Fire Alarm Systems.

Product Catalogue.

Table of Contents
1 2 General hints ..................................................................................................................................................... 4

Information about the structure of the catalogue .................................................................................................... 4


Modular control panels Integral IP MX................................................................................................................. 5

2.1 2.2 2.3 2.4 2.5 2.6 2.7


3

Integral IP MXF fire alarm control panel .......................................................................................................... 8 Integral IP MXE controller unit for multizone extinguishing systems ......................................................... 9 Built-in operating panel MAP for Integral IP MX panels............................................................................. 11 Integral IP MX modules ..................................................................................................................................... 12 Modules for system modernisation................................................................................................................... 23 Accessories & replacement parts....................................................................................................................... 25 Software ................................................................................................................................................................. 27 Fire alarm control panel Integral IP CXF........................................................................................................ 28 Integral IP CXF modules ................................................................................................................................... 30 Fire alarm control panel Integral IP CXA ....................................................................................................... 34 Fire alarm control panel Integral IP CXB........................................................................................................ 35 Controller unit for single zone extinguishing systems Integral IP CXE..................................................... 36 Built-in operating panel MAP for Integral IP CX panels.............................................................................. 37 Accessories & replacement parts....................................................................................................................... 38

Compact control panels Integral IP CX ............................................................................................................... 28

3.1 3.2 3.3 3.4 3.5 3.6 3.7


4 5

External indicator & operating panels ................................................................................................................ 41 Management system SecoLOG ......................................................................................................................... 46

5.1 SecoLOG software packs ................................................................................................................................... 47 5.2 SecoLOG components & accessories .............................................................................................................. 48
6 Integral X-LINE ................................................................................................................................................. 49

6.1 6.2 6.3 6.4 6.5


7

Automatic detectors & bases ............................................................................................................................. 49 Manual call points ................................................................................................................................................ 54 X-LINE modules ................................................................................................................................................. 58 Accessories ............................................................................................................................................................ 70 Testing devices ..................................................................................................................................................... 72 Linear smoke detector ......................................................................................................................................... 75 Flame detectors .................................................................................................................................................... 79 Hazardous areas ................................................................................................................................................... 80 Linear temperature detectors ............................................................................................................................. 88 Smoke aspirating system AirSCREEN ASD 535 ........................................................................................... 89 Radio-linked detectors ........................................................................................................................................ 97 Fire gas detectors ................................................................................................................................................. 99

Special detectors .............................................................................................................................................. 75

7.1 7.2 7.3 7.4 7.5 7.6 7.7


8

Accessories .................................................................................................................................................... 100

8.1 Fire brigade key safe & plan case .................................................................................................................... 100 8.2 Modems & converters....................................................................................................................................... 102 8.3 Transmission devices......................................................................................................................................... 105 8.4 Sirens & flashing lights...................................................................................................................................... 107 8.5 Holding magnets ................................................................................................................................................ 112 8.6 Power supplies.................................................................................................................................................... 114 8.7 Hold-open systems ............................................................................................................................................ 120 8.8 Cables................................................................................................................................................................... 124 8.9 Inscription panels & stickers............................................................................................................................125 8.10 Printed items & brochures ...............................................................................................................................126
Responsible for the content of this document: Michaela Schwantner Product Management Fire Alarm Systems Tel: +43-1-81157-304 m.schwantner@schrack-seconet.com

General hints Information about the structure of the catalogue

1 General hints
This product catalogue describes the most important components of the Integral IP fire alarm system, thereby representing a mere fraction of our very extensive range of products. All information which is not contained in this catalogue is available upon request at any time from one of our offices. All Schrack fire alarm systems are developed in Austria and constitute the technological state-of-the-art and the latest scientific findings, whilst observing the currently enforced standards (European standards, fire brigade specifications, and certification from European Testing and Certification Centres etc.). Schrack Seconet frequently cooperates with technical universities and international companies, as well as with testing and accreditation centres, fire prevention centres and fire brigade associations, so that our products can be constantly improved and adapted to meet new demands. Our employees are active in all important national and international bodies (such as CEN, DIN, ON, VB etc.). Schrack Seconets high quality is documented in a quality management system, which has been certified in accordance with ISO 9001 for all the companys divisions. The planning of fire alarm systems as well as the installation, commissioning and maintenance of products and the systems which they form required specialist expert knowledge, and therefore may only be undertaken by specially trained experts. The product-specific training of staff members must be carried out by Schrack Seconet or by people who have been specifically authorised to carry out this duty by Schrack Seconet. In addition to this, the currently applicable country-specific regulations and guidelines for the planning, construction of and use of the products must be observed and complied with without fail. Damage and consequential damage which have been caused due to interference or modifications made to our products or by improper handling of them are excluded from liability. The same is also true for inappropriate storage of items or other detrimental external factors. We would explicitly like to point out that the fire alarm system must be periodically serviced in accordance with the respective relevant standards (e.g. NORM F 3070, DIN 14675 etc.), in order to also ensure that the system's range of functions and protective scope is also maintained in the long term. The descriptions and technical information contained below corresponds to the current status stands at the time of printing. We reserve the right to make alterations, particularly where they are the result of technical improvements. The products illustrated in this document may differ in terms of their appearance as a result of the constant continued development from those products which are delivered. The design of this catalogue is subject to copyright. Printing or transferring of texts, illustrations and photos in all media (e.g. Print, CD ROM, the Internet etc.) from this catalogue, both as excerpts as well as in their entirety, is only permitted with our explicit written permission. We assume no liability for misprints and blatant errors. When ordering or making an enquiry, please quote part numbers.

Information about the structure of the catalogue


B3-OM8 Module for monitored outputs For connecting peripheral devices (flashing lights, sirens etc.); with eight 1.5 A controller outputs monitored for short circuits and wire breaks. Power supply: internally via the system BUS Current consumption: 9 mA Ambient temperature: 0 to +50C Output voltage: 22 V min. / 24 V typ. / 28 V max. Output current: 1,5 A max. Short circuit current: 1,77 A min. / 2,17 A typ. / 3,14 A max.
Description Type Art. No.

Name, Description & Technical Specifications

No.: EG072813

Illustration of the main article with article number

B3-OM8 Module for monitored outputs Connector plug for B3-OM8

B3-OM8 ST-OM8

EG072813 FG74095

Product variants, accessories & replacement parts with type name and article number

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX

2 Modular control panels Integral IP MX


The Integral IP MX system is a modular, decentrally constructed system, comprising of individual components, and which is programmed and configured according to the requirements of the individual system in question. The system can be deployed as a fire alarm control panel, as a multizone extinguishing system control panel or as a combined fire alarm control panel and extinguishing system control panel. A detailed description of the system is contained in the Integral IP MX System Description document.

Complete redundancy
One of the main features of the system is its complete, intelligent redundancy. This means that not only is the microprocessor structure duplicated, but all system structures, components and electronic elements in the control panel are present in duplicate. The occurrence of a fault in the active system causes the system to be automatically switched over to the second system running in parallel and for a system fault to be indicated. All functions, such as detection, triggering of alarms, plain text indication and controlling of fire alarm devices etc. remain unaffected by this occurrence. The data circuits to the external operating panels and the connections between the subcontrol units are also present in duplicate, in order to also guarantee in all instances that the system remains fully functional even in the event of wire breaks or faults.

Subcontrol unit
The fire alarm control panel comprises of 1 to 16 subcontrol units, which are spread around the building as required. The system is operated in a clear manner from a single location, with the system operating, despite its decentralized construction, exactly like a traditional centralized fire alarm control panel. The interconnection of several subcontrol units to a single fire alarm control panel is known as an Integral LAN.

Integral LAN and Mesh Network


In the Integral LAN mesh network, multiple connections are established between the individual control panels, in order to ensure, even in the event of connection faults that might occur, that every device still continues to have a connection to the network. The completely freely selectable topology of the cabling allows the mesh network to be adapted optimally to suit the physical configuration of the building. There are network modules with different interfaces (RS485, optic fibre, DSL) available for the Integral LAN, thereby making external modems and converters a thing of the past. The Integral IP control panels can be directly connected to the IT infrastructure of a building, with access via Intranet or Internet being possible without requiring any additional effort. Various parallel indicator tableaux or superordinated centralized indication devices may, as long as they are not dedicated to alarming the emergency services, use the existing communications paths of the PC networks.

SecoNET Network
Every Integral LAN is suitable for connection building management systems and field buses. If more than 16 subcontrol units are required, then Integral LANs are connected to the SecoNET Fire Alarm Network. In the SecoNET, all connected fire alarm control panels (Integral, Integral IP MX, Integral IP CX, Integral LAN, etc.) are configured separately from one another, and furthermore, in every SecoNET device, there is an interface set aside for SecoNET. A standardised interface protocol is used for connecting control systems produced by different manufacturers with one another, which allows the connection to occur with the device functioning fully.

Length of wires
The distance between two Integral IP MX or Integral IP CX control panels may be up to 1200 metres. Neither repeaters nor other additional devices such as modems are required, and only the types of cable used and the environmental factors must be observed. In special cases where the distance has to be greater than 1,200 metres then additional external transmission equipment can be used.
B-HB-008EN Product catalogue fire alarm systems 2011 V 2.0

Modular control panels Integral IP MX

External Operating Panels & Devices Bus


External operating panels and devices and connected to the control panel via the MMI BUS. Up to 8 devices can be connected to this serial data bus - without using any additional devices e.g. repeaters etc. and can be located up to 1200 metres away from the control panel. Data communication uses redundant digital communication circuits, with the devices being able to be used in any possible combination regardless of the devices locations. For safety reasons the data circuit as well as the power supply circuit are both fully redundant. The Integral MAP operating panel also has an EPI-BUS interface. Up to 3 non-redundant indication and operating devices can be connected and can be located up to 1 metre away from the control panel. A maximum of 15 devices can be connected per MMI BUS, of which there may be a maximum of 8 MMI bus devices.

Overvoltage protection
The Integral IP system is fitted with a comprehensive integrated overvoltage protection concept, which protects all peripheral inputs, including the power supply in accordance with EN50130-4 (EMC) and EN50082-2 (interference in industrial use). The EMC protection concept involves the deployment of measures such as a zonal concept, tranzorb diodes, filters and broadband decoupling of the power supply to protect the electronic devices. As a result, no additional measures, e.g. an overvoltage arrester etc. are required for operation within building where heavy- and medium-duty protection is installed (protection against lightning strikes, supply side overvoltage arrester).

Approvals
VdS Device and System Approval: G298029, S298029, G207087 EC Conformity Certificate No. 0786-CPD-20240 (VdS) Austrian Testing Centre for Fire Prevention Technology: Nos. FT 14/170/08/96 and FT 14/171/08/96 VB Cert Austria: Nos. 002/BM-PSys/008, 002/BM-PSys/009, 002/BM-PSys/010 German Institute for Construction: Z-6.5-1871 Test for Electromagnetic Compatibility: TV Austria No. M/EMV-96/381 Country-specific approvals in Austria, Germany, Denmark, Italy, Croatia, The Netherlands, Poland, Romania, Russia, Sweden, Switzerland, Slovakia, Czech Republic, Turkey, Hungary, Ukraine and many more.

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX

Important Features
Microprocessor-controlled and monitored system topology Fully redundant system composition to ensure that the system remains fully operational, even in the event of a fault or in the event that one half of the processor unit fails Constant automatic test routines for all system components and programs Six line display for displaying the system status in plain text (alarms, faults etc.) Acoustic and optical alarm notification for alarms and faults Alarm buffering Possibility to manually test the control panel and its functions Plain text indication of individual detector and indicator zones Up to 8 external operating panels per control panel, maximum distance 1200 m Operating panel language (labelling and display indication) can be selected, can be toggled between up to 4 languages while in operation External device bus for up to 15 indication and operation devices Serial data log printer with UPS power supply, with an event memory and message filter Suitable for connection to the fire brigades public alarm notification system 11 free connection slots for modules (detector zones, inputs and outputs, relays etc.) System configuration saved using flexible flash memory technology Emergency power supply for a supply interruption period of 72 hours

Options
Control panel networking using a TCP/IP-based local mesh network: up to 16 control panels can be networked to form a logical unit without requiring a superordinated management system Mesh network with up to 4 connections per subcontrol unit: in the event of a device failing or a connection fault occurring, it is possible for data communications to continue by diverting (routing) the data Data transmission at 625/2500 Kbit Flexible topology: stub connection to loop is possible Ethernet protocol: Using the customer's IT infrastructure Access to the control unit over the Intranet and Internet Standardised IT components are used Can be connected to hierarchically superior computer systems or fire alarm control systems via serial data interfaces with a full range of functions (message and command modes) Connection for fire brigade control panels pursuant to NORM F3031, DIN 14661, SN 054002 and DIN 14662 Daytime/Night time operation mode switching can be individually programmed for each detector zone and every week day Intervention mode Detectors can be freely assigned and linked to controller criteria - software controlled Software-controlled two zone dependency or two detector dependency for alarm notification and controlling of devices Recognition and evaluation of the status of detectors (contamination) Disablement of individual detectors Can be networked with all Schrack fire alarm control panels

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

Modular control panels Integral IP MX Integral IP MXF fire alarm control panel

2.1

Integral IP MXF fire alarm control panel


Integral IP MXF cabinet variants Integral IP MX cabinet in basic configuration, consisting of: Sheet steel cabinet B5-MCU main processor unit B5-PSU power supply unit Module rack with BUS circuit boards Power clips and battery cable Space for fitting rechargeable cells (max. size 2 x 12 V/45 Ah) Input voltage / frequency: Input power: Output voltage: Output current: Quiescent current:
B5-SCU-C No.: FG052101

B5-SCU No.: FG052100

B5-SCU-CP No.:FG052102

Batteries that can be used: Emergency power supply with batteries: Protection class (DIN 40050): Ambient temperature: Rel. air humidity: Air pressure: Case: Dimensions: Weight of basic version: Weight per battery:
Description

230 VAC +15%/-20% 47-63 Hz max. 280 W 26,3 VDC (+50C) to 28,3 VDC (0C) 7,5 A 74 mA (wihtout operating panel, without printer) 2 pcs. 12 V / 38...40 Ah in series 72 h normal operation + 0.5 h alarm IP 30 0 to +50C 5 to 95%, without condensation 80 kPa, up to 2,000 m above sea level sheet steel, red RAL 3000 600 x 445 x 225 mm (HxWxD) 15 kg (without batteries) 15 kg
Type Art. No.

B5-SCU-CP-EAT32 No.:FG052107

Integral IP MXF basic version Cabinet with full door Integral IP MXF basic version Cabinet with cutaway for built-in operating panel Integral IP MXF basic version Cabinet with cutaway for built-in operating panel and log printer Integral IP MXF basic version, cabinet with cutaway, log printer and LED indicator panel for 32 detector zones

B5-SCU B5-SCU-C B5-SCU-CP

FG052100 FG052101 FG052102

B5-SCU-CP-EAT32

FG052107

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX Integral IP MXE controller unit for multizone extinguishing systems

2.2

Integral IP MXE controller unit for multizone extinguishing systems

Due to the special redundancy concept and the particular degree of safety that it provides for the widest range of usages, the Integral IP MX system can able be used as an Integral IP MXE extinguishing system control panel (electronic control and delay unit) or as a combined Integral IP MXF/MXE fire alarm control panel/extinguishing system control panel. For this purpose, different types of cabinet are available, which also contain an additional LED parallel indicator tableau. As a result of this enhancement in accordance with standards and directives EN 12094-1 and VdS 2496, the Integral IP MXE is now suitable and approved for use for controlling and monitoring the following types of fire extinguishing systems: CO2 high and low pressure extinguishing systems where life is or is not endangered Inert gas and argon extinguishing systems where life is or is not endangered Water spray and mist water deluge systems Pre-action sprinkler systems Sprinkler Systems Chemical extinguishing systems

B5-SCU-CP4L No.: FG052103

Integral IP MXE Cabinet B5-SCU-CP4L Integral IP MX cabinet in basic configuration, consisting of: Sheet steel cabinet B5-MCU main processor unit B5-PSU power supply unit Module rack with BUS circuit boards Power clips and battery cable Space for fitting rechargeable cells (max. size 2 x 12 V/45 Ah) Cutaway for built-in operating panel built-in log printer Indicator panel for 4 extinguishing zones Input voltage / frequency: 230 VAC +15%/-20% 47-63 Hz Input power: max. 280 W Output voltage: 26,3 VDC (+50C) to 28,3 VDC (0C) Output current: 7,5 A Quiescent current: 74 mA (without operating panel, without printer) Batteries that can be used: 2 pcs. 12 V / 38...40 Ah in series Emergency power supply with batteries: 72 h normal operation + 0.5 h alarm Protection class (DIN 40050): IP 30 Ambient temperature: 0 to +50C Rel. air humidity: 5 to 95%, without condensation Air pressure: 80 kPa, to 2000 m above sea level Case: sheet steel, red RAL 3000 Dimensions: 600 x 445 x 225 mm (HxWxD) Weight of basic version: 15 kg (without batteries) Weight per battery: 15 kg
Description Type Art. No.

Integral basic cabinet with cutaway for operating panel, log printer and LED indicator panel for 4 extinguishing zones

B5-SCU-CP4L

FG052103

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

Modular control panels Integral IP MX Integral IP MXE controller unit for multizone extinguishing systems

B5-SCU-CP4L No.: FG052105

Integral IP MXE Cabinet B5-SCU-CP4L-IP55 Integral IP MX cabinet in basic configuration, consisting of: IP 55 case with doors B5-MCU main processor unit B5-PSU power supply unit Module rack with BUS circuit boards Power clips and battery cable Space for fitting rechargeable cells (max. size 2 x 12 V/45 Ah) Cutaway for built-in operating panel built-in log printer LED indicator panel for 4 extinguishing zones Input voltage / frequency: 230 VAC +15%/-20% 47-63 Hz Input power: max. 280 W Output voltage: 26,3 VDC (+50C) to 28,3 VDC (0C) Output current: 7,5 A Quiescent current: 74 mA (without operating panel, without printer) Batteries that can be used: 2 pcs. 12 V / 38...40 Ah in series Emergency power supply with batteries: 72 h normal operation + 0.5 h alarm Protection class: IP 55 Ambient temperature: 0 to +50C Rel. air humidity: 5 to 95%, without condensation Case: 1,5 mm sheet steel Tipping frame: sheet steel, red RAL 3000 Front door: Aluminium strand pressed profile, 3 mm acrylic glass Dimensions: 600 x 600 x 370 mm (HxWxD) Weight: ca. 35 kg (without batteries)
Description Type Art. No.

Integral IP MX basic version in IP 55 case

B5-SCU-CP4L-IP55

FG052105

10

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX Built-in operating panel MAP for Integral IP MX panels

2.3

Built-in operating panel MAP for Integral IP MX panels


B5-CII-RU Integral MAP built-in operating panel Operating panel for installation in all Integral IP MX cabinets with door cutaways, available in many different language versions (key labelling and display indication). Listed below are the German and English language versions, and other languages are available on request. Display with 6 lines, 40 characters per line Conforms to all options of EN 54-2:2006 can be deployed as a main operating panel in a SecoNET Up to 4 languages can be switched between in normal operation Connection for EPI-Bus (various other indication and operating devices) 2 freely programmable and labelable buttons 2 freely programmable and labelable 3 colour LEDs 5 status lists (alarms, faults, disablements, etc.) Status indication on the first line of the display Zone operation (e.g. disable zone 1-10) Group operation (e.g. simultaneously disable all detector zones) individual user management with password and user level every change of user is logged in the event log memory
Description Type Art. No.

B5-CII-RU No.: FG91606-9

B5 MAP internal operating panel German B5 MAP internal operating panel English B5 MAP internal operating panel Russian

B5-CII-DE B5-CII-EN B5-CII-RU

FG91600-9 FG91601-9 FG91606-9

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

11

Modular control panels Integral IP MX Integral IP MX modules

2.4

Integral IP MX modules

All modules and components of the Integral IP MX system are constructed redundantly for system availability reasons, which also guarantees in the event of a fault that indication information, signal processing and the controlling of all connected fire alarm devices is ensured. The module rack of every Integral IP MX always contains the B5-MCU main processor unit connected in slot 1 whilst the B5-PSU power supply unit is always connected in slot 10. If one of the networking modules of types B5 LAN, B5-NET2-485 or B5-NET4-485 is used, then this must be connected to connection slot 2. Connection slots 11 to 13 are intended solely for connecting relay modules of types B3-REL10/16/16E, with connection slots 3 to 9 suitable for the fitting of all other types of module as required. When using connection slots 11 to 13, then one of the modules of the type B5-BAF, B5-MRI16 or B3-LPI must be connected to connection slot 9. The connector plugs for the B3-REL10, B3-REL16(E) and B5 MRI16 relay modules must be ordered separated, with the connector plugs for all other modules being supplied. B5-MCU main processor unit The B5-MCU communicates with all other modules and with the operating panel, manages configuration data and the system clock, and undertakes all processes that are necessary for the logical behaviour of the system. System states are indicated using LEDs, with the loading of software and configuration files, as well as system diagnostics is carried out using a PC via a USB 1.1 device (service) interface located on the front panel. On the front panel there is also a USB 1.1 host interface for connecting memory sticks or a dongle stick and an interface (slot) for a SD card for saving customer texts and configuration parameters. The B5-MCU is shipped as standard with all Integral IP MX control panels. Power supply: via system bus from B5-PSU Quiescent current: 38 mA typ. (battery current) Operating voltage: Battery voltage VL+22 V .. 30 V Logic voltage VCC+5,0 V 5% Logic voltage VCC+3,3V 5% Service interface: USB 1.1 Device, Connector type B USB 1.1 Host, Connector type A Ambient temperature: 0 to +50C Rel. air humidity: 5 to 95 %, without condensation
Description Type Art. No.

B5-MCU No.: EG072939

SD-CARD No.: FG020325

B5-MCU main processor unit (replacement) SD-CARD 2GB

B5-MCU SD-CARD

EG072939 FG020325

B5-PSU No.: EG072918

B5-PSU power supply unit The B5-PSU 7A power supply supplies the supply voltages required internally by every Integral IP MX control panel - 3.3V, 5 V and 27 V. It feed in standby and parallel operation two 38...40Ah rechargeable cells for supplying emergency power and also makes five separately fused 27 V outputs for external devices via connectable screw-type terminals. The rechargeable cell monitoring circuitry present on the module is controlled and evaluated by the B5-MCU main processor unit. The B5-PSU power supply unit is shipped as standard with all Integral IP MX control panels. Mains supply voltage / frequency:230 VAC +15%/-20% 47-63 Hz Outputs for external devices: 5 x 27 V, 2,5 A FF Current uptake: max. 280 VA
Description Type Art. No.

B5-PSU power supply unit (replacement) Replacement fuse Connection plug for external devices

B5-PSU ZUB SICH 2.5FF ST-PSU EV

EG072918 IS625228 FG74090

12

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX Integral IP MX modules

B5-DXI2 No.: EG072912

B5-DXI2 module for X-LINE For connecting two loop circuits (loops) to the relevant detectors and Integral X-LINE technology modules. Alternatively one loop circuit and two stub lines or four stub lines can be connected. Controlling digital loop communications and backing up of data Detectors can be linked via modules and subcontrol units Alarm criteria and control criteria can be linked Disablement of individual detectors Evaluation of detector states (contamination recognition) Monitoring of all detectors and modules that are attached Localisation of wire breaks and short circuits on the loop Power supply: Current consumption: Ambient temperature: Elements: Logical elements: Short circuit isolator: Individual detector identification: Cable: Loop length: Max. line resistance: internally via the system BUS ca. 35 mA typ. -5 to +50C 2 Loop circuits, each with max. 250 devices max. 750 per B5-DXI2 integrated into detectors and controller modules integrated as standard 1 x 2 x 0,8 mm shielded (Standard) max. 3500 m 255

The B5-DXI2 module is supported from software V 6.2. In addition, this module requires the B5-platform (at least B3-MCU32E, B5-PSU, B5-BUS). From the software V 7.2 the X-LINE loop technology is fully supported.
Description Type Art. No.

B5-DXI2 module for X-LINE 16 pole connector plug (replacement)

B5-DXI2 ST-B3 16

EG072912 YY970138

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

13

Modular control panels Integral IP MX Integral IP MX modules

B5-BAF Control Module For connecting fire brigade control panels, transmission equipment (main detectors), alarm systems (sirens) and for controlling the relay bus. The module also controls an interface for the MMI-BUS (bus for external devices) to which external operating panels and the Austrian fire brigade operating panel among other devices are connected. Power supply: Current consumption: Ambient temperature: Relay bus interface: Interface FBP (DIN14661): Transmission type: Range: OM1 interface: OM2 interface: MMI-BUS interface:
Description

B5-BAF No.: EG072908

internally via the system BUS typically 35 mA with output controller turned on without peripheral current 0 to +50C for B3-REL10 or B3-REL16(E) 12 pin connectable screw clip plug parallel, bidirectional max. 5 m Transmission equipment or monitored output, 26 V/1.5 A monitored output, 26 V/1.5 A galvanically isolated RS 485, max. 1200 m
Type Art. No.

B5-BAF Control Module IDC connector MMI-BUS (replacement) Solder plug terminal connector MMI-BUS (replacement) Connector plug for fire brigade panel (replacement) Connector plugs for monitored inputs/outputs (replacement)

B5-BAF ST-BAF-MMI-S ST-BAF-MMI-L ST-BAF-FBD ST-BAF-OM

EG072908 FG74085 FG74086 YK130459 FG74088

B3-OM8 Module for monitored outputs For connecting peripheral devices (flashing lights, sirens etc.); with eight 1.5 A controller outputs monitored for short circuits and wire breaks. The maximum total output current for outputs 1 to 4, and for outputs 5 to 8 is 3A, with the total output current of the module being dependent on the capacity of the power supply unit and how the system is configured. Power supply: Current consumption: Ambient temperature: Output voltage: Output current: Short circuit current: Load range: Range 1 (354-1000 Range 2 (85-354 Range 3 (16-85
Description

B3-OM8 No.: EG072813

internally via the system BUS 9 mA 0 to +50C 22 V min. / 24 V typ. / 28 V max. 1,5 A max. 1,77 A min. / 2,17 A Type. / 3,14 A max. Controlling current Line resistance 1 mA max. 50 3 mA max. 20 15 mA max. 5
Type Art. No.

B3-OM8 Module for monitored outputs Connector plug for B3-OM8 (replacement)

B3-OM8 ST-OM8

EG072813 FG74095

14

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX Integral IP MX modules

B3-IM8 Module for monitored inputs For connecting up to eight stub lines, which can either be configured as detector zones (Hekatron 130 detector series or Hochiki Ex-i detectors) or as monitored inputs (e.g. VdS extinguishing interface, primary inputs, valve monitoring etc.). The operating mode of the individual stub lines can be set independently of one another using programming and jumper cap settings on the module. Power supply: Current consumption: Ambient temperature: Connection:
Description

B3-IM8 No.: EG072855

internally via the system BUS 9 mA (battery current without peripherals) 0 to +50C 8 detector zones or 8 monitored inputs
Type Art. No.

B3-IM8 Module for monitored inputs Connector plug for B3-IM8 (replacement) Jumper 953R f. B3-IM8 (8 pcs.) Jumper 110R f. B3-IM8 (8 pcs.)

B3-IM8 ST-MTI8 JUMP-IM8-953R JUMP-IM8-110R

EG072855 FG74087 FG74113 FG74114

B3-USI4 No.: EG072815

B3-USI4 Universal Interface Module For connecting Integral subcontrol units to control systems, for controlling external printers, pagers, ComBOX units, telephone servers etc. and for interconnecting several Integral subcontrol units (in loop configuration serially via 2 redundant cables each). A total of 4 redundant, serial, asynchronous interfaces can be used as redundant RS 485 connections in half-duplex mode (for loops) or as non-redundant RS 422 connections in full-duplex mode (for lines). Furthermore, two of the four interfaces can also be operated as RS 232 in full-duplex operation (line) each with 2 control circuits. The selection of each interfaces operating mode is done by programming and hardware configuration, with it also being possible to select between a connection being made to a subcontrol unit loop and/or a redundant/non-redundant connection to control systems etc. A maximum of five B3-USI4 units can be fitted per subcontrol unit. Power supply: Current consumption: Ambient temperature: Range: Transmission type: Baud rate: Interfaces: internally via the system BUS 20 mA 0 to +50C RS 485 = 1200 m RS 232 = 15 m serial, asynchronous 57,6 kBaud 2x2 redundant half-duplex RS 485, also full-duplex operation, galvanically isolated 2 redundant RS232 interfaces, galvanically isolated
Type Art. No.

Description

B3-USI4 Universal Interface Module 9 pole solder lug terminal connector for B3-USI4 (replacement) 15 pole solder lug terminal connector for B3-USI4 (replacement)

B3-USI4 ST-LPI/USI4/HFI ST-USI4

EG072815 FG74097 FG74098

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

15

Modular control panels Integral IP MX Integral IP MX modules

B3-LPI Module for subcontrol unit coupling The module contains two RS 485 interfaces, a connection slot for a PCMCIA modem and an interface for controlling the Integral relay bus. For interconnection of Integral subcontrol units and for remote access to the control panel. The PCMCIA modem is not supplied and must be ordered separately as required. Power supply: Current consumption: Ambient temperature: Range: Transmission rate: Interfaces:
PCMCIA No.: FG020317

B3-LPI No.: EG072810

internally via the system BUS 20 mA 0 to +50C RS 485 = 1200 m RS 485 = 76,8 kBit/s Modem = 33,6 kBit/s 2 redundant half-duplex RS 485, galvanically isolated modem interface (for use with dedicated line and dial-up line connections) relay driver interface
Type Art. No.

Description

B3-LPI Module for subcontrol unit coupling PCM CIA modem 9 pole solder lug terminal connector for B3-LPI (replacement)

B3-LPI PCMCIA ST-LPI/USI4/HFI

EG072810 FG020317 FG74097

B5-LAN Network module For non-redundant networking of Integral IP MX control panels and for non-redundant connection of PC applications. Two 8 pole RJ-45 sockets can be found on the front side of the module. The module can only be fitted in connection slot 2 in the module rack. Power supply: Current consumption: Ambient temperature: Transmission type: Physical characteristics: Direction: LAN- interface: Speed: Distance:
Description

B5-LAN No.: EG072903

internally via the system BUS 0 mA 0 to +50C TCP/IP 2 x RJ-45 sockets - 8 pole bidirectional, full-duplex Ethernet 100 Base TX max. 100 Mbit/s max. 100 m
Type Art. No.

B5-LAN Network module RJ45- connector Cat5e RJ45 crimping tool

B5-LAN RJ45-IP CRIMP-IP

EG072903 MM010008 MM010001

16

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX Integral IP MX modules

B5-NET2-485 No.: EG072910

B5-NET2-485 Network module For redundant networking of Integral IP MX control panels or for redundant connection of PC applications. The module consists of two network connectors (RS 485 interface) and two 100 Base TX interfaces. On the front side there are 6 RJ 45 sockets for connecting from the subcontrol unit network and to the Ethernet. The module can only be fitted in connection slot 2 in the module rack. Power supply: internally via the system BUS Current consumption: 120 mA Ambient temperature: 0 to +50C Transmission type: TCP/IP Physical characteristics: 6 x RJ-45 sockets - 8 pole Direction: bidirectional, full-duplex LAN- interfaces: 2 x Ethernet 100 Base TX Speed: max. 100 Mbit/s Distance: max. 100 m RS485-interfaces: 2 x RS485 with redundant cabling, of which 1 galvanically isolated Speed: max. 2,5 Mbit/s Distance: max. 1200 m Cable: UTP Cat5
Description Type Art. No.

