You are on page 1of 14

INTERCONNECTION CABLE DETAILS FOR

220KV BUS COUPLER (BAY #01)

AREVA T&D INDIA Ltd.

PROJECT

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)

Date

Revision

OWNERS CONSULTANT

L&T S&L

31.08.2011

01

EPC CONTRACTOR

L&T POWER, VADODARA

CONTRACTORS CONSULTANT DCPL, KOLKATA


EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.
5257PN100 - MLW - E - SYD - INT - 0203-BAY 201

REFERENCE DRAWING:
Document No.

5257PN100-MLW-E-SYD-GAD-1683
5257PN100-MLW-E-SYD-GAD-1633
5257PN100-MLW-E-SYD-GAD-1633
220KV ANNEXURE-1
220KV ANNEXURE-1
5257PN100-MLW-E-SYD-SCH-1586
5257PN100-MLW-E-SYD-SCH-1524
5257PN100-MLW-E-SYD-SCH-3309
5257PN100-MLW-E-SYD-GAD-2501
LTSSTPP-AREVA-DWG-E-0011
5257PN100-MLW-E-SYD-ARR-0010
5257PN100-MLW-E-SYD-CAB-0045
<5257PN100-MLW-E-SYD-SCH-2214>
<5257PN100-MLW-E-SYD-SCH-2214>
<5257PN100-MLW-E-SYD-SCH-2103>
5257PN100-MLW-E-SYD-GAD-2354 & SCH-2355
5257PN100-MLW-E-SYD-GAD-2396 & SCH-2397
5257PN100-MLW-E-SYD-GAD-2370 & SCH-2371
5257PN100-MLW-E-SYD-GAD-2372 & SCH-2373

Revision
00
02
02
00
00
02
02
01
00
02
02
00
02
02
01
02
01
02
02

MADHYA PRADESH POWER


GENERATING COMPANY LIMITED

Prepared by

VVG

Checked by
Approved by

VVG
NAG

Document Name
245KV CVT Drawing Name Plate Details
245KV CT Drawing Name Plate Details
245KV TARIFF METERING CT Drawing Name Plate Details
245KV CT JB TERMINAL DISTRIBUTION
245KV CVT JB TERMINAL DISTRIBUTION
245KV ISOLATOR Scheme Drawing
245KV CIRCUIT BREAKER Scheme Drawing
400KV/220KV ICT Scheme Drawing
PLCC Drawing (ABB)
AC KIOSK Drawing
CONTROL ROOM BUILDING PANEL ARRANGEMENT Layout
CABLE TRENCH Layout
DCDB Drawings
ACDB Drawings
BMK Drawings
220KV CRP SCHEMATICS OF BUS COUPLER PROTECTION PANEL
220KV CRP SCHEMATICS OF BUS COUPLER & ICT#01 CONTROL PANEL
220KV CRP SCHEMATICS OF BUS BAR PROTECTION
220KV CRP SCHEMATICS OF ISLANDING PROTECTION

CABLE NUMBERING SYSTEM

01

001
CABLE SL. NO. STARTING FROM 001
AND INCREMENT SUBSEQUENTLY
THIS FIELD WILL BE SELECTED ON FOLLOWING CONDITIONS:
1 FOR CABLES WITHIN SWYD EQUIPMENTS.
2 FOR CABLES FROM SWYD EQPT/BMK/JB TO CONTROL & RELAY PANEL
3 FOR CABLES WITHIN CONTROL AND RELAY PANLES
4 AC/DC POWER CABLE FOR CRP/PLCC/RTCC.
BAY NUMBER (01)
SWITCHYARD
7 FOR 765KV SWYD
4 FOR 400KV SWYD
2 FOR 220KV SWYD
1 FOR 132/110KV SWYD

Note :
a) Loop length after glanding shall be sum of width & height of panel/Equipment cubicle.
b) Drum details/actual length shall be filled prior to cable laying at site
c) Drum cutting schedule to be prepared by site Engineer prior to cable laying/cutting.
1 OF 18

FOR 66KV SWYD

FOR 33KV SWYD

9
5

FOR 11KV SWYD


FOR AUX.SYSTEM

INTERCONNECTION CABLE DETAILS FOR


PROJECT

SL.
NO

AREVA T&D INDIA LTD.


CABLE NO.
EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201
SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

ROUTING DETAILS

220KV BUS COUPLER (BAY #01)

Date

Revision

31.08.2011

01

INTERCONNECTION DETAILS

Ferrule Nos.

Prepared by

VVG

Checked by

VVG

Approved by

NAG

APPLICATION

CORE

FROM

TO

FROM

TO

REF. DRAWING. NO :
SHEET NO.

