal insulation with high noise reduction.

Rockwool Marine Slab 60 Black Tissue


Product description Rockwool Marine Slab 60 Black Tissue is a semi-rigid insulation slab of stone wool. The black tissue gives a dust free surface. Excellent properties for easy handling and installation. Application Marine Slab 60 Black is primarily used for ventilation duct insulation. The product is perfect as thermal insulation with high noise reduction.

Rockwool Marine Slab 80


Product description Rockwool Marine Slab 80 is a semi-rigid slab of stone wool. Excellent properties for easy handling and installation. Application Marine Slab 80 is primarily used for sound insulation.

Rockwool Marine Slab 80 Black Tissue


Product description Rockwool Marine Slab 80 Black Tissue is a semi-rigid slab of stone wool. The black tissue gives a dust free surface. Excellent properties for easy handling and installation. Application Marine Slab 80 Black Tissue is generally developed for sound insulation. The product can also be used as finishing surface in areas where the surface just needs to be dust free. Another application could be behind perforated plates in panels or simlilar. 88

Rockwool Marine Slab 140


Product description Rockwool Marine Slab 140 is a semi-rigid slab made of stone wool. This product has a special fibre structure which gives an optimal dynamic stiffness. Application Marine Slab 140 is developed for floating floor insulation only with approved top layer.

Rockwool Marine Slab 150


Product description Rockwool Marine Slab 150 is a strong, rigid insulation slab made of stone wool. The high density and the structure of the material provide good noise reduction. Application Marine Slab 150 is primarily used for floating decks with a pressure-equalizing plate of steel or moulding material. The product is used where load capacity is required. Marine Slab 150 can also be cut up and used in panels.

Rockwool Marine Slab 200


Product description Rockwool Marine Slab 200 is a strong, rigid insulation slab made of stone wool. The high density and the structure of the material provide a good noise reduction. Application Marine Slab 200 is primarily used for floating floors with a pressure-equalizing plate of steel or moulding material. The product is used where great load capacity is required. The product forms part of an A-60 floating floor construction tested with 2 mm steel plate. Top layer according to the static calculations. Marine Slab 200 can also be cut up and used in panels.

Rockwool Marine Firebatts 100


Product description Rockwool Marine Firebatts 100 is a semi-rigid slab made of stone wool. The product can be supplied with reinforced alu foil or glass fabric. Application Marine Firebatts 100 is primarily used as part of approved A constructions for deck and bulkhead.

89

Products

Products

Rockwool Marine Firebatts 110


Product description Rockwool Marine Firebatts 110 is a semi-rigid slab made of stone wool. Application Marine Firebatts 110 is primarily used as high temperature insulation. Furthermore the products can be used as insulation of structures where the temperature exceeds 250C. Max. service temp. wool: 750C

Rockwool Marine Firebatts 130


Product description Rockwool Marine Firebatts 130 is a semi-rigid slab made of stone wool. The product can be supplied with reinforced alu or glass fabric. Application Marine Firebatts 130 is primarily used as part of approved A constructions for deck and bulkhead.

Rockwool HC Wired Mat 150


Product description Rockwool HC Wired Mat 150 is made of stone wool. One side is faced with 1 galvanised wire mesh. The wire netting is stitched on with galvanised wire. Application Rockwool HC Wired Mat 150 is used for hydrocarbon fire protection of bulkheads and firewalls.

Rockwool HC Firebatts 150


Product description Rockwool HC Firebatts 150 is a slab made of stone wool. The product is specially developed to provide maximum fire protection. HC Firebatts 150 can be supplied with reinforced alu foil. Application HC Firebatts 150 is used for hydrocarbon fire protection of bulkheads, decks and firewalls.

90

Rockwool Marine Lamella Mat 32


Product description Rockwool Marine Lamella Mat 32 consists of stone wool lamellas placed edgewise, the majority of the fibres being perpendicular to the facing. The product is as standard delivered with a reinforced alu foil. Application Marine Lamella Mat 32 is used for insulation of pipes, tanks and ventilation ducts. Max. service temperature 250C. Facing 80C.