B5-NET2-485 Network Module RJ45-connector Cat5e RJ45-crimping tool 9-Sub-D RJ45 coupling 15-Sub-D RJ45 coupling

B5-NET2-485 RJ45-IP CRIMP-IP KUP 9RJ45 KUP 15RJ45

EG072910 MM010008 MM010001 20-1400000-01 20-1400001-01

B5-NET4-485 No.: EG072915

B5-NET4-485 Network module For redundant networking of Integral IP MX control panels or for redundant connection of PC applications. The module consists of four network connectors (RS 485 interface) and two 100 Base TX interfaces. On the front side there are 10 RJ45 sockets for connecting from the subcontrol unit network and to the Ethernet. The module can only be fitted in connection slot 2 in the module rack. Power supply: internally via the system BUS Current consumption: 127 mA Ambient temperature: 0 to +50C Transmission type: TCP/IP Physical characteristics: 10 x RJ-45 sockets - 8 pole Direction: bidirectional, full-duplex LAN-interfaces: 2 x Ethernet 100 Base TX Speed: max. 100 Mbit/s Distance: max. 100 m RS485-interfaces: 4 x RS485 with redundant cabling, of which 2 galvanically isolated Speed: max. 2,5 Mbit/s Distance: max. 1200 m Cable: UTP Cat5
Description Type Art. No.

B5-NET4-485 Network Module RJ45-connector Cat5e RJ45-crimping tool 9-Sub-D RJ45 coupling 15-Sub-D RJ45 coupling
B-HB-008EN Product catalogue fire alarm systems 2011 V 2.0

B5-NET4-485 RJ45-IP CRIMP-IP KUP 9RJ45 KUP 15RJ45

EG072915 MM010008 MM010001 20-1400000-01 20-1400001-01

17

Modular control panels Integral IP MX Integral IP MX modules

B5-NET2-FXM Network module For redundant networking of Integral IP MX control panels or for redundant connection of PC applications. The module consists of two network connectors (RS 485 interface), two optical network connections that are realized on the basis of the standard FXM, and two 100 Base TX interfaces. On the front side there are 6 RJ45 and 2 x MTRJ sockets for connecting from the subcontrol unit network and to the Ethernet. The module can only be fitted in connection slot 2 in the module rack. From the software V 7.2 the B5-NET2-FXM module is fully supported.
B5-NET2-FXM No.: 20-1000001-01-01

Power supply: Current consumption: Ambient temperature: Transmission type: Physical characteristics: Direction: LAN-interfaces: Speed: Distance: RS485-interfaces: Speed: Distance: Cable: Ethernet FXM: Transceiver: Speed: Distance: Cable:

MTRJ

KUP 9RJ45 / KUP 15RJ45

internally via the system BUS 205 mA -5 to +50C TCP/IP 6 x RJ-45 sockets - 8 pole 2 x MTRJ (FXM) bidirectional, full-duplex 2 x Ethernet 100 Base TX max. 100 Mbit/s max. 100 m 4 x RS485 with redundant cabling, of which 2 galvanically isolated max. 2,5 Mbit/s max. 1200 m UTP Cat5 Avago AFBR5903Z, Multimode Laser max. 100 Mbit/s max. 2 000 m Multimode 62,5/125 m (FXM) Multimode 50/125 m (FXM)
Type Art. No.

Description

B5-NET2-FXM Network Module RJ45-connector Cat5e RJ45-crimping tool 9-Sub-D RJ45 coupling 15-Sub-D RJ45 coupling

B5-NET2-FXM RJ45-IP CRIMP-IP KUP 9RJ45 KUP 15RJ45

20-1000001-01-01 MM010008 MM010001 20-1400000-01 20-1400001-01

18

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX Integral IP MX modules

B5-NET2-FXS Network module For redundant networking of Integral IP MX control panels or for redundant connection of PC applications. The module consists of two network connectors (RS 485 interface), two optical network connections that are realized on the basis of the standard FXS, and two 100 Base TX interfaces. On the front side there are 6 RJ45 and 2 x LC2x5 sockets for connecting from the subcontrol unit network and to the Ethernet. The module can only be fitted in connection slot 2 in the module rack. From the software V 7.2 the B5-NET2- FXS module is fully supported.
B5-NET2-FXS No.: 20-1000000-01-01

Power supply: Current consumption: Ambient temperature: Transmission type: Physical characteristics: Direction: LAN-interfaces: Speed: Distance: RS485-interfaces:

LC 2x5 (Duplex)

KUP 9RJ45 / KUP 15RJ45

Speed: Distance: Cable: Ethernet FXS: Transceiver: Speed: Distance: Cable:


Description

internally via the system BUS 180 mA -5 to +50C TCP/IP 6 x RJ-45 sockets - 8 pole 2 x LC2x5 (FXS) bidirectional, full-duplex 2 x Ethernet 100 Base TX max. 100 Mbit/s max. 100 m 4 x RS485 with redundant cabling, of which 2 galvanically isolated max. 2,5 Mbit/s max. 1200 m UTP Cat5 Avago AFCT5971FZ, Singlemode Laser max. 100 Mbit/s max. 10 000 m Singlemode 9/125 m (FXS)
Type Art. No.

B5-NET2-FXS Network Module RJ45-connector Cat5e RJ45-crimping tool 9-Sub-D RJ45 coupling 15-Sub-D RJ45 coupling

B5-NET2-FXS RJ45-IP CRIMP-IP KUP 9RJ45 KUP 15RJ45

20-1000000-01-01 MM010008 MM010001 20-1400000-01 20-1400001-01

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

19

Modular control panels Integral IP MX Integral IP MX modules

B3-HFI Module for Fibre Optic Cable Dual interface converter from V.24 (RS 232) interface level to optic fibre for connecting Integral subcontrol units in areas where data transmission via optical fibre is necessary due to electromagnetic interference or distances involved being too great. One or two data converters can be fitted in the module, which are also supplied with current by it (buffered). For data transmission, the module B3USI4 is also required, with both the connection cables required for this being shipped with the B3-HFI module.
B3-HFI No.: EG072829

Power supply: Current consumption: Ambient temperature: Connection: Electrical: Physical characteristics:

internally via the system BUS 20 mA including 2 converters: typically 186 mA 0 to +50C Line/Loop to B3-USI4 RS 232, asynchronous, 57.6 KBit/s/s bidirectional, half-duplex each using a 9 pin Sub D connector plug 2 connection slots for fibre optic cable converter

OZDV 2471G data converter for optical fibre Dual interface converter from V.24 (RS 232) interface level to optical fibre, for fitting in module B3-HFI.
OZDV 2471G No.: FG020211

Bit rate: Electrical: Optical: Wavelength: Range: Transmission type: Direction: Physical characteristics:
Description

up to 115 Kbit/sec RS 232 Optical fibre G 50/125 or G 62.5/125 850 nm Optical fibre G 50/125 to 6700 m Optical fibre G 62,5/125 to 6600 m serial, asynchronous bidirectional, full-duplex 25 pin Sub D for RS 232; BFOC 2.5 (STR) for optical fibre
Type Art. No.

B3-HFI Module for Fibre Optic Cable 9 pin solder lug terminal connector for B3-HFI Data converter for optical fibre cabling

B3-HFI ST-LPI/USI4/HFI OZDV 2471G

EG072829 FG74097 FG020211

20

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX Integral IP MX modules

B3-REL10 Relay module The module contains 10 bistable, freely programmable 230 V/3 A relay contacts. Whether a contact is a make contact or a break contact is ascertained by configuration using software. By programming a fail-safe position the status of every individual relay can be defined in the event of a supply voltage failure or the fire alarm control panel being switched off. A module of type B5-BAF, B3-LPI or B5-MRI16 must be fitted to connection slot 9 of the Integral module rack for controlling the relay. Module B3-REL10 can only be fitted to connection slots 11 to 13 of the module rack.
B3-REL10 No.: EG072804

Power supply: Ambient temperature: Relay construction: Contact resistance: Maximum switching surge: Max. switching current: Caution:
Description

internally via the system/relay BUS 0 to +50C bistable 30 m 230 VAC / 125 VDC 3A both poles routed to terminals

The connection plugs for the relay outputs are not shipped with the module and must be ordered separately!
Type Art. No.

B3-REL10 Relay module 2 pcs. connector plug (standard) 2 pcs. connector plug, can be connected front on

B3-REL10 ST-SET REL10 W ST-SET REL10

EG072804 FG74103 FG74104

B3-REL16 No.: EG072807

B3-REL16 Relay module The module contains 16 bistable, freely programmable 24 V/3 A relay contacts and is used for controlling sirens, holding magnets, relays etc. Whether the contact is a make or break contact is determined by software-based programming. By programming a fail-safe position the status of every individual relay can be defined in the event of a supply voltage failure or the fire alarm control panel being switched off. A module of type B5-BAF, B3-LPI or B5MRI16 must be fitted to connection slot 9 of the Integral module rack for controlling the relays. Module B3-REL16 can only be fitted to connection slots 11 to 13 of the module rack. Power supply: Ambient temperature: Relay construction: Contact resistance: Maximum switching surge: Max. switching current: Caution:
Description

internally via the system/relay BUS 0 to +50C bistable 30 m 30 VAC/ 30 VDC 3A both poles routed to terminals

The connection plugs for the relay outputs are not shipped with the module and must be ordered separately!
Type Art. No.

B3-REL16 Relay module 2 pcs. connector plug (standard) 2 pcs. connector plug, can be connected front on

B3-REL16 ST-SET REL16 W ST-SET REL16

EG072807 FG74105 FG74106

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

21

Modular control panels Integral IP MX Integral IP MX modules

B3-REL16E Relay module Identical to module B3-REL16 in terms of technical specifications and function, but, however, also contains additional fused relay contacts (the fuses are not monitored) and resistors (3.3k monitoring resistance and 680 working resistance) for use as a VdS extinguishing interface. Using jumpers it is possible to choose between normal relay contacts and VdS interfaces. Kontaktschutz: Kleinstsicherung 3,15 A mit trger Auslse-Charakteristik
B3-REL16E No.: EG072822

Caution:
Description

The connection plugs for the relay outputs are not shipped with the module and must be ordered separately!
Type Art. No.

B3-REL16E Relay module 2 pcs. connector plug (standard) 2 pcs. connector plug, can be connected front on

B3-REL16E ST-SET REL16 W ST-SET REL16

EG072822 FG74105 FG74106

B5-MRI16 No.: EG072956

B5-MRI16 Relay module The module contains 16 bistable, freely programmable 24 V/3 A relay contacts. Whether a contact is a make contact or a break contact is ascertained by configuration using software. By programming a fail-safe position the status of every individual relay can be defined in the event of a supply voltage failure or the fire alarm control panel being switched off. The B5-MRI16 can be fitted in any of connection slots 2-9 of the Integral module rack and also contains an interface for controlling the relay bus. By fitting the module to connection slot 9, relay modules of type B3-REL10, B3-REL16 and B3REL16E can also be controlled. Power supply: Current consumption: Ambient temperature: Relay construction: Contact resistance: Maximum switching surge: Max. switching current: Caution:
Description

internally via the system BUS 6 mA typ. (battery current) 0 to +50C bistable 30 m 30 VAC / 30 VDC 3A both poles routed to terminals

The connection plugs for the relay outputs are not shipped with the module and must be ordered separately !
Type Art. No.

B5-MRI16 relay module 2 pcs. connector plug (standard) 2 pcs. connector plug, can be connected front on

B5-MRI16 ST-SET REL16 W ST-SET REL16

EG072956 FG74105 FG74106

22

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX Modules for system modernisation

2.5

Modules for system modernisation


B3-MTI8 Module for Monologue Technology For connection of up to eight stub lines, which can either be configured as detector zones using Monologue Technology or as monitored inputs. For reasons relating to approvals, this module may only be used for renovation purposes. Power supply: internally via the system BUS Current consumption: 9 mA Ambient temperature: 0 to +50C Detector zones: 8 (max. 62 detectors per zone) Individual detector identification: integrated as standard Cable diameter: 0,6 or 0,8 mm Range: max. 1000 m
Description Type Art. No.

B3-MTI8 No.: EG072809

B3-MTI8 Module for monologue technology Connector plug for B3-MTI8

B3-MTI8 ST-MTI8

EG072809 FG74087

B3-DTI2 No.: EG072853

B3-DTI2 Module for dialogue technology For connection of two loop circuits (loops) or 4 stub lines to the relevant BMZ Maxima dialogue technology detectors and modules. The module only functions in conjunction with B3-MCU32E2 or B5-MCU main processor units, and may only be deployed for renovation purposes according to approvals. Power supply: internally via the system BUS Current consumption: 52 mA Ambient temperature: 0 to +50C Devices/Elements: 2 Loop circuits, each with max. 128 devices Individual detector identification: integrated as standard Cable: 1 x 2 x 0,8 mm shielded (standard) Loop length: max. 1100 m
Description Type Art. No.

B3-DTI2 Module for dialogue technology 16 pole connector plug

B3-DTI2 ST-B3 16

EG072853 YY970138

B3-DCI6 No.: EG072811

B3-DCI6 Module for DC Technology For connecting up to 6 inputs, which can be set either as detector zones using DC technology, as monitored inputs or as extinguisher inputs (e.g. VdS extinguishing interface, primary inputs, valve monitoring etc.) via jumper caps and via programming. Power supply: internally via the system BUS Current consumption: 30 mA max. current limited Connection: 6 detector zones (max. 30 detectors / zone) Terminal resistance: 11,8 k Alarm resistor: 560 Line resistance: max. 71,5 per core Ambient temperature: 0 to +50C Individual detector identification: possible with detector zone recognition Range: max. 2000 m Cable diameter: 2-core: 0.6 or 0.8 mm 3 pole: 0.8 mm
Description Type Art. No.

B3-DCI6 Module for DC Technology Connector plug for B3-DCI6 (replacement)

B3-DCI6 ST-DCI6

EG072811 FG74099

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

23

Modular control panels Integral IP MX Modules for system modernisation

B3-LEE23 module for 140 detector series For connecting up to eight stub lines each with a maximum of 30 series 140 detectors. A maximum of five B3-LEE23 modules can be fitted to connection slots 2 to 8 of an Integral module rack, however this module is only permitted for use in cases where the system is being reconditioned due to the terms of the approvals of the module. Power supply: Current consumption: Ambient temperature: Detector zones: Addressing: Wiring length:
Description

B3-LEE23 No.: EG072851

internally via the system BUS 22 mA 0 to +50C max. 8 logical detector zones per stub line the hardware address assigned to the detector can be assigned whatever logical software address is required max. 1000 m
Type Art. No.

B3-LEE23 module for 140 detector series 16 pole connector plug

B3-LEE23 ST-B3 16

EG072851 YY970138

B3-LEE24 module for 150 detector series For connecting up to four loops each with a maximum of 127 series HX 150 detectors. A maximum of five modules of type B3-LEE24 can be fitted in connection slots 2 to 8 of the module rack of an Integral module rack. The module only functions in conjunction with B3-MCU32E2 or B5-MCU main processor units, and may only be deployed for renovation purposes according to approvals. Power supply: Current consumption: Ambient temperature: Devices/Elements: Addressing: Range:
Description

B3-LEE24 No.: EG072852

internally via the system BUS 27 mA 0 to +50C 4 loop circuits each with max. 127 devices the hardware address assigned to the detector can be assigned whatever logical software address is required max. 1000 m
Type Art. No.

B3-LEE24 module for 150 detector series 16 pole connector plug

B3-LEE24 ST-B3 16

EG072852 YY970138

24

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX Accessories & replacement parts

2.6

Accessories & replacement parts


Integral MX empty cabinet B5-CAB Empty cabinet in Integral IP MX design with full door for use as a cabinet for rechargeable cells, as a storage unit etc. Dimensions: 600 x 445 x 225 mm (HxWxD) Case colour: red RAL 3000 Weight: ca. 10 kg
Description Type Art. No.

B5-CAB No.: 20-1400110-01

Integral MX empty cabinet

B5-CAB

20-1400110-01

B5-CBE No.: 20-1400112-01

Integral MX Battery Cabinet B5-CBE Empty cabinet in Integral IP MX design with full door, with built-in rechargeable cell holder for extending rechargeable cell capacity. Dimensions: 600 x 445 x 225 mm (HxWxD) Case colour: red RAL 3000 Weight: ca. 12 kg
Description Type Art. No.

Integral MX battery cabinet

B5-CBE

20-1400112-01

B5-CTR No.: 20-1400114-01

Integral MX Top hat rail cabinet B5-CTR Cabinet in Integral IP MX design with full door, built-in top-hat rail and cable conduits for use as a distributor case, for installation of modules etc. Dimensions: 600 x 445 x 225 mm (HxWxD) Case colour: red RAL 3000 Weight: ca. 11 kg
Description Type Art. No.

Integral MX top hat rail cabinet

B5-CTR

20-1400114-01

Accessories and Spare Parts for Integral IP MX control panels


Description Type Art. No.

Battery for emergency power supply USB cable 3 m for Service PC USB cable 4,5 m for Service PC B5 battery holder set B5 distance piece set Battery current measuring cable Front blanking panel for module rack Papierrolle fr Protokolldrucker Paper roll for Log Printer B5 battery cable set B5 battery cable set long Bayonet fuses for cable set Lock for Integral MX/CX cabinets Key for Integral MX/CX cabinets

AKKU 38 KAB USB 3 KAB USB 45 B5-BATH-SET B5-DISTH-SET KAB PSU B5 BFP PD PPR PD FRB B5 BATKAB1 B5 BATKAB2 ZUB SICH8 SCU LOCK SCU LOCK KEY

HG691017 FG022051 FG022052 FG74108 FG74110 FG81720 FG06240 PPF-519057 HG694076 FG29910 FG29911 IS625040 FG29516 750000027

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

25

Modular control panels Integral IP MX Accessories & replacement parts

Connection socket for Integral IP MX modules The necessary connector plugs are supplied with the modules, with the items listed below intended for ordering as replacements. Exception: Connector plugs must always be ordered separately for relay modules B3-REL10, B3-REL16, B3-REL16E and B5-MRI16!
Description Type Art. No.

Connector for B3-DAI2 16 pole connector for detector zones/inputs Connector for B3-DCI6 18 pole connector for detector zones Connector for B3-DTI2 16 pole connector for detector zones Connector for B3-HFI 9 pole connector for interfaces Connector for B3-IM8 16 pole connector for inputs Connector for B3-LEE23 16 pole connector for detector zones Connector for B3-LEE24 16 pole connector for detector zones Connector for B3-LPI 9 pole connector for interfaces Connector for B3-MTI8 16 pole connector for detector zones Connector for B3-OM8 16 pole connector for monitored outputs Connector for B3-REL10 2 connectors for relay outputs can be connected sideways 2 connectors for relay outputs can be connected front on Connector for B3-REL16(E) 2 connectors for relay outputs can be connected sideways 2 connectors for relay outputs can be connected front on Connector for B3-USI4 9 pole connector for interfaces 15 pole connector for interfaces Connector for B5-BAF 6 pole connector for monitored outputs 13 pole connector f. fire brigade panel DIN14661 9 pole solder lug connector for MMI-BUS 9 pole IDC connector for MMI-BUS Connector for B5-MRI16 2 connectors for relay outputs can be connected sideways 2 connectors for relay outputs can be connected front on Connector for B5-PSU 10 pole connector for external devices Connector for B5-LAN & B5-NETx485 RJ45-connector Cat5e RJ45-crimping tool 9-Sub-D RJ45 coupling 15-Sub-D RJ45 coupling

ST-B3 16 ST-DCI6 ST-B3 16 ST-LPI/USI4/HFI ST-MTI8 ST-B3 16 ST-B3 16 ST-LPI/USI4/HFI ST-MTI8 ST-OM8 ST-SET REL10W ST-SET REL10

YY970138 FG74099 YY970138 FG74097 FG74087 YY970138 YY970138 FG74097 FG74087 FG74095 FG74103 FG74104

ST-SET REL16W ST-SET REL16

FG74105 FG74106 FG74097 FG74098 FG74088 YK130459 FG74086 FG74085 FG74105 FG74106 FG74090 MM010008 MM010001 20-1400000-01 20-1400001-01

ST-LPI/USI4/HFI ST-USI4 ST-BAF-OM ST-FBF ST-BAF-MMI-L ST-BAF-MMI-S ST-SET REL16W ST-SET REL16 ST-PSU EV RJ45-IP CRIMP-IP KUP 9RJ45 KUP 15RJ45

26

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Modular control panels Integral IP MX Software

2.7

Software
Integral Software V 7.x For configuring Integral IP MX and Integral IP CX systems. The software only functions using a dongle and can be downloaded free of charge from our website. Operating system: Hardware requirements: Windows 2000/ XP/VISTA Windows 7 (32-Bit / 64-Bit) CPU Pentium 1 GHz, min. 1 GB RAM (2 GB recommended) 300 MB free hard drive space VGA graphics card 1280x1024 pixels 2 free USB ports Internet connection f. unlocking the dongle

Integral VirtualMAP For accessing data in the fire alarm system from one or more PC workstations. The operating panel of the fire alarm control panel is represented 1:1 on the monitor, and it is possible to access all the information in the fire alarm system using the keyboard and the mouse. A multi-layer security concept ensures that non-authorised system access is blocked. The software only functions using a dongle and can be downloaded free of charge from our website. Operating system: Hardware requirements: Windows 2000/ XP/VISTA Windows 7 (32-Bit / 64-Bit) CPU Pentium 1 GHz, min. 1 GB RAM (2 GB recommended) 300 MB free hard drive space VGA graphics card 1280x1024 pixels 1 free USB port Internet connection f. unlocking the dongle
Type Art. No.

Description

ULM-Dongle Schrack Export RUS ULM-Dongle Integral VirtualMAP

DONGLE USB RUS DONGLE IVM

20-1300109-01-01 20-1300200-01-01

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

27

Compact control panels Integral IP CX Fire alarm control panel Integral IP CXF

3 Compact control panels Integral IP CX


3.1 Fire alarm control panel Integral IP CXF
The Integral IP CXF is a cost-optimized fire alarm control panel for small systems, and in its basic form up to 500 elements can be connected to 2 loop circuits. Additionally, the unit also has an interface to which a LAN networking module can be connected, or two more loop circuits, a universal interface module or an input/output module can be connected.

Important Features
Microprocessor-controlled and monitored system topology Software redundancy pursuant to TRVB S 123, annex 6/1, Point 2.2. (from SW V 6.1) Constant automatic test routines for all system components and programs. Six line display for displaying the system status in plain text (alarms, faults etc.) Acoustic and optical alarm notification for alarms and faults Alarm buffering Possibility to manually test the control panel and its functions Plain text indication of individual detector and indicator zones Up to 8 external operating panels per control panel, maximum distance 1200 m Operating panel language (labelling and display indication) can be selected, can be constantly toggled between up to 4 languages. External device bus for up to 15 indication and operation devices. Serial data log printer with UPS power supply, with an event memory and message filter. Suitable for connection to the fire brigades public alarm notification system System configuration saved using flexible flash memory technology Emergency power supply for a supply interruption period of 72 hours

Options
Control panel networking using a TCP/IP-based local mesh network: up to 16 control panels can be networked to form a logical unit without requiring a superordinated management system Mesh network with up to 3 connections per subcontrol unit: in the event of a device failing or a connection fault occurring, it is possible for data communications to continue by diverting (routing) the data. Data transmission at 625/2500 Kbit Flexible topology: stub connection to loop is possible Ethernet protocol: Using the customer's IT infrastructure Access to the control unit over the Intranet and Internet Standardised IT components are used Serial data interfaces for connection to fire alarm management systems, external log printers etc. Connection for fire brigade panels pursuant to NORM F3031, DIN 14661, SN 054002 and DIN 14662 Daytime/Night time operation mode switching can be individually programmed for each detector zone and every week day Intervention mode Detectors can be freely assigned and linked to controller criteria - software controlled Software-controlled two zone dependency or two detector dependency for alarm notification and controlling of devices Recognition and evaluation of the status of detectors (contamination) Disablement of individual detectors Can be networked with all Schrack fire alarm control panels B-HB-008EN Product catalogue fire alarm systems 2011 V 2.0 28

Compact control panels Integral IP CX Fire alarm control panel Integral IP CXF

Approvals
VdS Device and System Approval: G200081, S200081, G206045, G206055, S206055 EC Conformity Certificate No. 0786-CPD-20239 (VdS) Austrian Testing Centre for Fire Prevention Technology: FT 14/170/08/96 and FT 14/171/08/96 VB Cert Austria: Nos. 002/BM-PSys/008, 002/BM-PSys/009, 002/BM-PSys/010 Country-specific approvals in Austria, Germany, Denmark, Italy, Croatia, The Netherlands, Poland, Romania, Russia, Sweden, Switzerland, Slovakia, Czech Republic, Turkey, Hungary, Ukraine and many more

B6-X2 No.: FG052600

Integral IP CXF cabinet variants All variants of Integral CXF units contain the following basic structure: Sheet steel cabinet B6-BCU-X2 main processor unit B6-PSU power supply unit Power clips and battery cable Connections for two loops 2 monitored outputs for transmission equipment and alarm systems Connector plug for two monitored inputs five relay outputs (24 V/3 A) Connection for fire brigade control panel (acc. to DIN 14661) Connection for external operating panels and fire brigade indicator panels (FAT) conformant to DIN 14662 Interface for either B6-LAN, B4-USI or B4-DAI2 or B4-EIO Maximum rechargeable cell size 2 x 12 V/18 Ah Input voltage / frequency: Input power: Output voltage: Output current: Batteries that can be used: Emergency power supply with batteries: Ambient temperature: Case: Rel. air humidity: Air pressure: Protection class (DIN 40050): Dimensions: Weight:
Description

B6-X2-C No.: FG052601

230 VAC, +15% -20% / 47-63 Hz 160 W 26,3 VDC (50C) to 28,3 VDC (0C) 4A 2 pcs. 12 V / 15...18 Ah in series 72 h normal operation + 0.5 h alarm 0 to +50C sheet steel, red RAL 3000 5 to 95%, without condensation 80 kPa, to 2000 m above sea level IP 30 400 x 445 x 140 mm (HxWxD) 19 kg incl. batteries
Type Art. No.

B6-X2-CP No.: FG052602

Integral IP CXF basic version Cabinet with full door Integral IP CXF basic version, cabinet with cutaway for built-in operating panel Integral IP CXF basic version Cabinet with cutaway and log printer

B6-X2 B6-X2-C B6-X2-CP

FG052600 FG052601 FG052602

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

29

Compact control panels Integral IP CX Integral IP CXF modules

3.2

Integral IP CXF modules


B4-DAI2 Loop module For connecting two extra loop circuits to the relevant detectors and Integral loop technology modules to the Integral CXF. Alternatively one loop circuit and two stub lines or four stub lines can be controlled. The module is connected to the B6-BCU-X2 main processor unit. Power supply: Current consumption: Ambient temperature: Elements: Short circuit isolator: internally over the B6-BCU-X2 30 mA 0 to +50C 2 loops, 128 elements each integrated into detectors and controller modules Individual detector identification: integrated as standard Loop length: max. 2000 m Dimensions: 143 x 94 x 18 mm
Description Type Art. No.

B4-DAI2 No.: EG072835

B4-DAI2 Loop module Connector plug for B4-DAI2

B4-DAI2 ST-LOOP/DAI

EG072835 YK130295

B4-EIO No.: EG072858

B4-EIO Input/output module For connection of up to 10 stub lines each with a maximum of 30 detectors from the 130 A detector series, primary inputs or VdS sprinkler interfaces and eight monitored outputs each with an output current of max. 1.5 A. Furthermore it is suitable for connection from intrinsically safe detectors for use in hazardous areas of the MSD/UTD 523 and MCP 525 detector series (or SSD/UTD 521) over a safety barrier. The module is connected to the B6-BCU-X2 main processor unit. Power supply: Current consumption: Ambient temperature: Number of inputs: Number of outputs: Wiring length: Dimensions:
Description

internally over the B6-BCU-X2 13,5 mA 0 to +50C max. 10 max. 8 max. 1000 m 143 x 94 x 18 mm
Type Art. No.

B4-EIO Input/output module B4-EIO Replacement connector set

B4-EIO ST-SET-EIO

EG072858 FG74109

30

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Compact control panels Integral IP CX Integral IP CXF modules

B6-LAN No.: EG072940

B6-LAN Network module For non-redundant networking of Integral IP CXF control panels for nonredundant connection of PC applications. The module is connected to the B6-BCU-X2 main processor unit. Power supply: Current consumption: Ambient temperature: Transmission type: Physical characteristics: Direction: LAN-interface: Speed: Distance:
Description

internally over the B6-BCU-X2 0 mA 0 to +50C TCP/IP 1 x RJ45 connector bidirectional, full-duplex Ethernet 100 Base TX max. 100 Mbit/s max. 100 m
Type Art. No.

B6-LAN Network module RJ45-connector Cat5e RJ45-crimping tool 9-Sub-D RJ45 coupling 15-Sub-D RJ45 coupling

B6-LAN RJ45-IP CRIMP-IP KUP 9RJ45 KUP 15RJ45

EG072940 MM010008 MM010001 20-1400000-01 20-1400001-01

B6-NET2-485 No.: EG072934

B6-NET2-485 Network module For redundant networking of Integral IP CXF control panels or for redundant connection of PC applications. The module consists of 2 network connectors (RS 485 interface) and one 100 Base TX interfaces. The module is connected to the B6-BCU-X2 main processor unit. Power supply: Current consumption: Ambient temperature: Transmission type: Physical characteristics: Direction: LAN-interface: Speed: Distance: RS485-interfaces: Speed: Distance: Cable:
Description

internally over the B6-BCU-X2 53 mA 0 to +50C TCP/IP RJ-45 connector bidirectional, full-duplex Ethernet 100 Base TX max. 100 Mbit/s max. 100 m 2 x RS485 with redundant cabling, of which 1 galvanically isolated max. 2,5 Mbit/s max. 1200 m UTP Cat5
Type Art. No.

B6-NET2-485 Network module RJ45-connector Cat5e RJ45-crimping tool 9-Sub-D RJ45 coupling 15-Sub-D RJ45 coupling

B6-NET2-485 RJ45-IP CRIMP-IP KUP 9RJ45 KUP 15RJ45

EG072934 MM010008 MM010001 20-1400000-01 20-1400001-01

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

31

Compact control panels Integral IP CX Integral IP CXF modules

B6-NET2-FXM No.: 20-1100001-01-01

B6-NET2-FXM Network module For redundant networking of Integral IP CXF control panels or for redundant connection of PC applications. The module consists of 2 network connectors (RS 485 interface), two optical network connections that are realized on the basis of the standard FXM and one 100 Base TX interfaces. The module is connected to the B6-BCU-X2 main processor unit. From the software V 7.2 the B6-NET2-FXM module is fully supported. Power supply: Current consumption: Ambient temperature: Transmission type: Physical characteristics: Direction: LAN-interface: Speed: Distance: RS485-interfaces: Speed: Distance: Cable: Ethernet FXM: Transceiver: Speed: Distance: Cable:
Description

MTRJ

KUP 9RJ45 / KUP 15RJ45

internally over the B6-BCU-X2 122 mA 0 to +50C TCP/IP RJ-45 connector bidirectional, full-duplex Ethernet 100 Base TX max. 100 Mbit/s max. 100 m 2 x RS485 with redundant cabling, of which 1 galvanically isolated max. 2,5 Mbit/s max. 1200 m UTP Cat5 Avago AFBR5903Z, Multimode Laser max. 100 Mbit/s max. 2 000 m Multimode 62,5/125 m (FXM) Multimode 50/125 m (FXM)
Type Art. No.

B6-NET2-FXM Network module RJ45-connector Cat5e RJ45-crimping tool 9-Sub-D RJ45 coupling 15-Sub-D RJ45 coupling

B6-NET2-FXM RJ45-IP CRIMP-IP KUP 9RJ45 KUP 15RJ45

20-1100001-01-01 MM010008 MM010001 20-1400000-01 20-1400001-01

32

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Compact control panels Integral IP CX Integral IP CXF modules

B6-NET2-FXS No.: 20-1100000-01-01

LC 2x5 (Duplex)

KUP 9RJ45 / KUP 15RJ45

B6-NET2-FXS Network module For redundant networking of Integral IP CXF control panels or for redundant connection of PC applications. The module consists of 2 network connectors (RS 485 interface), two optical network connections that are realized on the basis of the standard FXS and one 100 Base TX interfaces. The module is connected to the B6-BCU-X2 main processor unit. (ver. SW 7.2) Power supply: internally over the B6-BCU-X2 Current consumption: 99 mA Ambient temperature: 0 to +50C Transmission type: TCP/IP Physical characteristics: RJ-45 connector Direction: bidirectional, full-duplex LAN-interface: Ethernet 100 Base TX Speed: max. 100 Mbit/s Distance: max. 100 m RS485-interfaces: 2 x RS485 with redundant cabling, of which 1 galvanically isolated Speed: max. 2,5 Mbit/s Distance: max. 1200 m Cable: UTP Cat5 Ethernet FXS: Transceiver: Avago AFCT5971FZ, Singlemode Laser Speed: max. 100 Mbit/s Distance: max. 10 000 m Cable: Singlemode 9/125 m (FXS)
Description Type Art. No.