CABLES WITHIN SWITCHYARD

1 2

01

1001

CT
2-1 CTA-R

2-1 CTA JB

10CX2.5

15

1,2
3.4
5,6
7,8
9,10

R1S1
R1S2
R1S3
R1S4
SPARE

TB1-1
TB1-2
TB1-3
TB1-4

-2-1 CTA JB-TB1-1 / R1S1


2-1 CTA JB-TB1-2 / R1S2
2-1 CTA JB-TB1-3 / R1S3
2-1 CTA JB-TB1-4 / R1S4

CT-2-1 CTA-R-R1S1 / TB1-1


2-1 CTA-R-R1S2 / TB1-2
2-1 CTA-R-R1S3 / TB1-3
2-1 CTA-R-R1S4 / TB1-4

2 2

01

1002

2-1 CTA-R

2-1 CTA JB

10CX2.5

15

1,2
3.4
5,6
7,8
9,10

R2S1
R2S2
R2S3
R2S4
SPARE

TB2-1
TB2-2
TB2-3
TB2-4

2-1 CTA JB-TB2-1 / R2S1


2-1 CTA JB-TB2-2 / R2S2
2-1 CTA JB-TB2-3 / R2S3
2-1 CTA JB-TB2-4 / R2S4

3 2

01

1003

2-1 CTA-R

2-1 CTA JB

10CX2.5

15

1,2
3.4
5,6
7,8
9,10

R3S1
R3S2
R3S3
R3S4
SPARE

TB3-1
TB3-2
TB3-3
TB3-4

4 2

01

1004

2-1 CTA-R

2-1 CTA JB

10CX2.5

15

1,2
3.4
5,6
7,8
9,10

R4S1
R4S2
R4S4
R4S4
SPARE

5 2

01

1005

2-1 CTA-R

2-1 CTA JB

10CX2.5

15

1,2
3.4
5,6
7,8
9,10

6 2

01

1006

2-1 CTA-Y

2-1 CTA JB

10CX2.5

10

7 2

01

1007

2-1 CTA-Y

2-1 CTA JB

10CX2.5

8 2

01

1008

2-1 CTA-Y

2-1 CTA JB

10CX2.5

9 2

01

1009

2-1 CTA-Y

2-1 CTA JB

10 2

01

1010

2-1 CTA-Y

11 2

01

1011

12 2

01

1012

CORE-1

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

2-1 CTA-R-R2S1 / TB2-1


2-1 CTA-R-R2S2 / TB2-2
2-1 CTA-R-R2S3 / TB2-3
2-1 CTA-R-R2S4 / TB2-4

CORE-2

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

2-1 CTA JB-TB3-1 / R3S1


2-1 CTA JB-TB3-2 / R3S2
2-1 CTA JB-TB3-3 / R3S3
2-1 CTA JB-TB3-4 / R3S4

2-1 CTA-R-R3S1 / TB3-1


2-1 CTA-R-R3S2 / TB3-2
2-1 CTA-R-R3S3 / TB3-3
2-1 CTA-R-R3S4 / TB3-4

CORE-3

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

TB4-1
TB4-2
TB4-3
TB4-4

2-1 CTA JB-TB4-1 / R4S1


2-1 CTA JB-TB4-2 / R4S2
2-1 CTA JB-TB4-3 / R4S4
2-1 CTA JB-TB4-4 / R4S4

2-1 CTA-R-R4S1 / TB4-1


2-1 CTA-R-R4S2 / TB4-2
2-1 CTA-R-R4S4 / TB4-3
2-1 CTA-R-R4S4 / TB4-4

CORE-4

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

R5S1
R5S2
R5S5
R5S5
SPARE

TB5-1
TB5-2
TB5-3
TB5-4

2-1 CTA JB-TB5-1 / R5S1


2-1 CTA JB-TB5-2 / R5S2
2-1 CTA JB-TB5-3 / R5S5
2-1 CTA JB-TB5-4 / R5S5

2-1 CTA-R-R5S1 / TB5-1


2-1 CTA-R-R5S2 / TB5-2
2-1 CTA-R-R5S5 / TB5-3
2-1 CTA-R-R5S5 / TB5-4

CORE-5

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

1,2
3.4
5,6
7,8
9,10

Y1S1
Y1S2
Y1S3
Y1S4
SPARE

TB1-5
TB1-6
TB1-7
TB1-8

2-1 CTA JB-TB1-5 / Y1S1


2-1 CTA JB-TB1-6 / Y1S2
2-1 CTA JB-TB1-7 / Y1S3
2-1 CTA JB-TB1-8 / Y1S4

2-1 CTA-Y-Y1S1 / TB1-5


2-1 CTA-Y-Y1S2 / TB1-6
2-1 CTA-Y-Y1S3 / TB1-7
2-1 CTA-Y-Y1S4 / TB1-8

CORE-1

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

10

1,2
3.4
5,6
7,8
9,10

Y2S1
Y2S2
Y2S3
Y2S4
SPARE

TB2-5
TB2-6
TB2-7
TB2-8

2-1 CTA JB-TB2-5 / Y2S1


2-1 CTA JB-TB2-6 / Y2S2
2-1 CTA JB-TB2-7 / Y2S3
2-1 CTA JB-TB2-8 / Y2S4

2-1 CTA-Y-Y2S1 / TB2-5


2-1 CTA-Y-Y2S2 / TB2-6
2-1 CTA-Y-Y2S3 / TB2-7
2-1 CTA-Y-Y2S4 / TB2-8

CORE-2

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

10

1,2
3.4
5,6
7,8
9,10

Y3S1
Y3S2
Y3S3
Y3S4
SPARE

TB3-5
TB3-6
TB3-7
TB3-8

2-1 CTA JB-TB3-5 / Y3S1


2-1 CTA JB-TB3-6 / Y3S2
2-1 CTA JB-TB3-7 / Y3S3
2-1 CTA JB-TB3-8 / Y3S4

2-1 CTA-Y-Y3S1 / TB3-5


2-1 CTA-Y-Y3S2 / TB3-6
2-1 CTA-Y-Y3S3 / TB3-7
2-1 CTA-Y-Y3S4 / TB3-8

CORE-3

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

10CX2.5

10

1,2
3.4
5,6
7,8
9,10

Y4S1
Y4S2
Y4S3
Y4S4
SPARE

TB4-5
TB4-6
TB4-7
TB4-8

2-1 CTA JB-TB4-5 / Y4S1


2-1 CTA JB-TB4-6 / Y4S2
2-1 CTA JB-TB4-7 / Y4S3
2-1 CTA JB-TB4-8 / Y4S4

2-1 CTA-Y-Y4S1 / TB4-5


2-1 CTA-Y-Y4S2 / TB4-6
2-1 CTA-Y-Y4S3 / TB4-7
2-1 CTA-Y-Y4S4 / TB4-8

CORE-4

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

2-1 CTA JB

10CX2.5

10

1,2
3.4
5,6
7,8
9,10

Y5S1
Y5S2
Y5S3
Y5S4
SPARE

TB5-5
TB5-6
TB5-7
TB5-8

2-1 CTA JB-TB5-5 / Y5S1


2-1 CTA JB-TB5-6 / Y5S2
2-1 CTA JB-TB5-7 / Y5S3
2-1 CTA JB-TB5-8 / Y5S4

2-1 CTA-Y-Y5S1 / TB5-5


2-1 CTA-Y-Y5S2 / TB5-6
2-1 CTA-Y-Y5S3 / TB5-7
2-1 CTA-Y-Y5S4 / TB5-8

CORE-5

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

2-1 CTA-B

2-1 CTA JB

10CX2.5

15

1,2
3.4
5,6
7,8
9,10

B1S1
B1S2
B1S3
B1S4
SPARE

TB1-9
TB1-10
TB1-11
TB1-12

2-1 CTA JB-TB1-9 / B1S1


2-1 CTA JB-TB1-10 / B1S2
2-1 CTA JB-TB1-11 / B1S3
2-1 CTA JB-TB1-12 / B1S4

2-1 CTA-B-B1S1 / TB1-9


2-1 CTA-B-B1S2 / TB1-10
2-1 CTA-B-B1S3 / TB1-11
2-1 CTA-B-B1S4 / TB1-12

CORE-1

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

2-1 CTA-B

2-1 CTA JB

10CX2.5

15

1,2
3.4
5,6
7,8
9,10

B2S1
B2S2
B2S3
B2S4
SPARE

TB2-9
TB2-10
TB2-11
TB2-12

2-1 CTA JB-TB2-9 / B2S1


2-1 CTA JB-TB2-10 / B2S2
2-1 CTA JB-TB2-11 / B2S3
2-1 CTA JB-TB2-12 / B2S4

2-1 CTA-B-B2S1 / TB2-9


2-1 CTA-B-B2S2 / TB2-10
2-1 CTA-B-B2S3 / TB2-11
2-1 CTA-B-B2S4 / TB2-12

CORE-2

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

201-BUS COUPLER_05.09.2011

Page 2 of 18

Cables within SWYD

INTERCONNECTION CABLE DETAILS FOR


PROJECT

SL.
NO

AREVA T&D INDIA LTD.


CABLE NO.
EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201
SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

ROUTING DETAILS

220KV BUS COUPLER (BAY #01)

Date

Revision

31.08.2011

01

INTERCONNECTION DETAILS

Ferrule Nos.

Prepared by

VVG

Checked by

VVG

Approved by

NAG

APPLICATION

CORE

FROM

TO

FROM

TO

REF. DRAWING. NO :
SHEET NO.