Rockwool Marine Wired Mat 80


Product description Rockwool Marine Wired Mat 80 is made of stone wool. One side is faced with 1 galvanized wire mesh. The wire netting is stitched on with galvanized wire. Application Marine Wired Mat 80 is used for insulation of technical installations, particularly pipes with a temperature exceeding 250C. Max. service temp. wool: 640C acc. to EN 14706. Facing 80C.

Rockwool Marine Wired Mat 90


Product description Rockwool Marine Wired Mat 90 is made of stone wool. One side is faced with 1 galvanized wire netting. The wire netting is stitched on with galvanized wire. The product can be supplied with glass fabric. Application Marine Wired Mat 90 is used for insulation of technical installations, particularly pipes with a temperature exceeding 250C. The product can be used as fire insulation in approved A constructions. Max. service temp. 650C acc. to EN 14706. Facing 80C.

Rockwool Marine Wired Mat 105


Product description Rockwool Marine Wired Mat 105 is made of stone wool. One side is faced with 1 galvanized wire netting. The wire netting is stitched on with galvanized wire. The product can be supplied with reinforced alu foil or glass fabric. Application Marine Wired Mat 105 is used for insulation of technical installations, particularly pipes with a temperature exceeding 250C. The product can be used as fire insulation in approved A constructions. Marine Wired Mat 105 can be used for insulation of pipe penetrations in connection with A constructions. Max. service temp. wool 680C acc. to EN 14706. Facing 80C 91

Products

Products

Rockwool Pipe Sections 850 and 864


Product description Rockwool Pipe Sections 850 and 864 are pressure-resistant and non-combustible preformed pipe sections. Pipe Section 864 is supplied with reinforced alu foil. Application Pipe Sections 850 and 864 are suitable for steam and process pipings. Max. service temperature 620C acc. to EN 14707. Facing max. 80C.

Rockwool Marine Universal Pipe Section w. tape


Product description Rockwool Marine Universal Pipe Section is made of stone wool. The facing consists of reinforced alu foil. The effect of the facing is that the pipe section is so flexible that it can be used for insulation of elbows without preparation. Universal Pipe Section is delivered with self-adhesive tape. Application Thermal and condensation insulation of pipes and elbows. The product is easy to work with and is particularly suited for pipes in crawl spaces. Marine Universal Pipe Sections can be used for condensation insulation when all joints are closed with alu tape. The operation of the plant must be discontinuous. Max. service temperature 250C. Facing max. 80C.

92

There are many reasons for choosing insulation products with facings. In most cases it is done to obtain a vapour barrier, which prevents formation of condensation on the cold side of a construction. If vapour is the reason for choosing a new surface Rockwool markets different products with reinforced aluminium foil. In other cases it is necessary to have a better look than the pure wool; Rockwool markets different surfaces such as glass tissue and glass cloth. If the need is to secure the product then a surface with wire mesh might be to prefer.

ROCKWOOL

Plain Rockwool:
This is the basic Rockwool product which is approved and suitable for almost any purpose. The products are based on stone wool which can withstand temperatures above 1,000C without melting.
WIRED MAT

Wired Mat with wire mesh:


Some of our fire rated constructions are based on Wired Mat and the wire mesh can form an additional safety to secure the product. Within technical insulation a Wired Mat if often used for high temperatures applications or if you need to bend the insulation around e.g. a pipe.
WIRED MAT REINFORCED ALU

Wired Mat with reinforced aluminium foil and wire mesh:


This surface has the same properties as the Wired Mat but has further more the property of securing a dust free surface.
REINFORCED ALU

Reinforced aluminium foil: The reinforced aluminium surface will be the best solution if you need a vapour barrier. The product will secure that no vapour will enter the product and result in corrosion of steel and damaged wool.
GLASS CLOTH - 200 g/m2 (GW200) + 400 g/m2 (GW400)

Glass cloth:
This surface has three major properties: impact resistant, dust free surface and a nicer outlook. This surface will in many cases save the use of an extra metal cladding as the woven cloth is strong enough to resist most impact from the surroundings.
GLASS TISSUE BLACK

Black glass tissue:


The thin black tissue is often used in ventilation shafts or behind a perforated plate as it secures a dust free surface and a nice outlook.