B6-NET2-FXS Network module RJ45-connector Cat5e RJ45-crimping tool 9-Sub-D RJ45 coupling 15-Sub-D RJ45 coupling

B6-NET2-FXS RJ45-IP CRIMP-IP KUP 9RJ45 KUP 15RJ45

20-1100000-01-01 MM010008 MM010001 20-1400000-01 20-1400001-01

B4-USI No.: EG072834

PCMCIA No.: FG020317

B4-USI Universal Interface Module For connecting Integral CXF control units to Integral networks, to management systems, for controlling external printers, pagers, ComBOX, telephone servers etc. The module contains an interface for a PCMCIA modem and two serial asynchronous interfaces. The module is connected to the B6BCU-X2 main processor unit. The PCMCIA modem is not supplied and must be ordered separately as required. Power supply: internally over the B6-BCU-X2 Current consumption: 21 mA, with PCM-CIA modem 40 mA Ambient temperature: 0 to +50C Range: RS 485 to 1200 m RS 232 to 15 m Interfaces: 1 galv. isolated redundant RS 485 1 galv. isolated RS 232/RS 485 Modem interface for PCM-CIA modem (dedicated line and dial-up line enabled) Dimensions: 143 x 102 x 12 mm
Description Type Art. No.

B4-USI Universal interface module PCM CIA modem 9 pole solder lug connector for B4-USI 15 pole solder lug connector for B4-USI

B4-USI PCMCIA ST-LPI/USI4/HFI ST-USI4

EG072834 FG020317 FG74097 FG74098

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

33

Compact control panels Integral IP CX Fire alarm control panel Integral IP CXA

3.3

Fire alarm control panel Integral IP CXA

The Integral CXA fire alarm control panel is a cost-optimized single loop fire alarm control panel for the smallest sized systems, suitable for connecting a single loop circuit with a maximum of 250 devices. The main processor unit contains all necessary interfaces for the connection to the fire brigade (transmission and alarm systems, interface for connecting various types of fire brigade control panels), as well as five 230V / 3A relay outputs and a connection for the external device bus (MMI-BUS). The Integral IP CXA can not be networked, and can also not be connected to superordinated systems (e.g. management systems).

Approvals
VdS Device and System Approval: G206055, S206055 EC Conformity Certificate No. 0786-CPD-20602 (VdS) Austrian Testing Centre for Fire Prevention Technology: FT 14/170/08/96 and FT 14/171/08/96 VB Cert Austria: Nos. 002/BM-PSys/008, 002/BM-PSys/009, 002/BM-PSys/010 Country-specific approvals in Austria, Germany, Denmark, Italy, Croatia, The Netherlands, Poland, Romania, Russia, Sweden, Switzerland, Slovakia, Czech Republic, Turkey, Hungary, Ukraine and many more.

B6-X1F-C No.: FG052611

1 loop fire alarm control panel Integral IP CXA All variants of Integral CXA units contain the following basic structure: Sheet steel cabinet B6-BCU-X1F main processor unit B6-PSU 24V/4A power supply unit Power clips and battery lead 1 Loop circuit (max. 250 devices) 1 Main detector output (Transmission equipment) 1 Monitored Output (Alarm systems) 5 relay outputs (230V/3A) Connection for fire brigade panel in accordance with DIN 14661 MMI-BUS connection (external operating panels, FWB Austria, FAT)) Input voltage / frequency: Input power: Output voltage: Output current: Batteries that can be used: Emergency power supply with batteries: Ambient temperature: Case: Rel. air humidity: Air pressure: Protection class (DIN 40050): Dimensions: Weight:
Description

B6-X1F-CP No.: FG052612

230 VAC, +15% -20% / 47-63 Hz 160 W 26,3 VDC (50C) to 28,3 VDC (0C) 4A 2 pcs. 12 V / 15...18 Ah in series 72 h normal operation + 0.5 h alarm 0 to +50C sheet steel, red RAL 3000 5 to 95%, without condensation 80 kPa, up to 2,000 m above sea level IP 30 400 x 445 x 140 mm (HxWxD) 19 kg incl. batteries
Type Art. No.

Integral IP CXA basic version, cabinet with cutaway for built-in operating panel Integral IP CXA basic version cabinet with cutaway and log printer

B6-X1F-C B6-X1F-CP

FG052611 FG052612

34

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Compact control panels Integral IP CX Fire alarm control panel Integral IP CXB

3.4

Fire alarm control panel Integral IP CXB

The Integral CXB fire alarm control panel is a cost-optimized single loop fire alarm control panel for the smallest sized systems, suitable for connecting a single loop circuit with a maximum of 250 devices. The main processor unit also contains a connection to the external device bus (MMI-BUS) in addition to the connection to the loop circuit. The Integral IP CXB can not be networked, and can also not be connected to superordinated systems (e.g. management systems).

Approvals
VdS Device and System Approval: G206055, S206055 EC Conformity Certificate No. 0786-CPD-20602 (VdS) Austrian Testing Centre for Fire Prevention Technology: FT 14/170/08/96 and FT 14/171/08/96 VB Cert Austria: Nos. 002/BM-PSys/008, 002/BM-PSys/009, 002/BM-PSys/010 Country-specific approvals in Austria, Germany, Denmark, Italy, Croatia, The Netherlands, Poland, Romania, Russia, Sweden, Switzerland, Slovakia, Czech Republic, Turkey, Hungary, Ukraine and many more.

B6-X1F-C No.: FG052613

1 loop fire alarm control panel Integral Integral IP CXB The Integral CXB is only available in a single version and consists of: B6-BCU-X1B main processor unit B6-PSU 24V/4A power supply unit Power clips and battery lead 1 Loop circuit (max. 250 devices) MMI-BUS connection (external operating panels, FWB Austria, FAT) Input voltage / frequency: Input power: Output voltage: Output current: Batteries that can be used: Emergency power supply with batteries: Ambient temperature: Case: Rel. air humidity: Air pressure: Protection class (DIN 40050): Dimensions: Weight:
Description

230 VAC, +15% -20% / 47-63 Hz 160 W 26,3 VDC (50C) to 28,3 VDC (0C) 4A 2 pcs. 12 V / 15...18 Ah in series 72 h normal operation + 0.5 h alarm 0 to +50C sheet steel, red RAL 3000 5 to 95%, without condensation 80 kPa, up to 2,000 m above sea level IP 30 400 x 445 x 140 mm (HxWxD) 19 kg incl. batteries
Type Art. No.

Integral IP CXA basic version, cabinet with cutaway for built-in operating panel

B6-X1F-C

FG052613

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

35

Compact control panels Integral IP CX Controller unit for single zone extinguishing systems Integral IP CXE

3.5

Controller unit for single zone extinguishing systems Integral IP CXE

The Integral IP CX system can also be deployed as an Integral IP CXE extinguishing system control panel (electronic control and delay unit) or as a combined Integral IP CXF/CXE fire detector/extinguishing system control panel. There is a separate version of the case available for this purpose, which contains an additional LED parallel indicator tableau for a single extinguishing zone and also contains additional freely programmable inputs and outputs. In this version, the Integral CXE, in accordance with standards and directives EN 12094-1 and VdS 2496, is now suitable and approved for use for controlling and monitoring the following types of fire extinguishing systems: CO2 - high and low pressure extinguishing systems where life is or is not endangered. Inert gas and argon extinguishing systems where life is or is not endangered. Water spray systems Pre-action sprinkler systems Sprinkler Systems Mist water deluge systems Chemical extinguishing systems Single zone extinguishing panel Integral IP CXE The Integral CXE is only available in a single version and consists of: Cabinet made of sheet steel with a cutaway for a built-in operating panel built-in log printer B4-EIO input/output module LED indicator panel for indications from an extinguishing zone B6-BCU-X2 main processor unit B6-PSU power supply unit Power clips and battery cable Connection for two loop circuits (max. 500 elements) 2 monitored outputs for transmission equipment and alarm systems Connector plug for two monitored inputs five relay outputs (24 V/3 A) Connection for fire brigade panel in accordance with DIN 14661 Connection for external operating panels and fire brigade indicator panels (FAT) conformant to DIN 14662 Maximum rechargeable cell size 2 x 12 V/18 Ah Input voltage / frequency: Input power: Output voltage: Output current: Batteries that can be used: Emergency power supply with batteries: Ambient temperature: Case: Rel. air humidity: Air pressure: Protection class (DIN 40050): Dimensions: Weight:
Description

B6-X2-CP1L No.: FG052603

230 VAC, +15% -20% / 47-63 Hz 160 W 26,3 VDC (50C) to 28,3 VDC (0C) 4A 2 pcs. 12 V / 15...18 Ah in series 72 h normal operation + 0.5 h alarm 0 to +50C sheet steel, red RAL 3000 5 to 95%, without condensation 80 kPa, up to 2,000 m above sea level IP 30 400 x 445 x 140 mm (HxWxD) 19 kg incl. batteries
Type Art. No.

Integral IP CXE cabinet with cutaway for built-in operating panel, log printer and LED indicator panel for a single extinguishing zone

B6-X2-CP1L

FG052603

36

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Compact control panels Integral IP CX Built-in operating panel MAP for Integral IP CX panels

3.6

Built-in operating panel MAP for Integral IP CX panels


B6-CII-RU Built-in operating panel Integral MAP Operating panel for installation in all Integral IP CX cabinets with door cutaways, available in many different language versions (key labelling and display indication). Listed below are the German and English language versions, and other languages are available on request. Display with 6 lines, 40 characters per line Conforms to all options of EN 54-2:2006 can be deployed as a main operating panel in a SecoNET Up to 4 languages can be switched between in normal operation Connection f. EPI-Bus (various other indication and operating devices) 2 freely programmable and labelable buttons 2 freely programmable and labelable 3 colour LEDs 5 status lists (alarms, faults, disablements, etc.) Status indication on the first line of the display Zone operation (e.g. disable zone 1-10) Group operation (e.g. simultaneously disable all detector zones) individual user management with password and user level every change of user is logged in the event log memory
Type Art. No.

B6-CII-RU No.: FG91306-9

Description

B6 MAP internal operating panel German B6 MAP internal operating panel English B6 MAP internal operating panel Russian

B6-CII-DE B6-CII-EN B6-CII-RU

FG91300-9 FG91301-9 FG91306-9

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

37

Compact control panels Integral IP CX Accessories & replacement parts

3.7

Accessories & replacement parts


B6-BCU X2 Main processor unit The B6-BCU-X2 is a component of every Integral IP CXF and CXE and contains all the interfaces required for the connection of peripheral devices, relay contacts, MMI Bus, monitored outputs and the service PC, as well as a connection slot in which an additional module (B4-DAI2, B4-USI or B4EIO) can be fitted. Power is supplied by the B6-PSU, with the built-in operating panel being connected via a 34 pole ribbon cable connector. Power supply: via power supply unit B6-PSU Operating voltage: Battery voltage VL+22 V .. 30 V Logic voltage VCC+5.0 V 5% Logic voltage VCC+3.3V 5% Power consumption: Battery current (idle) typically 48 mA Ambient temperature: 0 to +50C Rel. air humidity: 5 to 95 %, without condensation
Description Type Art. No.

B6-BCU X2 No.: EG072938

SD-CARD No.: FG020325

B6-BCU X2 Main processor unit SD-CARD 2GB

B6-BCU-X2 SD-CARD

EG072938 FG020325

B6-BCU-X1F No.: EG072937

SD-CARD No.: FG020325

B6-BCU-X1F Main processor unit The B6-BCU-X1F is a component of every Integral IP CXA control panel and contains all the interfaces required for connecting peripherals, relay contacts, MMI-BUS, monitored outputs and Service PC. Power is supplied by the B6-PSU, with the built-in operating panel being connected via a 34 pole ribbon cable connector. Power supply: via power supply unit B6-PSU Operating voltage: Battery voltage VL+22 V .. 30 V Logic voltage VCC+5.0 V 5% Logic voltage VCC+3.3V 5% Power consumption: Battery current (idle) typically 47 mA Ambient temperature: 0 to +50C Rel. air humidity: 5 to 95 %, without condensation
Description Type Art. No.

B6-BCU X1F Main processor unit SD-CARD 2GB

B6-BCU-X1F SD-CARD

EG072937 FG020325

B6-BCU-X1B No.: EG072932

SD-CARD No.: FG020325

B6-BCU-X1B Main processor unit The B6-BCU-X1B is a component of every Integral IP CXB control panel and contains all the interfaces required for connecting peripherals, MMIBUS, and the service PC. Power is supplied by the B6-PSU, with the built-in operating panel being connected via a 34 pole ribbon cable connector. Power supply: via power supply unit B6-PSU Operating voltage: Battery voltage VL+22 V .. 30 V Logic voltage VCC+5.0 V 5% Logic voltage VCC+3.3V 5% Power consumption: Battery current (idle) typically 43 m Ambient temperature: 0 to +50C Rel. air humidity: 5 to 95 %, without condensation
Description Type Art. No.

B6-BCU X1B Main processor unit SD-CARD 2GB

B6-BCU-X1B SD-CARD

EG072932 FG020325

38

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Compact control panels Integral IP CX Accessories & replacement parts

B6-PSU No.: EG072950

B6-PSU Power supply unit The internal 4A power supply in every Integral IP CX control unit supplies the required output voltages of 3.3V, 5V and 27V. It is always fitted in the case of every Integral CX on the right hand side next to the main processor unit and is always connected to it using a 64 pin multipoint connector. On the bottom side of the power supply unit there is a 2 pole clip for connection to the rechargeable batteries and a 10 pin pluggable screw connector, to which external devices can be connected using five separately fused outputs. The B6-PSU power supply contains a battery monitoring facility, which is controlled and evaluated by the main processor unit. Mains supply voltage/frequency: 230 VAC +15%/-20% 47-63 Hz Power consumption: max. 200 VA, max. 160W Mains fuse: with 10A current surge-resistant Mains fuses in power supply: 4.0A T Outputs for internal devices: 3.3V/3A, 5V/1A, 27V/4A Outputs for external devices: 5 x 27V / 2.5A FF Charging output for batteries: 27V / 3.2A Replacement fuses F1 to F5: 2.5A superfast, glass tube 5x20 mm
Description Type Art. No.

B6-PSU Power supply unit Replacement connection plug f. external devices Replacement fuses F1 to F5 Battery current measuring cable

B6-PSU ST-PSU EV ZUB SICH 2.5FF KAB PSU

EG072950 FG74090 IS625228 FG81720

Connection socket for Integral IP CX modules The necessary connector plugs are supplied with the respective modules, or shipped with the Integral CX control panels, with the items listed below intended for ordering as replacements.
Description Type Art. No.

Connector for B4-DAI 16 pole for detector zones Connector for B4-EIO 2x10 & 1x16-pole, inputs/outputs Connector for B4-USI 9 pole interfaces 15 pole interfaces Connector for B6-BCU-X1B 16 pole detector zones 9 pole solder lug terminal connector MMI-BUS Connector for B6-BCU-X1F 16 pole detector zones 5 pole monitored outputs 13 pole, fire brigade panel DIN 14661 10 pole relay outputs 9 pole solder lug terminal connector MMI-BUS Connector for B6-BCU-X2 16 pole detector zones 5 pole monitored outputs 13 pole, fire brigade panel DIN 14661 10 pole relay outputs 9 pole solder lug terminal connector MMI-BUS Connector for B6-PSU 10 pole, external devices 3 pole power connector plug B6 Connector for B6-LAN & B6-NET2-485 RJ45-connector Cat5e RJ45-crimping tool 9-Sub-D RJ45 coupling 15-Sub-D RJ45 coupling
B-HB-008EN Product catalogue fire alarm systems 2011 V 2.0

ST-LOOP/DAI ST-SET EIO ST-LPI/USI4/HFI ST-USI4 ST-LOOP/DAI ST-BAF-MMI-L ST-LOOP/DAI ST-B6-OM ST-FBF ST-B6-REL ST-BAF-MMI-L ST-LOOP/DAI ST-B6-OM ST-FBF ST-B6-REL ST-BAF-MMI-L ST-PSU EV ST-PSU NS RJ45-IP CRIMP-IP KUP 9RJ45 KUP 15RJ45

YK130295 FG74109 FG74097 FG74098 YK130295 FG74086 YK130295 FG74116 YK130459 FG74115 FG74086 YK130295 FG74116 YK130459 FG74115 FG74086 FG74090 YK130302 MM010008 MM010001 20-1400000-01 20-1400001-01

39

Compact control panels Integral IP CX Accessories & replacement parts

B6-CAB No.: 20-1400111-01

Integral CX empty cabinet B6-CAB Empty cabinet in Integral IP CX design with full door for use as a cabinet for rechargeable cells, as a storage unit etc. Dimensions: 400 x 445 x 140 mm (HxWxD) Case colour: red RAL 3000 Weight: ca. 6 kg
Description Type Art. No.

Integral CX Empty cabinet

B6-CAB

20-1400111-01

B6-CBE No.: 20-1400113-01

Integral CX Battery cabinet B6-CBE Empty cabinet in Integral IP CX design with full door, with built-in rechargeable cell holder for extending rechargeable cell capacity. Dimensions: 400 x 445 x 140 mm (HxWxD) Case colour: red RAL 3000 Weight: ca. 8 kg
Description Type Art. No.

Integral CX Battery cabinet

B6-CBE

20-1400113-01

B6-CTR No.: 20-1400115-01

Integral CX Top hat rail cabinet B6-CTR Cabinet in Integral IP CX design with full door, built-in top-hat rail and cable conduits for use as a distributor case, for installation of modules etc. Dimensions: 400 x 445 x 140 mm (HxWxD) Case colour: red RAL 3000 Weight: ca. 7 kg
Description Type Art. No.

Integral CX Top hat rail cabinet

B6- CTR

20-1400115-01

Various accessories for Integral IP CX control panels


Description Type Art. No.

Battery for emergency power supply USB cable 3 m for Service PC USB cable 4,5 m for Service PC B6 battery holder set B6 distance piece set Battery current measuring cable Paper roll for log printer Colour printer ribbon cassette for log printer B6 battery cable set Bayonet fuses for cable set Lock for Integral MX/CX cabinets Key for Integral MX/CX cabinets

AKKU 17 KAB USB 3 KAB USB 45 B6-BATH-SET B6-DISTH-SET KAB PSU PD PPR PD FRB B6 BATKAB ZUB SICH8 SCU LOCK SCU LOCK KEY

HG691013 FG022051 FG022052 FG74112 FG74111 FG81720 PPF-519057 HG694076 EI29940 IS625040 FG29516 750000027

40

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

External indicator & operating panels Accessories & replacement parts

4 External indicator & operating panels


All external operating panels and devices in the Integral system whose device descriptor contains the letters MMI are connected via the MMI-BUS and can therefore be connected to all Integral, IP MX and Integral IP CX control panels. Caution: Both versions of the high-end operating panel - B5-MMI-HCIP and B5-MMI-HCPP - can only by connected to Integral CX control panels from version 7.1 onwards of the Integral software! The interface for connection the MMI-BUS can be found on module B5-BAF for the Integral IP MX control panels and on the main processor unit B6-BCU-X2 or B6-BCU-X1x for the Integral IP CX control panels. The external Integral operating panels B3-MMI-CIP and B3-MMI-CPP, as well as both high end operating fields B5-MMI-HCIP and B5-MMI-HCPP are available in a wide range of languages. External Operating Panel MAP External operating panel with or without a log printer for connection to the MMI-BUS, available in many language versions (key labels and indicator display). Listed below are the German and English language versions, and other languages are available on request. Display with 6 lines, 40 characters per line Conforms to all options of EN 54-2:2006 can be deployed as a main operating panel in a SecoNET Up to 4 languages can be switched between in normal operation Connection for EPI-Bus (other indication and operating devices) 2 freely programmable and labelable buttons 2 freely programmable and labelable 3 colour LEDs 5 status lists (alarms, faults, disablements, etc.) Status indication on the first line of the display Zone operation (e.g. disable zone 1-10) Group operation (e.g. simultaneously disable all detector zones) individual user management with password and user level every change of user is logged in the event log memory Operating voltage: 10 to 30 V Quiescent current: 20 mA Data transmission: MMI-BUS Electrical: galvanically isolated RS 485 Protocol: serial, DIN 19244-3 Distance to subcontrol unit: max. 1200 m Protection class: IP 30 Ambient temperature: 0 to +50C Dimensions without printer: 230 x 445 x 35 mm (HxWxD) Dimensions with printer: 360 x 445 x 45 mm (HxWxD) Case colour: red RAL 3000
Description Type Art. No.

B5-MMI-CIP-RU No.: FG052206

B5-MMI-CPP-RU No.: FG052306

B5-MMI-CII-RU No.: FG91606A9

External operating panel MAP German External operating panel MAP Englisch External operating panel MAP Russian External operating panel MAP with printer German External operating panel MAP with printer English External operating panel MAP with printer Russian Ext. operating panel MAP without case German Ext. operating panel MAP without case English External operating panel MAP without case Russian

B5-MMI-CIP-DE B5-MMI-CIP-EN B5-MMI-CIP-RU B5-MMI-CPP-DE B5-MMI-CPP-EN B5-MMI-CPP-RU B5-MMI-CII-DE B5-MMI-CII-EN B5-MMI-CII-RU

FG052200 FG052201 FG052206-FG052300 FG052301 FG052306 FG91600A9 FG91601A9 FG91606A9

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

41

External indicator & operating panels Accessories & replacement parts

B5-MMI-HCIP No.: FG052500

High end operating panels B5-MMI-HCIP and B5-MMI-HCPP External operating panel with VGA colour display and multi-function keys for centralised operation and indication of a fire alarm control panel or an entire SecoNET fire alarm network, in accordance with EN 54-2 and EN 544 as well as NORM F 3000. Available with or without log printer in many language versions (key labelling and indicator display). Listed below is the German and language versions, and other languages are available on request. The high-end operating panel can only by connected to Integral CX control panels from version 7.1 onwards of the Integral software. Operating voltage: Quiescent current: Data transmission: Electrical: Protocol: Distance to subcontrol unit: Protection class: Ambient temperature: Dimensions without printer: Dimensions with printer: Case colour:
Description

B5-MMI-HCPP No.: FG052501

10 to 30 V 97 mA MMI-BUS galvanically isolated RS 485 serial, DIN 19244-3 max. 1200 m IP 30 0 to +50C 230 x 445 x 35 mm (HxWxD) 360 x 445 x 45 mm (HxWxD) red RAL 3000
Type Art. No.

High-end operating panel without printer High-end operating panel with printer Inscription Label Russian

B5-MMI-HCIP B5-MMI-HCPP B5-MMI-HCS-RUS

FG052500 FG052501 FG27506---

B3-MMI-IPEL No.: FG050250

External LED indicator panel for 8 extinguishing zones External LED indicator panel for eight extinguishing zones (twelve LEDs per extinguishing zone and group indicator with nine LEDs), including case, key switch and controller module. The labelling uses push-in strips (not supplied) with the device also available without a case for fitting in switching cabinets. Operating voltage: Quiescent current: Data transmission: Electrical: Protocol: Distance to subcontrol unit: Protection class: Ambient temperature: Dimensions: Case colour:
Description

10 to 30 V 2 mA per lit LED MMI-BUS galvanically isolated RS 485 serial, DIN 19244-3 max. 1200 m IP 30 0 to +50C 228 x 445 x 48 mm (HxWxD) red RAL 3000
Type Art. No.

External LED indicator panel for 8 exting. zones External LED indicator panel for 8 exting. zones without case

B3-MMI-IPEL B3-MMI-IPES BFE

FG050250 FG81620

42

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

External indicator & operating panels Accessories & replacement parts

External LED indicator panel for 64 detector zones LED indicator panel for indication of alarm, fault and disablement states for 64 detector zones. The labelling uses push-in strips (not supplied) with the device also available without a case for fitting in switching cabinets.
B3-MMI-EAT64 No.: FG050251

Operating voltage: Quiescent current: Data transmission: Electrical: Protocol: Distance to subcontrol unit: Protection class: Ambient temperature: Dimensions: Case colour:
Description

10 to 30 V 2 mA per lit LED MMI-BUS galvanically isolated RS 485 serial, DIN 19244-3 max. 1200 m IP 30 0 to +50C 228 x 445 x 48 mm (HxWxD) red RAL 3000
Type Art. No.

External LED indicator panel for 64 detector zones External LED indicator panel for 64 detector zones without case

B3-MMI-EAT64 B3-MMI-EAT64 BFE

FG050251 FG81623

Fire Brigade Panel B3-MMI-FPA Fire Brigade Control Panel conforming to NORM F 3031, including LCD display, case and controller module with keys and LEDs. For visually displaying the more important operating states of fire alarm control panels for simple and uniform operation of a fire alarm system by fire brigade members.
B3-MMI-FPA No.: FG050400

Operating voltage: Quiescent current: Data transmission: Electrical: Protocol: Distance to subcontrol unit: Protection class: Ambient temperature: Dimensions: Case colour:
Description

10 to 30 V 14 mA MMI-BUS galvanically isolated RS 485 serial, DIN 19244-3 max. 1200 m IP 30 0 to +50C 300 x 200 x 55 mm (HxWxD) red RAL 3000
Type Art. No.

Fire birigade panel B3-MMI-FPA Metal key

B3-MMI-FPA DKM SCHL

FG050400 FG020015

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

43

External indicator & operating panels Accessories & replacement parts

B3-MMI-FAT No.: FG050403

Fire brigade display panel B3-MMI-FAT Indicator panel conforming to the requirements of DIN 14662, including an LCD display, case and controller module with keys and LEDs. Visually displays the more important operating states of fire alarm control panels to ensure simple and uniform operation of a fire alarm system by fire brigade members. A fire brigade control panel in accordance with DIN 14661 can also be connected to the fire brigade display panel. Operating voltage: Quiescent current: Data transmission: Electrical: Protocol: Distance to subcontrol unit: Protection class: Ambient temperature: Dimensions: Dimensions without case: Case colour: VdS-Approval:
Description

22 to 30 V 21 mA MMI-BUS galvanically isolated RS 485 serial, DIN 19244-3 max. 1200 m IP 30 0 to +50C 185 x 255 x 65 mm (HxWxD) 180 x 240 x 40 mm (HxWxD) grey RAL 7032 G206116
Type Art. No.

B3-MMI-FAT Fire brigade display panel B3-MMI-FAT Fire brigade display panel without case

B3-MMI-FAT B3-MMI-FAT-BFE

FG050403 FG050405

44

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

External indicator & operating panels Accessories & replacement parts

B3-MMI-UIO No.: EG072827

UIO GEH No.: FG69041

UIO KAB 34 No.: FG81725

B3-MMI-UIO Universal Input/Output Module For controlling the floor plan and parallel display panels or as a remotely located input/output module for querying potential-free contacts (sprinkler systems), or also for controlling non-monitored horns, lamps, relays etc. The module is either built directly in to the relevant panel or in branch cases. The system connection is via the MMI-BUS. Operating voltage: 10 to 30 V Current consumption: 14 mA Data transmission: MMI-BUS Electrical: galvanically isolated RS 485 Protocol: serial, DIN 19244-3 Distance to subcontrol unit: max. 1200 m Connection: Floor plan panels, parallel indicator panels, flashing lights, sirens, horns, sprinkler systems, etc. Connection information: 64 LED outputs 2 mA max. 256 LED outputs / control panel 8 open collector outputs up to max.100 mA output voltage max. +30 V 8 inputs with 8 outputs can be interconnected as an 8 x 8 matrix input voltage +5 V input current max. 3.3 mA Ambient temperature: 0 to +50C Dimensions: 160 x 105 x 20 mm VdS-Approval: G200116 CPD-Certificate: 0786-CPD-20422 Plastic case and steel mounting board for B3-MMI-UIO For fitting the module B3-MMI-UIO. The UIO STP steel mounting board consists of a zinc-plated sheet steel with 5 insertion pins and is used to secure the B3-MMI-UIO module into the plastic case. Protection class: IP 66 flame resistant Ambient temperature: up to +70C Case: impact-resistant plastic (polystyrol) Case colour: grey RAL 7035 Case Dimensions: 182 x 180 x 90 mm (HxWxD) Dimensions steel mounting board: 150 x 173 x 1,5 mm
Description Type Art. No.

UIO KAB 40 No.: FG81726

Universal Input/Output Module Plastic case for B3-MMI-UIO Steel mounting plate for B3-MMI-UIO 34 pole ribbon cable (1 m) for B3-MMI-UIO 40 pole ribbon cable (1 m) for B3-MMI-UIO Diode terminal block f. UIO 34 pole UIO connection module 40 pole UIO connection module

B3-MMI-UIO UIO GEH UIO STP UIO KAB 34 UIO KAB 40 DK 20 UM 45-FLK 34 UM 45-FLK 40

EG072827 FG69041 FG05203 FG81725 FG81726 FG020980 FG020981 FG020982

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

45

Management system SecoLOG Accessories & replacement parts

5 Management system SecoLOG


The SecoLOG fire alarm management system is a multi-location graphical control system which is used to monitor the state of and operate Schrack Seconet fire alarm systems from a central location. All messages and states of attached fire alarm control panels are displayed using a clear graphical user interface. The system is operated using a mouse and keyboard. SecoLOG was developed in Austria and has been tested and approved in accordance with applicable Austrian Standard NORM F 3003 (fire alarm control systems).

Features
Simple standardised operation of fire alarm systems using messages and commands (controlling fire alarm systems and fire alarm devices) Maximum reliability For use with one or several work stations, modular extension Compatible with all Schrack fire alarm systems Clear 2 monitor user interface with automatic switchover in the event of a fault High performance graphic representation with dynamic zoom function Hierarchical password system with individually assigned access privileges and passwords The user interface language can be changed whilst the system is still online Alarm print out, messages and reaction texts can be individually configured Automatic backup of data providing an online backup All connected fire alarm systems and wiring is monitored Continuous logging - with note and reports functions Events can be displayed and the system operated either using symbols or text fields in the building floor plan Fastest print out times for graphical representations of the alarm and reaction texts Floor plans for reaction diagrams can be imported from all current graphics and CAD programs Data can be received from detectors to allow automatic positioning and level assignment (autoconfiguration) Configurable processes and control processes can be triggered manually or automatically Tested and approved in accordance with Austrian Standard NORM F 3003

System Requirements
PC with either an AMD or Intel Pentium Processor (min. processor speed 1.5GHz) and 256 MB RAM (512 MB recommended) 2 mirrored hard drives, each with at least 2 GB Microsoft Windows 2000/XP operating system Hard disk controller for RAID 1 operation (mirroring) 10/100 Mbit network adapter Dual output graphics card with at least 32 MB RAM (minimum resolution 2560 x 1024) 2 serial COM interfaces and 2 USB interfaces 40 speed CD ROM drive Mouse and keyboard Sound card and speakers 2 colour monitors Professional colour printer

46

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Management system SecoLOG SecoLOG software packs

5.1

SecoLOG software packs


SecoLOG Software licence - Entry Level Version for connecting, displaying and controlling up to 2500 elements on the attached Schrack fire alarm control panel (e.g. detectors, controller devices etc.), including a CD containing the system software and dongle, as well as basic configuration for the control computer. SecoLOG Softwarelizenz Erweiterung Erweiterung der SecoLOG Grundpaket Softwarelizenz um 1.000 Elemente.
SECOLOG GP No.: FG022000-A

SecoLOG Network license Each license is for a single workstation in multiple workstation-capable SecoLOG systems. SecoLOG Software licence - Entry Level 1000 for connecting, displaying and controlling up to 1000 elements on the attached Schrack fire alarm control panel (e.g. detectors, controller devices etc.), including a CD containing the system software and dongle, as well as basic configuration for the control computer. SecoLOG Software licence Expansion Pack 1000 Expansion pack for the SecoLOG entry level 1000 software license to expand it to control up to 2,500 elements.
Description Type Art. No.