CABLES WITHIN SWITCHYARD


13 2

01

1013

2-1 CTA-B

2-1 CTA JB

10CX2.5

15

1,2
3.4
5,6
7,8
9,10

B3S1
B3S2
B3S3
B3S4
SPARE

TB3-9
TB3-10
TB3-11
TB3-12

2-1 CTA JB-TB3-9 / B3S1


2-1 CTA JB-TB3-10 / B3S2
2-1 CTA JB-TB3-11 / B3S3
2-1 CTA JB-TB3-12 / B3S4

2-1 CTA-B-B3S1 / TB3-9


2-1 CTA-B-B3S2 / TB3-10
2-1 CTA-B-B3S3 / TB3-11
2-1 CTA-B-B3S4 / TB3-12

CORE-3

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

14 2

01

1014

2-1 CTA-B

2-1 CTA JB

10CX2.5

15

1,2
3.4
5,6
7,8
9,10

B4S1
B4S2
B4S3
B4S4
SPARE

TB4-9
TB4-10
TB4-11
TB4-12

2-1 CTA JB-TB4-9 / B4S1


2-1 CTA JB-TB4-10 / B4S2
2-1 CTA JB-TB4-11 / B4S3
2-1 CTA JB-TB4-12 / B4S4

2-1 CTA-B-B4S1 / TB4-9


2-1 CTA-B-B4S2 / TB4-10
2-1 CTA-B-B4S3 / TB4-11
2-1 CTA-B-B4S4 / TB4-12

CORE-4

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

15 2

01

1015

2-1 CTA-B

2-1 CTA JB

10CX2.5

15

1,2
3.4
5,6
7,8
9,10

B5S1
B5S2
B5S3
B5S4
SPARE

TB5-9
TB5-10
TB5-11
TB5-12

2-1 CTA JB-TB5-9 / B5S1


2-1 CTA JB-TB5-10 / B5S2
2-1 CTA JB-TB5-11 / B5S3
2-1 CTA JB-TB5-12 / B5S4

2-1 CTA-B-B5S1 / TB5-9


2-1 CTA-B-B5S2 / TB5-10
2-1 CTA-B-B5S3 / TB5-11
2-1 CTA-B-B5S4 / TB5-12

CORE-5

CPD KN17 SC51 SHT02


CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02
CPD KN17 SC51 SHT02

16 2

01

1016

BCVT
2- B1CVT-R

2-1 CVT JB

7CX2.5

15

1,2
3,4
5,6
7

R1a1
SPARE
R1n
SPARE

TB1-1

2-1 CVT JB-TB1-1 / R1a1

2- B1CVT-R-R1a1 / TB1-1

WDG-1

TB1-3

2-1 CVT JB-TB1-3 / R1n

2- B1CVT-R-R1n / TB1-3

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

1,2
3,4
5,6
7

R2a1
SPARE
R2n
SPARE

TB2-1

2-1 CVT JB-TB2-1 / R2a1

2- B1CVT-R-R2a1 / TB2-1

WDG-2

TB2-3

2-1 CVT JB-TB2-3 / R2n

2- B1CVT-R-R2n / TB2-3

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

1,2
3,4
5,6
7

R3a1
SPARE
R3n
SPARE

TB3-1

2-1 CVT JB-TB3-1 / R3a1

2- B1CVT-R-R3a1 / TB3-1

WDG-3

TB3-3

2-1 CVT JB-TB3-3 / R3n

2- B1CVT-R-R3n / TB3-3

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

1,2
3,4
5,6
7

R4a1
SPARE
R4n
SPARE

TB4-1

2-1 CVT JB-TB4-1 / R4a1

2- B1CVT-R-R4a1 / TB4-1

WDG-4

TB4-3

2-1 CVT JB-TB4-3 / R4n

2- B1CVT-R-R4n / TB4-3

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

1,2
3,4
5,6
7

Y1a1
SPARE
Y1n
SPARE

TB1-4

2-1 CVT JB-TB1-4 / Y1a1

2- B1CVT-Y-Y1a1 / TB1-4

WDG-1

TB1-6

2-1 CVT JB-TB1-6 / Y1n

2- B1CVT-Y-Y1n / TB1-6

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

1,2
3,4
5,6
7

Y2a1
SPARE
Y2n
SPARE

TB2-4

2-1 CVT JB-TB2-4 / Y2a1

2- B1CVT-Y-Y2a1 / TB2-4

WDG-2

TB2-6

2-1 CVT JB-TB2-6 / Y2n

2- B1CVT-Y-Y2n / TB2-6

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

1,2
3,4
5,6
7

Y3a1
SPARE
Y3n
SPARE

TB3-4

2-1 CVT JB-TB3-4 / Y3a1

2- B1CVT-Y-Y3a1 / TB3-4

WDG-3

TB3-6

2-1 CVT JB-TB3-6 / Y3n

2- B1CVT-Y-Y3n / TB3-6

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

1,2
3,4
5,6
7

Y4a1
SPARE
Y4n
SPARE

TB4-4

2-1 CVT JB-TB4-4 / Y4a1

2- B1CVT-Y-Y4a1 / TB4-4

WDG-4

TB4-6

2-1 CVT JB-TB4-6 / Y4n

2- B1CVT-Y-Y4n / TB4-6

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

1,2
3,4
5,6
7

B1a1
SPARE
B1n
SPARE

TB1-7

2-1 CVT JB-TB1-7 / B1a1

2- B1CVT-B-B1a1 / TB1-7

WDG-1

TB1-9

2-1 CVT JB-TB1-9 / B1n

2- B1CVT-B-B1n / TB1-9

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

1,2
3,4
5,6
7

B2a1
SPARE
B2n
SPARE

TB2-7

2-1 CVT JB-TB2-7 / B2a1

2- B1CVT-B-B2a1 / TB2-7

WDG-2

TB2-9

2-1 CVT JB-TB2-9 / B2n

2- B1CVT-B-B2n / TB2-9

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

1,2
3,4
5,6
7

B3a1
SPARE
B3n
SPARE

TB3-7

2-1 CVT JB-TB3-7 / B3a1

2- B1CVT-B-B3a1 / TB3-7

WDG-3

TB3-9

2-1 CVT JB-TB3-9 / B3n

2- B1CVT-B-B3n / TB3-9

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

17 2

18 2

19 2

20 2

21 2

22 2

23 2

24 2

25 2

26 2

01

01

01

01

01

01

01

01

01

01

1017

1018

1019

1020

1021

1022

1023

1024

1025

1026

2- B1CVT-R

2- B1CVT-R

2- B1CVT-R

2- B1CVT-Y

2- B1CVT-Y

2- B1CVT-Y

2- B1CVT-Y

2- B1CVT-B

2- B1CVT-B

2- B1CVT-B

201-BUS COUPLER_05.09.2011

2-1 CVT JB

2-1 CVT JB

2-1 CVT JB

2-1 CVT JB

2-1 CVT JB

2-1 CVT JB

2-1 CVT JB

2-1 CVT JB

2-1 CVT JB

2-1 CVT JB

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

15

15

15

10

10

10

10

15

15

15

Page 3 of 18

Cables within SWYD

INTERCONNECTION CABLE DETAILS FOR


PROJECT

SL.
NO

AREVA T&D INDIA LTD.


CABLE NO.
EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201
SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

ROUTING DETAILS

220KV BUS COUPLER (BAY #01)

Date

Revision

31.08.2011

01

INTERCONNECTION DETAILS

Ferrule Nos.

Prepared by

VVG

Checked by

VVG

Approved by

NAG

APPLICATION

CORE

FROM

TO

FROM

TO

1,2
3,4
5,6
7

B4a1
SPARE
B4n
SPARE

TB4-7

2-1 CVT JB-TB4-7 / B4a1

2- B1CVT-B-B4a1 / TB4-7

TB4-9

2-1 CVT JB-TB4-9 / B4n

2- B1CVT-B-B4n / TB4-9

1,2
3,4
5,6
7

R1a1
SPARE
R1n
SPARE

TB1-1

2-2 CVT JB-TB1-1 / R1a1

2- B2CVT-R-R1a1 / TB1-1

TB1-3

2-2 CVT JB-TB1-3 / R1n

2- B2CVT-R-R1n / TB1-3

1,2
3,4
5,6
7

R2a1
SPARE
R2n
SPARE

TB2-1

2-2 CVT JB-TB2-1 / R2a1

2- B2CVT-R-R2a1 / TB2-1

TB2-3

2-2 CVT JB-TB2-3 / R2n

2- B2CVT-R-R2n / TB2-3

1,2
3,4
5,6
7

R3a1
SPARE
R3n
SPARE

TB3-1

2-2 CVT JB-TB3-1 / R3a1

2- B2CVT-R-R3a1 / TB3-1

TB3-3

2-2 CVT JB-TB3-3 / R3n

2- B2CVT-R-R3n / TB3-3

1,2
3,4
5,6
7

R4a1
SPARE
R4n
SPARE

TB4-1

2-2 CVT JB-TB4-1 / R4a1

2- B2CVT-R-R4a1 / TB4-1

TB4-3

2-2 CVT JB-TB4-3 / R4n

2- B2CVT-R-R4n / TB4-3

1,2
3,4
5,6
7

Y1a1
SPARE
Y1n
SPARE

TB1-4

2-2 CVT JB-TB1-4 / Y1a1

2- B2CVT-Y-Y1a1 / TB1-4

TB1-6

2-2 CVT JB-TB1-6 / Y1n

2- B2CVT-Y-Y1n / TB1-6

1,2
3,4
5,6
7

Y2a1
SPARE
Y2n
SPARE

TB2-4

2-2 CVT JB-TB2-4 / Y2a1

2- B2CVT-Y-Y2a1 / TB2-4

TB2-6

2-2 CVT JB-TB2-6 / Y2n

2- B2CVT-Y-Y2n / TB2-6

1,2
3,4
5,6
7

Y3a1
SPARE
Y3n
SPARE

TB3-4

2-2 CVT JB-TB3-4 / Y3a1

2- B2CVT-Y-Y3a1 / TB3-4

TB3-6

2-2 CVT JB-TB3-6 / Y3n

2- B2CVT-Y-Y3n / TB3-6

1,2
3,4
5,6
7

Y4a1
SPARE
Y4n
SPARE

TB4-4

2-2 CVT JB-TB4-4 / Y4a1

2- B2CVT-Y-Y4a1 / TB4-4

TB4-6

2-2 CVT JB-TB4-6 / Y4n

2- B2CVT-Y-Y4n / TB4-6

1,2
3,4
5,6
7

B1a1
SPARE
B1n
SPARE

TB1-7

2-2 CVT JB-TB1-7 / B1a1

2- B2CVT-B-B1a1 / TB1-7

TB1-9

2-2 CVT JB-TB1-9 / B1n

2- B2CVT-B-B1n / TB1-9

1,2
3,4
5,6
7

B2a1
SPARE
B2n
SPARE

TB2-7

2-2 CVT JB-TB2-7 / B2a1

2- B2CVT-B-B2a1 / TB2-7

TB2-9

2-2 CVT JB-TB2-9 / B2n

2- B2CVT-B-B2n / TB2-9

1,2
3,4
5,6
7

B3a1
SPARE
B3n
SPARE

TB3-7

2-2 CVT JB-TB3-7 / B3a1

2- B2CVT-B-B3a1 / TB3-7

TB3-9

2-2 CVT JB-TB3-9 / B3n

2- B2CVT-B-B3n / TB3-9

1,2
3,4
5,6
7

B4a1
SPARE
B4n
SPARE

TB4-7

2-2 CVT JB-TB4-7 / B4a1

2- B2CVT-B-B4a1 / TB4-7

TB4-9

2-2 CVT JB-TB4-9 / B4n

2- B2CVT-B-B4n / TB4-9

REF. DRAWING. NO :
SHEET NO.

CABLES WITHIN SWITCHYARD


27 2

28 2

29 2

30 2

31 2

32 2

33 2

34 2

35 2

36 2

37 2

38 2

39 2

01

01

01

01

01

01

01

01

01

01

01

01

01

1027

1028

1029

1030

1031

1032

1033

1034

1035

1036

1037

1038

1039

2- B1CVT-B

2- B2CVT-R

2- B2CVT-R

2- B2CVT-R

2- B2CVT-R

2- B2CVT-Y

2- B2CVT-Y

2- B2CVT-Y

2- B2CVT-Y

2- B2CVT-B

2- B2CVT-B

2- B2CVT-B

2- B2CVT-B

201-BUS COUPLER_05.09.2011

2-1 CVT JB

2-2 CVT JB

2-2 CVT JB

2-2 CVT JB

2-2 CVT JB

2-2 CVT JB

2-2 CVT JB

2-2 CVT JB

2-2 CVT JB

2-2 CVT JB

2-2 CVT JB

2-2 CVT JB

2-2 CVT JB

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

7CX2.5

15

15

15

15

15

10

10

10

10

15

15

15

15

Page 4 of 18

WDG-4

CPD KN17 SC51 SHT07


CPD KN17 SC51 SHT07
CPD KN17 SC51 SHT07

WDG-1

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

WDG-2

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

WDG-3

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

WDG-4

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

WDG-1

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

WDG-2

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

WDG-3

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

WDG-4

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

WDG-1

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

WDG-2

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

WDG-3

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

WDG-4

CPD KN17 SC51 SHT08


CPD KN17 SC51 SHT08
CPD KN17 SC51 SHT08

Cables within SWYD

INTERCONNECTION CABLE DETAILS FOR


PROJECT

SL.
NO

AREVA T&D INDIA LTD.


CABLE NO.
EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201
SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

220KV BUS COUPLER (BAY #01)

Date

Revision

31.08.2011

01

INTERCONNECTION DETAILS

ROUTING DETAILS

Ferrule Nos.

Prepared by

VVG

Checked by

VVG

Approved by

NAG

APPLICATION

CORE

FROM

TO

FROM

TO

REF. DRAWING. NO :
SHEET NO.