GLASS TISSUE NATURAL/WHITE

White glass tissue:


The thin white surface will secure a dust free surface. The white/transparent look will give a bright surface.

93

Surfaces

Surfaces

Aquaduct

94

Aquaduct - Thermal Insulation Solutions for Sub-sea Pipelines

Traditional solution; Aquaduct CL used for Pipe in Pipe

Rockwools unique product properties are also available for thermal insulation of Sub Sea Pipelines. Advantages Resistant to high temperatures Resilient; good recovery following deformation Unaffected by welding of field joints Free from HFCs and other blowing gases Reliable performance; thermal conductivity cannot degrade due to loss of entrapped gas Easy to handle and install Rockwool Insulation is recyclable and its life cycle analysis proves that it contributes actively to improve the environment.
Alternative Aquaduct Solutions

Due to the flexibility of the product range of Aquaduct Solutions we have the capability to offer specific solutions to meet specific demands, regardless of the complexity of Pipe Bundle configurations. These are some examples of the solutions that we have previously offered. Rockwool insulation products can be tailor made for individual projects and purposes. The most typical products are described below.

Aquaduct CL Aquaduct CL are special patented Rockwool products where the vertical direction of the fibres provides an excellent compression resistance at low thicknesses (down to 10 mm thickness). The fibres are bonded to a reinforced aluminium foil outer facing and the product can be supplied with very low tolerances. In most cases Aquaduct CL will be the optimal choice for Pipe in Pipe solutions.

Aquaduct Sections Aquaduct Sections are rigid pre-formed circular units of Rockwool insulation supplied with or without an outer covering. Aquaduct is available in almost any combination of diameter, thickness and length and can be adapted to individual needs and specifications. Aquaduct Sections are the optimal choice for bigger sizes of pipe.

95

Aquaduct

Health and safety - Green Passport

Health and Safety - Green Passport

Scientific research of man-made mineral fibres goes back to 1930; to the beginning of the production of these fibres, which has expanded enormously in a wide range of insulation applications since. The growth in the use of mineral fibres - also known as Man-Made Vitreous Fibres (MMVFs) - has meant that scientists have needed to describe the effects on public health. Independent institutes worldwide have, consequently, been carrying out extensive animal and epidemiological studies of mineral (glass, rock and slag) wool workers for more than seventy years. Rockwool Marine & Offshore is part of the Rockwool Group and one of Rockwools largest R&D projects ever resulted in the high-alumina low-silica wool generation. This is a quality wool with higher biosolubility as a result of its chemical composition (see box) and thus a wool with an increased safety margin in comparison with traditional mineral wool. Roxul1000 fibers are world wide exonerated from any classification. The product quality of this wool is, of course, consistently high, retaining all technical features. Green Passport All Rockwool Marine & Offshore stone wool insulation materials for the marine and offshore market, produced at any of the European Rockwool production plants, will NOT be classified as hazardous materials in relation to the mentioned IMO resolution guideline A.962(23). Therefore Rockwool insulation should not be mentioned in any Green passport listings.

Facts & figures

Legislation on Classification

Wool type Roxul1000 (high-alumina, low-silica wool) Traditional wool

Europe Exonerated from classification as a carcinogen Classified in category 3: Possibly Carcinogenic

WHO/IARC Non carcinogenic in experimental animals* Group 3: not classifiable as to their carcinogenicity to humans
* WHO press release 137

96

Leading supplier of marine insulation Rockwool Marine & Offshore is one of the leading suppliers of marine and offshore insulation for a large part of the world. Our expertise is based on years of experience in development, production, sale and marketing of products based on stone wool. Rockwool Marine & Offshore markets a wide range of specially developed products and constructions, which have been tested and approved according to the latest IMO regulations and by all leading classification societies, just as Rockwool Marine & Offshore is certified according to the latest MED directive.