SecoLOG Software licence - entry level version SecoLOG Software licence - expansion SecoLOG Network license SecoLOG Software licence - entry level 1000 SecoLOG Software licence - expansion pack SecoLOG Demo version SecoLOG Dongle for demo version

SECOLOG GP SECOLOG SW EP1 SECOLOG NWG SECOLOG GP 1000 SECOLOG SW EP1000 SECOLOG DEMO SECOLOG DEMODON

FG022000-A FG022001 FG022010 FG022007-A FG022008-A FG022004-FG022005--

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

47

Management system SecoLOG SecoLOG components & accessories

5.2

SecoLOG components & accessories


SecoLOG Control System Computer PC including operating system, suitable for SecoLOG operation. Information about current system specifications is available on request. SecoLOG Flat panel monitor Active TFT matrix monitor (resolution of at least 1280 x 1024 pixels), suitable for use in two monitor operating mode with SecoLOG. SecoLOG Modem V.92 analogue modem (bidirectional 56K6) for operating SecoLOG remote diagnostics. The device conforms to telephony standards in Austria. SecoLOG ISDN Adapter ISDN adapter for SecoLOG remote diagnostics. The device conforms to telephony standards in Austria. SecoLOG emergency power supply To ensure the integrity of a SecoLOG workstation in the event of a shortterm power failure (for at least 5 minutes). SecoLOG PC Cable RS 232/USI Connection cable (15 m) for directly connecting the SecoLOG control system computer to B3-USI4 or B4-USI modules via the RS 232 interface. SecoLOG Printer Professional colour printer corresponding to SecoLOG's current specification as well as the current state of the art. The printer can print at least 12 pages of A4 per minute, with the alarm printout (pursuant to NORM F 3003) being printed with 60 seconds. Details about the current system specifications are available upon request. SecoLOG Printer Cable Connection cable for connecting the printer to the SecoLOG control system computer.
Description Type Art. No.

SecoLOG Control System Computer SecoLOG Flat panel monitor Analogue modem USB V.92 modem ISDN Modem USB V2.1 ISDN controller SecoLOG emergency power supply SecoLOG PC cable RS 232/USI SecoLOG Printer USB printer cable (3m) USB printer cable (4.5m)

SECOLOG ELR SECOLOG BS19 SECOLOG PD KAB SECOLOG USB-ISDN SECOLOG EPS SECOLOG PC KAB SECOLOG EDR KAB USB 3 KAB USB 45

FG022040-G FG022042 FG022055 FG022056 FG022046 FG022047-B FG022048 FG022051-FG022052--

48

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE Automatic detectors & bases

6 Integral X-LINE
6.1 Automatic detectors & bases
Multiple Sensor Detector MTD 533X The MTD 533X multiple sensor detector can be used as a smoke detector, as a heat detector or as a combined smoke/heat detector upon demand and is programmed and setup specifically for the environmental conditions that it is part of. It detects smouldering and open fires at an early stage by being able to detect and evaluate the characteristics of fire and smoke (Tyndall principle) as well as heat (NTC sensor principle). The sensitivity of the detector can be adjusted using software within the scope of EN 54. The detector provides an integrated short circuit isolator that, in case of a short circuit on the loop, enables the isolation of the faulty element while maintaining the operation of all other detectors. A dynamic alarm filter is used to detect and filter out deceptive alarms, furthermore a pre-alarm can be evaluated and forwarded to the control panel, if required. To compensate changing environmental influences, the detector adjusts itself at periodic intervals to its surroundings. For planning and installation, the country-specific guidelines for planning and installation of automatic fire alarm systems apply. It could be possible, that additional guidelines and regulations for combined fire detectors must be taken into account, if continuously or temporarily one of the detection principles is switched off. For use in areas where there are difficult environmental conditions, the MTD 533X CP version is available, which has improved protection against increased air humidity. It is shipped including a protective dust cap. Fire alarm triggered by smoke, heat or smoke and heat Smoke sensor with CUBUS levelling for automatic adaptation to environmental conditions without time-consuming setting of parameters Sensitivity for smoke and heat class can be set acc. to EN 54 temperature-based smoke evaluation Pre-alarm evaluation at 30% and at 75% of the alarm threshold level 2 level contamination detection Integrated short circuit isolator Adjustment of alarm thresholds to compensate for environmental influences Alarm filter for reducing the number of deceptive alarms Alarm output for external indication of alarms Operating time / contamination level values can be read out Operating voltage: 12 to 30 VDC Quiescent current: 120 A typ Alarm output: 3 levels programmable 0,1 mA/1 mA/5 mA Alarm-LED active: 1,6 mA Alarm current: min. 0,5 mA, max. 10 mA Output current: programmable X-LINE: 5V Loop technology: 6,3 V Detector base: USB 501-x Principle of function: Combined smoke/heat detector (Tyndall effect and/or NTC sensor) Signal transmission: serial biphase data transmission, 2-wire -technology
Product catalogue fire alarm systems 2011 V 2.0

MTD 533X No.:30-5000003-01-01

RAL colours available upon request

B-HB-008EN

49

Integral X-LINE Automatic detectors & bases

Sensitivity: Protection class: Ambient temperature: Rel. humidity: at 34 C: at > 34 C: Permissible air speed: Dimensions with base: Case colour: Case material: Weight: VdS-Approval: CPD-Certificate:
Description

smoke acc. to EN 54-7 heat acc. to EN 54-5; (classes A1, A2 and B (Index S and R) IP 44 (with base USB 501-1) -25 to +60C permanent, without condensation: 10 ... 95 % rel/F max. 35 g/m max. 20 m/s 118 x 67,5 mm (DxH) electric white (similar to RAL 9016) other RAL colours available upon request ABS / PC 125 g G210115 0786-CPD-20993
Type Art. No.

MTD 533X Multiple Sensor Detector MTD 533X CP Multiple Sensor Detector Grey ring stickers (20 pcs.) Dust protection cap for USB 533

MTD 533X MTD 533X CP S GR DDC 533

30-5000003-01-01 30-5000003-51-01 FG28422 FG030398

50

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE Automatic detectors & bases

USB 501-1 No.: FG030126

USB 501-6 No.: FG030700

KL USB501 No.: FG030132

Detector bases USB 501-1 and USB 501-6 For connecting automatic fire detectors to the Integral X-LINE, set up for surface mounting with a built-in 6 pole terminal block An additional 4 pin terminal block can be fitted in the designated snap-fit holder to form additional isolation points. The detector is attached by means of a bayonet fitting. When using the USB 501-1, the installation can be checked easily even when detectors are not used, using an integrated automatic circuit closing mechanism built into the terminal block, while the USB501-6 does not possess such a circuit closing mechanism, with the loop circuit only being closed when the detector is inserted. Area for deployment: dry and wet rooms Installation type: Surface mounting Connection: screw-type terminals, max. 2 x 1.5 mm Protection class: IP 44 Ambient temperature: -20 to +70C Rel. air humidity: briefly without condensation 95% rel/F permanent without condensation 70%rel/F Dimensions: 118 x 28 mm (DxH) Case colour: electrical white (all RAL colours upon request) Case material: ABS / PC, FR90 Weight: 65 g VdS-Approval: G204106 CPD-Certificate: 0786-CPD-20246
Description Type Art. No.

Detector base USB 501-1 Detector base USB 501-1 SW (black, RAL 9005) Detector base USB 501-1 MC (all RAL colours) USB 501-6 detector base without base contact Detector base USB 501-6 SW (black, RAL 9005) Detector base USB 501-6 MC (all RAL colours) Isolation point terminal block for USB 501-x

USB 501-1 USB 501-1 SW USB 501-1 MC USB 501-6 USB 501-6 SW USB 501-6 MC KL USB501

FG030126 FG030164 upon request FG030700 FG030701 upon request FG030132

USB 501-2 No.: FG030135

Countersunk base for fitting in cavity ceilings USB 501-2 For connecting automatic fire detectors to the Integral X-LINE, suitable for installation in standard cavity ceilings, consisting of standard base USB 5011, fitting ring with fastening clips, collar and bezel ring. Apertures and predetermined breaking points are present in the fitting ring for feeding in the cable, while the bezel ring is fitted together with the detector. Area for deployment: dry rooms, cavity ceiling installation Connection: screw-type terminals, max. 2 x 1.5 mm Protection class: IP 44 Ambient temperature: -20 to +70C Rel. air humidity: briefly without condensation 95% rel/F permanent without condensation 70%rel/F Dimensions: 158 x 52,5 mm (DxH) Colour of bezel ring: white Case material: ABS / PC, FR90 Weight: 100 g VdS-Approval: G204106 CPD-Certificate: 0786-CPD-20246
Description Type Art. No.

USB 501-2 detector base for cavity ceilings Isolation point terminal block for USB 501-x

USB 501-2 KL USB501

FG030135 FG030132

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

51

Integral X-LINE Automatic detectors & bases

USB 501-3 No.: FG030136

Detector base for use in wet rooms USB 501-3 For connecting automatic detectors to the Integral X-LINE, consisting of a fitting case with 4 cable inlets, USB 501-1 standard base, and a sealing ring made of closed cell rubber. Taking into consideration the environmental conditions that are permissible for the detector to be used, it can be used in wet rooms, or anywhere where the installation process requires the use of thick cabling. The cable is fed in through the installation case, with the detector base only being attached to the case after cable has been fed in, using the screws supplied. A 6 pole terminal block is used for connecting the fire alarm cabling, and an additional 4 pole terminal block can be clipped into the dedicated snap-fit holder, if required, to form additional isolation points. The sealing ring is inserted between the detector and the USB 501-3 base. Area of deployment: wet rooms Installation type: Surface mounting Connection: screw-type terminals, max. 2 x 1.5 mm Protection class: IP 54 Ambient temperature: -20 to +70C Rel. air humidity: briefly without condensation 95% rel/F permanent without condensation 70%rel/F Dimensions: 123 x 53 mm (DxH) Case colour: white Case material: ABS / PC, FR90 Weight: 200 g VdS-Approval: G204106 CPD-Certificate: 0786-CPD-20246
Description Type Art. No.

Detector base USB 501-3 for use in wet rooms Isolation point terminal block for USB 501-x

USB 501-3 KL USB501

FG030136 FG030132

52

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE Automatic detectors & bases

LKM 531 No.: FG030191

Ventilation duct detector LKM 531 For use in places where there is a high airspeed and strong smoke dispersal e.g. air conditioning and ventilation ducts. The LKM 531 comprises of a plastic case with a built-in SSD 531K smoke detector and is equipped for use in ventilation ducts between 15cm and 1m in size and in circular ducts with a diameter of 20cm to 1m. It can be deployed in areas where the air speed is between 1 to 20 m/s. The case has a clever cover, so that the smoke detectors alarm LED can be seen externally. The detector, detector base, as well as all stopped and sealers are supplied with the unit as standard. Operating voltage: 15 to 30 V DC Current consumption: 190 A Areas for use: ventilation ducts oblong ventilation duct: lengths of sides from 15 cm to 1 m circular ventilation ducts: diameter 20 cm to 1 m Dimensions without pipe: 100 x 250 x 135 mm (HxWxD) Ventilation pipe length: 140 to 345 mm Apertures for fittings: for inlet/outlet pipe: 2 x 28-30 mm / 150 mm distance for fastening the case: 2 x max. 6 mm / 206 mm distance Cable entry points: 4 x 6-10 mm Colour: blue / transparent Material: PC / anodised aluminium pipe Suitable for detector type: SSD 531K Airflow speed: 1 to 20 m/s Protection class: IP 54 Weight: without pipe: ca. 392 g with pipe: ca. 485 g VdS-Approval: G206086 Optical Smoke Detector SSD 531K for LKM 531 Only for use in LKM 531 ventilation duct detector. The SSD 531K is shipped as standard with the LKM 531, the order number is listed only for ordering replacement parts. Operating voltage: 15 to 30 VDC Quiescent current: 250 A max. Alarm current: 20 mA max. Usable detector bases: USB 501-1 in LKM 531 Functional Principle: Scattered light (Tyndall effect) Signal transmission: serial, 2 wire technology Protection class: IP 54 in LKM 531 Ambient temperature: -20 to +60C Sensitivity: 0,14 dB/m (EN 54-7) Dimensions: 118 x 67,5 mm (DxH) Case colour: pure white with blue ring Case material: ABS / PC, FR90 Weight: 105 g VdS-Approval: G206086
Description Type Art. No.

SSD 531K No.: FG030189

LKM 531 ventilation duct detector SSD 531K optical smoke detector

LKM 531 SSD 531K

FG030191 FG030189

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

53

Integral X-LINE Manual call points

6.2

Manual call points


Manual call point MCP 535X-1 For manually triggering a fire alarm, suitable for connection to the Integral X-LINE with integrated short circuit isolator. The alarm is triggered by smashing the glass panel and pressing the button. The push button remains locked, and the actuated state is indicated by means of the built-in LED. The protection class can be increased to IP 54 by using a sealing rubber, the blue version can be labelled using stickers. Operating voltage: 7 to 31 VDC Quiescent current: max. 120 A typ. 90 A Alarm current: 20 mA max. Functional Principle: manual call point type B acc. to EN 54-11 Signal transmission: serial, 2 wire technology Connection: screw clips, maximum 1.5 mm Protection class: IP 52 (IP 54 with sealing rubber) Ambient temperature: -20 to +50C Dimensions: 134 x 134 x 36 mm Case: red plastic (RAL 3001) blue plastic (RAL 5005) Weight: 450 g VdS-Approval: G210095 CPD-Certificate: 0786-CPD-20988 Manual triggering device MCP 535X-5 For manually triggering an extinguishing operation using gas extinguishing agents conformant to EN 12094-3. The gas extinguishing system is triggered by smashing the glass panel and pressing the button. The push button remains locked, and the actuated state is indicated by means of the built-in LED. The detector is suitable for connection to the Integral X-LINE and contains an integrated short circuit isolator. Labelling is done using stickers. Operating voltage: 7 to 31 VDC Quiescent current: max. 120 A typ. 90 A Alarm current: 20 mA max. Functional Principle: Electrical triggering device (EN 12094-3) Signal transmission: serial, 2 wire technology Connection: screw clips, maximum 1.5 mm Protection class: IP 52 Ambient temperature: -20 to +50C Dimensions: 134 x 134 x 36 mm Case colours: yellow plastic (RAL 1003) Weight: 450 g VdS-Approval: G210096 CPD-Certificate: 0786-CPD-20989
Description Type Art. No.

MCP 535X-1 No.: 30-5700007-01-01

MCP 535X-3 No.: 30-5700007-03-01

MCP 535X-5 No.: 30-5700007-05-01

MCP 535 red IP 52 manual call point MCP 535 blue IP 52 manual call point MCP 535 yellow IP 52 manual call point Hand symbol sticker for MCP535 Labelling strip for MCP 535 Replacement glass panel for MCP 535 Key for MCP 535 Sealing rubber for MCP 535

MCP535X-1 MCP535X-3 MCP535X-5 MCP535 AK MCP535 BGD MCP535 GLAS DKM SCHL MCP535 DG

30-5700007-01-01 30-5700007-03-01 30-5700007-05-01 FG030230 FG030232 FG030231 FG020015 30-4100001-01

54

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE Manual call points

MCP 535X-7 No.: 30-5700007-07-01

Stop device MCP 535X-7 To manually interrupt the triggering of an extinguishing process using gasbased extinguishing agents during the pre-warning period. Triggering then occurs indirectly, i.e. after the glass panel has been smashed, the control element must be pushed in order to interrupt the triggering of the extinguishing operation. The control element does not lock. The detector is suitable for connection to the Integral X-LINE and contains an integrated short circuit isolator. Labelling is done using stickers. Operating voltage: Quiescent current: Alarm current: Functional Principle: Signal transmission: Connection: Protection class: Ambient temperature: Dimensions: Case colour: Weight: VdS-Approval: CPD-Certificate:
Description

7 to 31 VDC max. 120 A typ. 90 A max. 2,5 mA max. 20mA backup-alarm Electrical stop device (EN 12094-3) serial, 2 wire technology screw clips, maximum 1.5 mm IP 54 -20 to +50C 134 x 134 x 36 mm blue plastic (RAL 5005) 450 g G210097 0786-CPD-20990
Type Art. No.

MCP 535 Stop device Hand symbol sticker for MCP535 Replacement glass panel for MCP 535 Key for MCP 535 Sealing rubber for MCP 535 Labelling strip for MCP 535

MCP535X-7 MCP535 AK MCP535 GLAS DKM SCHL MCP535 DG MCP535 BGD

30-5700007-07-01 FG030230 FG030231 FG020015 30-4100001-01 FG030232

Weather resistant case for MCP 535X To further protect MCP 535X series manual call points from water ingress on the top or back side when used in difficult environmental conditions (outdoors). The weather resistant case has four drill holes on it to allow it to be screwed in with manual call points.
MCP WSG No.: FG030235

Material: Dimensions: Colour:


Description

1 mm sheet steel 160 x 184 x 100 mm (HxWxD) red RAL 3000 (painted)
Type Art. No.

Weather resistant case for MCP 535

MCP WSG

FG030235

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

55

Integral X-LINE Manual call points

MCP545X-1R No.: FG030900

MCP545X-2R No.: FG030901

Manual call point MCP 545X For manually triggering a fire alarm, suitable for connection to the Integral X-LINE. The three different versions differ merely in terms of their case construction and IP protection class. The electronics, connection and how they function is identical for all types. The detectors contain a short circuit isolator and a red alarm LED. The alarm is triggered by pushing in the glass panel or by pressing the plastic panel. The alarm remains triggered until a new glass panel is fitted or the plastic panel is reset. A testing key is used to check that it works properly. The MCP 545X-1 is suitable for use indoors and is surface mounted. The case is fixed to the wall using two screws, whilst the points for attaching the key section must be horizontal. Cable inlets required for surface mounting must be drilled into the case as required. The MCP 545X-2 is suitable for use indoors and is fitted straight into a standard size 1 (round or square) countersunk mounting case. The MCP 545X-3 is also suitable for use outdoors and is for surface mounting. The detector has IP 67 protection class (waterproof); with the cables being fed in from above or below using an M20 cable gland. 2 pcs. M 20 connection joints and 2 pcs. blanking stoppers, as well as the fitting screws are supplied as standard. Operating voltage: Quiescent current: Alarm current: Screw connections: Signal transmission: Protection class Ambient temperature: Case colour: Case material: Weight MCP 545X-1/-2/3: Approval: 7 to 31 VDC 120 A at 30 VDC 4 mA max. 2,5 mm serial, 2 wire technology MCP 545X-1/2: IP 24 MCP 545X-3: IP 67 -20 to +50C red, RAL 3001, yellow RAL 1006, blue RAL 5002 Fibreglass reinforced plastic 160g / 110g / 240g LPC, CE, EN 54-11, EN 54-17

MCP545X-3R No.: FG030902

PS200 No.: FG030921 Description Type Art. No.

Manual call point MCP545X-1R red IP 24 Manual call point MCP545X-2R red IP 24 Manual call point MCP545X-3R red IP 67 Manual call point MCP545X-1Y yellow IP 24 Manual call point MCP545X-2Y yellow IP 24 Manual call point MCP545X-3Y yellow IP 67 Manual call point MCP545X-1B blue IP 24 Manual call point MCP545X-2B blue IP 24 Manual call point MCP545X-3B blue IP 67 Back panel for surface mounting Transparent cover Cover seal Plastic triggering element Replacement glass panel for MCP 545A/MCP1A Replacement test key

MCP545X-1R MCP545X-2R MCP545X-3R MCP545X-1Y MCP545X-2Y MCP545X-3Y MCP545X-1B MCP545X-2B MCP545X-3B MUS041W PS200 P 037 PS210 DKM K GLAS SC070

FG030930-FG030931-FG030932-FG030933-FG030934-FG030935-FG030936-FG030937-FG030938-FG030332 FG030921 FG030331 FG030920 FG030328 FG030329

56

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE Manual call points

C31 No.: FG020286

Manual call point with C31 with IP66 protection class Non-automatic detector for use outdoors or in damps rooms (Type B according to EN 54-11). The manual call point contains a 560 ohm integrated resistor, however, both terminating resistors the 19k1 for connection to the BX-AIM loop circuit module or the 11k8 for connection to the B3-DCI are not supplied as standard. Built into a robust plastic case protected from dust and water, suitable for surface mounting and countersunk mounting. The detector is available with or without an LED alarm indicator. Operating voltage: Operating current: Connection: Cable entry points: Protection class: Ambient temperature: Dimensions: Colour: Material: Weight: VdS-Approval: CPD-Certificate:
Description

up to max. 30 VDC 55 mA screw-type terminals, 0.08 to 2.5 mm 2 x M20 x 1,5; diameter: 6 - 12 mm IP 66 -35 to +60C 135 x 135 x 61 mm (HxWxD) red RAL 3000 PC 475 g G206113 0786-CPD-20309
Type Art. No.

Manual call point C31 Manual call point C31 with LED Replacement glass panel Key

C31 C31 LED C31 GV DKM SV

FG020285 FG020286 FG020282 FG020289

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

57

Integral X-LINE X-LINE modules

6.3

X-LINE modules
BX-OI3 Input/output module Contains a relay output with a programmable fail-safe position, two inputs for monitored querying of potential-free contacts and an optocoupler input which can be used, if required, for monitoring external voltages. In addition, the voltage on the loop circuit is internally monitored for undervoltage. The BX-OI3 is particularly well-suited for connecting special detectors (flame and line detectors, smoke aspirating systems etc.) using the Integral X-LINE. Both the addressing of the module and the setting of parameters for connected special detectors (e.g. how they behave when there is an alarm or a fault) is carried out via the fire alarm control panel using PC software. An IP 66 protection class plastic case is used for fitting the module, which can be fitted with various different cable inlets as required. Shipped including 4 180 Ohm resistors for the monitored inputs. Operating voltage: Power consumption: Signal transmission: Relay output: Monitored inputs: Optocoupler input: Connection: Short circuit isolator: Protection class: Ambient temperature: Rel. air humidity: Dimensions: Case: Colour: VdS-Approval: CPD-Certificate:
Description

BX-OI3 No.: 20-2100001-01-02

12 to 30 VDC typ. 550 A serial, 2 wire technology bistable change-over contact 230 V/2 A, (max. 60 W) for potential-free contacts Querying of potentially-bound signals, or external voltages from 0 to 30 VDC screw clips, maximum 1.5 mm integrated IP 66 with case -20 to +60C 5 to 95% without condensation 67 x 67 x 20 mm with case: 94 x 94 x 57 mm Polystyrol, halogen-free grey (RAL 7035) G210133 0786-CPD-21011
Type Art. No.

BX-OI3 Input/output module IP66 case for loop module Extension connection joint M 16 Stepped nipple M 20 Lock nut M16

BX-OI3 GEH MOD IP66 MM ANB M16 MM SN M20 MM GM M16

20-2100001-01-02 FG020234 MM000185 MM000181 MM000186

58

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE X-LINE modules

BX-AIM No.: 20-2100005-01-01

BX-AIM Input module Can be configured as a monitored input for querying potential-free contacts or as a collectively addressable detector zone (DC technology). The monitored input can, if required, be used as a standard extinguishing interface in accordance with VdS directives, and furthermore a balancing function of the fault thresholds for the quiescent current level is also possible (pursuant to EN 54-13 or VdS 2489). By interconnecting a Zener barrier and by using intrinsically safe detectors it is also possible to monitor hazardous areas. An IP 66 protection class plastic case is used for fitting the module, which can be fitted with various different cable inlets as required. Supplied including an alarm resistor (560 Ohm) and a terminating resistor (19k1). Operating voltage: Power consumption: Signal transmission: Function: Connection: Short circuit isolator: Protection class: Ambient temperature: Rel. air humidity: Dimensions: Case: VdS-Approval: CPD-Certificate:
Description

10 to 29 VDC (from the loop circuit) without DC branch: Type 460 A with DC branch: Type. 1800 A serial, 2 wire technology DC branch module, monitored input screw clips, maximum 1.5 mm integrated IP 66 with case -20 to +60C 5 to 95%, without condensation 67 x 67 x 20 mm with case: 94 x 94 x 57 mm Polystyrol, halogen-free, grey RAL7035 G208138 0786-CPD-20601
Type Art. No.

BX-AIM input module IP66 case for loop module Extension connection joint M 16 Stepped nipple M 20 Lock nut M16

BX-AIM GEH MOD IP66 MM ANB M16 MM SN M20 MM GM M16

20-2100005-01-01 FG020234 MM000185 MM000181 MM000186

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

59

Integral X-LINE X-LINE modules

BX-IOM No.: 20-2100002-01-01

BX-IOM Input/output module For controlling monitored devices, which are supplied with power by an external power supply (e.g. sirens etc.). The module contains a short circuit resistant monitored output (suitable for continuous operation of fur a configurable pulse emission with emission time limitation) and a galvanically isolated input which can be used either as a voltage input or for external voltage monitoring. In addition, the voltage on the loop circuit is internally monitored for undervoltage. Both the addressing of the module and the setting of its parameters, which are set separately for every input, are carried out using PC software via the fire alarm control panel. An IP 66 protection class plastic case is used for fitting the module, which can be fitted with various different cable inlets as required. Operating voltage: Power consumption: Signal transmission: Function: Connection: Monitored output: Output current: Quiescent current: Optokoppler input: Short circuit isolator: Protection class: Ambient temperature: Rel. air humidity: Dimensions: Case: Colour: VdS-Approval: CPD-Certificate:
Description

12 to 30 VDC 430 A serial, 2 wire technology 1 short circuit resistant monitored output, 1 optocoupler input screw clips, maximum 1.5 mm Loads of 20 to 1k, 3 load ranges max. 1,3 A short circuit resistant 1 to 15 mA can be set using software IM1+: 20-30V VEXT: 20-30V integrated IP 66 with case -20 to +60C 5 to 95% without condensation 67 x 67 x 20 mm with case: 94 x 94 x 57 mm Polystyrol, halogen-free grey RAL 7035 G210132 0786-CPD-21010
Type Art. No.

BX-IOM Input/output module IP66 case for loop module Extension connection joint M 16 Stepped nipple M 20 Lock nut M16

BX-IOM GEH MOD IP66 MM ANB M16 MM SN M20 MM GM M16

20-2100002-01-01 FG020234 MM000185 MM000181 MM000186

60

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE X-LINE modules

BX-REL4 No.: 20-2100004-01-02

BX-REL4 Relay module Contains 4 relays each with a potential-free double-throw contact with a switching capacity of up to 2 A and up to 230 V. The BX-REL 4 is also suitable for emitting switching impulses. The relay outputs can be switched to a fail-safe position in the event of voltage loss on the loop circuit, and the voltage on the loop circuit is also internally monitored for under voltage. Both the addressing of the module and the setting of its parameters, which are set separately for every input, are carried out using PC software via the fire alarm control panel. An IP 66 protection class plastic case is used for fitting the module, which can be fitted with various different cable inlets as required. Operating voltage: Power consumption: Signal transmission: Function: Connection: Relay output connection: Length of wires: Short circuit isolator: Protection class: Ambient temperature: Rel. air humidity: Relay output: Switching power: Switching frequency: Pulse emission: Dimensions: Case: Colour: VdS-Approval: CPD-Certificate:
Description

12 to 30 VDC typ. 510 A serial, 2 wire technology 4 potential-free relay outputs screw clips, maximum 1.5 mm screw clips, maximum 2.5 mm max. 100 m integrated IP 66 with case -20 to +60C 5 to 95% without condensation bistable change-over contact 230 V/2 A 60 W (230 V, 0.25 A) max. 3.125 Hz 200 ms to 25 s in 100 ms intervals 100 x 67 x 20 mm with case: 130 x 94 x 57 mm Polystyrol, halogen-free grey RAL 7035 G210134 0786-CPD-21012
Type Art. No.

BX-REL4 Relay module Case for BX-REL4 IP66 Extension connection joint M 16 Stepped nipple M 20 Lock nut M16

BX-REL4 GEH MOD2 IP66 MM ANB M16 MM SN M20 MM GM M16

20-2100004-01-02 FG020235 MM000185 MM000181 MM000186

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

61

Integral X-LINE X-LINE modules

BX-O2I4 No.: 20-2100014-01-01

BX-O2I4 Input/output module The input/output module BX-O2I4 is suitable for the connection to Integral X-LINE. It contains two relay outputs - which are suitable to emit impulses - and four primary inputs for requesting isolated electrical contacts. If the supply voltage drops, the relay outputs can be switched into a fail-safe position. This attitude is adjustable and defined by the software. During the start-up of the loop, the BX-O2I4 independently perceives a short circuit on the X-LINE. Thereby the loop start-up time can be essential reduced, because in case of a short circuit the loop voltage doesnt drop and all other participants stay supplied. The BX-O2I4 is installed in a IP 66 protection class plastic case, which can be fitted with different cable inlets depending on requirements. A shielded cable installation is recommended, particularly in cases, where electromagnetic disturbances occur, or such could be caused periodically during working processes. The country-specific guidelines for planning and installation of automatic fire alarm systems are applicable. From the software V 7.2 the BX-O2I4 module is fully supported. Operating voltage: Power consumption: Signal transmission: Function: Connection: Function: Connection: Relay output connection: Length of wires: Short circuit isolator: Protection class: Ambient temperature: Rel. air humidity: Relay output: Switching power: Switching frequency: Pulse emission: Dimensions: Case: Colour: VdS-Approval: CPD-Certificate:
Description

12 to 30 VDC typ. 630 A serial, 2 wire technology 2 potential-free relay outputs screw clips, maximum 1.5 mm 4 inputs for monitored or non-monitored querying of potential-free contacts screw clips, maximum 1.5 mm screw clips, maximum 2.5 mm max. 100 m integrated IP 66 with case -20 to +60C 5 to 95% without condensation bistable change-over contact 230 V/2 A 60 W (230 V, 0.25 A) max. 3.125 Hz 200 ms to 25 s in 100 ms intervals 100 x 67 x 20 mm with case: 130 x 94 x 57 mm Polystyrol, halogen-free grey RAL 7035 submitted submitted
Type Art. No.

BX-O2I4 Input/output module Case for BX-REL4 IP66 Extension connection joint M 16 Stepped nipple M 20 Lock nut M16

BX-O2I4 GEH MOD2 IP66 MM ANB M16 MM SN M20 MM GM M16

20-2100014-01-01 FG020235 MM000185 MM000181 MM000186

62

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE X-LINE modules

BX-IM4 No.: 20-2100003-01-02

BX-IM4 Input module For indication and monitoring of various types of acknowledgements, e.g. door contacts, fire zones, extinguishing systems, sprinkler messages, etc. The module contains 4 inputs for monitored and non-monitoring querying of potential-free contacts, which are suitable for processing switching states of longer than 330ms. Both the addressing of the module and the setting of its parameters, which are set separately for every input, are carried out using PC software via the fire alarm control panel. An IP 66 protection class plastic case is used for fitting the module, which can be fitted with various different cable inlets as required. Operating voltage: Power consumption: Signal transmission: Function: Connection:
Short circuit isolator:

12 to 30 VDC typ. 450 A serial, 2 wire technology 4 inputs for monitored or non-monitored querying of potential-free contacts screw clips, maximum 1.5 mm
integrated

Protection class: Ambient temperature: Rel. air humidity:


Dimensions: Case: Colour:

IP 66 with case -20 to +60C 5 to 95%, without condensation


67 x 67 x 20 mm with case: 94 x 94 x 57 mm Polystyrol, halogen-free grey RAL 7035

VdS-Approval: CPD-Certificate:
Description

G210131 0786-CPD-21009
Type Art. No.

BX-IM4 Input module IP66 case for loop module Extension connection joint M 16 Stepped nipple M 20 Lock nut M16

BX-IM4 GEH MOD IP66 MM ANB M16 MM SN M20 MM GM M16

20-2100003-01-02 FG020234 MM000185 MM000181 MM000186

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

63

Integral X-LINE X-LINE modules

BX-ESL No.: 20-2100007-01-02

BX-ESL End position switch The end position module BX-ESL is suitable for the connection to Integral X-LINE and is used, for amongst other things, in the area of sprinkler monitoring and lock equipment. It contains an optical light barrier, which measure the action of an activity pusher. Therewith the function of the end position switch is realised. The BX-ESL is installed in an IP 65 protection class plastic case. Addressing and setting the parameters of the module are carried out via the central fire alarm system using PC-software. The BX-ESL contains a short circuit isolator which guarantees, that a possible failure is located and that the loop stays in unrestricted function even in case of a wire break or a short circuit. A shielded cable installation is recommended, particu- larly in cases, where electromagnetic disturbances occur, or such could be caused periodically during working processes. The country-specific guidelines for planning and installation of automatic fire alarm systems are applicable. Operating voltage: Power consumption: Signal transmission: Function: Response Time: Connection: Short circuit isolator: Protection class: Ambient temperature: Rel. air humidity: Dimensions: Case: Colour: VdS-Approval: CPD-Certificate:
Description

12 to 30 VDC without lit LED: 400 A with lit LED: 1300 A serial, 2 wire technology 1 optical light barrier 500 ms screw clips, maximum 1.5 mm integrated IP 65 with case -20 to +60C 5 to 95%, without condensation 58 x 58 x 34 mm with case PA-Taromid (Thermoplastic) case red (RAL 3016) cover black (RAL 9005) G210130 0786-CPD-21014
Type Art. No.