CABLES WITHIN SWITCHYARD

40 2

01

CB INTERPOLE CABLING
1040
CB-R

CBCC

19CX2.5

20

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

TB1-10
TB1-16
TB1-9
TB1-11
TB1-14
TB1-17
TB1-19
TB1-7
TB1-8
TB1-18
TB1-12
TB1-13
TB1-15
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

TB1-10
TB1-16
TB1-9
TB1-11
TB1-14
TB1-17
TB1-19
TB1-7
TB1-8
TB1-18
TB1-12
TB1-13
TB1-15

CBCC-TB1-10 / TB1-10
CBCC-TB1-16 / TB1-16
CBCC-TB1-9 / TB1-9
CBCC-TB1-11 / TB1-11
CBCC-TB1-14 / TB1-14
CBCC-TB1-17 / TB1-17
CBCC-TB1-19 / TB1-19
CBCC-TB1-7 / TB1-7
CBCC-TB1-8 / TB1-8
CBCC-TB1-18 / TB1-18
CBCC-TB1-12 / TB1-12
CBCC-TB1-13 / TB1-13
CBCC-TB1-15 / TB1-15

CB-R-TB1-10 / TB1-10
CB-R-TB1-16 / TB1-16
CB-R-TB1-9 / TB1-9
CB-R-TB1-11 / TB1-11
CB-R-TB1-14 / TB1-14
CB-R-TB1-17 / TB1-17
CB-R-TB1-19 / TB1-19
CB-R-TB1-7 / TB1-7
CB-R-TB1-8 / TB1-8
CB-R-TB1-18 / TB1-18
CB-R-TB1-12 / TB1-12
CB-R-TB1-13 / TB1-13
CB-R-TB1-15 / TB1-15

CLOSING COIL
CLOSING COIL
ANTI P/P
ANTI P/P
SF6 LOW PRE.
SF6 LOW PRE.
SF6 LOW PRE.
TC1
TC1
TC1
PD
PD
PD

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

41 2

01

1041

CB-R

CBCC

19CX2.5

20

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

TB1-22
TB1-23
TB1-26
TB1-24
TB1-25
TB1-29
TB1-30
TB1-31
TB1-32
TB1-33
TB1-34
TB1-27
TB1-28
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

TB1-22
TB1-23
TB1-26
TB1-24
TB1-25
TB1-29
TB1-30
TB1-31
TB1-32
TB1-33
TB1-34
TB1-27
TB1-28

CBCC-TB1-22 / TB1-22
CBCC-TB1-23 / TB1-23
CBCC-TB1-26 / TB1-26
CBCC-TB1-24 / TB1-24
CBCC-TB1-25 / TB1-25
CBCC-TB1-29 / TB1-29
CBCC-TB1-30 / TB1-30
CBCC-TB1-31 / TB1-31
CBCC-TB1-32 / TB1-32
CBCC-TB1-33 / TB1-33
CBCC-TB1-34 / TB1-34
CBCC-TB1-27 / TB1-27
CBCC-TB1-28 / TB1-28

CB-R-TB1-22 / TB1-22
CB-R-TB1-23 / TB1-23
CB-R-TB1-26 / TB1-26
CB-R-TB1-24 / TB1-24
CB-R-TB1-25 / TB1-25
CB-R-TB1-29 / TB1-29
CB-R-TB1-30 / TB1-30
CB-R-TB1-31 / TB1-31
CB-R-TB1-32 / TB1-32
CB-R-TB1-33 / TB1-33
CB-R-TB1-34 / TB1-34
CB-R-TB1-27 / TB1-27
CB-R-TB1-28 / TB1-28

TC-2
TC-2
TC-2
SF6 L/O
SF6 L/O
IND. CB CL
IND. CB CL
IND. CB OPEN
IND. CB OPEN
IND. CB SPRING CHARGED
IND. CB SPRING CHARGED
SPRING CHARGED NC
SPRING CHARGED NC

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

42 2

01

1042

CB-R

CBCC

24CX2.5

20

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
TB2-9
TB2-10
TB2-11
TB2-12
TB2-13
TB2-14
TB2-15
TB2-16
TB2-33
TB2-34
TB2-35
TB2-36
SPARE
SPARE
SPARE
SPARE

TB5-1
TB5-2
TB5-3
TB5-4
TB5-5
TB5-6
TB5-7
TB5-8
TB5-9
TB5-10
TB5-11
TB5-12
TB5-13
TB5-14
TB5-15
TB5-16
TB5-33
TB5-34
TB5-35
TB5-36

CBCC-TB5-1 / TB2-1
CBCC-TB5-2 / TB2-2
CBCC-TB5-3 / TB2-3
CBCC-TB5-4 / TB2-4
CBCC-TB5-5 / TB2-5
CBCC-TB5-6 / TB2-6
CBCC-TB5-7 / TB2-7
CBCC-TB5-8 / TB2-8
CBCC-TB5-9 / TB2-9
CBCC-TB5-10 / TB2-10
CBCC-TB5-11 / TB2-11
CBCC-TB5-12 / TB2-12
CBCC-TB5-13 / TB2-13
CBCC-TB5-14 / TB2-14
CBCC-TB5-15 / TB2-15
CBCC-TB5-16 / TB2-16
CBCC-TB5-33 / TB2-33
CBCC-TB5-34 / TB2-34
CBCC-TB5-35 / TB2-35
CBCC-TB5-36 / TB2-36

CB-R-TB2-1 / TB5-1
CB-R-TB2-2 / TB5-2
CB-R-TB2-3 / TB5-3
CB-R-TB2-4 / TB5-4
CB-R-TB2-5 / TB5-5
CB-R-TB2-6 / TB5-6
CB-R-TB2-7 / TB5-7
CB-R-TB2-8 / TB5-8
CB-R-TB2-9 / TB5-9
CB-R-TB2-10 / TB5-10
CB-R-TB2-11 / TB5-11
CB-R-TB2-12 / TB5-12
CB-R-TB2-13 / TB5-13
CB-R-TB2-14 / TB5-14
CB-R-TB2-15 / TB5-15
CB-R-TB2-16 / TB5-16
CB-R-TB2-33 / TB5-33
CB-R-TB2-34 / TB5-34
CB-R-TB2-35 / TB5-35
CB-R-TB2-36 / TB5-36

NO CONTACT

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

201-BUS COUPLER_05.09.2011

Page 5 of 18

NO CONTACT
NO CONTACT
NO CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NO CONTACT
NO CONTACT

Cables within SWYD

INTERCONNECTION CABLE DETAILS FOR


PROJECT

SL.
NO

AREVA T&D INDIA LTD.


CABLE NO.
EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201
SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

220KV BUS COUPLER (BAY #01)

Date

Revision

31.08.2011

01

INTERCONNECTION DETAILS

ROUTING DETAILS

Ferrule Nos.

Prepared by

VVG

Checked by

VVG

Approved by

NAG

APPLICATION

CORE

FROM

TO

FROM

TO

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

TB2-17
TB2-18
TB2-19
TB2-20
TB2-21
TB2-22
TB2-23
TB2-24
TB2-25
TB2-26
TB2-27
TB2-28
TB2-29
TB2-30
TB2-31
TB2-32
TB2-37
TB2-38
TB2-39
TB2-40
SPARE
SPARE
SPARE
SPARE

TB5-17
TB5-18
TB5-19
TB5-20
TB5-21
TB5-22
TB5-23
TB5-24
TB5-25
TB5-26
TB5-27
TB5-28
TB5-29
TB5-30
TB5-31
TB5-32
TB5-37
TB5-38
TB5-39
TB5-40

CBCC-TB5-17 / TB2-17
CBCC-TB5-18 / TB2-18
CBCC-TB5-19 / TB2-19
CBCC-TB5-20 / TB2-20
CBCC-TB5-21 / TB2-21
CBCC-TB5-22 / TB2-22
CBCC-TB5-23 / TB2-23
CBCC-TB5-24 / TB2-24
CBCC-TB5-25 / TB2-25
CBCC-TB5-26 / TB2-26
CBCC-TB5-27 / TB2-27
CBCC-TB5-28 / TB2-28
CBCC-TB5-29 / TB2-29
CBCC-TB5-30 / TB2-30
CBCC-TB5-31 / TB2-31
CBCC-TB5-32 / TB2-32
CBCC-TB5-37 / TB2-37
CBCC-TB5-38 / TB2-38
CBCC-TB5-39 / TB2-39
CBCC-TB5-40 / TB2-40

CB-R-TB2-17 / TB5-17
CB-R-TB2-18 / TB5-18
CB-R-TB2-19 / TB5-19
CB-R-TB2-20 / TB5-20
CB-R-TB2-21 / TB5-21
CB-R-TB2-22 / TB5-22
CB-R-TB2-23 / TB5-23
CB-R-TB2-24 / TB5-24
CB-R-TB2-25 / TB5-25
CB-R-TB2-26 / TB5-26
CB-R-TB2-27 / TB5-27
CB-R-TB2-28 / TB5-28
CB-R-TB2-29 / TB5-29
CB-R-TB2-30 / TB5-30
CB-R-TB2-31 / TB5-31
CB-R-TB2-32 / TB5-32
CB-R-TB2-37 / TB5-37
CB-R-TB2-38 / TB5-38
CB-R-TB2-39 / TB5-39
CB-R-TB2-40 / TB5-40

REF. DRAWING. NO :
SHEET NO.