Optimal insulation and maximum of safety All the constructions have been developed so they take the optimal insulation result and consequently the maximum safety into account, and at the same time ensure a quick and easy installation. Special attention is focused on fire safety requirements in connection with insulation for marine and offshore, for which purposes Rockwool products are very suitable due to the special properties of the stone wool.

Product development Our products and constructions are being constantly developed to keep abreast of the requirements of the market. The latest news is always available on our web site www.rockwool-marine.com where it is also possible to register for our marine news service, which ensures that you will always be updated on the latest marine news from Rockwool Marine & Offshore.

Member of the Rockwool International Group Rockwool Marine & Offshore, a member of the Rockwool International Group, has its headquarters in Hedehusene, west of Copenhagen (Denmark). The Rockwool Group has over 20 factories and representation in numerous countries all over the world. Visit www.rockwool.com

97

About Rockwool Marine & Offshore

About Rockwool Marine & Offshore

Notes

Notes

98

The Technical Guidelines are to be considered as guidance only. As material supplier, Rockwool A/S can only assist with technical guidance and service and we are not legally responsible for this guidance and service, including the specific use of the Technical Guidelines. Rockwool A/S reserves the right to make the necessary product changes at any time. Technical specifications are thus stated subject to change. Reprint is only allowed according to covenant with Rockwool A/S.
99

Notes

To learn more visit www.rockwool-marine.com

For further information please visit our website www.rockwool-marine.com or contact our local Rockwool companies.

BELGIUM Rockwool Technical Insulation Phone: +32 271 56820 Fax: +32 271 56848 DENMARK Rockwool A/S Phone: +45 46 56 16 16 Fax: +45 46 56 16 04 FINLAND Rockwool Finland Oy Phone: +358 9 8563 5880 Fax: +358 9 8563 5889 FRANCE Rockwool Technical Insulation Phone: +33 1 4077 82 11 Fax: +33 1 4077 80 40 GERMANY Rockwool Technical Insulation Phone: +49 2043 408-0 Fax: +49 2043-408 672

ITALY Rockwool Italia S.p.A. Phone: +39 02 34 613 1 Fax: +39 02 34 613 321 LATVIA Rockwool SIA Phone: +371 67 03 25 85 Fax: +371 67 03 25 86 LITHUANIA Rockwool UAB Phone: +370 52 12 60 24 Fax: +370 52 12 44 92 NETHERLANDS Rockwool Technical Insulation Phone: +31 475 35 3618 Fax: +31 475 35 3640 NORWAY A/S Rockwool Phone: +47 22 02 40 00 Fax: +47 22 15 91 78

POLAND Rockwool Polska Sp. z o. o Phone: +48 68 385 0131 Fax: +48 68 385 0122 RUSSIA ZAO Mineralnaya Vata Rockwool Russia Phone: +7 495 995 77 55 Fax: +7 495 995 77 55 SWEDEN Roxull AB Phone: +46 36 570 5200 Fax: +46 36 570 5283 UNITED KINGDOM Rockwool Limited Phone: +44 871 222 1780 Fax: +44 871 222 1781

UKRAINE LLC Rockwool Ukraine Phone: +380 44 586 49 73/76 Fax: +380 44 586 49 74 HONG KONG (FAR EAST REGION) Rockwool A/S Hong Kong office Phone: +852 2866 6180 Fax: +852 2866 9555 REST OF THE WORLD RMO Export Phone: +45 46 56 16 16 Fax: +45 46 56 16 04

Rockwool A/S Hovedgaden 501 2640 Hedehusene Denmark Tlf. +45 46 56 16 16 Fax +45 46 56 16 04

3B Reklame 0809

You might also like