BX-ESL End position switch

BX-ESL

20-2100007-01-02

64

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE X-LINE modules

BX-RGW Radio gateway The radiogateway BX-RGW is suitable for connection to Integral X-LINE and serves as the communications interface between the control panel and radio-linked smoke detector DOW 1171 and SMF 6120.
BX-RGW No.: 20-2100006-01-01

Up to 30 radio-linked smoke detectors can be connected to a gateway. If the radio connection between the detector and the gateway is briefly interrupted, then a diversion via the neighbouring detector will be automatically established to the next gateway. Addressing of the module as well as setting the parameters is carried out by the control panel. The built-in battery is used for commissioning and for ensuring the power supply during revision.

SPU 6002 No.: FG030171

The BX-RGW contains a short circuit isolator which guarantees, that a possible failure is located and that the loop stays in unrestricted function even in case of a wire break or a short circuit, in addition the voltage on the loop line is internally monitored on under voltage. The BX-RGW is installed in an IP 54 protection class plastic case, with an integrated LED which displays the operating status. It can also be fitted with different cable inlets depending on requirements. A shielded cable installation is recommended, particularly in cases, where electromagnetic disturbances occur, or such could be caused periodically during working processes. The country-specific guidelines for planning and installation of automatic fire alarm systems are applicable. Operating voltage: Power consumption: Wireless module interface: Buffer battery: Frequency range: Transmission strength: No. of connectible detectors: Range in buildings: Aerial: Protection class: Ambient temperature: Rel. air humidity: Dimensions: Case: Colour: VdS-Approval: CE-Certificate:
Description

BATT FM No.: FG030173

12 to 30 VDC typ. 950 A 20 pin 2 rowed multipoint connector 9V Lithium/ Manganese (lifespan>5 years) 868 to 870 MHz max. 5 mW max. 30 up to 40 metre where there is intervisibility integrated, separate transmitter and receiver aerials IP 54 with case -10 to +55C 5 to 95% without condensation 93 x 70 x 24 mm with case: 120 x 80 x 57 mm Polystyrol, halogen-free grey RAL 7035 G210135 0786-CPD-21013
Type Art. No.

BX-RGW Radio gateway Radio module Battery for radio module Extension connection joint M 16 Stepped nipple M 20 Lock nut M16

BX-RGW SPU 6002 BATT FM MM ANB M16 MM SN M20 MM GM M16

20-2100006-01-01 FG030171 FG030173 MM000185 MM000181 MM000186

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

65

Integral X-LINE X-LINE modules

BX-SOL-R No.: 20-2100008-01-01

BX-SOL-W No.: 20-2100008-02-01

BX-SOL Loop siren The loop sounder BX-SOL is used to signal a fire alarm in interior rooms and conforms to environmental category type A according to EN 54-3. The device is available in red or white and is connected directly to Integral X-LINE by means of a 6 pin screw clip. Up to 62 BX-SOL devices can be connected to an Integral X-LINE, with the quantity being determined by the volume that has been configured, the combination of other devices as well as the cable diameter. The tone types Slow Whoop, DIN tone, Swedish Toneor permanent tone are set directly at the fire alarm control panel, even during ongoing operation, whilst the required volume can be set by using software or setting DIP switches. In particular when deployed in areas where there are EMC disturbances, or where such disturbances can occur periodically as a result of working processes, we recommend that a shielded fire alarm cable is used. Like every element of Integral X-LINE, the loop sounder BX-SOL also contains a short circuit isolator, which ensures in the event of a wire break or a short circuit that the fault is localised and that the loop circuits operation is simultaneously maintained in its entirety. The country-specific guidelines for planning and installation of automatic fire alarm systems are applicable. Operating voltage: Power consumption: Volume: Possible tones: 12 to 30 VDC 2,3 mA @ 24 VDC (volume low) 4,7 mA @ 24 VDC (volume high) 89 dB (99 dB) 3 dB(A)/m @ 24 VDC DIN 1200 ~ 500 Hz (acc. to DIN 33404) Slow Whoop 500 ~ 1200 Hz (EN 2575) Continuous tone 990 Hz (pulse can be set) Sweden-Tone (150 ms on/ 150 ms off) integrated IP 21c -10 to +55C max. 108 x 91 mm (D x H) white or red ABS 230 g G210086 0786-CPD-20986
Type Art. No.

Short circuit isolator: Protection class: Ambient temperature: Dimensions: Case colour: Case material: Weight: VdS-Approval: CPD-Certificate:
Description

BX-SOL-R Loop siren red BX-SOL-W Loop siren white

BX-SOL-R BX-SOL-W

20-2100008-01-01 20-2100008-02-01

66

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE X-LINE modules

BX-FOL-RR No.: 20-2100009-01-03

BX-FOL-WR No.: 20-2100009-02-03

BX-FOL-RR Loop flashing light The loop flashlight BX-FOL is used to optically signal a fire alarm in interior rooms and conforms to environmental category type A according to EN 54-3. The device is available in red or white with red or orange lens and is connected directly to Integral X-LINE by means of a 6 pin screw clip. Up to 23 BX-FOL devices can be connected to an Integral X-LINE, with the quantity being determined by the combination of other devices as well as the cable diameter. The required flash frequency can be set to Slow or Fast by using software or a DIP switch, with Fast being the factory setting. In particular when deployed in areas where there are EMC disturbances, or where such disturbances can occur periodically as a result of working processes, we recommend that a shielded fire alarm cable is used. Like every element of Integral X-LINE, the loop flashlight BX-FOL also contains a short circuit isolator, which ensures in the event of a wire break or a short circuit that the fault is localised and that the loop circuits operation is simultaneously maintained in its entirety. The country-specific guidelines for planning and installation of automatic fire alarm systems are applicable. Operating voltage: Alarm current: Quiescent current: Signal transmission: Flashing frequency: Short circuit isolator: Protection class: Ambient temperature: Dimensions: Case colour: Case material: Weight: VdS-Approval: CPD-Certificate:
Description

BX-FOL-RO No.: 20-2100009-03-03

BX-FOL-WO No.: 20-2100009-04-03

12 to 30 VDC max. 6,5 mA @ 24 VDC 500 A serial, 2 wire technology 0,5 Hz (slow) or 1 Hz (fast) integrated IP 21c -10 to +50C 93 x 54 mm (DxH) white or red ABS 110 g G210085 (EN 54-3, EN 54-17) 0786-CPD-20987 (EN 54-17)
Type Art. No.

BX-FOL loop flashing light red, red lens BX-FOL loop flashing light white, red lens BX-FOL loop flashing light red, orange lens BX-FOL loop flashing light white, orange lens

BX-FOL-RR BX-FOL-WR BX-FOL-RO BX-FOL-WO

20-2100009-01-03 20-2100009-02-03 20-2100009-03-03 20-2100009-04-03

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

67

Integral X-LINE X-LINE modules

BX-API No.: 20-2100010-01

Base siren BX-API For fitting in USB 501-x Integral loop technology detector base for local acoustic warnings of a fire. The BX-API snaps directly into the detector base and connects directly to its connector clips. If a detector is activated, then module BX-API is triggered as well as the alarm message being sent, with the base-mounted siren emitting an acoustic alarm signal. The volume setting (LOW or HIGH) is set by means of a DIP switch. Operating voltage: 15 to 30 VDC Power consumption: Low max. 2mA, High max. 4mA Connection: USB 501-x detector base Tone types: can be selected by dip switches: DIN 1200 ~ 500 Hz (acc. to DIN 33404) Slow Whoop 500 ~ 1200 Hz (EN 2575) Continuous tone 990 Hz (pulse can be set) Sweden-Tone (150 ms on/ 150 ms off) Volume: Low 65dB @24VDC @1m @90 High 75dB @24VDC @1m @90 Ambient temperature: +5C to +40C VdS-Approval: applied for CPD-Certificate: applied for
Description Type Art. No.

BX-API Base-siren

BX-API

20-2100010-01

BX-SBL501-W No.: 20-2100011-02-01

Base siren BX-SBL501-W For signalling a fire alarm in interior rooms (EN 54-3/type A), fitted as a unit with a USB 501 detector base and directly connected to the X-LINE. The siren is available in white, four different tone types and the volume can be set by software or by using DIP switches. The cable inlet is from above, with variant BX-SBL501-WDB with a higher base being available for a cable inlet from the side. Operating voltage: 12 to 30 VDC Quiescent current: max. 0,5 mA Power consumption: 1,5 mA @ 24 VDC (volume low) 4,0 mA @ 24 VDC (volume high) Volume: 80 dB (90 dB) 3 dB(A)/m @ 24 VDC Types of tone: DIN 1200 ~ 500 Hz (acc. to DIN 33404) Slow Whoop 500 ~ 1200 Hz (EN 2575) Continuous tone 990 Hz (pulse can be set) Sweden-Tone (150 ms on/ 150 ms off) Connection: screw clips, maximum 2.5 mm Short circuit isolator: integrated Protection class: IP 31 D Ambient temperature: -10 to +55C Dimensions: 114 x 32 mm (DxH) 114 x 36 mm (DxH) with high base Case material: PC-ABS Case colour: white RAL 9003 Weight: ca. 170 g VdS-Approval: applied for CPD-Certificate: applied for
Description Type Art. No.

Base-siren BX-SBL501 white Base-siren BX-SBL501 white high base

BX-SBL501-W BX-SBL501-WDB

20-2100011-02-01 20-2100011-01-01

68

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE X-LINE modules

BX-SBL502-W No.: 20-2100012-04-01

Platform siren BX-SBL502 For signalling a fire alarm in indoor areas (EN 54-3/ type A), suitable for direct connection to the Integral X-LINE. The siren is available in red or white, four different tone types and the volume can be set by software or by using DIP switches. The cable inlet is from above, with variants BXSBL502-WDB and BX-SBL502-RDB with a higher base being available for a cable inlet from the side. Operating voltage: Quiescent current: Power consumption: Volume: Types of tone: 12 to 30 VDC max. 0,5 mA 1,5 mA @ 24 VDC (volume low) 4,0 mA @ 24 VDC (volume high) 80 dB (90 dB) 3 dB(A)/m @ 24 VDC DIN 1200 ~ 500 Hz (acc. to DIN 33404) Slow Whoop 500 ~ 1200 Hz (EN 2575) Continuous tone 990 Hz (pulse can be set) Sweden-Tone (150 ms on/ 150 ms off) Screw clips, maximum 2.5 mm integrated IP 31 D -10 to +55C 114 x 32 mm (DxH) 114 x 36 mm (DxH) with high base PC-ABS white RAL 9003 ca. 165 g applied for applied for
Type Art. No.

BX-SBL502-R No.: 20-2100012-03-01

Connection: Short circuit isolator: Protection class: Ambient temperature: Dimensions: Case material: Case colour: Weight: VdS-Approval: CPD-Certificate:
Description

Platform siren BX-SBL502 white Platform siren BX-SBL502 white high Platform siren BX-SBL502 red Platform siren BX-SBL502 red high

BX-SBL502-W BX-SBL502-WDB BX-SBL502-R BX-SBL502-RDB

20-2100012-04-01 20-2100012-02-01 20-2100012-03-01 20-2100012-01-01

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

69

Integral X-LINE Accessories

6.4

Accessories
BX-UPI Parallel indicator The BX-UPI parallel indicator serves as an individual detector indicator for localisation of a fire alarm, if the alarm LED on the detector is not visible (e.g. concealed in intermediate floors or ceilings etc.). In the event of the detector being activated, the parallel indicator will also be controlled in parallel to the alarm message being sent, and will flash red. The BX-UPI consists of a white plastic case with a red triangular illuminated surface and built-in electronics with a red LED. The parallel indicator is connected using a 2 pole screw-type terminal directly to the alarm output of the fire detector or to the BX-AIM X-LINE module. The BX-UPI is also backwards compatible and can also replace parallel indicators BA-UPI. Planning hint: up until version 7.1 of the Integral Software a maximum of 3 pcs. BX-UPI can be controlled simultaneously on a loop circuit, while from version 7.2 of the software the simultaneous controlling of the BX-UPI can be dynamically planned. Operating voltage: 4,5 to 30 VDC Power consumption: 0.9 mA Type. Flashing frequency: 1.2 to 3 Hz Connection: screw clips, maximum 1.5 mm to USB 501 Protection class: IP 42 Ambient temperature: 0 to +60C Rel. air humidity: 5 to 95 % without condensation Dimensions: 85 x 85 x 30 mm (HxWxD) Weight: ca. 50 g
Description Type Art. No.

PIG No.: FG020093

BX-UPI No.: 20-2100030-01-01

Parallel indicator panel case BA-UPI Parallel Indicator (electronics)

PIG BX-UPI

FG020093 20-2100030-01-01

SKORB No.: FG020026

Protective Cage for Detector White painted metal protective cage for preventing detectors from sustaining physical damage. Suitable for all automatic detectors. Dimensions: 160 x 110 mm (DxH)

G KAPPE 501 No.: FG020189

Transparent rubber cap Transparent rubber cap made of silicon to protect the USB-501 detector base against moisture. The rubber cap is placed over the USB 501 detector base prior to fitting, in particular in areas where there are difficult environmental conditions where condensation water and moisture can quickly form, in order to prevent moisture from getting into the base. Fitting set for rubber cap Consisting of a fitting clip, 2 fixed distance pieces and two M4 x 16 cheese head screws for fitting detector bases in damp rooms. Supplied without detector base.

MON SET GK No.: MM000250

70

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE Accessories

DBZ1190A-AC No.: FG020480

Detector heater for USB 501 The detector heater allows the MTD 533 CP multiple sensor detectors with the USB 501 detector base in critical atmospheric conditions, e.g. where there is a risk of icing up or dew formation, in cold stores, walk-in freezers, collectors, attics, cheese cellars, power stations, loading bays etc. By fitting the detector heater the detector's temperature is increased by approx. 5C compared to the ambient temperature. An external power supply unit must be used to supply the detector heater with power, as the unit can not be supplied directly from the loop. The detector heater is controlled using the base terminal block for the USB501, with the unit being fastened in the detector base using cable ties. Operating voltage: 20 to 30 VDC Residual ripple: max. 2V Operating current: 35 to 55 mA Wattage: 1,2 W Resistance: 580 Wire diameter / terminal: 2 x 0,5 to 2,5 mm Deployment temperature: -30C to +40C
Description Type Art. No.

Detector heater Isolating point terminal block for USB501 Cable tie holder - adhesive

DBZ1190A-AC KL USB501 MM KBH KL

FG020480 FG030132 MM000047

STBLECH G / STBLECH

Baffle plate for riser cable shafts Hot-dip galvanized 1.2 mm thick sheet steel for improving detection properties of smoke detectors in vertical ducts, including drill holes for fitting and cable inlet for installation. Dimensions FG020205: 130 x 130 mm Dimensions FG020206: 300 x 300 mm
Description Type Art. No.

Baffle plate 130x130mm Baffle plate 300x300mm

STBLECH STBLECH G

FG020205 FG020206

MMK 200/350 No.: FG020520

Detector fitting console MMK 200/350 The console can be tilted from 0 to 90 and height can be adjusted between 200 and 350 mm. The detector is attached using 2 M4 screws. Both USB 501 and Hochiki bases can be fitted on to the console. Adjustable height: 200 to 350 mm with 4 mm Allen key Angle of tilt: 0 to 90 with 3 mm Allen key Material: Sheet steel, powder coated Colour: light grey (RAL 7035) Dimensions: 175 x 105 x 200 to 350 (LxWxH)
Description Type Art. No.

Detector fitting console

MMK 200/350

FG020520

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

71

Integral X-LINE Testing devices

6.5

Testing devices
UTP Universal telescopic bar Locking telescopic bar, suitable for all Schrack detector removers and testing equipment. Available with a length of three or four metres, with the range of the telescopic bar can be increased by 1.5 m to 6 m or 7 m respectively using the 1.3 m extension. Transport length UTP 3: 1,7 m for installation heights of up to 4,5 m Transport length UTP 4: 2,2 m for installation heights of up to 5,5 m Weight: UTP 3: 1 kg, UTP 4: 1,2 kg
Description Type Art. No.

Universal telescopic bar 3m Universal telescopic bar 4m Extension 1.3m for UTP 3 & 4

UTP3 UTP4 UTP V

FG030200 FG030201 FG030208

UTP 30kV Telescopic bar Telescopic bar with voltage sustaining capability of up to 30kV, for installation heights of up to 4.5m. Suitable for use with all Schrack detector removers and testing devices. Transport length UTP3 30KV: 1,7 m for installation heights of up to 4,5 m Transport length UTP10 30KV: 1,7 m for installation heights of up to 11 m Weight: UTP3 30KV: 2,2 kg, UTP10 30KV: 3,9 kg
Description Type Art. No.

Universal telescopic bar 3m 30kV Universal telescopic bar 11m 30kV

UTP3 30KV UTP10 30KV

FG030209 FG030210

Test gas for smoke detectors Suitable for function test from automatic smoke detectors. The test aerosol does not contain halogenated hydrocarbons (CFCs or similar). The FDT 533 holder with trigger mechanism is used to hold the test gas bottle.
No.: FG030202 with FG030117 Description Type Art. No.

Testing gas 918/5 for Smoke Detectors Holder unit for testing gas FDT 533

PRUEFGAS FDT 533

FG030117 FG030202

72

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Integral X-LINE Testing devices

No.: FG030240

No.: FG030241

Detector remover UDR 533 For fitting MTD 533 multiple sensor detectors to or removing them from USB 501 detector bases. Detector removers UDR 533S and UDR 533K can be fitted on to UTP series telescopic bars, with the UDR 533K detector remover also being suitable for remote fitting and removal of the detector thanks to its cardan joint. The UDR 533A adapter can be placed in the UDR 531K detector remover (for 531 detector series). Dimensions Weight UDR 533A 62 x 71 x 98 mm 150 g UDR 533S 100 x 100 x 232 mm 200 g UDR 533K 160 x 170 x 232 mm 530 g
Description Type Art. No.

Detector remover UDR 533A Detector remover UDR 533S Detector remover UDR 533K Replacement rubber for UDR 533

UDR 533A UDR 533S UDR 533K UDR 533 G

FG030240 FG030241 FG030242 FG030243

TESTIFIRE 1001 No.: FG030280

TS3 No.: FG030282

Detector testing device TESTIFIRE 1001 Combination testing device for smoke and temperature testing of automatic fire detectors. Thanks to the combination of different functions in a single device, it is possible to test not only optical smoke detectors, but also temperature detectors (maximum temperature or temperature change) and multiple sensor detectors simply and efficiently. The device is battery operated and is completely user friendly and environmentally friendly. The testing agent required for the smoke and temperature test is contained in a cartridge that can be easily replaced. Two cylindrical rechargeable cells and a charger are supplied as standard, and the device can be fitted on to UTP series telescopic bar using the Adapter UTP SOL. Electrical Power Source: Rechargeable battery pack 7.2V / 2.2 Ah NiMH rechargeable cell Rechargeable cell charging time: 75-90 min. (if fully discharged) Operating temperature: +5C to +45C Protection class: IP 20 Weight: 0,75 kg Dimensions: 224 x 153 mm (H x D)
Description Type Art. No.

TESTIFIRE 1001 detector testing device Adapter for telescopic bar Smoke cartridge for Testifire (replacement) Replacement rechargeable cell for Testifire (replacements) Quick charger for Testifire (replacement)

TESTIFIRE 1001 UTP SOL TS3 SOLO 720 SOLO 725

FG030280 FG030281 FG030282 FG030283 FG030284

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

73

Integral X-LINE Testing devices

B6-LAI No.: FG052606

Loop Assistant Interface B6-LAI With the Loop Assistance Interface, a service PC and the necessary software are all present, it is possible to check and program (assignment of logical addresses) Integral X-LINE on-site even if there is no fire alarm control panel. The programming is saved on the service PC and then transferred to the fire alarm control panel thereafter. The device consists of a case, modules, main processor unit, power supply unit, operating panel and rechargeable cells (to permit operation for up to 4 hours) and is supplied in a red impact-resistant plastic case including a power connection cable. Connection: max. two loop circuits each with max. 250 elements Programming connection: Service PC over USB Range: max. 10 m Batteries: 24 V / 1,2 Ah Protection class: IP 20 Ambient temperature: 0 to +50C Dimensions: 440 x 310 x 100 mm (HxWxD) Weight: 8 kg
Description Type Art. No.

B6-LAI LoopAssistant Interface USB Cable 3m USB Cable 4,5m

B6-LAI KAB USB 3 KAB USB 45

FG052606 FG022051 FG022052

Loop circuit testing device STB 01E (Loop technology) Testing device to simply check the Integral loop technology without fire alarm control panel attached with step-by-step and fully automatic modes. Supplied complete with power supply and connection plug.

STB 01E Description Type Art. No.

Loop circuit testing device

STB 01E

FG030218

Loop circuit testing device STB 01X (X-LINE) Testing device to simply check the Integral X-LINE without fire alarm control panel attached with step-by-step and fully automatic modes. Supplied complete with power supply and connection plug.

STB 01X Description Type Art. No.

Loop circuit testing device

STB 01X

upon request

74

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Special detectors Linear smoke detector

7 Special detectors
7.1 Linear smoke detector
Linear smoke detector SPC-E Line smoke detector SPC-E comprises of a transmitter and receiver unit, which are fitted opposite one another between 5 and 100 m away from each other. In the event of a fire, the rising smoke reduces the intensity of the infrared ray between the transmitter and receiver and an alarm is sent to the fire alarm control panel. The SPC-E is particularly reliable where the ambient temperature or air humidity is constantly changing and is simple to install and configure. Operating voltage: Quiescent current: Alarm current: Monitoring length: Signal processing: Sensitivity: Indicators: Compensation:
BEAM WH SPBC No.: FG020125

SPC-E No.: FG020073

Protection class: Ambient temperature: Max. air humidity: Colour: Dimensions: Weight: VdS-Approval: CPD-Certificate:
Description

BEAM DH SPBC No.: FG020126

15 to 33 VDC 250 A max. 50 mA max. 5 to 100 m 8-bit micro processor 3 levels can be set 25%, 50%, 60% LEDs for operation, fault and alarm Contamination of the optical sensor compensated to 1% every half hour IP 42 -10 to + 50C 95 % non-condensing white 86 x 100 x 145 (transmitter and receiver) receiver: 685 g transmitter: 600 g G207152 0832-CPD-0547
Type Art. No.

Linear smoke detector SPC-E Wall mounting joint: Ceiling mounting joint:

SPC-E BEAM WH SPBC BEAM DH SPBC

FG020073 FG020125 FG020126

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

75

Special detectors Linear smoke detector

ARDEA S No.: FG020207

Linear smoke detector ARDEA S Line infrared light absorption detector, consisting of transmitter and receiver units. The detection process involves the measuring of light absorption whilst dynamic parameters (smoke modulation) are observed. Usage: Large rooms in industrial and social areas e.g. manufacturing areas, warehouses, supermarkets, cinemas, theatres, trade fair halls, stations, churches, schools etc. The mounting brackets are supplied as standard. Operating voltage: 18,5 to 32,5 VDC Quiescent current: 76 (5m) to 112 mA (150m) Alarm current: 118 mA max. Monitoring length: 5 to 150 m Protection class: IP 44 Ambient temperature: -25 to +60C Max. air humidity: 95% Case: Aluminium anodised Colour: black/anthracite RAL 7035 Dimensions with bracket: 224 x 119 x 313 mm Dimensions without bracket: 200 x 119 x 148 mm Weight: Transmitter: 1,3 kg Receiver: 1,5 kg Fitting brackets: je 500 g VdS-Approval: G294043 CPD-Certificate: 0786-CPD-20215 Linear smoke detector ARDEA SF Its construction, functions and technical specifications are the same as those of the ARDEA S, although the detector also responds to the flame frequencies of open fires. Fitting bracket are included as supplied. Quiescent current: 99 mA (5m) to 144,5 mA (150m) Alarm current: 168,5 mA max. Linear smoke detector ARDEA DUST Its construction, functions and technical specifications are the same as those of the ARDEA SF, although the detector can also be used in areas where there are difficult environmental conditions (e.g. high dust concentration etc.) thanks to its additional special evaluation process. Fitting bracket are included as supplied.

ARDEA SF No.: FG020216

ARDEA DUST No.: FG020370

ADM Adapter For optimized setting the sensitivity of the ARDEA linear smoke detector in accordance with the prevailing atmospheric conditions. SAC Simulator For testing settings and functions of ARDEA S and SF detectors. The SAC can check that the detectors are roughly correctly set-up by carrying out simulations of the Fire and Smoke response thresholds, as well as checking signal strength.
Description Type Art. No.

ARDEA ADM No.: FG020375

ARDEA S Linear smoke detector ARDEA SF Linear smoke detector ARDEA DUST Linear smoke detector ADM Adapter SAC Simulator

ARDEA S ARDEA SF ARDEA DUST ARDEA ADM ARDEA SAC

FG020207 FG020216 FG020370 FG020375 FG020376


B-HB-008EN

76

Product catalogue fire alarm systems 2011 V 2.0

Special detectors Linear smoke detector

ARDEA S EX No.: FG020373

Linear smoke detector ARDEA for hazardous areas Its construction and principle functions are the same as those of the ARDEA S, but the detector also reacts particularly well to fires in their earliest stages containing hydrocarbon-based propellants, plastic and rubber mixtures and is suitable and approved for monitoring areas where there is a risk of explosion. Operating voltage: 12 to 24 VDC 20% Quiescent current: 37 mA (low), 58 mA (high) Alarm current: 62 mA (low), 84 mA (high) Monitoring length: 5 to 100 m Protection class: IP 66 (with cable clamps) Ambient temperature: -10 to +65C Case: Aluminium Dimensions with bracket: 365 x 241 x 215 mm Dimensions without bracket: 220 x 190 x 170 mm Weight: transmitter and receiver je 4,6 kg Approval: INERIS 02 ATEX 0090X
Description Type Art. No.

ARDEA S EX Linear smoke detector Test filter for ECO & ARDEA

ARDEA S EX STF4

FG020373 FG020398

ECO ES50 No.: FG020390

SSM No.: FG020254

Linear smoke detector ECO ES50 Consisting of a combined transmitter/receiver unit and reflector, which are fitted at a distance of between 2 and 50 metres opposite one another. The infrared beam that is emitted by the transmitter is bounced back by the reflector and evaluated. The unit is fitted as standard directly on the wall, using a jointed mounting bracket on diagonally sloping or walls that are not flat. A reflector and an SSM jointed mounting bracket are supplied. Operating voltage: 12 to 24 V Quiescent current: up to 25 m monitoring distance: 19 mA up to 50 m monitoring distance: 39 mA Alarm current: up to 25 m monitoring distance: 32 mA up to 50 m monitoring distance: 52 mA Contact rating: alarm relay: 1 A @ 30 V fault relay: 170mA @ 30V Maximum cable length: 1000m with 0,8mm, 2000m with 1,0mm Monitoring length: 2 to 50 m (2 switch positions) Monitoring width: 15 m in accordance with EN 54-14 Protection class: IP 44 Ambient temperature: -20 to +60C Rel. air humidity: 95% Dimensions without fixing joint: 103 x 110 x 63 mm Dimensions with fixing joint: 103 x 110 x 119 mm Case material top: Polycarbonate / ABS Case colour: white RAL 1013 Weight (without fixing joint): 360 g VdS-Approval: G205128 CPD-Certificate: 0786-CPD-20214
Description Type Art. No.

ECO ES50 Linear smoke detector Jointed mounting bracket (2 pcs.) Test filter for ECO & ARDEA Reflector for ECO (replacement)

ECO ES50 SSM STF4 MBK40

FG020390 FG020254 FG020398 FG020259

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

77

Special detectors Linear smoke detector

ECO ES25-I No.: FG020392

Linear smoke detector ECO ES25-I The unit is largely the same as the ECO ES50, but is intended for being built into a wall (countersunk installation). This version is shipped with the jointed mounting bracket for fitting the reflector as standard. Case: blue, similar to RAL 5017 Front panel: black Dimensions without fixing joint: 136 x 140 x 73 mm Weight: ca. 350 g VdS-Approval: G205128
Description Type Art. No.

Linear smoke detector ECOES25-I Test filter for ECO & ARDEA

ECO ES25-I STF4

FG020392 FG020398

78

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Special detectors Flame detectors

7.2

Flame detectors
Infrared flame detector DF 1191 For detection of liquid and gas fires without smoke formation as well as open fires with smoke formation, which occur during the combustion of carbon-based materials such as wood, plastics, gases, oil products etc. The detector is suitable for simple interior applications and contains an infrared sensor, which measures the hot carbon dioxide in the flames at a specific wavelength. Operating voltage: 16 to 28 VDC Quiescent current: 500 A Field of detection: 90 Detection distance: 27 m with 0 angle of sight (standard) 46 m with 0 angle of sight (increased) Protection class: IP 44 Ambient temperature: -25 to +70C Rel. air humidity: 95% (no strong build-up of dew) Case material: Pressure case aluminium Colour: white (similar to RAL 9010) Dimensions incl. base: 135 x 135 x 77 mm (HxWxD) Gewicht incl. base: 750 g VdS-Approval: G299085
Description Type Art. No.

DF 1191 No.: FG020360

DFB 1190 No.: FG020363

IR Flame Detector DF 1191 Base for flame detector DFB 1190 Installation bracket for DFxx detectors Fitting joint MWV1 Rain protection hood DFZ1190

DF 1191 DFB 1190 MV1 MWV1 DFZ1190

FG020360 FG020363 FG020364 FG020365 FG020366

DF 1192 No.: FG020361

DFB 1190 No.: FG020363

Triple infrared flame detector DF 1192 Three sensor infrared flame detector with fuzzy logic and wavelet analysis, suitable for the detection of smokeless liquid and gas fires, as well as open fires with smoke formation, which arise from the burning of materials containing carbon. The detector is suitable for use both indoors and outdoors. Operating voltage: 16 to 28 VDC Quiescent current: 500 A Field of detection: 90 Detection distance: 27 m with 0 angle of sight (standard) 46 m with 0 angle of sight (increased) Protection class: IP 67 Ambient temperature: -35 to +70C Rel. air humidity: 100% (no strong build-up of dew) Case material: Pressure case aluminium Colour: white (similar to RAL 9010) Dimensions incl. base: 135 x 135 x 77 mm (HxWxD) Weight incl. base: 750 g VdS-Approval: G299085
Description Type Art. No.

DF 1192 Triple infrared Flame Detector Base for flame detector DFB 1190 Installation bracket for DFxx detectors Fitting joint MWV1 Rain protection hood DFZ1190

DF 1192 DFB 1190 MV1 MWV1 DFZ1190

FG020361 FG020363 FG020364 FG020365 FG020366

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

79

Special detectors Hazardous areas

7.3

Hazardous areas
Optical smoke detector for hazardous areas SLR-E-IS For use in areas where there is a risk of explosion - zones 1 and 2 The detector contains two LEDs lined up opposite one another for alarm indication and is connected via the YBN-R/4IS detector base and with a safety barrier being interconnected to either the BX-AIM module or to the Integral DC technology. Operating voltage: Quiescent current: Alarm current: Protection class: Ambient temperature: Max. air humidity: Diameter: Unit height with base: Colour: Material: Weight: Marking: Approval: CPD-Certificate:
Description

SLR-E-IS No.: FG020070

15 to 30 VDC 50 A 40 mA max. IP 42 -10 to +50C 95% non-condensing at +40C 100 mm 46 mm Ivory white ABS 115 g (160 g with base) EX II 1G EEx ia IIC T5 BAS 01 ATEX 1281 0832-CPD-0113
Type Art. No.