CABLES WITHIN SWITCHYARD


43 2

01

1043

CB-R

CBCC

24CX2.5

20

NO CONTACT

NO CONTACT

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

NO CONTACT
NO CONTACT
NO CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NO CONTACT

44 2

01

1044

CB-Y

CBCC

19CX2.5

15

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

TB1-10
TB1-16
TB1-9
TB1-11
TB1-14
TB1-17
TB1-19
TB1-7
TB1-8
TB1-18
TB1-12
TB1-13
TB1-15
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

TB2-10
TB2-16
TB2-9
TB2-11
TB2-14
TB2-17
TB2-19
TB2-7
TB2-8
TB2-18
TB2-12
TB2-13
TB2-15

CBCC-TB2-10 / TB1-10
CBCC-TB2-16 / TB1-16
CBCC-TB2-9 / TB1-9
CBCC-TB2-11 / TB1-11
CBCC-TB2-14 / TB1-14
CBCC-TB2-17 / TB1-17
CBCC-TB2-19 / TB1-19
CBCC-TB2-7 / TB1-7
CBCC-TB2-8 / TB1-8
CBCC-TB2-18 / TB1-18
CBCC-TB2-12 / TB1-12
CBCC-TB2-13 / TB1-13
CBCC-TB2-15 / TB1-15

CB-Y-TB1-10 / TB2-10
CB-Y-TB1-16 / TB2-16
CB-Y-TB1-9 / TB2-9
CB-Y-TB1-11 / TB2-11
CB-Y-TB1-14 / TB2-14
CB-Y-TB1-17 / TB2-17
CB-Y-TB1-19 / TB2-19
CB-Y-TB1-7 / TB2-7
CB-Y-TB1-8 / TB2-8
CB-Y-TB1-18 / TB2-18
CB-Y-TB1-12 / TB2-12
CB-Y-TB1-13 / TB2-13
CB-Y-TB1-15 / TB2-15

CLOSING COIL
CLOSING COIL
ANTI P/P
ANTI P/P
SF6 LOW PRE.
SF6 LOW PRE.
SF6 LOW PRE.
TC1
TC1
TC1
PD
PD
PD

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

45 2

01

1045

CB-Y

CBCC

19CX2.5

15

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

TB1-22
TB1-23
TB1-26
TB1-24
TB1-25
TB1-29
TB1-30
TB1-31
TB1-32
TB1-33
TB1-34
TB1-27
TB1-28
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

TB2-22
TB2-23
TB2-26
TB2-24
TB2-25
TB2-29
TB2-30
TB2-31
TB2-32
TB2-33
TB2-34
TB2-27
TB2-28

CBCC-TB2-22 / TB1-22
CBCC-TB2-23 / TB1-23
CBCC-TB2-26 / TB1-26
CBCC-TB2-24 / TB1-24
CBCC-TB2-25 / TB1-25
CBCC-TB2-29 / TB1-29
CBCC-TB2-30 / TB1-30
CBCC-TB2-31 / TB1-31
CBCC-TB2-32 / TB1-32
CBCC-TB2-33 / TB1-33
CBCC-TB2-34 / TB1-34
CBCC-TB2-27 / TB1-27
CBCC-TB2-28 / TB1-28

CB-Y-TB1-22 / TB2-22
CB-Y-TB1-23 / TB2-23
CB-Y-TB1-26 / TB2-26
CB-Y-TB1-24 / TB2-24
CB-Y-TB1-25 / TB2-25
CB-Y-TB1-29 / TB2-29
CB-Y-TB1-30 / TB2-30
CB-Y-TB1-31 / TB2-31
CB-Y-TB1-32 / TB2-32
CB-Y-TB1-33 / TB2-33
CB-Y-TB1-34 / TB2-34
CB-Y-TB1-27 / TB2-27
CB-Y-TB1-28 / TB2-28

TC-2
TC-2
TC-2
SF6 L/O
SF6 L/O
IND. CB CL
IND. CB CL
IND. CB OPEN
IND. CB OPEN
IND. CB SPRING CHARGED
IND. CB SPRING CHARGED
SPRING CHARGED NC
SPRING CHARGED NC

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

201-BUS COUPLER_05.09.2011

Page 6 of 18

Cables within SWYD

INTERCONNECTION CABLE DETAILS FOR


PROJECT

SL.
NO

AREVA T&D INDIA LTD.


CABLE NO.
EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201
SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

220KV BUS COUPLER (BAY #01)

Date

Revision

31.08.2011

01

INTERCONNECTION DETAILS

ROUTING DETAILS

Ferrule Nos.

Prepared by

VVG

Checked by

VVG

Approved by

NAG

APPLICATION

CORE

FROM

TO

FROM

TO

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
TB2-9
TB2-10
TB2-11
TB2-12
TB2-13
TB2-14
TB2-15
TB2-16
TB2-33
TB2-34
TB2-35
TB2-36
SPARE
SPARE
SPARE
SPARE

TB6-1
TB6-2
TB6-3
TB6-4
TB6-5
TB6-6
TB6-7
TB6-8
TB6-9
TB6-10
TB6-11
TB6-12
TB6-13
TB6-14
TB6-15
TB6-16
TB6-33
TB6-34
TB6-35
TB6-36

CBCC-TB6-1 / TB2-1
CBCC-TB6-2 / TB2-2
CBCC-TB6-3 / TB2-3
CBCC-TB6-4 / TB2-4
CBCC-TB6-5 / TB2-5
CBCC-TB6-6 / TB2-6
CBCC-TB6-7 / TB2-7
CBCC-TB6-8 / TB2-8
CBCC-TB6-9 / TB2-9
CBCC-TB6-10 / TB2-10
CBCC-TB6-11 / TB2-11
CBCC-TB6-12 / TB2-12
CBCC-TB6-13 / TB2-13
CBCC-TB6-14 / TB2-14
CBCC-TB6-15 / TB2-15
CBCC-TB6-16 / TB2-16
CBCC-TB6-33 / TB2-33
CBCC-TB6-34 / TB2-34
CBCC-TB6-35 / TB2-35
CBCC-TB6-36 / TB2-36

CB-Y-TB2-1 / TB6-1
CB-Y-TB2-2 / TB6-2
CB-Y-TB2-3 / TB6-3
CB-Y-TB2-4 / TB6-4
CB-Y-TB2-5 / TB6-5
CB-Y-TB2-6 / TB6-6
CB-Y-TB2-7 / TB6-7
CB-Y-TB2-8 / TB6-8
CB-Y-TB2-9 / TB6-9
CB-Y-TB2-10 / TB6-10
CB-Y-TB2-11 / TB6-11
CB-Y-TB2-12 / TB6-12
CB-Y-TB2-13 / TB6-13
CB-Y-TB2-14 / TB6-14
CB-Y-TB2-15 / TB6-15
CB-Y-TB2-16 / TB6-16
CB-Y-TB2-33 / TB6-33
CB-Y-TB2-34 / TB6-34
CB-Y-TB2-35 / TB6-35
CB-Y-TB2-36 / TB6-36

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

TB2-17
TB2-18
TB2-19
TB2-20
TB2-21
TB2-22
TB2-23
TB2-24
TB2-25
TB2-26
TB2-27
TB2-28
TB2-29
TB2-30
TB2-31
TB2-32
TB2-37
TB2-38
TB2-39
TB2-40
SPARE
SPARE
SPARE
SPARE

TB6-17
TB6-18
TB6-19
TB6-20
TB6-21
TB6-22
TB6-23
TB6-24
TB6-25
TB6-26
TB6-27
TB6-28
TB6-29
TB6-30
TB6-31
TB6-32
TB6-37
TB6-38
TB6-39
TB6-40

CBCC-TB6-17 / TB2-17
CBCC-TB6-18 / TB2-18
CBCC-TB6-19 / TB2-19
CBCC-TB6-20 / TB2-20
CBCC-TB6-21 / TB2-21
CBCC-TB6-22 / TB2-22
CBCC-TB6-23 / TB2-23
CBCC-TB6-24 / TB2-24
CBCC-TB6-25 / TB2-25
CBCC-TB6-26 / TB2-26
CBCC-TB6-27 / TB2-27
CBCC-TB6-28 / TB2-28
CBCC-TB6-29 / TB2-29
CBCC-TB6-30 / TB2-30
CBCC-TB6-31 / TB2-31
CBCC-TB6-32 / TB2-32
CBCC-TB6-37 / TB2-37
CBCC-TB6-38 / TB2-38
CBCC-TB6-39 / TB2-39
CBCC-TB6-40 / TB2-40

CB-Y-TB2-17 / TB6-17
CB-Y-TB2-18 / TB6-18
CB-Y-TB2-19 / TB6-19
CB-Y-TB2-20 / TB6-20
CB-Y-TB2-21 / TB6-21
CB-Y-TB2-22 / TB6-22
CB-Y-TB2-23 / TB6-23
CB-Y-TB2-24 / TB6-24
CB-Y-TB2-25 / TB6-25
CB-Y-TB2-26 / TB6-26
CB-Y-TB2-27 / TB6-27
CB-Y-TB2-28 / TB6-28
CB-Y-TB2-29 / TB6-29
CB-Y-TB2-30 / TB6-30
CB-Y-TB2-31 / TB6-31
CB-Y-TB2-32 / TB6-32
CB-Y-TB2-37 / TB6-37
CB-Y-TB2-38 / TB6-38
CB-Y-TB2-39 / TB6-39
CB-Y-TB2-40 / TB6-40

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

TB1-10
TB1-16
TB1-9
TB1-11
TB1-14
TB1-17
TB1-19
TB1-7
TB1-8
TB1-18
TB1-12
TB1-13
TB1-15
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

TB3-10
TB3-16
TB3-9
TB3-11
TB3-14
TB3-17
TB3-19
TB3-7
TB3-8
TB3-18
TB3-12
TB3-13
TB3-15

CBCC-TB3-10 / TB1-10
CBCC-TB3-16 / TB1-16
CBCC-TB3-9 / TB1-9
CBCC-TB3-11 / TB1-11
CBCC-TB3-14 / TB1-14
CBCC-TB3-17 / TB1-17
CBCC-TB3-19 / TB1-19
CBCC-TB3-7 / TB1-7
CBCC-TB3-8 / TB1-8
CBCC-TB3-18 / TB1-18
CBCC-TB3-12 / TB1-12
CBCC-TB3-13 / TB1-13
CBCC-TB3-15 / TB1-15

CB-B-TB1-10 / TB3-10
CB-B-TB1-16 / TB3-16
CB-B-TB1-9 / TB3-9
CB-B-TB1-11 / TB3-11
CB-B-TB1-14 / TB3-14
CB-B-TB1-17 / TB3-17
CB-B-TB1-19 / TB3-19
CB-B-TB1-7 / TB3-7
CB-B-TB1-8 / TB3-8
CB-B-TB1-18 / TB3-18
CB-B-TB1-12 / TB3-12
CB-B-TB1-13 / TB3-13
CB-B-TB1-15 / TB3-15

REF. DRAWING. NO :
SHEET NO.

