Rev. 1
1,2
XALL-9001
XALL-9002
XALL-9003
XALL-9004
PAL-9000
TAG NO.
XY-9000
XY-9000
XY-9000
BA-9001
XY-9000 12
CAUSE
NO. 10 11 13 17 18 19 20 21 22 23 24 25 26 27 28 29 30 TAG NO.
XSH/L-9001 XSH/L-9002 XSH/L-9003 XSH/L-9004 BE-9001 PAL-9000 TI-9001 TI-9001 PI-9001A PI-9001B PI-9001C PI-9001A PI-9001B PI-9001C PI-9001A PI-9001B PI-9001C
Staging skid stage stage 3 control valve opens Staging skid stage 3 control valve closes, purge cycle begins Stage 2 and Stage 3 control valves open, purge cycle begins, trouble alarm.
EFFECT
SYSTEM ACTION
Purge Alarm
ZA-9000
TI-9001
TI-9001
SERVICE Pilot 1 Flame Detection - No Flame Pilot 2 Flame Detection - No Flame Pilot 3 Flame Detection - No Flame Pilot 4 Flame Detection - No Flame Flame Scanner - Flame detected Purge Alarm Temperature Alarm (TAH@2000F) Temperature Alarm (TAHH@2100F) Staging manifold pressure exceeds 4.0 psig
NOTES 1 1 1 1 1 1,2 1 1 3
Staging manifold pressure drops below 0.6 psig with Stage 2 Open
1,2,4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
X X X X X X X X X
31 Page 1 of 2
PI-9001B
PI-9001A
PI-9001B
PI-9001A
TAG NO.
PI-9001C
PI-9001C
Alarms/Action Type: 1. Alarm. 2. Start Purge, ZAO-9003,9004 3. Open Staging Valves, ZAO-9001,9002 4. Close Staging Valves, ZAC-9001,9002 5. PI-9001A,B,C operate in 2oo3 logic. In the case one of the PI's are removed the remaining two operate with 2oo2 logic.
BPRV-9001
BPRV-9002
4/14/2011
CAUSE
Staging manifold pressure drops below 0.85 psig with Stage 3 Open
EFFECT
SYSTEM ACTION TAG NO. NOTES
NOTES 1 1,2,4
1,2,3 1,2,3 1,2,3 NO. 1 2 3 4 5 X X 7 8 9 10 11 X 12 X X X X X 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 X X 6 Pilot Failure Alarm Pilot Failure Alarm Pilot Failure Alarm Pilot Failure Alarm Flare Event Detected Purge Alarm 18 19 20 21 22 23 24 25 28
1 1 1 1 1 1,2
Temperature Alarm (TAH@2000F) Temperature Alarm (TAHH@2100F) Staging skid stage stage 2 control valve opens Staging skid stage 2 control valve closes, purge cycle begins
TI-9001 TI-9001 XY-9000 XY-9000 XY-9000 XY-9000 ZA-9000 Stage 2 Buckling Pin Failure Alarm Stage 3 Buckling Pin Failure Alarm ZAH-9002 ZAH-9001
1 1 3 1,2,4 3 1,2,4 1,2,3 1,2,3 1,2,3 Staging skid stage stage 3 control valve opens Staging skid stage 3 control valve closes, purge cycle begins Stage 2 and Stage 3 control valves open, purge cycle begins, trouble alarm.
Rev. 1
Page 2 of 2