Optical smoke detector for hazardous areas Detector base YBN for hazardous areas

SLR-E-IS YBN-R/4IS

FG020070 FG020071

DCD-1E-IS No.: FG020072

Temperature detector for hazardous areas DCD-1E-IS Conventional class 1 maximum/rate-of-rise temperature detector with an extra fixed alarm threshold of 60C for use in zone 1 and 2 hazardous areas. The detector contains two LEDs lined up opposite one another for alarm indication and is connected via the YBN-R/4IS detector base and with a safety barrier being interconnected to either the BX-AIM loop circuit module or to the Integral DC technology. Operating voltage: Quiescent current: Alarm current: Protection class: Ambient temperature: Max. air humidity: Diameter: Unit height with base: Colour: Material: Weight: Marking: Approval: CPD-Certificate:
Description

15 to 30 VDC 50 A 50 mA max. IP 63 -10 to +55C 95% non-condensing (at +40C) 100 mm 46 mm Ivory white Polycarbonate 95 g (140 g with base) EX II 1 G EEx ia IIC T5 BAS 01 ATEX 1021 0832-CPD-0121
Type Art. No.

DCD-1E-IS temperature detector f. hazardous areas Detector base YBN for hazardous areas

DCD-1E-IS YBN-R/4IS

FG020072 FG020071

80

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Special detectors Hazardous areas

Manual call point for hazardous areas DC31 For manually triggering a fire alarm in hazardous areas of group II, category 2GD (Zone 1, 2, 21 and 22), conformant to type B pursuant to EN 54-11. There are three different models available for connection to different wiring technologies, each of which can be connected as a detector in series as well as being used as the terminal detector. Supplied with cable glands and blanking stoppers.
DC31 No.: FG020460

Operating voltage: Current consumption: Power loss: Connection: Cable entry points: Protection class: Ambient temperature: Dimensions: Colour: Material: Weight: Ignition protection class: ATEX-Approval: VdS-Approval: CPD-Certificate:
Description

max. 30 VDC serial detector 0 mA terminal detector: ca. 2 mA with B3-DCI6 ca. 1,5 mA with BX-AIM max. 1,3 W 0,08 to 2,5 mm 2 x M20 x 1,5 6 to 12 mm IP 66 -20 to +60C 135 x 135 x 61 mm (HxWxD) red RAL 3000 PC ca. 500 g EX II2G Ex emb IIC T6 EX II2D Ex tD A21 IP6x T80C BVS 09 ATEX E 016 X G206113, G207079, G207099 0786-CPD-20309, 0786-CPD-20310, 0786-CPD-20311
Type Art. No.

dC31 manual call point for hazardous areas red 560R/11k8 for connecting to B3-DCI dC31 manual call point for hazardous areas red 560R/19k1 for connecting to BX-AIM dC31 manual call point red 1k5/3k for connection to B3-IM8, B3-MTI8 and B4-EIO Metal key for manual call point Replacement glass for manual call point

DC31 DC31 DC31 DKM SV DKM GV

FG020460 FG020461 FG020462 FG020463 FG020464

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

81

Special detectors Hazardous areas

MCP 1A AP No.: FG030909

MCP 1A UP No.: FG030910

Manual call point for hazardous areas MCP/WCP 1A The intrinsically safe manual call points for hazardous areas MCP/WCP 1A conform to standard EN54-11 (type A) as well as ATEX 100a and are connected to the BX-AIM input module through an interconnected Zener barrier. The four different versions differ from one another solely in terms of their case form and IP protection class, with the electronic circuitry, connection and how they function being identical for all types. The MCP 1A surface mounting version is suitable for indoor applications, with the case being fastened to the wall using two screws. Cable inlets required for surface mounting must be drilled into the case as required. The countersunk mounting version MCP 545A-2 is suitable for use indoors, and the detector is fitted straight into a standard size 1 (round or square) countersunk mounting case. The WCP 1A is also suitable for use outdoors and is surface mounted. The detector has IP 67 protection class (waterproof); with the cables being fed in from above or below using an M20 cable gland. 2 pcs. M 20 connection joints and 2 pcs. blanking stoppers, as well as the fitting screws are supplied as standard. Operating voltage: Quiescent current: Alarm current: Connection: Screw connections: Protection class: Ambient temperature: Case colour: Case material: Weight: 15 to 30 VDC ca. 900 A 5 mA over the BX-AIM and Zener barrier max. 2,5 mm MCP 1A: IP 24 WCP 1A: IP 67 -30 to +70C red, RAL 3001 Fibreglass reinforced plastic MCP 1A (aP): 160g MCP 1A (uP): 110g WCP 1A: 240g SIRA 04 ATEX 2350X
Type Art. No.

WCP 1A No.: FG030911

PS200 No.: FG030921

Approval:
Description

MCP 1A manual call point for hazardous areas red, IP24 (indoor), with surf. mount. base MCP 1A manual call point for hazardous areas red, IP24 (indoor), without base WCP 1A manual call point for hazardous areas red, IP67 (waterproof) Plastic triggering element Transparent cover Cover seal Glass panel for MCP 545A / MCP 1A Back panel for surface mounting 10 pcs. replacement test key

MCP 1A AP MCP 1A UP WCP 1A PS210 PS200 P 037 DKM K GLAS MUS041W SC070

FG030909 FG030910 FG030911 FG030920 FG030921 FG030331 FG030328 FG030332 FG030329

82

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Special detectors Hazardous areas

Infrared flame detector for hazardous areas DF 1101Ex For use in areas where there is a risk of explosion - zones 1 and 2 The detector is suitable for the detection of smokeless liquid and gas fires, as well as open fires with smoke formation, which arise from the burning of materials containing carbon and is suitable for indoor and outdoor use.
DF 1101EX No.: FG020362

Operating voltage: Quiescent current: Field of detection: Detection distance: Protection class: Ambient temperature: Rel. air humidity: Case: Dimensions incl. base: Gewicht incl. base: Marking: Approval: VdS-Approval: CPD-Certificate:
Description

DFB 1190 No.: FG020363

Stabex HF No.: FG020367

16 to 28 VDC 500 A 90 27 m with 0 angle of sight (standard) 46 m with 0 angle of sight (increased) IP 67 -25 to +70C 100% (no strong build-up of dew) Aluminium-Druckguss, white 135 x 135 x 77 mm (HxWxD) 750 g EEx ib IIC T4 PTB 02 ATEX 2161 G299085 0786-CPD-20497
Type Art. No.

DF 1101Ex IR-Flame Detector f. hazardous areas Base for flame detector DFB 1190 Test lamp for DFx flame detector

DF 1101EX DFB 1190 Stabex HF

FG020362 FG020363 FG020367

MV1 No.: FG020364

Fitting bracket for DFx flame detector Fitting bracket for fixing flame detectors DF 1191, DF 1192 and DF 1101 Ex at an angle of 45. Weight: 285 g Dimensions: 120 x 136 x 120 mm (HxWxD) Angle of tilt: 45 fixed Fitting joint for DFx flame detector For special arrangements (e.g. facility monitoring without a 45 angle) fitting using the MWV1 fitting joint is recommended. This part allows the detector to be fitted simply and directly in the room to be monitored. Dimensions: 118 x 120 x 78 mm (HxWxD) Rain protection cover for DFx flame detector To protect the case when being used outside. Dimensions: 165 x 150 x 130 mm (HxWxD)

MWV1 No.: FG020365

DFZ1190 No.: FG020366

Description

Type

Art. No.

Installation bracket for DFxx detectors Fitting joint MWV1 Rain protection hood DFZ1190

MV1 MWV1 DFZ1190

FG020364 FG020365 FG020366

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

83

Special detectors Hazardous areas

X2200 No.: FG020320

Ultraviolet flame detector X2200 Particularly suitable for use in areas with high temperatures, munitions stores, hydrogen, silane, turbines etc. and offers the highest degree of reliability, even in the event that multiple disturbing sources are present simultaneously (electric arcing, sunlight, etc.). The detector has a 90 angle of sight, has an automatic self-test function, a three colour LED for indicating the detector status and current configuration, as well as integrated sensor heating for installation outdoors. The X2200 can be used in zone 1 and 2 hazardous areas. The bracket for mounting it on walls or ceiling is supplied. Operating voltage: 18 to 30 VDC Power consumption: 13,1 W max. with heating unit Signal transmission: potential-free relay contacts Connection: screw clips, maximum 1.5 mm Protection class: IP 66 Ambient temperature: -40 to +75C Rel. air humidity: 0 to 95% Dimensions case: 246 x 119 x 122 mm Weight: Aluminium: 2,7 kg Stainless steel: 4,5 kg Marking: 0539 II 2 GD EEx d IIC T5-T6 T86C Approval: DEMKO 02 ATEX 132195 VdS-Approval: G203083
Description Type Art. No.

UV flame detector X2200 aluminium UV flame detector X2200 stainless steel UV test lamp for hazardous area

X2200 X2200

FG020320 upon request upon request

X3301 No.: FG020322

Triple infrared flame detector X3301 Detects burning light and heavy mineral oils, and is notable for its high resistance against deceptive alarms. Possible uses include e.g. on oil drilling platforms, in refineries, volume compressors, turbine systems, production lines etc. The detector is fitted out with three identical IR sensors, with the alarm only being triggered with all three sensors detect flames. The detector has a 90 angle of sight, has an automatic self-test function, a three colour LED for indicating the detector status and current configuration, as well as integrated sensor heating for installation outdoors. The X3301 can be used in zone 1 and 2 hazardous areas. The bracket for mounting it on walls or ceiling is supplied. Operating voltage: 18 to 30 VDC Power consumption: 14,5 W max. with heating unit Signal transmission: potential-free relay contacts Connection: screw clips, maximum 1.5 mm Protection class: IP 66 Ambient temperature: -40 to +75C Rel. air humidity: 0 to 95% Case Dimensions: 246 x 119 x 122 mm Weight: Aluminium: 2,7 kg, Stainless steel: 4,5 kg Approval: DEMKO 01 ATEX 130204 VdS-Approval: G202136
Description Type Art. No.

X3301 Triple IR Flame detector aluminium X3301 Triple IR Flame detector sheet steel Test lamps for hazardous areas

X3301 X3301

FG020322 upon request upon request

84

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Special detectors Hazardous areas

X9800 No.: FG020321

Infrared flame detector X9800 The single frequency infrared detector is suitable for detector of fires in areas where flames can be caused by the presence of high-pressure combustible hydrocarbons, and where there are high concentrations of oil or pollutants in the air (e.g. in pipelines, drilling platforms, petrochemical installations, turbines etc.). The detection allows reliable detection even in the simultaneous presence of sources of disturbance (e.g. sources of convected heat radiation, ovens etc.). The detector enjoys a 90 angle of sight, has an automatic selftest function, a 3 colour LED for indicating the detector status and current configuration, as well as integrated sensor heating for installation outdoors and can be deployed in hazardous area zones 1 and 2. The bracket for mounting it on walls or ceiling is supplied. Operating voltage: 18 to 30 VDC Power consumption: 12 W max. with heating unit Signal transmission: potential-free relay contacts Connection: screw clips, maximum 1.5 mm Protection class: IP 66 Ambient temperature: -40 to +75C Rel. air humidity: 0 to 95% Dimensions case: 246 x 119 x 122 mm Weight: Aluminium: 2,7 kg, Stainless steel: 4,5 kg Approval: DEMKO 02 ATEX 132195 Ex-Marking: 0539 II 2 GD EEx d IIC T5-T6 T86C VdS-Approval: G203084
Description Type Art. No.

IR flame detector X9800 aluminium IR flame detector X9800 stainless steel Test lamps for hazardous areas

X9800 X9800

FG020321 upon request upon request

X5200 No.: FG020323

Combined UV/IR flame detector X5200 Particularly suitable for uses where hydrocarbon fires may arise, or where there are sources of UV radiation present (e.g. in aircraft hangars, tank systems etc.). The detector enjoys a 90 angle of sight, has an automatic self-test function, a 3 colour LED for indicating the detector status and current configuration, as well as integrated sensor heating for installation outdoors and can be deployed in hazardous area zones 1 and 2. The bracket for mounting it on walls or ceiling is supplied. Operating voltage: 18 to 30 VDC Power consumption: 14,5 W max. with heating unit Signal transmission: potential-free relay contacts Connection: screw clips, maximum 1.5 mm Protection class: IP 66 Ambient temperature: -40 to +75C Rel. air humidity: 0 to 95% Dimensions case: 246 x 119 x 122 mm Weight: Aluminium: 2,7 kg, Stainless steel: 4,5 kg Approval: DEMKO 02 ATEX 132195 VdS-Approval: G203085
Description Type Art. No.

X 5200 UV/IR Flame Detector aluminium X 5200 UV/IR Flame Detector stainless steel Test lamps for hazardous areas

X5200 X5200

FG020323 upon request upon request

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

85

Special detectors Hazardous areas

Safety barrier Z787 The safety barriers for intrinsically safe detector zones prevent too high an energy level from entering a hazardous area, which could cause ignition sparks if discharged there. The barrier is connected in series into the wiring of the detector zone, and is tested and approved in accordance with the requirements of ATEX 100a for use in hazardous areas. Rated operational voltage: End-to-end resistance: Operating current: Total cabling length: Max. short circuit current: Max. external capacity: Max. external inductance: Ambient temperature: Marking: Approval: max. 28 V 285 , max. 340 35 mA max. 700 m 93 mA 0,07 F / 0,5 F (IIC/IIB) 4 mH / 15 mH (IIC/IIB) -20 to +60C EX II 3 G EEx n A II T4 TV 99 ATEX 1484 X BAS 01 ATEX 7005

Z787 No.: FG020121

Z787F No.: FG020430

Safety barrier Z787F Identical in function and construction to the Z787 safety barrier, but contains an integrated series fuse carrier in the safe part. The barrier is intended for use in exposed surroundings, where overvoltages, lightning strikes, voltage changes etc. could lead to the ex barrier being destroyed. The selective series fuses prevent the internal fuses from being destroyed and can be replaced. Rated operational voltage: End-to-end resistance: Operating current: Total cabling length: Max. short circuit current: Max. external capacity: Max. external inductance: Marking: Approval:
Description

max. 28 V 327 , max. 363 35 mA max. 350 m 93 mA 0,07 F / 0,5 F (IIC/IIB) 4 mH / 15 mH (IIC/IIB) EX II 3 G EEx n A II T4 TV 99 ATEX 1484 X BAS 01 ATEX 7096
Type Art. No.

Z787 safety barrier Z787.F safety barrier G fuse 50 mA F 5x20 for Z787.F (replacement) IP55/65 case for safety barrier

Z787 Z787F Z787F SI GEH EXB

FG020121 FG020430 FG020431 FG020432

86

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Special detectors Hazardous areas

No.: FG020432 & FG020433

IP55/65 case for safety barrier Case with a built-in 35mm fitting bracket for fitting up to 3 Z787 or Z787F safety barriers. When fitting only one safety barrier, the protective conductor terminal needed can also be fitted in the case. Shipped including three M 32 stoppers. The case contains ten M32/40 cable inlets, and the fastening bracket and two screws must be ordered separately. Installation type: Surface mounting Number of inlets: 10 Nominal diameter: 25 mm Measured isolating voltage Ui: 690 V Can be sealed with leads: yes Ambient temperature: -40 to +70 C Protection class: IP 65 / IP 55 with M40 stoppers Halogen-free: no Colour: light grey (RAL 7035) Material: plastic Dimensions: 200 x 160 x 98 mm (LxWxH)
Description Type Art. No.

IP55/65 case for safety barrier Mounting bracket for FG020432 Tallow-drop screw max. 4 x 8

GEH EXB GEH EXBW MS LKS 4-8

FG020432 FG020433 MS00004008

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

87

Special detectors Linear temperature detectors

7.4

Linear temperature detectors


Transafe ADW 511 Linear temperature detector with temperature change and maximum temperature processing. The detector works on the principle of a gas expanding in volume when it get hotter, and the associated increase in pressure in a pneumatically sealed system. The ADW 511 consists of a measuring unit and a copper sensor tube (stainless steel or Teflon tubes are available for use where there are particularly difficult environmental conditions). Pressure is artificially created in the sensor tube, with a fully electronic pressure sensor constantly measuring the absolute pressure in the tube, with a microprocessor carrying out the evaluation of the results. The sensitivity of the ADW 511 can be set via a using PCbased software, with disturbance factors such as weather-related fluctuations in temperature being filtered out. Damage to the sensor tube is also recognised, by means of a precisely defined surplus pressure being created in the sensor tube by means of a test motor and a pressure pump at regular intervals. Its robust construction makes the ADW 511 particularly suitable for use in detecting fires in hazardous areas (in tunnel systems, hazardous areas, industrial applications etc.). Operating voltage: Quiescent current: Alarm current: Max. current consumption: Connection: Protection class of case: Ambient temperature: Case colour: Dimensions case: Sensor tube length: Sensor tube diameter: Weight: VdS-Approval:
Description

ADW 511 No.: FG020900

10,5 to 30 VDC 90 mA at 24 VDC 99 mA at 24 VDC 108 mA at 24 VDC screw clips, maximum 1.5 mm IP 65 Evaluation unit: - 20 to +50C Sensor tube: - 40 to +160C grey RAL 7000 160 x 160 x 90 mm 20 to 80 m (for use in tunnels up to 130 m) internal: 4 mm / external: 5 mm 1,7 kg G200111
Type Art. No.

Transafe ADW 511 standard processing unit Copper sensor tube diameter=5/4mm Stainless steel sensor tube diameter=5/4mm Teflon sensor tube diameter=5/3mm ADW 511 test motor ADW-511 (ADP-51) base plate Brass cable gland Brass Terminating stopper Brass adapter Plastic sliding clip Plastic tubing Stainless steel cable gland Stainless steel terminating stopper Stainless steel support sleeve 4 mm Stainless steel support sleeve 3 mm

ADW 511 ADW CUFR ADW ESFR ADW TFFR ADW PM ADW ADP51 ADW MV ADW MEZ ADW MSH ADW KBRD ADW KSCHL ADW ESV ADW ESEZ ADW ESSH1 ADW ESSH2

FG020900 FG020910 FG020911 FG020912 FG020920 FG020921 FG020922 FG020923 FG020924 FG020925 FG020926 FG020927 FG020928 FG020929 FG020930

88

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Special detectors Smoke aspirating system AirSCREEN ASD 535

7.5

Smoke aspirating system AirSCREEN ASD 535


Smoke aspirating system AirSCREEN ASD 535 Active linear smoke aspirating system, consisting of one or two independent aspirating lines, each with a smoke sensing element with one built-in smoke sensor for monitoring rooms and establishments. A high performance fan transports the air from the room to be monitored through the aspirating line into the evaluation unit, where an increase in the smoke concentration is detected immediately. The aspirating line is constantly monitored for a pipe break and contamination. For every aspirating line three pre-alarms and one main alarm can be programmed, which are transmitted to the fire alarm control panel either over potential-free contacts or the loop circuit. The indicator and operating panel displays the smoke concentration of the aspirated air, as well as other alarm, fault and status messages. The ASD 535 also contains four connection slots, in which relay and interface modules can be fitted. The smoke sensors (not supplied as shipped) are available with different classes of sensitivity and can also be adapted to the environmental conditions. Using an ABS aspirating pipe and the corresponding accessories the devices can also be used in areas where there are low temperatures (deep freeze areas). The PipeFlow software can be used to calculate asymmetrical aspirating lines, with the PC commissioning software "ASD Config" being used for the commissioning of larger systems. Operating voltage: Quiescent current: Alarm current: Relay outputs: Additional modules (max. 4): Sensitivity range: Aspirating pipes: Cable entry points: Pipe lengths: Pipe diameter: Fan: Aspirating pressure: Aspirating noise: Protection class: Ambient temperature: Case material: Case colour: Dimensions: Weight: VdS-Approval: CPD-Certificate:
Description

ASD 535-1 No.: FG030800

ASD 535-2 No.: FG030801

ASD 535-3 No.: FG030802

ASD 535-4 No.: FG030803

10,5 to 30 VDC 290 mA @ 24 VDC 385 mA @ 24 VDC 3 freely programmable, potential-free contacts SLM 35, MCM 35, 2x RIM 35 see SSD 535 ABS and hard PVC 4 x M20, 1 x M25 max. 2 x 240m nacacc. to EN 54-20 25 mm external diameter radial, 5 different rotation speed levels > 400 Pa (level 5) 43 dB(A) (standard setting) IP 54 -30 to +60C ABS, UL 94-V0 grey RAL 280 7005 & RAL 300 2005 397 x 263 x 146 mm (HxWxD) 3,8 kg G208154 0786-CPD-20600
Type Art. No.

AirSCREEN ASD 535-1 (1 aspirating pipe) AirSCREEN ASD 535-2 (2 aspirating pipes) AirSCREEN ASD 535-3 1 aspirating pipe with smoke level indicator AirSCREEN ASD 535-4 2 aspirating pipes with smoke level indicators

ASD 535-1 ASD 535-2 ASD 535-3 ASD 535-4

FG030800 FG030801 FG030802 FG030803

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

89

Special detectors Smoke aspirating system AirSCREEN ASD 535

Replacement parts for ASD 535


Description Type Art. No.

Basic circuit board for ASD 535-1 & ASD 535-3

AMB 35-1

FG030830

Basic circuit board for ASD 535-2 & ASD 535-4

AMB 35-2

FG030831

Airflow sensor including connection cable

AFS 35

FG030833

Ventilator unit for ASD 535

AFU 35

FG030834

Standard Indicator Panel for ASD 535

BCB 35

FG030835

Enhanced Indicator Panel for ASD 535

ACB 35

FG030836

Module holder UMS 35

UMS 35

FG030826

SSD 535-1 No.: FG030810

SSD 535-2 No.: FG030811

SSD 535-3 No.: FG030812

Smoke sensor SSD 535 for ASD 535 Highly sensitive HD sensor using the scattered light principle for use in the various ASD 535 models. The sensor is designed to optimally fulfil the requirements of a smoke detection in conjunction with a aspirating smoke detector. The threshold sensitivity of the smoke sensor can be set anywhere in the given range. High power LED with lowest air resistance and highest resistance against contamination. Compares sample parameters for fires Intelligent alarm buffering Alarm threshold tracking with two level contamination indicator Dynamic particle suppression for detection and fading out of dust particles Auto learning function for critical atmospheric conditions Operating voltage: 5 V DC Protection class: IP 44 Alarm sensitivity range: SSD 535-1: 0,5 to 10 %/m SSD 535-2: 0,1 to 10 %/m SSD 535-3: 0,02 to 10 %/m Pre-signal sensitivity: 0,002 to 10 %/m Ambient temperature: -30 C to +60 C Dimensions: 145 x 120 x 95 mm (HxWxD) Case colour: grey VdS-Approval: G208154
Description Type Art. No.

SSD 535-1 smoke detector for ASD 535 SSD 535-2 smoke detector for ASD 535 SSD 535-3 smoke detector for ASD 535

SSD 535-1 SSD 535-2 SSD 535-3

FG030810 FG030811 FG030812


B-HB-008EN

90

Product catalogue fire alarm systems 2011 V 2.0

Special detectors Smoke aspirating system AirSCREEN ASD 535

MCM 35 No.: FG030821

SD-CARD No.: FG020325

Memory card module MCM 35 Additional module for fitting in the ASD 535 for recording operating data. The module enables recordings for a long period of time for smoke concentrations and air flows (sensor 1 and 2) as well as saving event data every second. A maximum of 251 log files each with 28,800 entries or 251 event files each with 64,000 events can be saved, and a maximum of two MCM 35 units can be fitted per ASD 535. One SD memory card and a fitting kit are supplied. Operating voltage: 5 V DC Current consumption: max. 25 mA Dimensions: 58 x 99 x 17 mm (HxWxD)
Description Type Art. No.

Memory card module MCM 35 for ASD 535 SD Card 2GB (replacement)

MCM 35 SD-CARD

FG030821 FG020325

SLM 35 No.: FG030820

Loop Circuit Module SLM 35 Additional module for connecting the ASD 535 to the Integral loop circuit. Operation, configuration and querying of data from the ASD 535 can be carried out directly from the fire alarm control panel. Shipped including fitting kit. Operating voltage: 5 V DC Current consumption: max. 20 mA Dimensions: 58 x 95 x 17 mm (HxWxD)
Description Type Art. No.

Loop Circuit Module SLM 535

SLM 35

FG030820

RIM 35 No.: FG030822

Relay module RIM 35 Additional module for fitting in the ASD 535 with five relays (potential-free change-over contacts). The module guarantees that the three pre-signal levels as well as the contamination/blockage statuses are available. The relays can be freely programmed in accordance with any control criteria, while a maximum of two RIM 35 units can be used per ASD 535. Shipped including fitting kit. Operating voltage: 5 V DC Current consumption: max. 15 mA Load for relay contact: max. 50 V DC/1 A/30 W Dimensions: 58 x 97 x 17 mm (HxWxD)
Description Type Art. No.

Relay Interface Module RIM 35

RIM 35

FG030822

Software for AirSCREEN ASD 535 The ASD PIPEFLOW calculation software is used for programming an aspiring line pursuant to EN 54-20. The ASD CONFIG configuration software is used for commissioning and configuring the ASD 535. Prerequisites: WIN XP/Vista, 1 GB RAM, 50 MB HD space
Description Type Art. No.

ASD PIPEFLOW calculation software ASD CONFIG configuration software USB connection cable ASD 535/PC (4.5m)

ASD PIPEFLOW ASD CONFIG KAB USB 45

FG030850 FG030851 FG022052

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

91

Special detectors Smoke aspirating system AirSCREEN ASD 535

DFU 535L No.: FG030386

DFU 535L EP No.: FG030387

Dust Filter Unit DFU 535L For installation in the aspirating pipe before the smoke aspirating systems highly sensitive smoke sensor in mildly dusty environments. Including filter cartridge, two PVC reduction units from 5/4 to 40 mm and two reduction units from 40 mm to 25 mm. Filter area: 1.200 cm Protection class: IP 65 Ambient temperature: 0 C to +60 C Dimensions: 165 x 220 x 220 mm (HxWxD) Case: ST 37, black Diameter of pipe connection: 40 or 25 mm Dust Filter Unit DFU 535XL For installation in the aspirating pipe before the smoke aspirating systems highly sensitive smoke sensor in normal to extremely dusty environments. Including filter cartridge, two PVC reduction units from 5/4 to 40 mm and two reduction units from 40 mm to 25 mm. Filter area: 3.400 cm Protection class: IP 65 Ambient temperature: 0 C to +60 C Dimensions: 230 x 250 x 250 mm (HxWxD) Case: ST 37, black Diameter of pipe connection: 40 or 25 mm
Description Type Art. No.

DFU 535XL No.: FG030388

Cartridges for air filter DFU 535L Replacement cartridge for DFU 535L Cartridges for air filter DFU 535XL Replacement cartridge for DFU 535XL

DFU 535L DFU 535L EP DFU 535XL DFU 535XL EP

FG030386 FG030387 FG030388 FG030389

REK 511 No.: FG030150

SSD 515-1S No.: FG030379

Individual area detection unit REK 511 For fitting in the individual pipe branches of the aspirating line of the smoke aspirating system for individual area detection. The alarm state of the triggered smoke detector is displayed using a Plexiglas stem on the surface of the case (LED). Shipped including 143 A detector base and 2 pcs. M32 connection joints, the smoke detector of type SSD 515-1S, -2S, or -3S must be ordered separately (see below for sensitivity). Operating voltage: 18 to 28 VDC Quiescent current: 18 to 20 mA Alarm current: 25 to 30 mA Suitable smoke detectors: SSD 515-1S: 1,2%/m (standard) SSD 515-2S: 0,6%/m (sensitive) SSD 515-3S: 0,3%/m (high sensitivity) Connection: screw clips, maximum 1.5 mm Cable inlet: for cables with diameter of up to 6 mm Protection class: IP 53 Ambient temperature: 0 to +50C Dimensions: 122 x 186 x 85 mm (HxWxD) Case: ABS, UL 94-V0; light grey RAL 7035 Weight: ca. 580 g
Description Type Art. No.

Single detector for RAS SSD 515-1S smoke detector SSD 515-2S smoke detector SSD 515-3S smoke detector

REK 511 SSD 515-1S SSD 515-2S SSD 515-3S

FG030150 FG030379 FG030380 FG030381


B-HB-008EN

92

Product catalogue fire alarm systems 2011 V 2.0

Special detectors Smoke aspirating system AirSCREEN ASD 535

Standard aspirating line material


The aspirating line forms part of the device approval for the ASD 535 (EN 54-20), for which reason only the materials listed hereafter may be used.
Description Type Art. No.

PVC pipe d25, 5m length

RAS R25

FG020805

PVC arch 90 d25

RAS B9025

FG020806

PVC angle 45 d25

RAS W4525

FG020808

PVC T piece d25

RAS T25

FG020809

PVC cross piece d25

RAS K25

FG020810

PVC coupling d25

RAS M25

FG020811

PVC terminal d25

RAS E25

FG020812

PVC fastening clamp IKS d25

RAS BSIKS25

MM000023

PVC terminal cap with thread d25

RAS VE25

FG020832

PVC connection coupling d25

RAS VE25M

FG020833

PVC connection joint PVC Clip d25/2,0mm PVC Clip d25/2,5mm PVC Clip d25/3,0mm PVC Clip d25/3,5mm PVC Clip d25/4,0mm PVC Clip d25/4,5mm PVC Clip d25/5,0mm PVC Clip d25/5,5mm PVC Clip d25/6,0mm PVC Clip d25/6,5mm PVC Clip d25/7,0mm PVC revision clip d25 Small funnel d25 Aspirating set for ceiling mounting M20 / 36 mm white, PVC

RAS V25 RAS CLP 2520 RAS CLP 2525 RAS CLP 2530 RAS CLP 2535 RAS CLP 2540 RAS CLP 2545 RAS CLP 2550 RAS CLP 2555 RAS CLP 2560 RAS CLP 2565 RAS CLP 2570 RAS CLP REV RAS KTR

FG020829 FG020840 FG020841 FG020842 FG020834 FG020835 FG020836 FG020843 FG020844 FG020845 FG020846 FG020847 FG020837 FG020855

SP M20 PVC-SET

FG020883

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

93

Special detectors Smoke aspirating system AirSCREEN ASD 535

Description

Type

Art. No.

Polywell tube 21.2 mm only for protection of premises! M20 straight quick locking adapter only for protection of premises! M20 PVC threaded ring only for projection of premises! PVC siphoning rose for PVC pipe d=25

RAS SCHL PW21

FG020860

RAS SCHL SV M20 RAS SCHL GR M20 RAS ASR

FG020861

FG020862

FG020863

Dust trap d25 160x250x90mm

RAS STF25

FG020850

Adhesive 0,5 kg Adhesive 1 kg

RAS KLK RAS KLG

FG020800 FG020801

Cleaner 1 Litre

RAS RNG

FG020802

Round brush 8mm

RAS RP8

FG020803

PVC-three way ballcock, d=25

RAS 3WKH25

FG020867

Filter box large d25 incl. filter, 120x122x85mm Replacement filter for filter case FG020864

RAS FKG25 RAS FM FKG

FG020864 FG020865

Water trap

RAS WATS

FG020881

Dust and centrifuge trap

RAS ST ZYKLON

FG020882

Cartridges for air filter DFU 535L Replacement cartridge for DFU 535L Cartridge-based air filter DFU 535XL, for very high levels of dust pollution Replacement cartridge for DFU 535XL

DFU 535L DFU 535L EP DFU 535XL DFU 535XL EP

FG030386 FG030387 FG030388 FG030389

REK 511 individual area detection unit Smoke detector for REK 511 1.2 %/m Smoke detector for REK 511 0.6 %/m Smoke detector for REK 511 0.3 %/m

RAS REK 511 RAS SSD 515-1S RAS SSD 515-2S RAS SSD 515-3S

FG030150 FG030379 FG030380 FG030381

94

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Special detectors Smoke aspirating system AirSCREEN ASD 535

Material for ABS aspirating lines in deepfreeze uses


The aspirating line forms part of the device approval for the ASD 535 (EN 54-20), for which reason only the materials listed hereafter may be used.
Description Type Art. No.