CABLES WITHIN SWITCHYARD


46 2

47 2

48 2

01

01

01

1046

1047

1048

CB-Y

CB-Y

CB-B

201-BUS COUPLER_05.09.2011

CBCC

CBCC

CBCC

24CX2.5

24CX2.5

19CX2.5

15

15

20

Page 7 of 18

NO CONTACT
NO CONTACT
NO CONTACT
NO CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NO CONTACT
NO CONTACT

NO CONTACT

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

NO CONTACT

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

CLOSING COIL
CLOSING COIL
ANTI P/P
ANTI P/P
SF6 LOW PRE.
SF6 LOW PRE.
SF6 LOW PRE.
TC1
TC1
TC1
PD
PD
PD

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

NO CONTACT
NO CONTACT
NO CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NO CONTACT

Cables within SWYD

INTERCONNECTION CABLE DETAILS FOR


PROJECT

SL.
NO

AREVA T&D INDIA LTD.


CABLE NO.
EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201
SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

220KV BUS COUPLER (BAY #01)

Date

Revision

31.08.2011

01

INTERCONNECTION DETAILS

ROUTING DETAILS

Ferrule Nos.

Prepared by

VVG

Checked by

VVG

Approved by

NAG

APPLICATION

CORE

FROM

TO

FROM

TO

REF. DRAWING. NO :
SHEET NO.

CABLES WITHIN SWITCHYARD


49 2

01

1049

CB-B

CBCC

19CX2.5

15

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

TB1-22
TB1-23
TB1-26
TB1-24
TB1-25
TB1-29
TB1-30
TB1-31
TB1-32
TB1-33
TB1-34
TB1-27
TB1-28
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

TB3-22
TB3-23
TB3-26
TB3-24
TB3-25
TB3-29
TB3-30
TB3-31
TB3-32
TB3-33
TB3-34
TB3-27
TB3-28

CBCC-TB3-22 / TB1-22
CBCC-TB3-23 / TB1-23
CBCC-TB3-26 / TB1-26
CBCC-TB3-24 / TB1-24
CBCC-TB3-25 / TB1-25
CBCC-TB3-29 / TB1-29
CBCC-TB3-30 / TB1-30
CBCC-TB3-31 / TB1-31
CBCC-TB3-32 / TB1-32
CBCC-TB3-33 / TB1-33
CBCC-TB3-34 / TB1-34
CBCC-TB3-27 / TB1-27
CBCC-TB3-28 / TB1-28

CB-B-TB1-22 / TB3-22
CB-B-TB1-23 / TB3-23
CB-B-TB1-26 / TB3-26
CB-B-TB1-24 / TB3-24
CB-B-TB1-25 / TB3-25
CB-B-TB1-29 / TB3-29
CB-B-TB1-30 / TB3-30
CB-B-TB1-31 / TB3-31
CB-B-TB1-32 / TB3-32
CB-B-TB1-33 / TB3-33
CB-B-TB1-34 / TB3-34
CB-B-TB1-27 / TB3-27
CB-B-TB1-28 / TB3-28

TC-2
TC-2
TC-2
SF6 L/O
SF6 L/O
IND. CB CL
IND. CB CL
IND. CB OPEN
IND. CB OPEN
IND. CB SPRING CHARGED
IND. CB SPRING CHARGED
SPRING CHARGED NC
SPRING CHARGED NC

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

50 2

01

1050

CB-B

CBCC

24CX2.5

15

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
TB2-9
TB2-10
TB2-11
TB2-12
TB2-13
TB2-14
TB2-15
TB2-16
TB2-33
TB2-34
TB2-35
TB2-36
SPARE
SPARE
SPARE
SPARE

TB7-1
TB7-2
TB7-3
TB7-4
TB7-5
TB7-6
TB7-7
TB7-8
TB7-9
TB7-10
TB7-11
TB7-12
TB7-13
TB7-14
TB7-15
TB7-16
TB7-33
TB7-34
TB7-35
TB7-36

CBCC-TB7-1 / TB2-1
CBCC-TB7-2 / TB2-2
CBCC-TB7-3 / TB2-3
CBCC-TB7-4 / TB2-4
CBCC-TB7-5 / TB2-5
CBCC-TB7-6 / TB2-6
CBCC-TB7-7 / TB2-7
CBCC-TB7-8 / TB2-8
CBCC-TB7-9 / TB2-9
CBCC-TB7-10 / TB2-10
CBCC-TB7-11 / TB2-11
CBCC-TB7-12 / TB2-12
CBCC-TB7-13 / TB2-13
CBCC-TB7-14 / TB2-14
CBCC-TB7-15 / TB2-15
CBCC-TB7-16 / TB2-16
CBCC-TB7-33 / TB2-33
CBCC-TB7-34 / TB2-34
CBCC-TB7-35 / TB2-35
CBCC-TB7-36 / TB2-36

CB-B-TB2-1 / TB7-1
CB-B-TB2-2 / TB7-2
CB-B-TB2-3 / TB7-3
CB-B-TB2-4 / TB7-4
CB-B-TB2-5 / TB7-5
CB-B-TB2-6 / TB7-6
CB-B-TB2-7 / TB7-7
CB-B-TB2-8 / TB7-8
CB-B-TB2-9 / TB7-9
CB-B-TB2-10 / TB7-10
CB-B-TB2-11 / TB7-11
CB-B-TB2-12 / TB7-12
CB-B-TB2-13 / TB7-13
CB-B-TB2-14 / TB7-14
CB-B-TB2-15 / TB7-15
CB-B-TB2-16 / TB7-16
CB-B-TB2-33 / TB7-33
CB-B-TB2-34 / TB7-34
CB-B-TB2-35 / TB7-35
CB-B-TB2-36 / TB7-36

NO CONTACT

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

TB2-17
TB2-18
TB2-19
TB2-20
TB2-21
TB2-22
TB2-23
TB2-24
TB2-25
TB2-26
TB2-27
TB2-28
TB2-29
TB2-30
TB2-31
TB2-32
TB2-37
TB2-38
TB2-39
TB2-40
SPARE
SPARE
SPARE
SPARE

TB7-17
TB7-18
TB7-19
TB7-20
TB7-21
TB7-22
TB7-23
TB7-24
TB7-25
TB7-26
TB7-27
TB7-28
TB7-29
TB7-30
TB7-31
TB7-32
TB7-37
TB7-38
TB7-39
TB7-40

CBCC-TB7-17 / TB2-17
CBCC-TB7-18 / TB2-18
CBCC-TB7-19 / TB2-19
CBCC-TB7-20 / TB2-20
CBCC-TB7-21 / TB2-21
CBCC-TB7-22 / TB2-22
CBCC-TB7-23 / TB2-23
CBCC-TB7-24 / TB2-24
CBCC-TB7-25 / TB2-25
CBCC-TB7-26 / TB2-26
CBCC-TB7-27 / TB2-27
CBCC-TB7-28 / TB2-28
CBCC-TB7-29 / TB2-29
CBCC-TB7-30 / TB2-30
CBCC-TB7-31 / TB2-31
CBCC-TB7-32 / TB2-32
CBCC-TB7-37 / TB2-37
CBCC-TB7-38 / TB2-38
CBCC-TB7-39 / TB2-39
CBCC-TB7-40 / TB2-40

CB-B-TB2-17 / TB7-17
CB-B-TB2-18 / TB7-18
CB-B-TB2-19 / TB7-19
CB-B-TB2-20 / TB7-20
CB-B-TB2-21 / TB7-21
CB-B-TB2-22 / TB7-22
CB-B-TB2-23 / TB7-23
CB-B-TB2-24 / TB7-24
CB-B-TB2-25 / TB7-25
CB-B-TB2-26 / TB7-26
CB-B-TB2-27 / TB7-27
CB-B-TB2-28 / TB7-28
CB-B-TB2-29 / TB7-29
CB-B-TB2-30 / TB7-30
CB-B-TB2-31 / TB7-31
CB-B-TB2-32 / TB7-32
CB-B-TB2-37 / TB7-37
CB-B-TB2-38 / TB7-38
CB-B-TB2-39 / TB7-39
CB-B-TB2-40 / TB7-40

1
2
3
4
5

TB4-19
TB4-42
SPARE
SPARE
SPARE

TB7-19
TB7-20

2-189BE2-TB7-19 / TB4-19
2-189BE2-TB7-20 / TB4-42

2-152-TB4-19 / TB7-19
2-152-TB4-42 / TB7-20

51 2

52 2

01

01

1051

1052

CB-B

2-152

201-BUS COUPLER_05.09.2011

CBCC

2-189BE2

24CX2.5

5CX2.5

15

35

Page 8 of 18

NO CONTACT
NO CONTACT
NO CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NO CONTACT
NO CONTACT

NO CONTACT
NO CONTACT
NO CONTACT
NO CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NC CONTACT
NO CONTACT
NO CONTACT

CB LOCAL CLOSING I/L

5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH
5257PN100-MLW-E-SYD-SCH-1524 SH

CPD KN17 SC51 SHT12


CPD KN17 SC51 SHT12

Cables within SWYD

INTERCONNECTION CABLE DETAILS FOR


PROJECT

SL.
NO

AREVA T&D INDIA LTD.


CABLE NO.
EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201
SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

220KV BUS COUPLER (BAY #01)

Date

Revision

31.08.2011

01

INTERCONNECTION DETAILS

ROUTING DETAILS

Ferrule Nos.

Prepared by

VVG

Checked by

VVG

Approved by

NAG

APPLICATION

CORE

FROM

TO

FROM

TO

REF. DRAWING. NO :
SHEET NO.

CABLES WITHIN SWITCHYARD

53 2

01

1053

2-152

2-189AE2

5CX2.5

65

1
2
3
4
5

TB4-20
TB4-42
SPARE
SPARE
SPARE

TB7-19
TB7-20

2-189AE2-TB7-19 / TB4-20
2-189AE2-TB7-20 / TB4-42

2-152-TB4-20 / TB7-19
2-152-TB4-42 / TB7-20

CB LOCAL CLOSING I/L

CPD KN17 SC51 SHT12


CPD KN17 SC51 SHT12

54 2

01

1054

2-1 89A

2-1 89AE1

5CX2.5

14

1
2
3
4
5

TB3-24
TB3-25
TB1-1
TB1-2
SPARE

TB1-3
TB1-4
TB1-1
TB1-2

2-1 89AE1-TB1-3 / TB3-24


2-1 89AE1-TB1-4 / TB3-25
2-1 89AE1-TB1-1 / TB1-1
2-1 89AE1-TB1-2 / TB1-2

2-1 89A-TB3-24 / TB1-3


2-1 89A-TB3-25 / TB1-4
2-1 89A-TB1-1 / TB1-1
2-1 89A-TB1-2 / TB1-2

DC, I/L
X- spare TB shall be identified at site

CPD KN17 SC65 SHT10


CPD KN17 SC65 SHT10
CPD KN17 SC51 SHT14
CPD KN17 SC51 SHT14

55 2

01

1055

2-1 89B

2-1 89BE1

5CX2.5

14

1
2
3
4
5

TB3-24
TB3-25
TB1-1
TB1-2
SPARE

TB1-3
TB1-4
TB1-1
TB1-2

2-1 89BE1-TB1-3 / TB3-24


2-1 89BE1-TB1-4 / TB3-25
2-1 89BE1-TB1-1 / TB1-1
2-1 89BE1-TB1-2 / TB1-2

2-1 89B-TB3-24 / TB1-3


2-1 89B-TB3-25 / TB1-4
2-1 89B-TB1-1 / TB1-1
2-1 89B-TB1-2 / TB1-2

DC, I/L

CPD KN17 SC65 SHT11


CPD KN17 SC65 SHT11
CPD KN17 SC65 SHT11
CPD KN17 SC51 SHT14
CPD KN17 SC51 SHT14

56 2

01

1056

2-1 89A

2-1 89AE2

5CX2.5

14

1
2
3
4
5

TB4-48
TB4-49
TB1-1
TB1-2
SPARE

TB1-3
TB1-4
TB1-1
TB1-2

2-1 89AE2-TB1-3 / TB4-48


2-1 89AE2-TB1-4 / TB4-49
2-1 89AE2-TB1-1 / TB1-1
2-1 89AE2-TB1-2 / TB1-2

2-1 89A-TB4-48 / TB1-3


2-1 89A-TB4-49 / TB1-4
2-1 89A-TB1-1 / TB1-1
2-1 89A-TB1-2 / TB1-2

DC, I/L

CPD KN17 SC65 SHT10


CPD KN17 SC65 SHT10
CPD KN17 SC51 SHT14
CPD KN17 SC51 SHT14

57 2

01

1057

2-1 89B

2-1 89BE2

5CX2.5

14

1
2
3
4
5

TB4-48
TB4-49
TB1-1
TB1-2
SPARE

TB1-3
TB1-4
TB1-1
TB1-2

2-1 89BE2-TB1-3 / TB4-48


2-1 89BE2-TB1-4 / TB4-49
2-1 89BE2-TB1-1 / TB1-1
2-1 89BE2-TB1-2 / TB1-2

2-1 89B-TB4-48 / TB1-3


2-1 89B-TB4-49 / TB1-4
2-1 89B-TB1-1 / TB1-1
2-1 89B-TB1-2 / TB1-2

DC, I/L

X-SPARE TB SHALL BE ARRANGED AT SITE

CPD KN17 SC65 SHT11


CPD KN17 SC65 SHT11
CPD KN17 SC51 SHT14
CPD KN17 SC51 SHT14

58 2

01

1058

2-1 89A

2-1 89AE1

5CX2.5

14

1
2
3
4
5

TB3-21
TB3-22
TB3-23
SPARE
SPARE

TB6-1
TB6-2
TB7-18

2-1 89AE1-TB6-1 / TB3-21


2-1 89AE1-TB6-2 / TB3-22
2-1 89AE1-TB7-18 / TB3-23

2-1 89A-TB3-21 / TB6-1


2-1 89A-TB3-22 / TB6-2
2-1 89A-TB3-23 / TB7-18

DI

CPD KN17 SC65 SHT08


CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08

59 2

01

1059

2-1 89B

2-1 89BE1

5CX2.5

14

1
2
3
4
5

TB3-21
TB3-22
TB3-23
SPARE
SPARE

TB6-1
TB6-2
TB7-18

2-1 89BE1-TB6-1 / TB3-21


2-1 89BE1-TB6-2 / TB3-22
2-1 89BE1-TB7-18 / TB3-23

2-1 89B-TB3-21 / TB6-1


2-1 89B-TB3-22 / TB6-2
2-1 89B-TB3-23 / TB7-18

DI

CPD KN17 SC65 SHT08


CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08

60 2

01

1060

2-1 89A

2-1 89AE2

5CX2.5

14

1
2
3
4
5

TB4-45
TB4-46
TB4-47
SPARE
SPARE

TB6-1
TB6-2
TB7-18

2-1 89AE2-TB6-1 / TB4-45


2-1 89AE2-TB6-2 / TB4-46
2-1 89AE2-TB7-18 / TB4-47

2-1 89A-TB4-45 / TB6-1


2-1 89A-TB4-46 / TB6-2
2-1 89A-TB4-47 / TB7-18

DI

CPD KN17 SC65 SHT08


CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08

61 2

01

1061

2-1 89B

2-1 89BE2

5CX2.5

14

1
2
3
4
5

TB4-45
TB4-46
TB4-47
SPARE
SPARE

TB6-1
TB6-2
TB7-18

2-1 89BE2-TB6-1 / TB4-45


2-1 89BE2-TB6-2 / TB4-46
2-1 89BE2-TB7-18 / TB4-47

2-1 89B-TB4-45 / TB6-1


2-1 89B-TB4-46 / TB6-2
2-1 89B-TB4-47 / TB7-18

DI

CPD KN17 SC65 SHT08


CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08

62 2

01

2062

2- B189

2- B189E

5CX2.5

14

1
2
3
4
5

TB4-45
TB4-46
TB1-1
TB1-2
SPARE

TB1-3
TB1-4
TB1-1
TB1-2

2- B189E-TB1-3 / TB3-21
2- B189E-TB1-4 / TB3-22
2- B189E-TB1-1 / TB3-23
2- B189E-TB1-2 / SPARE

2- B189-TB3-21 / TB1-3
2- B189-TB3-22 / TB1-4
2- B189-TB3-23 / TB1-1
2- B189-SPARE / TB1-2

DC, I/L

CPD KN17 SC65 SHT11


CPD KN17 SC65 SHT11
CPD KN17 SC51 CHT15
CPD KN17 SC51 CHT15

63 2

01

2063

2- B189

2- B189E

5CX2.5

14

1
2
3
4
5

TB3-21
TB3-22
TB3-23
SPARE
SPARE

TB6-1
TB6-2
TB7-18

2- B189E-TB6-1 / TB3-21
2- B189E-TB6-2 / TB3-22
2- B189E-TB7-18 / TB3-23

2- B189-TB3-21 / TB6-1
2- B189-TB3-22 / TB6-2
2- B189-TB3-23 / TB7-18

DI

CPD KN17 SC65 SHT09


CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09

64 2

01

2064

2- B289

2- B289E

5CX2.5

14

1
2
3
4
5

TB4-45
TB4-46
TB1-1
TB1-2
SPARE

TB1-3
TB1-4
TB1-1
TB1-2

2- B289E-TB1-3 / TB4-45
2- B289E-TB1-4 / TB4-46
2- B289E-TB1-1 / TB1-1
2- B289E-TB1-2 / TB1-2

2- B289-TB4-45 / TB1-3
2- B289-TB4-46 / TB1-4
2- B289-TB1-1 / TB1-1
2- B289-TB1-2 / TB1-2

DC, I/L

CPD KN17 SC65 SHT12


CPD KN17 SC65 SHT12
CPD KN17 SC51 SHT15
CPD KN17 SC51 SHT15

201-BUS COUPLER_05.09.2011

Page 9 of 18

Cables within SWYD

INTERCONNECTION CABLE DETAILS FOR


PROJECT

SL.
NO

AREVA T&D INDIA LTD.


CABLE NO.
EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201
SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

220KV BUS COUPLER (BAY #01)

Date

Revision

31.08.2011

01

INTERCONNECTION DETAILS

ROUTING DETAILS

Ferrule Nos.

Prepared by

VVG

Checked by

VVG

Approved by

NAG

APPLICATION

CORE

FROM

TO

FROM

TO

1
2
3
4
5

TB3-21
TB3-22
TB3-23
SPARE
SPARE

TB6-1
TB6-2
TB7-18

2- B289E-TB6-1 / TB3-21
2- B289E-TB6-2 / TB3-22
2- B289E-TB7-18 / TB3-23

2- B289-TB3-21 / TB6-1
2- B289-TB3-22 / TB6-2
2- B289-TB3-23 / TB7-18

REF. DRAWING. NO :
SHEET NO.