ABS pipe d25, 5m length

RAS R25 ABS

FG020789

ABS arch 90 d25

RAS B9025 ABS

FG020790

ABS angle 45 d25

RAS W4525 ABS

FG020791

ABS T piece d25

RAS T25 ABS

FG020792

ABS coupling d25

RAS M25 ABS

FG020794

ABS terminal d25

RAS E25 ABS

FG020795

ABS fastening clamp IKS d25

RAS BSIKS25

MM000023

ABS connection joint

RAS V25 ABS

FG020793

ABS aspirating fitting set with heating, red (aspirating point 5.7 mm corresponds to 3 mm)

HEAT 3.0 ABS

FG020870

ABS aspirating fitting set with heating, blue (aspirating point 6.1 mm corresponds to 3.5 mm)

HEAT 3.5 ABS

FG020872

ABS aspirating fitting set with heating, green (aspirating point 6.3 mm corresponds to 4.0 mm)

HEAT 4.0 ABS

FG020873

ABS aspirating fitting set with heating, black (aspirating point 6.7 mm corresponds to 4.5 mm)

HEAT 4.5 ABS

FG020875

ABS aspirating fitting set with heating, brown (aspirating point 7.1 mm corresponds to 5 mm)

HEAT 5.0 ABS

FG020877

ABS-cable connector set for cable splitting when there is pipe branching

CCF 25 ABS

FG020878

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

95

Special detectors Smoke aspirating system AirSCREEN ASD 535

Description

Type

Art. No.

Cable connection box for ASD535

WCU 535PC

FG030840

Silicon stranded wire white Silicon stranded wire black

SLW 0.5 WT SLW 0.5 BK

FG020879 FG020880

ABS Adhesive 1kg

RAS KLK ABS

FG020796

ABS cleaner 0,5 kg Round brush 8mm

RAS RNG ABS RAS RP8 RAS 3WKH25 ABS

FG020797 FG020803

ABS three way ballcock, d=25

FG020799

Filter box large d25 incl. filter, 120x122x85mm Replacement filter for filter case FG020864

RAS FKG25 RAS FM FKG

FG020864 FG020865

REK 511 individual area detection unit

RAS REK 511

FG030150

Smoke detector for REK 511 1.2 %/m Smoke detector for REK 511 0.6 %/m Smoke detector for REK 511 0.3 %/m

RAS SSD 515-1S RAS SSD 515-2S RAS SSD 515-3S

FG030379 FG030380 FG030381

96

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Special detectors Radio-linked detectors

7.6

Radio-linked detectors
Radio-linked smoke detector DOW 1171 Radio-linked wireless optical smoke detector for extending fire alarm systems in areas, where architectural aspects or particular operating processes do not allow wires to be laid (e.g. in historical buildings, hotels, museums etc.). The system comprises of one or more optical DOW 1171 radio-linked smoke detectors and a receiver unit (radio gateway with wireless module), which is connected directly to the Integral loop technology. The transmission of data between wireless smoke detectors and the receiver unit is bidirectional using the SRD waveband (868-870 MHz), thereby ensuring the highest possible degree of transmission security and operational security. The detector is supplied with power by two batteries, the receiver via the loop circuit. Up to 30 radio-linked smoke detectors can communicate with a single wireless module. Supplied including a detector base and 2 pcs. 9V batteries. Operating voltage: 2 Stk. 9V- lithium batteries Average current consumption: 68 A Battery operating life: > 5 years in normal use Frequency range: 868 to 870 MHz (SRD band) Channel spacing: 25 kHz Transmission strength: max. 5 mW Range in buildings: up to 40 m where there is intervisibility Aerials: double integrated aerials Protection class: IP 44 Ambient temperature: -10 to +55C Rel. air humidity: max. 95% at 34C Dimensions: 119 x 73 mm (D x H) Case material: PC / ABS plastic Colour: white, similar to RAL 9010 Weight: 335 g Radio approval: CE 0123 VdS-Approval: G200112 CPD-Certificate: 0786-CPD-20089 Battery for radio-linked smoke detectors and radio gateway The 9V lithium ultralife battery is used both for supplying power to the radio gateway (1 battery required for commissioning and for ensuring that the configuration settings are maintained during maintenance), as well as also acting as a replacement in the radio controlled detector (2 pcs). Caution: Due to their construction, the batteries are very vulnerable to impacts! System: Lithium/Mangan Dioxid Description: NEDA 1604 LC Rated voltage: 9V Leist Wattage ung: 1,2 Ah @ 900 to 5,4 V @ 23C Maximum discharge: 120 mA Ambient temperature: -20 to +60C Case: Aluminium/Mylar Safety: less than 2g lithium; no transport restrictions
Description Type Art. No.

DOW 1171 No.: FG030172

BATT FM No.: FG030173

Radio-linked smoke detector DOW 1171 Battery for radio-linked smoke detectors and radio gateway

DOW 1171 BATT FM

FG030172 FG030173

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

97

Special detectors Radio-linked detectors

SMF 121 No.: FG030176

Radio-linked manual call point For manually triggering a fire alarm in areas, where architectural aspects or particular operating processes mean that cables can only be laid with difficulty, or not at all. The alarm is triggered by smashing the glass panel and pressing the button. The detector communicates bidirectionally with the BX-RGW radio gateway over the 868-870 MHz Short Range Device frequency band. Power is supplied by 2 batteries (not supplied). Power supply: 2 Stk. 3,6V-lithium batteries Average current consumption: 60 A Battery life: at least 5 years in normal use Frequency range: 868 - 870 MHz (SRD) Frequency selection: 16 groups with 5 channels Channel spacing: 25 kHz Transmission strength: max. 5 mW Range in buildings: up to 40 m where there is intervisibility Aerials: double integrated aerials Protection class: IP 43 Ambient temperature: -10 to +55C Rel. air humidity: 95%, without condensation Dimensions: 125 x 125 x 57 mm (HxWxD) Case material: ABS Colour: red RAL 3000 Weight: 350 g Radio approval: CE 0123 VdS-Approval: G203060
Description Type Art. No.

SMF 121 Radio-linked Manual callpoint Radio detector base for SMF 121 Lithium battery 3.6 V Key for manual call point Replacement glass panel for SMF 6120

SMF 121 SMF 6120 SMF 6120 BATT DKM SV SMF 6120 GLAS

FG030176 FG030177 FG030178 FG020289 FG030187

Wireless testing device The FTG wireless testing device is used to check radio transmission conditions in situ (using a field strength check between two points) and supports the necessary number of detectors and gateways in the planning stage.
FTG No.: FG030174

Radiospy For configuration, commissioning and checking installed wireless detectors. This tool only works in combination with a PC or laptop and is user for measuring the strength of the fields (to assist in configuration), for observing and monitoring wireless communications, for changing the configuration of a wireless cell (e.g. changing detectors without reconfiguration).
Description Type Art. No.

Radio testing device DZW1171 Radiospy

FTG FRSP

FG030174 FG030175

98

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Special detectors Fire gas detectors

7.7

Fire gas detectors


Fire gas detector GSME Gas sensor with multiple criteria technology for use in environments where there is a heightened chance of risk, for selective detection of gases with characteristics of a fire, which are released in the initial phase of a fire (even where there is no open fire or visible smoke formation). The robust construction and the pressure cast aluminium case offers a high level of immunity against moisture and dust, with sources of interference e.g. vehicle exhaust fumes being filtered out by the multiple criteria evaluation. The standard connection cable (5m) with bayonet locking mechanism is not supplied as standard and must be ordered separately with all types of detector. Hose-proofing and detector heating elements must be ordered when the detector is ordered, since they are fitted in factory as optional extras. It is not possible to fit them afterwards, as the detector can not be guaranteed to work properly. Areas of use: Industry, coal processing, wood processing and wood-based industries, grain silos etc. (see technical documentation for details) Operating voltage: 40 VDC (min. 20V , max. 40V) Current uptake at 27V: GSME-L3/HC: 74 mA GSME-F: 93 mA GSME-FR: 130 mA Power consumption: GSME-L3/HC: 2,0VA GSME-F: 2,5VA GSME-FR: 3,5VA Electrical connection: Plug and socket connection with bayonet locking mechanism Installation type: Surface mounting Protection class: IP 64 Ambient temperature: -10 to +50C (briefly -20 to +60C) Rel. air humidity: 20 to 99% (non-condensing) Dimensions case: 60 x 100 x 100 mm (HxWxD) Case: coated aluminium pressure die case (corrosion resistant) Case colour: grey Weight: 0,6 kg
Description Type Art. No.

GSME-L3 No.: FG030950

GSME-L3 with alarm resistor 180R GSME-HC with alarm resistor 180R GSME-F with alarm resistor 180R GSME-FR with alarm resistor 180R standard connection cable 5m Hose-proofing protection for GSME-x Detector heating 24V for GSME-x Mounting plate f. GSME-x and connection box Connection box for GSME-x

GSME-L3 GSME-HC GSME-F GSME-FR GSME Kabel GSME SWS GSME MHZ GSME MPL GSME ASB

FG030950 FG030951 FG030952 FG030953 FG030954 FG030955 FG030956 FG030957 FG030958

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

99

Accessories Fire brigade key safe & plan case

8 Accessories
8.1 Fire brigade key safe & plan case
Fire brigade key safe conforming to NORM F 3032 For installing in the outside wall of a building for storing the building key in a thief-proof case. In the event of a fire, the fire brigade can open the door with their key and take out the keys to the building. Power consumption: Releasing building keys: Door opener: Buzzer: Equipotential bonding: Connection clips: Alarm current resistance: Profile half cylinder:

FSS No.: FG020507

FSS AP No.: FG020515

210 mA typ. 130 mA typ. 30 mA typ. 4 mm max. 1,5 mm 2,2 k 5% max. length: 40mm, lock measure: 30mm; stop lug can be rotated 45 Protection class: IP 44 Ambient temperature: -25 to +60C Dimensions of safe: 350 x 280 x 115 mm (HxWxD) Dimensions build-in frame: 300 x 270 x 140 mm (HxWxD) Dimensions surface mounted case: 352 x 282 x 130 mm (HxWxD) Material: Stainless steel Weight: 12,5 kg / 17 kg with build-in frame Approval: in accordance with NORM F 3032 Controller device For connecting the fire brigade key safe to the fire alarm control panel. Operating voltage: 24 VDC Quiescent current: 30 mA Protection class: IP 30 Ambient temperature: -10 to +50C Colour: red RAL 3000 Dimensions: 300 x 200 x 50 mm (HxWxD) Weight: 2 kg
Description Type Art. No.

FSS AD No.: FG020509

Fire Brigade Key Safe Flush mounted frame for key safe Surface mounted case for key safe Controller device for key safe Fire brigade cylinder MHZ52NI Austria Locking pin for key safe (replacement part) Sticker with Schrack logo (40 x 10 mm)

FSS FSS UP FSS AP FSS AD FSS ZYL A FSS AS S LOGO1

FG020507 FG020508 FG020515 FG020509 FG020510 FG020512 FG28407

100

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Fire brigade key safe & plan case

FSS FASB No.: FG020513

Fire brigade key box FASB In addition to the fire brigade key safe, without electronic unlocking, particularly suitable for storage of gate and engine room keys for fire brigade access, lift companies, electricians or emergency services. The panel mounting cylinder is not supplied and must be ordered separately. Dimensions: 150 x 150 x 57 mm (HxWxD) Colour: grey RAL 7032
Description Type Art. No.

Fire brigade key box FASB Fire brigade panel mounting cylinder MHZ52NI

FSS FASB FSS ZYL B

FG020513 FG020514

FWPK AP No.: FG020511

Fire brigade plan case Metal case for secure storage of documentation for the emergency services (e.g. alarm organisation, fire safety plans, detector zone directories, operating instructions for the fire alarm control panel etc.) in immediate reach from the fire alarm control panel conformant to TRVB S 115. The fire brigade plan cupboard is fitted with the fire brigade lock, which is also used on fire brigade control panels and manual call points. The box is supplied with one key and three mounting screws. Dimensions: 400 x 350 x 110 mm (HxWxD) Colour: red RAL 3000 Weight: ca. 4,5 kg
Description Type Art. No.

Fire brigade plan case Key (replacement) Fire brigade plans sign (replacement)

FWPK AP DKM SCHL S FWP

FG020511 FG020015 FG27800

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

101

Accessories Modems & converters

8.2

Modems & converters


Optic fibre modem RS485 / single mode Single mode optic fibre modems are used to connect Integral subcontrol units and are deployed in SecoNET fire alarm networks, if the connection between the individual control units is greater than 1,200 m or a single mode fibre optic connection (9/125m) is necessary. The fibre optic modems function in this process as an interface converter, from the Integral RS 422 / RS 485 interfaces to fibre optic cables. The modem to be used should be selected based on the type of fibres being used.

DL-485/13-SM-ST-L No.: FG021060

Operating voltage: Power uptake: Required battery capacity: Installation: Transmission type: Interface 1:
DL-485/13-SM-SC-A-L No.: FG021061

Interface 2 (1-fibres): Interface 2 (2-fibres): Range: Transmission speeds: Status - LEDs:

DL-485/13-SM-SC-B-L No.: FG021062

Ambient temperature: Dimensions: Case: Weight:


Description 2 fibres per modem section

SC/ST AD SM No.: FG021063

12 to 30 VDC max. 2,4 W (<100mA at 24V) 7,2 Ah for 72h supply interruption period 2,5 Ah for 24h supply interruption period on a 35 mm DIN top-hat rail Half duplex RS 485 on DB 9 and 6 pin screw connection clip 1 SC optic fibre connection; Single mode 9/125m 2 ST optic fibre connections; Single mode 9/125m typically 15 km (depending on the insulation of the fibres and the number of connections) up to 1.5 Mbit/s Power supply (green) Data received (yellow) Optical connection faulty (red) -10C to +55C (operating) -40C to +85C (storage) 115 x 61 x 113 mm (HxWxD) Stainless steel, powder-coated 500 g
Type Art. No.

Optic fibre modem RS485 single mode 1 channel, 2x fibre optic cables 9/125m, ST connector
1 fibre per modem section (only as pairs for channel A+B)

DL-485/13-SM-ST-L

FG021060

Optic fibre modem RS485 single mode Channel A, 1x fibre optic cable 9/125m, SC connector Optic fibre modem RS485 single mode Channel B, 1x fibre optic cable 9/125m, SC connector Adapter SC to ST single mode

DL-485/13-SM-SC-A-L DL-485/13-SM-SC-B-L SC/ST AD SM

FG021061 FG021062 FG021063

102

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Modems & converters

DL-485/13-MM-ST No.: FG021064

Optic fibre modem RS485 / multi mode Multi mode optic fibre modems are used to connect Integral subcontrol units and are deployed in SecoNET fire alarm networks, if the connection between the individual control units is greater than 1,200 m or a multi mode fibre optic connection (50(62)m) is necessary. The fibre optic modems function in this process as an interface converter, from the Integral RS 422 / RS 485 interfaces to fibre optic cables. The modem to be used should be selected based on the type of fibres being used.

Operating voltage: Power uptake: Required battery capacity: Installation: Transmission type: Interface 1: Interface 2 (1-fibres): Interface 2 (2-fibres): Range: Transmission speeds: Status - LEDs: Ambient temperature:
SC/ST AD MM No.: FG021067

DL-485/13-SM-SC-A No.: FG021065

DL-485/13-SM-SC-B No.: FG021066

Dimensions: Case: Weight:


Description 2 fibres per modem section

12 to 30 VDC max. 2,4 W (<100mA at 24V) 7,2 Ah for 72h supply interruption period 2,5 Ah for 24h supply interruption period on a 35 mm DIN top-hat rail Half duplex RS 485 on DB 9 and 6 pin screw connection clip 1 SC optic fibre connection Multi mode 50/125m 2 ST optic fibre connections Multi mode 50/125m typically 3 km (depending on insulation of the fibres and the number of connections) up to 1.5 Mbit/s Power supply (green) Data received (yellow) Optical connection faulty (red) -10C to +55C (operating) -40C to +85C (storage) 115 x 61 x 113 mm (HxWxD) Stainless steel, powder-coated 500 g
Type Art. No.

Optic fibre modem RS485 multi mode 1 channel, 2x fibre optic cables 50/125m, ST connector
1 fibre per modem section (only as pairs for channel A+B)

DL-485/13-MM-ST

FG021064

Optic fibre modem RS485 multi mode Channel A, 1 fibre, connector ST Optic fibre modem RS485 multi mode Channel B, 1 fibre, connector ST Adapter SC to ST multi mode

DL-485/13-SM-SC-A DL-485/13-SM-SC-B SC/ST AD MM

FG021065 FG021066 FG021067

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

103

Accessories Modems & converters

Telephone modem RS 422 / RS 485 Synchronous/asynchronous industrial modem, suitable both for telephony use (dedicated line), as for 2 and 4 wire operation for interconnecting Integral subcontrol units or SecoNET network if the distance between the subcontrol units is greater than 1,200 m and a optical fibre connection is not possible.
TD-36LV485 No.: FG021052

Operating voltage: Power uptake: Required battery capacity: Installation: Transmission types: Interface 1: Interface 2: Range: Transmission speed: LEDs: Ambient temperature: Rel. air humidity: Dimensions: Weight:
Description

12 to 48 VDC ca. 2 W (ca. 80 mA at 27 V ) 6.5 Ah (for 72 h supply interruption period) on a 35 mm DIN top-hat rail asynchronous, full duplex, half duplex or simplex EIA RS 422 / RS 485 / ITU-T V.11 5-pole screw-type terminal 2 or 4 core wire 4 pole screw-type terminal or dedicated telephone line over RJ-11 max. 24 km max. 33,6 kbps on wire max. 115 kbps on interface operation, TD, RD, RTS, DCD +5 to +50C 0 to 95%, non-condensing 100 x 55 x 128 mm (HxWxD) 300 g
Type Art. No.

Telephone modem RS 422 / 485

TD-36LV485

FG021052

ADAM 4520 No.: FG020212

Interface converter RS 232 to RS 422 / RS 485 Galvanically isolated interface converter for converting RS 232 to RS 422 / RS 485 for connecting Integral control panels to Maxima control panels, to superordinated control systems etc. If the interface converter is not fitted in the control panel, then an extra power supply is required. Operating voltage: Bit rate: Range RS 485/422: Range RS 232: Interfaces: Ambient temperature: Recommended cable types:
Description

10 to 30 VDC 115,2 kBit/sec. 1200 m 15 m RS 422 / RS 485 over screw-type terminals RS 232 using DB9-F 0 to +70C 2 x 2 x 0,5 twisted, unshielded e.g. MMI-BUS cable (L228022516)
Type Art. No.

Interface converter

ADAM 4520

FG020212

104

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Transmission devices

8.3

Transmission devices
SMS transmission device ComBOX As a communications medium for automatically forwarding information and events from the fire alarm system (e.g. alarm and fault messages, servicing requests etc.) via SMS. External data communications are carried out over the mobile phone network, with a built-in GSM modem being used to transmit the SMS. The data to be transmitted are filtered in the fire alarm control panel, transmitted to the ComBOX and then sent on from there to up to 100 freely- programmable telephone numbers.

COMBOX & COMBOX GEH No.: FG021010 & FG021006

ComBOX MFANT No.: FG021011

integrated dual band GPRS data modem (GSM900 / GSM1800) RS 422 / 485 interface for configuration and communications two RS 232 interfaces for communications 16 inputs, which can either be digitally or analogue controlled Remote configuration of important operating parameters by SMS/GPRS Power supplied by the fire alarm control panels batteries also in the event of a power failure up to a maximum of 100 participants (tel. nos.) can be freely configured Participants can be grouped Data transmission over GSM aerials Sheet steel case with top-hat rail in Integral Design 12 to 30 VDC ca. 100 mA without switching outputs and without modem GSM modem +5 to +55C 55 x 75 x 150mm (HxWxD) 300 x 345 x 100mm (HxWxD) red RAL 3000 IP 20 ca. 230 g 1 x RS 422 / RS 485 2 x RS 232 16 inputs, 8 outputs
Type Art. No.

Operating voltage: Current consumption: Data transmission: Ambient temperature: Dimensions ComBOX: Dimensions case: Case colour: Protection class: Weight: Interfaces:

ComBOX ANT WH No.: FG021012

Description

ComBOX ComBOX case, red, lockable Key for Integral MX/CX cabinets (replacement) ComBOX GSM aerial with magnetic foot with FME connector 5DB GSM aerial with wall mounting bracket and FME connector ComBOX case, red RAL3000, lockable RS232 to RS485/RS422 interface converter Service PC cable Glass tube fuse 2.5A T 5x20

COMBOX COMBOX GEH SCU LOCK KEY ComBOX MFANT ComBOX ANT WH ComBOX GEH ADAM 4520 KAB SPC ZUB SICH 2,5T

FG021010 FG021006 750000027 FG021011 FG021012 FG021006 FG020212 FG81719 IS625028

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

105

Accessories Transmission devices

MCP525-7 No.: FG020060

Manual call point MCP 525-7 For manually triggering a fire alarm, suitable for connection to the Integral DC technology. The detector can be used as an external manual call point (main detector) for TUS/Infranet controlling. The alarm is triggered by smashing the glass panel and pressing the button and then forwarded to the fire alarm control panel or directly to the emergency services. The built-in LED indicates the detectors triggered state. After pressing the alarm button, this button requires unlocking so that the system can be electronically reset at the fire alarm control panel. Operating voltage: Current consumption: Functional Principle: Installation type: Protection class: Ambient temperature: Dimensions: Case: Colour: Weight: VdS-Approval: CPD-Certificate:
Description

16,2 to 30 VDC prescribed by line technology used manual call point type B acc. to EN 54-11 Surface mounting IP 52 -10 to +55C 134 x 134 x 36 mm Plastic (ASA) red RAL 3001 450 g G 207007 0786-CPD-20294
Type Art. No.

MCP 525-7 manual call point red Hand symbol sticker Replacement glass panel Key

MCP525-7 MCP535 AK MCP535 GLAS DKM SCHL

FG020060 FG030230 FG030231 FG020015

2020E transmission device with case For transmitting hazard messages and/or technical alarms over an analogue telephone connection, in the form of spoken texts to as many telephone users as required, and/or in the form of digital signals to one or several alarm receiver systems. When connected to Schrack Seconet fire alarm control panels, a DC/DC stabiliser module must be used for converting the 24 V power into the 12V operating voltage required by the transmission device. Operating voltage: Quiescent current uptake: Operational current uptake: Dimensions: Environmental protection class: VdS-Approval:
Description

10,2 to 15 V DC ca. 30 mA at 12 V, ca. 20 mA at 24 V ca. 150 mA at 12 V, ca. 105 mA at 24 V 205 x 250 x 55 mm (HxWxD) class II acc. to VdS 2110 G105806
Type Art. No.

Comline 2002E/S3 DC / DC Stabiliser module

2002E DCDC STM

100073171 100046033

106

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Sirens & flashing lights

8.4

Sirens & flashing lights


Flashing light BL V4 RT Surface mounted flashing light to indicate a fire alarm visually. Operating voltage: 24 VDC Alarm current: 250 mA Flashing frequency: 1 Hz Protection class: IP 65 Ambient temperature: -25 to +40C Rel. air humidity: 95% at 40C Dimensions: 88 x 88 x 81 mm Weight: 240 g VdS-Approval: G28714
Description Type Art. No.

BL V4 RT No.: FG020147

Flashing Light V4 red Flashing Light V4 orange

BL V4 RT BL V4 OR

FG020147 FG020144

VTB01 No.: FG020342

VTB03 No.: FG020344

Combination siren and flashing light VTB Siren with built-in orange flashing light, suitable for indoor and outdoor usage. Sound type and volume can be set using DIP switches. The device is available in red or white and in protection classes IP 43 and IP 65. Operating voltage: 18 to 35 VDC Alarm current: 41 mA max. (dependent on sound) Signal volume: 78 to 98 dB @ 1 m @ 90 (dependent on sound) Signal frequency: 440 to 2900 Hz Types of tone: 32 (can be set) Protection class: IP 43 / IP 65 Ambient temperature: -20 to +70C Dimensions: IP 43: 93,6 x 89,6 mm (D x H) IP 65: 93,6 x 106,9 mm (D x H) Weight: IP 43: 233 g / IP 65: 258 g
Description Type Art. No.

Combined siren/flashing light - red case, IP43 Combined siren/flashing light - red case, IP65 Combined siren/flashing light - white case, IP43 Combined siren/flashing light - white case, IP65

VTB01 VTB02 VTB03 VTB04

FG020342 FG020343 FG020344 FG020345

BL D OR No.: FG020161

Revolving mirror light BL D OR Optical signalling device for indoor and outdoor installation. Shipped incl. halogen lamp. Operating voltage: 230 VAC Alarm current: 170 mA Mounting: on floor, or a bracket or on a pipe Rotating speed: 180 U/min. Protection class: IP 65 Ambient temperature: -30 to +60C Case: black, impact resistant ABS/polycarbonate Dome: Polycarbonate, shock-resistant, transparent amber Dimensions: 130,9 x 216 mm Weight: 680 g
Description Type Art. No.

Revolving mirror light orange 230V Wall mounting bracket


B-HB-008EN Product catalogue fire alarm systems 2011 V 2.0

BL D OR BL D ORW

FG020161 FG020162

107

Accessories Sirens & flashing lights

Siren SIR Y04 R To acoustically indicate a fire alarm, for indoor and outdoor use. 32 different alarm signals can be chosen from using a 5 way DIP switch. The device is available in red or white and in protection classes IP 54 and IP 65.
SIR Y04 R No.: FG020145

Operating voltage: Alarm current: Volume: Signal frequency: Connection: Protection class: Ambient temperature: Rel. air humidity: Case: Dimensions: Weight: VdS-Approval: CPD-Certificate:
Description

10 to 35 VDC 35 mA at 24 V 102 dB @ 1 m 800 to 1000 Hz screw clips, maximum 1.5 mm IP 54 or IP 65 -25 to +55C 95% at 40C red/white ABS 88 x 88 x 80,8 mm 215 g G28702 0086-CPD-496705
Type Art. No.

Siren Y04 red Siren Y04 red IP 65 Siren Y04 white Siren Y04 white IP 65

SIR Y04 R SIR Y04 R65 SIR Y04 W SIR Y04 W65

FG020145 FG020163 FG020218 upon request

CS200-W No.: FG020386

Siren CS 200 Signal emitter for acoustic signalling of a fire alarm in interior areas pursuant to EN 54-3. The device can be shipped in red or in white, has 32 different tone types, which can be set using a 5 switch DIP switch block. For every tone that is set, a second tone can be used as an addition alarm, with the volume being set using a rotary switch. Operating voltage: Alarm current: Volume: Connection: Possible tones (32): 18 to 28 VDC 16 mA at 24 VDC (tone 3) 100 dB(A) @ 1 m (tone 3) Screw clips, maximum 2.5 mm DIN: 1200 to 500 Hz Sweep: 800 to 970 Hz Alternating tone: 800 and 970 Hz IP 21c -10 to +55C red or white, ABS 96 x 62 mm 240 g G209123 0832-CPD-0523
Type Art. No.

CS200-R No.: FG020387

Protection class: Ambient temperature: Case: Dimensions: Weight: VdS-Approval: CPD-Certificate:


Description

CS200 warning tone siren white CS200 warning tone siren red

CS200-W CS200-R

FG020386 FG020387

108

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Sirens & flashing lights

ACW No.: FG020660

Siren for countersunk mounting ACW For acoustic indication of a fire alarm, suitable for installation in a standard installation case. The siren has 32 different types of tones, which are set using a 5 switch DIP switch block, with the volume setting being set using a rotary switch. Operating voltage: Current consumption: Signal volume: No. of sounds: Protection class: Ambient temperature: Material: Colour: Dimensions: Weight: VdS-Approval:
Description

9 to 28 VDC 6 to 35 mA 68 to 106 dB(A) typ. @ 1 m 32 (incl. DIN-tone) IP 54 (with fitting case) -25 to +70C ABS white 86 x 86 x 42 mm (HxWxD) ca. 100 g G206025
Type Art. No.

Siren for countersunk mounting

ACW

FG020660

Signal horn Loud small horn with sound funnel, suitable for indoor and outdoor installation. Available in a 24V or 230V version, with values which are different for the 230V version being listed in brackets. Operating voltage: Alarm current: Volume: Connection: Installation: Protection class: Ambient temperature: Colour: Dimensions: Weight: Case:
Description

SIR HUP1 No.: FG020177

24 VDC (230 VAC) 70 mA (15mA) 98 dB @ 1 m Screw connection, cable of up to 9mm with sound emission aperture facing downwards IP 43 -20 to +70C grey 170 x 70 x 78 mm 160 g ABS, impact resistant
Type Art. No.

Signal horn 24 V Signal horn 220V/30mA

SIR HUP1 SIR HUP2

FG020177 FG020178

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

109

Accessories Sirens & flashing lights

Alarm bell Robust motorised alarm bell with a sonorous tone and high sound output suitable for use indoors.
MBF-6WE No.: FG020270

Operating voltage: Alarm current: Signal volume: Ambient temperature: Air humidity: Case: Colour: Dimensions: Weight:
Description

24 VDC 15 mA 94 dB @ 1 m -10 bis+50C 45 to 85% Aluminium red 150 x 53 mm (DxH) 410 g


Type Art. No.

Alarm bell 24V

MBF-6WE

FG020270

CWB Flashing lights for hazardous areas For optical danger detection in areas with a risk of explosion of categories, 2G, 2D, 3G and 3D. The case is made of aluminium, thus making it suitable for use in all chemical, petrochemical and offshore facilities. The high protection class and the units stable mechanical construction also allow them to be used in the harshest operational conditions. Operating voltage range: Rated current draw: Rated power: Flash frequency: Flash energy: Connection type: Terminal range: Cable inlet: Protection class: Ambient temperature: Rel. air humidity: Dimensions: Case material: Dome material: Colour: Dome colour: Weight: Marking: Approval: Conformity certification:
Description

CWB EX GE No.: FG020381

22 to 26,5 V 230 mA 5,6 W ca. 1 Hz 5 Joule screw-type terminals max. 2 x 4 mm single core, max. 2 x 2,5 mm single core 1x gland seal connection joint M20 x1.5 terminal range 613 mm 1x connection gland, M20 x 1.5 IP 66 (EN 60529) -20 to +50C 90%, without condensation 70 x 260 mm (DxH) Aluminium alloy Polycarbonat (temperature resistant) Black base, yellow case red or yellow ca. 1,3 kg II 2G EEx de IIC T, II 2G EEx de IIC T, II 2D T 85 C IP66 LCIE 02 ATEX 6113 CE 0344 in accordance with 94/9EG
Type Art. No.

CWB ATEX flashing light for hazardous areas red CWB ATEX flashing light for hazardous areas yellow Wall mounting bracket

CWB EX RT CWB EX GE CWB EX WW

FG020380 FG020381 FG020382

110

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Sirens & flashing lights

Flashing light BL V6 EX for hazardous areas Robust explosion-proof flashing lights, suitable and approved for use in areas where there is a risk of explosion. Operating voltage: Peak current draw: Current consumption: Flashing frequency: Protection class: Ambient temperature: Dimensions: Colour: Weight: Ignition protection class: Approval:
Description

BL V6 EX No.: FG020276

24 VDC 2.5 A for a duration of ~100s when charging 860 mA typ. 1 Hz IP 66 -35 to +60C ca. 280 x 150 mm Case: red, Dome: orange 4,6 kg d (explosion proof) BAS 02 ATEX 0212X
Type Art. No.

Flashing light V6 for hazardous areas orange

BL V6 EX

FG020276

Siren Y04 EX for hazardous areas Robust intrinsically safe multisignal sirens, suitable and approved for use in areas where there is a risk of explosion. Operating voltage: Alarm current: Connection: Signal volume: Signal frequency: Protection class: Ambient temperature: Dimensions: Case colour: Weight: Approval:
Description

Y04 EX No.: FG020273

24 VDC (via Zener barrier) 23 mA screw clips, maximum 1.5 mm 99 dB @ 1 m 800 to 1000 Hz IP 55 -25 to +40C 178 x 88 x 80,8 mm red 430 g BAS 02 ATEX 0212 X
Type Art. No.

Siren YO4 for hazardous areas

Y04 EX

FG020273

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

111

Accessories Holding magnets

8.5

Holding magnets
Flexible armature Flexible armature for holding magnet on a plastic mounting plate Mounting is using four countersunk screws. Diameter of armature plate: 55 or 65 mm Dimensions: HM ANK01: 55 x 55 x 18 mm (HxWxD) HM ANK04: 75 x 75 x 23 mm (HxWxD)
Description Type Art. No.

HM ANK01 No.: FG020099

Flexible armature on mounting plate 55 mm Flexible armature on mounting plate 65 mm

HM ANK01 HM ANK04

FG020099 FG020227

HM ANK02 No.: FG020100

Swivelling armature Swivelling armature for holding magnet on a plastic mounting plate Mounting is using four countersunk screws. Diameter of armature plate: 55 mm (other diameters upon request) Swivel range: ca. 2 x 60 Dimensions: 55 x 55 x 50 mm (HxWxD)
Description Type Art. No.

Swivelling armature 55 mm

HM ANK02

FG020100

HM ANK03 No.: FG020226

Telescopic armature Moveable armature plate with telescopic damper. Mounting is using four countersunk screws. Diameter of armature plate: 55 mm Spring deflection: 20 mm Dimensions: 55 x 55 x 79 mm (HxWxD)
Description Type Art. No.

Telescopic armature

HM ANK03

FG020226

HM 04 No.: FG020222

Door holding magnet on mounting plate Electronic holding magnet on a plastic mounting place with concealed connection clips. Mounting is using four countersunk screws. Operating voltage: 24 VDC Wattage: 1,5 W Magnetic contact area: 50 mm (other diameters upon request) Maximum holding strength: 490 N Protection class: IP 40 Dimensions: 55 x 55 x 35 mm (HxWxD)
Description Type Art. No.

Door holding magnet on mounting plate

HM 04

FG020222

112

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Holding magnets

HM 02 No.: FG020098

Holding magnet for surface mounting Electromagnetic holding magnet with circuit breaker button in a plastic case for surface mounting. Supplied with PG cable glands and blanking stoppers. Operating voltage: 24 VDC Wattage: 1,5 W Magnetic contact area: 50 mm (other diameters upon request) Maximum holding strength: 490 N Protection class: IP 40 Dimensions: 120 x 85 x 38 mm (HxWxD)
Description Type Art. No.

Holding magnet for surface mounting

HM 02

FG020098

HM 05 No.: FG020223

Holding magnet for countersunk mounting Electronic holding magnet for countersunk fitting without a break key. Operating voltage: 24 VDC Wattage: 1,5 W Magnetic contact area: 63 mm Maximum holding strength: 700 N Protection class: IP 40 Dimensions: 85 x 85 x 15 mm (HxWxD)
Description Type Art. No.

Holding magnet for countersunk mounting

HM 05

FG020223

HM 06 No.: FG020224

Holding magnet for floor mounting Electromagnetic holding magnets for floor mounting in an aluminium case and with a circuit breaker button. The electronic connection is done before floor mounting, by connecting the unit to a two pole terminal. Operating voltage: 24 VDC Wattage: 1,5 W Magnetic contact area: 50 mm ( 63 mm upon request) Maximum holding strength: 490 N Protection class: IP 65 Dimensions: 109 x 120 x 86 mm (HxWxD)
Description Type Art. No.

Holding magnet for floor mounting

HM 06

FG020224

HM 07 No.: FG020225

Holding magnet for floor or wall mounting Electromagnetic holding magnets for floor or wall mounting in an aluminium case and with a circuit breaker button with a moveable head (can be fixed straight or at a right angle by means of a hexagon socket screw). Operating voltage: 24 VDC Wattage: 1,5 W Magnetic contact area: 50 mm Maximum holding strength: 490 N Protection class: IP 40 Dimensions: at right angles: 85 x 150 x 90 mm straight: 185 x 80 x 90 mm
Description Type Art. No.

Holding magnet for floor or wall mounting

HM 07

FG020225

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

113

Accessories Power supplies

8.6

Power supplies
12A Power supply unit BE-PSU12 It is used to supply peripheral devices with battery backed DC power in conformance with standards, for devices which can not be supplied with power by the fire alarm control panels power supply (e.g. smoke aspirating systems special detectors with a high quiescent current consumption). The BE-PSU12 power supply unit has an output voltage of 24 V and an output current of 12 A and is available in 2 different shapes. The CF version is suitable for fitting in an IP 54 wall-mounted cabinet, while the OF version is suitable for fitting in an IP 30 compact case. The mains supply voltage and the battery circuit are constantly monitored, with the loading current of the batteries being temperature-monitored. In the event of an overload, the maximum output current is limited accordingly, and in the event of the voltage falling below the cut-off voltage, low battery protection ensures that automatic load shedding occurs. Both devices are fitted with potential-free contacts, to allow the operating state to be queried and forwarded onto a superordinated system. Rated input voltage: Current uptake: Rated output voltage: Rated output current: Charge plateau voltage: Low battery protection and load shedding: Battery type: Mains fuse: Fuse DC battery circuit: Device fuse: Protection class: Ambient temperature: Dimensions CF version: Dimensions OF version: Weight: CPD-Certificate: VdS-Approval:
Description

PSU12-CF No.: 20-4000106-01

230 VAC (+10%-15%) max. 380 VA 24 VDC 12 A 27,4 VDC 0,4% (25C) 20,4 VDC 0,4% Lead rechargeable, no maintenance required 2 A, slow 15 A, FK2 10 x 1 A fairly slow IP 20 -5 to +40C 155 x 95 x 183 mm (HxWxD) 185 x 176 x 122 mm (HxWxD) ca 1,6 kg without battery 0786-CPD-20875 0786-CPD-20877 G209171, G209173
Type Art. No.

BE-PSU12-OF No.: 20-4000105-01

24V/12A power supply unit for IP 54 wall-mounted cabinet 24V/12A power supply unit for IP 30 compact case

BE-PSU12-CF BE-PSU12-OF

20-4000106-01 20-4000105-01

114

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Power supplies

Compact case BE-PSE12-C (24V / 12A / 65 Ah) With a built-in BE-PSU12-OF power supply unit, 10 monitored and an optional 10 additional output fuses. The cabinet includes space for fitting two rechargeable cells (max. 65 Ah). An input/output module can be fitted on the top-hat rail or directly connected to the power supply unit (for connection to the fire alarm control panel). The 4 LEDs on the front side of the unit are used for displaying the operating state. Case colour: Case dimensions: Protection class: Ambient temperature: Weight: CPD-Certificate: VdS-Approval:
Description

BE-PSE12-C No.: 20-4000100-01

light grey, RAL 7035 608 x 464 x 213 mm (HxWxD) IP 30 -5 to +40C ca 12,5 kg without batteries 0786-CPD-20875 G209171
Type Art. No.

24V/12A power supply unit in IP30 cabinet Basic fuse circuit board (replacement) Extension fuse circuit board (optional) BX-OI3 Input/Output module IP66 case for BX-OI3 (94 x 94 x 57mm) Fastening bracket for IP66 case Cylinder screw M5x10 for fastening bracket

BE-PSE12-C BE-FIB10 BE-FIE10 BX-OI3 GEH MOD IP66 BKL M5 MS ZS 05

20-4000100-01 20-4000107-01 20-4000108-01 20-2100001-01 FG020234 FG020238 MS00845010

Wall-mounted cabinet BE-PSE12-P45 (24V / 12A / 45Ah) With built-in BE-PSU12-CF power supply unit, 10 monitored and optional 10 extra output fuses, as well as including all clips required for connecting the peripherals and the rechargeable cells. The cabinet includes space for fitting two rechargeable cells (max. 45 Ah). An input/output module can be fitted next to the power supply unit (for connection to the fire alarm control panel). 12 pcs. M16 fitting screws and 8 pcs. M25/M16 reduction pieces supplied.
BE-PSE12-P45 o.: 20-4000101-01

Case colour: Case dimensions: Protection class: Ambient temperature: Weight: CPD-Certificate: VdS-Approval:
Description

light grey, RAL 7035 500 x 500 x 300 mm (HxWxD) IP 54 -5 to +40C ca 27,5 kg without batteries 0786-CPD-20877 G209173
Type Art. No.

24V/12A power supply unit in IP54 cabinet Temperature sensor for BE-PSE (replacement) Basic fuse circuit board (replacement) Extension fuse circuit board (optional) BX-OI3 Input/output module IP66 case for BX-OI3 (94 x 94 x 57mm) Fastening bracket for IP66 case Cylinder screw M5x10 for fastening bracket

BE-PSE12-P45 BE-TSENS BE-FIB10-P BE-FIE10-P BX-OI3 GEH MOD IP66 BKL M5 MS ZS 05

20-4000101-01 20-4000119-01 20-4000115-01 20-4000116-01 20-2100001-01 FG020234 FG020238 MS00845010

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

115

Accessories Power supplies

Wall-mounted cabinet BE-PSE12-P170 (24V / 12A / 85Ah) With built-in BE-PSU12-CF power supply unit, 10 monitored and optional 10 extra output fuses, as well as including all clips required for connecting the peripherals and the rechargeable cells. The cabinet includes space for fitting four rechargeable cells (max. 85 Ah). An input/output module can be fitted above the power supply unit (for connection to the fire alarm control panel). 12 pcs. M16 fitting screws and 8 pcs. M25/M16 reduction pieces supplied. Case colour: Case dimensions: Protection class: Ambient temperature: Weight: CPD-Certificate: VdS-Approval:
Description

BE-PSE12-P170 No.: 20-4000102-01

light grey, RAL 7035 1000 x 800 x 300 mm (HxWxD) IP 54 -5 to +40C ca 64,5 kg without batteries 0786-CPD-20877 G209173
Type Art. No.

24V/12A power supply unit in IP54 cabinet Basic fuse circuit board (replacement) Extension fuse circuit board (optional) Temperature sensor for BE-PSE (replacement) BX-OI3 Input/output module IP66 case for BX-OI3 (94 x 94 x 57mm) Fastening bracket for IP66 case Cylinder screw M5x10 for fastening bracket

BE-PSE12-P170 BE-FIB10-P BE-FIE10-P BE-TSENS BX-OI3 GEH MOD IP66 BKL M5 MS ZS 05

20-4000102-01 20-4000115-01 20-4000116-01 20-4000119-01 20-2100001-01 FG020234 FG020238 MS00845010

Wall-mounted cabinet BE-PSE24-P170 (24V / 24A / 170Ah) With two built-in BE-PSU12-CF (2 x 12A) power supply units, 10 monitored and optionally up to 3 x 10 extra output fuses, as well as including all clips required for connecting the peripherals and the rechargeable cells. The cabinet includes space for fitting up to four rechargeable cells (max. 85 Ah). An input/output module can be fitted above the power supply units (for connection to the fire alarm control panel). 12 pcs. M16 fitting screws and 8 pcs. M25/M16 reduction pieces supplied. Case colour: Case dimensions: Protection class: Ambient temperature: Weight: CPD-Certificate: VdS-Approval:
Description

BE-PSE24-P170 No.: 20-4000103-01

light grey, RAL 7035 1000 x 800 x 300 mm (HxWxD) IP 54 -5 to +40C ca 64,5 kg without batteries 0786-CPD-20877 G209173
Type Art. No.

2x 24V/12A power supply unit in IP54 cabinet Basic fuse circuit board (replacement) Extension fuse circuit board (optional) Temperature sensor for BE-PSE (replacement) BX-OI3 Input/output module IP66 case for BX-OI3 (94 x 94 x 57mm) Fastening bracket for IP66 case Cylinder screw M5x10 for fastening bracket

BE-PSE24-P170 BE-FIB10-P BE-FIE10-P BE-TSENS BX-OI3 GEH MOD IP66 BKL M5 MS ZS 05

20-4000103-01 20-4000115-01 20-4000116-01 20-4000119-01 20-2100001-01 FG020234 FG020238 MS00845010

116

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Power supplies

BE-PSU03-CF No.: 20-4000112-01

3A Power supply unit BE-PSU03 It is used to supply peripheral devices with battery backed DC power in conformance with standards, for devices which can not be supplied with power by the fire alarm control panels power supply (e.g. smoke aspirating systems special detectors with a high quiescent current consumption). The BE-PSU03 power supply unit has an output voltage of 24 V and an output current of 3 A and is available in 2 different shapes. The CF version is suitable for fitting in an IP 54 wall-mounted cabinet, while the OF version is suitable for fitting in an IP 30 compact case. The mains supply voltage and the battery circuit are constantly monitored, with the loading current of the batteries being temperature-monitored. In the event of an overload, the maximum output current is limited accordingly, and in the event of the voltage falling below the cut-off voltage, low battery protection ensures that automatic load shedding occurs. Both devices are fitted with potential-free contacts, to allow the operating state to be queried and forwarded onto a superordinated system. Rated input voltage: Current uptake: Rated output voltage: Rated output current: Charge plateau voltage: Low battery protection and load shedding: Battery type: Mains fuse: Fuse DC battery circuit: Device fuse: Protection class: Ambient temperature: Dimensions CF version: Dimensions OF version: Weight: CPD-Certificate: VdS-Approval:
Description

230 VAC (+10%-15%) max. 90 VA 24 VDC 3A 27,4 VDC 0,4% (25C) 20,4 VDC 0,4% Lead rechargeable, no maintenance required 2 A, slow 5 A, FK2/ FKS 5 x 1 A slow IP 20 -5 to +40C 155 x 75 x 128 mm (HxWxD) 185 x 126 x 120 mm (HxWxD) 1 kg 0786-CPD-20874, 0786-CPD-20876 G209170, G209172
Type Art. No.

BE-PSU03-OF No.: 20-4000111-01

24V/12A power supply unit for IP 54 wall-mounted cabinet 24V/3A power supply unit for IP 30 compact case

BE-PSU03-CF BE-PSU03-OF

20-4000112-01 20-4000111-01

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

117

Accessories Power supplies

BE-PSE03-C No.: 20-4000109-01

Compact case BE-PSE03-C (24V / 3A / 26Ah) With a built-in BE-PSU03-OF power supply unit, five monitored and an optional five additional output fuses. The cabinet includes space for fitting two rechargeable cells (max. 26 Ah). An input/output module can be fitted on the top-hat rail (for connection to the fire alarm control panel). The four LEDs on the front side of the unit are used for displaying the operating state. Case colour: Case dimensions: Protection class: Ambient temperature: Weight: CPD-Certificate: VdS-Approval:
Description

light grey, RAL 7035 608 x 464 x 145 mm (HxWxD) IP 30 -5 to +40C ca 12,5 kg without batteries 0786-CPD-20874 G209170
Type Art. No.

24V/3A power supply unit in IP30 cabinet Basic fuse circuit board (replacement) Extension fuse circuit board (optional) BX-OI3 Input/output module IP66 case for BX-OI3 (94 x 94 x 57mm) Fastening bracket for IP66 case Cylinder screw M5x10 for fastening bracket

BE-PSE03-C BE-FIB05 BE-FIE05 BX-OI3 GEH MOD IP66 BKL M5 MS ZS 05

20-4000109-01 20-4000113-01 20-4000114-01 20-2100001-01 FG020234 FG020238 MS00845010

Wall-mounted cabinet BE-PSE03-P (24V / 3A / 45Ah) With built-in BE-PSU03-CF power supply unit, five monitored and optional five extra output fuses, as well as all clips required for connecting the peripherals and the rechargeable cells. The cabinet includes space for fitting two rechargeable cells (max. 45 Ah). An input/output module can be fitted next to the power supply unit (for connection to the fire alarm control panel). 8 pcs. M16 fitting screws and 4 pcs. M25/M16 reduction pieces supplied.
BE-PSE03-P No.: 20-4000110-01

Case colour: Case dimensions: Protection class: Ambient temperature: Weight: CPD-Certificate: VdS-Approval:
Description

light grey, RAL 7035 500 x 500 x 300 mm (HxWxD) IP 54 -5 to +40C ca 25,5 kg without battery 0786-CPD-20876 G209172
Type Art. No.

24V/3A power supply unit in IP54 cabinet Basic fuse circuit board (replacement) Extension fuse circuit board (optional) Temperature sensor for BE-PSE (replacement) BX-OI3 Input/output module IP66 case for BX-OI3 (94 x 94 x 57mm) Fastening bracket for IP66 case Cylinder screw M5x10 for fastening bracket

BE-PSE03-P BE-FIB05-P BE-FIE05-P BE-TSENS BX-OI3 GEH MOD IP66 BKL M5 MS ZS 05

20-4000110-01 20-4000117-01 20-4000118-01 20-4000119-01 20-2100001-01 FG020234 FG020238 MS00845010

118

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Power supplies

Empty IP30 case for batteries For expanding rechargeable cell capacity, with space for fitting two rechargeable cells with max. 65 Ah. Protection class: Dimensions: Case colour: Weight:
BE-CBE12-C No.: 20-4000104-01 Description Type Art. No.

IP 30 608 x 464 x 213 mm (HxWxD) light grey, RAL 7035 11 kg without batteries

Empty IP30 case for batteries

BE-CBE12-C

20-4000104-01

Batteries for power supply unit cabinets


Description Type Art. No.

Battery 12 V / 17 Ah Battery 12 V / 24 Ah Battery 12 V / 38 Ah Battery 12 V / 65 Ah

AKKU 17 AKKU 24 AKKU 38 AKKU 65

HG691013 HG691023 HG691017 HG691018

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

119

Accessories Hold-open systems

8.7

Hold-open systems
Optical Smoke Switch ORS 142 For detecting smouldering and open fires with smoke formation, as well as for controlling hold-open systems on doors and gates. An additional temperature sensor is triggered when the ambient temperature reaches 70C, with the alarm threshold detection ensuring that the level of contamination is permanently monitored and the alarm threshold is therefore adapted automatically. The operating state of the unit is indicated visually by means of an LED. Operating voltage: 18 to 28 VDC Current draw at 28 VDC: idle: 21mA; alarm:10 mA, fault: 25mA Smoke detection: conforming to EN 54-7 Temperature: 70 C Relay contact: Opener Switching voltage: 30 VDC Switching current: 1A Switching power: 30 W Protection class: IP 42 Ambient temperature: -20 to +60C Dimensions incl. base: 80 x 65 mm (DxH) Colour: white, similar to RAL 9010 Weight: 120 g DIBt-Approval: Z-6.5-1571, Z-6.5-1725
Description Type Art. No.

ORS 142 No.: FG030600

143A No.: FG030602

Optical Smoke Switch ORS 142 Base 143A

ORS 142 143A

FG030600 FG030602

TDS 247 No.: FG030601

143A No.: FG030602

Rate-of-rise switch TDS 247 Temperature differential switch with maximum level for detecting open fires with or without smoke formation, when operating conditions mean that sources of interference like dust, smoke or steam are to be expected. Both the rate of temperature increase and the exceeding of a set threshold value are detected. The operating state of the unit is indicated visually by means of an LED. Operating voltage: 18 to 28 V DC Current draw at 28 VDC: idle: 21mA, alarm: 10mA, fault: 25mA Fire detection: temperature class A1 acc. to EN 54-5 Maximum range: +54 to +65C Relay contact: Opener Switching voltage: 30 VDC Switching current: 1A Switching power: 30 W Protection class: IP 42 Ambient temperature: -20 to +80C Dimensions incl. base: 80 x 65 mm (DxH) Colour: white, similar to RAL 9010 DIBt-Approval: Z-6.5-1571, Z-6.5-1725
Description Type Art. No.

Rate-of-rise switch TDS 247 Base 143A

TDS 247 143A

FG030601 FG030602

120

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Hold-open systems

143A No.: FG030602

Base 143A The 143A detector base with a bayonet fitting is suitable for attaching the ORS 142 optical smoke switch and the TDS 247 rate-of-rise switch for surface mounting in dry rooms. The electrical connection with the detector is by means of the base having contact springs enclosing the detectors connecting pins on two sides. The base has six terminals, with terminal 6 not having a connection to the detector, being intended merely as a supporting structure. Cable inlet: Protection class: Dimensions: Colour:
Description

max. 9 mm IP 42 80 x 33 mm (DxH) white, similar to RAL 9010


Type Art. No.

Base 143A

143A

FG030602

Manual triggering device HAT 02 Manual triggering device for installation in dry rooms, to manually actuate hold-open devices in accordance with DIBt regulations. Contact type: Switching voltage: Switching current: Protection class: Colour: Installation: Inscription:
Description

HAT 02 No.: FG030640

Opener 30 VDC 1A IP 20 Case white, rocker switch red Surface / countersunk mounting Tr schlieen
Type Art. No.

Manual triggering device HAT 02

HAT 02

FG030640

UT UP No.: FG020133

Break button To manually shut a fire prevention door, in order to checking whether the hold-open system is working properly even without a simulated fire.

Dimensions surface version: Dimensions countersunk version:


UT AP No.: FG020148 Description

80 x 80 x 35 mm (HxWxD) 80 x 80 mm (front plate), fits in countersunk mounting case 55mm


Type Art. No.

Countersunk mounting break button Surface mounting break button

UT UP UT AP

FG020133 FG020148

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

121

Accessories Hold-open systems

NG 519 No.: FG030630

Power supply unit NG 519 Power supply and triggering device for supplying smoke switches with power. The device contains a longitudinal controller and a thermal protection unit (special disablement technology to prevent the relay contacts from sticking in the event of a short circuit). Also there is a connection slot for fitting the extra SAB 04 circuit board. Rated input voltage: 230 VAC Current uptake: 21 VA Rated output voltage: 24 VDC Output current: 350 mA Output power: 8,4 W Relay contact: potential-free changeover contact Switching voltage: 30 VDC Switching current: 1A Switching power: 30 W Protection class: IP 30 Overvoltage category: II Ambient temperature: +5 to +40C Cable entry points: diameter 12 mm (2 on top, 3 below) Case material: Polycarbonate Colour: white, similar to RAL 9010 Installation: wall mounting, surface mounting DIBt-Approval: Z-6.5-1725
Description Type Art. No.

Power supply unit NG 519

NG 519

FG030630

FAD 01 No.: FG030631

Connection case FAD 01 The connection case for hold-open systems is used for connecting all components in a hold-open system. The connection for the smoke switch and the hold-open devices is electronically fuses at 900 mA, with this output also having the relevant relay contact available. This connection card contains special disablement technology to prevent the relay contacts from sticking in the event of a short circuit. Rated input voltage: 24 VDC Rated output voltage: 24 VDC Output current: 900 mA Output power: 21 W Relay contact: 1 potential-free, changeover contact Switching voltage: 250 VAC/ 30 VDC Switching current: 5 A @ 24 VDC, 3 A @ 30 VDC Protection class: IP 30 Ambient temperature: +5 to +40C Cable entry points: diameter 12 mm (2 on top, 3 below) Case: Polycarbonate Colour: white, similar to RAL 9010 Installation: on a wall, horizontally or vertically DIBt-Approval: Z-6.5-1571, Z-6.5-1725, Z-6.5-1871
Description Type Art. No.

Connection case FAD 01

FAD 01

FG030631

122

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Hold-open systems

SAB 04 SET No.: FG030632

Set signal indicator unit SAB 04 Set Connection card for saving alarm information if the connected smoke switch is triggered, with a red alarm LED and reset button. We recommend the SAB 04 when using optical and acoustic signalling devices, so that the signalling process is guaranteed to continue for the entire closing process until the reset occurs. To be fitted in NG 519, NAG 03 and NAG 04 power supply units and for fitting in FAD 01 connection cases.
Description Type Art. No.

Set signal indicator unit SAB 04 Set

SAB 04 SET

FG030632

SVG 522 No.: upon request

Power supply unit SVG 522 For hold-open systems with emergency power supplies for supplying power when there is an interruption in the power supply. Two emergency power supply batteries must be ordered separately. For fitting the door controller tableau (2 pcs. FAK 01) Short circuit resistance primary clocked maintenance-free emergency power supply Acoustic and visual announcement of power, battery and fuse failures, total discharge, processor faults and earth faults Indicator denotes readiness for operation Low battery protection and temperature protection Rated input voltage: 230 VAC Rated frequency: 50 Hz Current uptake: 48 VA Rated output voltage: 24 V DC Output voltage range: 21,6 to 27,6 V DC Output current: max. 1,3 A Output power: 43 W Battery charging monitor: yes Low voltage indication: <21 V DC Low battery protection: <20 V DC Fault indication: Power failure, battery fault, total discharge, earth fault Ambient temperature: +5 C to +40 C Protection class: IP 54 Case: sheet steel Cable inlets on top: 20 Colour: RAL 9010 Installation: wall mounted Weight without batteries: ca. 10 kg DIBt-Approval: Z-6.5-1725, Z-6.5-1871
Description Type Art. No.

SVG 522 Power supply unit Emergency power supply battery (2 pcs. required)

SVG 522

upon request upon request

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

123

Accessories Cables

8.8

Cables
Description Type Art. No.

Integral LAN data cable Cat 5e UTP (AWG24), halogen-free, red MMI-BUS cable red LF-2YY 2x2x0.5 MMI-BUS cable red LF-2YY 2x2x0.5, unshielded, halogen-free MMI-BUS cable red LF-2YACVY 1x2x0.5 shielded Earth cable 2x2x0.5 red Red shielded fire alarm cable 1x2x0.8 for Loop Technology Fire alarm cable blue shielded 1x2x0.8 for loop technology Red shielded fire alarm cable 1x2x0.8 for Loop Technology, halogen-free Fire alarm cable blue shielded 1x2x0.8 for loop technology (-20 to +105 ) Cable for high temperature detectors 2x0,75 orange (-50C to +180C) Fire alarm cable red 3x0.6 LF-XYY Fire alarm cable red 4x0.6 LF-XYY Fire alarm cable red F-YAY 10x2x0.6 Fire alarm cable red 2x0.6 LF-XYY Cable YMM 2x2.5 grey Cable YYSCH3x0.6 grey, 100m Cable YYSCH 5x0.6 grey, 100m Cable YMM-J red 3x1.5 without overprint Cable YMM-J red 3x2.5 without overprint

UTP 100 FRH KAB MMI RT KAB MMI RTHF KAB MMI RT S LI-2YCYV KAB 1*2*0,8 S KAB 1*2*0,8 S BL KAB 1*2*0,8 S HF JB-Y(ST)Y 1X2X0,8BL SIHF-O 2X0,75 KAB 3*0,6 RT KAB 4*0,6 RT KAB 10*2*0,6 RT KAB 2*0,6 KAB 2*2,5 KAB 3*0,6 GR KAB 5*0,6 GR KAB 3*1,5 KAB 3*2,5

20-4100000-01 L228022516 L228022520 L228022518 L228022519 L198200800 L198200802 L198200803 L198200805 L198275800 L198300607 L198400607 L225010267 L198200607 MM000110 MM000111 MM000112 MM000113 MM000114

124

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Inscription panels & stickers

8.9

Inscription panels & stickers


Description Dimensions Art. No.

Sticker Brandmelderzentrale

161 x 33 mm 173 x 51 mm 297 x 110 mm 173 x 51 mm 161 x 33 mm 242 x 51 mm

FG27812 FG27803 FG28405 FG27801 FG27810 FG27811

Sticker Brandmeldesystem Teilzentrale/Black box Sticker Externes Anzeigefeld Sticker Externe Energieversorgungseinrichtung fr Brandmeldeanlage Sticker Feuerwehrplne

297 x 105 mm

FG27800

Sticker with arrow Sticker red/white Brandmelder for detector labelling in false ceilings Sticker red/white Brandmelder for detector labelling in false ceilings Schrack Logo sticker black Grey ring stickers for MTD 533 (20 pcs.)

292 x 103 mm

FG27802

90 x 20 mm 87 x 27 mm 40 x 10 mm d=2 cm for labels up to 45 x 75 mm

FG27842 FG28406 FG28407 FG28422

Inscription panel for USB 501 detector base

FG030138

Detector inscription sign for high-ceilinged areas printed unprinted

120 x 175 mm 120 x 175 mm

FG28399 FG28398

Detector labelling card

80 x 55 mm

FG28400

Warning sticker Brandfallsteuerungen (6 pcs.) blank labels (6 pcs.)

174 x 15 mm 174 x 15 mm

FG28408 FG28409

Security seal (20 pcs.)

50 x 20 mm

FG28410

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

125

Accessories Printed items & brochures

8.10 Printed items & brochures


Brochures No. German No. English

Integral IP MX Integral IP CX Schrack Fire Alarm Systems High-End Operating Panel Network SecoNET Management System SecoLOG Multiple Sensor Detector MTD 533 Integral MX system overview Integral CX system overview Integral LAN system overview AirSCREEN ASD 535 ComBOX
Handbooks and printed items

B-PR-591DE B-PR-592DE B-PR-577D B-PR-579D 7PRST578-D B-PR-571D B-PR-585DE B-PR-595DE B-PR-596DE B-PR-597DE B-PR-590DE 7PRST586-D
No. German

B-PR-591EN B-PR-592EN B-PR-577E B-PR-579 7PRST578-E B-PR-571E B-PR-585EN B-PR-595EN B-PR-596EN B-PR-597EN B-PR-590EN -No. English

Integral MAP operating instructions Integral MAP brief operating instructions Log book for fire alarm systems SecoLOG operating instructions Product catalogue fire alarm systems 2010 Integral MX system description Integral CX system description Poster INTEGRAL IP (50 x 70 cm) Poster INTEGRAL MAP (50 x 70 cm) Poster AirSCREEN ASD 535 (50 x 70 cm) Poster MTD 533 (50 x 70 cm)
Forms

B-HB-020DE B-HB-021DE B-HB-003DE FG022027DE B-HB-010DE B-HB-014DE B-HB-014DE B-DS-010DE-EN B-DS-011DE-EN B-DS-012DE-EN B-DS-013DE-EN
No. German

B-HB-020EN B-HB-021EN -FG022027DE B-HB-008EN B-HB-014EN B-HB-014EN ----No. English

Handover log Commissioning log Function log Training log Defects log Hours & Inventory Maintenance log (NORM F 3070)

A-DS-200D A-DS-202D A-DS-204DE A-DS-205D A-DS-206D A-DS-207DE A-DS-208DE

--------

126

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Accessories Printed items & brochures

B-HB-008EN

Product catalogue fire alarm systems 2011 V 2.0

127

Accessories Printed items & brochures

SCHRACK SECONET AG A-1122 Vienna, Eibesbrunnergasse 18 Tel.: +43-1-81157-0 office@schrack-seconet.com Technical support Fire Alarm Systems Tel.: +43-1-81157-570 Branch offices Austria: A-6850 Dornbirn, Sebastianstrae 13a Tel.: +43-5572-51199-0 A-8055 Graz, Neuseiersberger Strae 157 Tel.: +43-316-407676-0 A-6021 Innsbruck, Valiergasse 56 Tel.: +43-512-365366-0 A-9020 Klagenfurt, Feldkirchner Strae 138 Tel.: +43-463-429362-0 A-4060 Leonding-Hart, Kornstrae 16 Tel.: +43-732-677900-0 A-5020 Salzburg, Vogelweiderstrae 44a Tel.: +43-662-887122-0
Czech Rep. CZ-100 00 Prague 10, V labin 1490/70 Tel.: +420-2-74782284 Hungary HU-1119 Budapest, Fehrvri t 89-95 Tel.: +36-1-4644300 Poland PL-02-583 Warsaw, ul. Wooska 9 Tel.: +48-22-3300620 Romania RO-021723 Bucharest, Sos.lancului nr. 6A, Sector 2 Tel.: +40-21-6533246 Russia RU-129626 Moscow, Ul. Staroalexejevskaja 5 Tel.: +7-495-510 50 15 Slovakia SK-83003 Bratislava 33, P.O. Box 31, Odborrska ul. 52 Tel.: +421-2-44635595 Sweden SE-145 53 Norsborg, Fgelviksvgen 9, Uppg. H Tel.: +46-8-680 18 60 Turkey TR-34722 Kadky-stanbul, Sokak no.: 5/12 Tel.: +90-216-345 51 99

Partner in BG BIH BY CH CY DK E EST ET F GE GR HR I IL IND IR KS KSA KWT KZ L LT LV MK NL P PK RB RL RO SLO SRB TM UA UAE UZ

128

Product catalogue fire alarm systems 2011 V 2.0

B-HB-008EN

Schrack Productions B-HB-008EN - V 2.0

Subject to technical modifications!