CABLES WITHIN SWITCHYARD


65 2

01

2065

2- B289

201-BUS COUPLER_05.09.2011

2- B289E

5CX2.5

14

Page 10 of 18

DI

CPD KN17 SC65 SHT09


CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09

Cables within SWYD

INTERCONNECTION CABLE DETAILS FOR


PROJECT

EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)


Date

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201

AREVA T&D INDIA LTD.


CABLE NO.

SL.
NO

220KV BUS COUPLER (BAY #01)

SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

ROUTING DETAILS

Prepared by

VVG

Checked by

VVG

Revision

31.08.2011

01

Approved by
Ferrule Nos.

INTERCONNECTION DETAILS

APPLICATION

CORE

FROM

TO

FROM

TO

NAG
REMARK

REF. DRAWING. NO :
SHEET NO.

CABLES BETWEEN SWITCHYARD TO KIOSK-CR

01

2001

Protection PANEL
2-1 B1CVT JB

P1

10CX2.5

73

1,2
3,4
5,6
7,8
9,10

TB1-1
TB1-4
TB1-7
TB1-9
SPARE

TB1-17
TB1-19
TB1-21
TB1-23

-P1-TB1-17 / TB1-1
P1-TB1-19 / TB1-4
P1-TB1-21 / TB1-7
P1-TB1-23 / TB1-9

Protection PANEL-2-1 B1CVT JB-TB1-1 / TB1-17


2-1 B1CVT JB-TB1-4 / TB1-19
2-1 B1CVT JB-TB1-7 / TB1-21
2-1 B1CVT JB-TB1-9 / TB1-23

01

2002

2-1 B1CVT JB

P1

10CX2.5

73

1,2
3,4
5,6
7,8
9,10

TB2-1
TB2-4
TB2-7
TB2-9
SPARE

TB1-25
TB1-27
TB1-29
TB1-31

P1-TB1-25 / TB2-1
P1-TB1-27 / TB2-4
P1-TB1-29 / TB2-7
P1-TB1-31 / TB2-9

2-1 B1CVT
2-1 B1CVT
2-1 B1CVT
2-1 B1CVT

01

2003

2-1 B1CVT JB

P1

10CX2.5

73

1,2
3,4
5,6
7,8
9,10

TB3-1
TB3-4
TB3-7
TB3-9
SPARE

TB1-33
TB1-35
TB1-37
TB1-39

P1-TB1-33 / TB3-1
P1-TB1-35 / TB3-4
P1-TB1-37 / TB3-7
P1-TB1-39 / TB3-9

01

2004

2-1 B1CVT JB

P1

10CX2.5

73

1,2
3,4
5,6
7,8
9,10

TB4-1
TB4-4
TB4-7
TB4-9
SPARE

TB1-41
TB1-43
TB1-45
TB1-47

01

2005

2-1 B2CVT JB

P1

10CX2.5

91

1,2
3,4
5,6
7,8
9,10

TB1-1
TB1-4
TB1-7
TB1-9
SPARE

01

2006

2-1 B2CVT JB

P1

10CX2.5

91

1,2
3,4
5,6
7,8
9,10

01

2007

2-1 B2CVT JB

P1

10CX2.5

91

01

2008

2-1 B2CVT JB

P1

10CX2.5

01

2009

2-1 CTA JB

P1

10CX2.5

10

01

2010

P1

2-1 CB

24CX2.5

201-BUS COUPLER_05.09.2011

WDG-1

CPD KN17 SC51 SH07


CPD KN17 SC51 SH07
CPD KN17 SC51 SH07
CPD KN17 SC51 SH07

JB-TB2-1 / TB1-25
JB-TB2-4 / TB1-27
JB-TB2-7 / TB1-29
JB-TB2-9 / TB1-31

WDG-2

CPD KN17 SC51 SH07


CPD KN17 SC51 SH07
CPD KN17 SC51 SH07
CPD KN17 SC51 SH07

2-1 B1CVT
2-1 B1CVT
2-1 B1CVT
2-1 B1CVT

JB-TB3-1 / TB1-33
JB-TB3-4 / TB1-35
JB-TB3-7 / TB1-37
JB-TB3-9 / TB1-39

WDG-3

CPD KN17 SC51 SH07


CPD KN17 SC51 SH07
CPD KN17 SC51 SH07
CPD KN17 SC51 SH07

P1-TB1-41 / TB4-1
P1-TB1-43 / TB4-4
P1-TB1-45 / TB4-7
P1-TB1-47 / TB4-9

2-1 B1CVT
2-1 B1CVT
2-1 B1CVT
2-1 B1CVT

JB-TB4-1 / TB1-41
JB-TB4-4 / TB1-43
JB-TB4-7 / TB1-45
JB-TB4-9 / TB1-47

WDG-4 TARIFF METERING

CPD KN17 SC51 SH07


CPD KN17 SC51 SH07
CPD KN17 SC51 SH07
CPD KN17 SC51 SH07

TB2-1
TB2-3
TB2-5
TB2-7

P1-TB2-1 / TB1-1
P1-TB2-3 / TB1-4
P1-TB2-5 / TB1-7
P1-TB2-7 / TB1-9

2-1 B2CVT
2-1 B2CVT
2-1 B2CVT
2-1 B2CVT

JB-TB1-1 / TB2-1
JB-TB1-4 / TB2-3
JB-TB1-7 / TB2-5
JB-TB1-9 / TB2-7

WDG-1

CPD KN17 SC51 SH08


CPD KN17 SC51 SH08
CPD KN17 SC51 SH08
CPD KN17 SC51 SH08

TB2-1
TB2-4
TB2-7
TB2-9
SPARE

TB2-9
TB2-11
TB2-13
TB2-15

P1-TB2-9 / TB2-1
P1-TB2-11 / TB2-4
P1-TB2-13 / TB2-7
P1-TB2-15 / TB2-9

2-1 B2CVT JB-TB2-1 / TB2-9


2-1 B2CVT JB-TB2-4 / TB2-11
2-1 B2CVT JB-TB2-7 / TB2-13
2-1 B2CVT JB-TB2-9 / TB2-15

WDG-2

CPD KN17 SC51 SH08


CPD KN17 SC51 SH08
CPD KN17 SC51 SH08
CPD KN17 SC51 SH08

1,2
3,4
5,6
7,8
9,10

TB3-1
TB3-4
TB3-7
TB3-9
SPARE

TB2-17
TB2-19
TB2-21
TB2-23

P1-TB2-17 / TB3-1
P1-TB2-19 / TB3-4
P1-TB2-21 / TB3-7
P1-TB2-23 / TB3-9

2-1 B2CVT
2-1 B2CVT
2-1 B2CVT
2-1 B2CVT

JB-TB3-1 / TB2-17
JB-TB3-4 / TB2-19
JB-TB3-7 / TB2-21
JB-TB3-9 / TB2-23

WDG-3

CPD KN17 SC51 SH08


CPD KN17 SC51 SH08
CPD KN17 SC51 SH08
CPD KN17 SC51 SH08

91

1,2
3,4
5,6
7,8
9,10

TB4-1
TB4-4
TB4-7
TB4-9
SPARE

TB2-25
TB2-27
TB2-29
TB2-31

P1-TB2-25 / TB4-1
P1-TB2-27 / TB4-4
P1-TB2-29 / TB4-7
P1-TB2-31 / TB4-9

2-1 B2CVT
2-1 B2CVT
2-1 B2CVT
2-1 B2CVT

JB-TB4-1 / TB2-25
JB-TB4-4 / TB2-27
JB-TB4-7 / TB2-29
JB-TB4-9 / TB2-31

WDG-4 TARIFF METERING

CPD KN17 SC51 SH08


CPD KN17 SC51 SH08
CPD KN17 SC51 SH08
CPD KN17 SC51 SH08

25

1,2
3,4
5,6
7,8
9,10

TB2-1
TB2-5
TB2-9
TB2-12

TB1-9
TB1-11
TB1-13
TB1-15

P1-TB1-9 / TB2-1
P1-TB1-11 / TB2-5
P1-TB1-13 / TB2-9
P1-TB1-15 / TB2-12

2-1 CTA JB-TB2-1 / TB1-9


2-1 CTA JB-TB2-5 / TB1-11
2-1 CTA JB-TB2-9 / TB1-13
2-1 CTA JB-TB2-12 / TB1-15

BACK UP

CPD KN17 SC51 SH09


CPD KN17 SC51 SH09
CPD KN17 SC51 SH09
CPD KN17 SC51 SH09

45

1,2
3,4
5,6
7,8
9,10
11,12
13
14
15
16
17
18
19-24

TB3-8
TB3-9
TB3-10
TB3-11
TB3-12
TB3-13
TB3-14
TB3-15
TB3-16
TB3-17
TB3-18
TB3-19
SPARE

TB4-13
TB4-14
TB4-22
TB1-5
TB2-5
TB3-5
TB1-6
TB1-8
TB2-6
TB2-8
TB3-6
TB3-8

2-1 CB-TB4-13 / TB3-8


2-1 CB-TB4-14 / TB3-9
2-1 CB-TB4-22 / TB3-10
2-1 CB-TB1-5 / TB3-11
2-1 CB-TB2-5 / TB3-12
2-1 CB-TB3-5 / TB3-13
2-1 CB-TB1-6 / TB3-14
2-1 CB-TB1-8 / TB3-15
2-1 CB-TB2-6 / TB3-16
2-1 CB-TB2-8 / TB3-17
2-1 CB-TB3-6 / TB3-18
2-1 CB-TB3-8 / TB3-19

P1-TB3-8 / TB4-13
P1-TB3-9 / TB4-14
P1-TB3-10 / TB4-22
P1-TB3-11 / TB1-5
P1-TB3-12 / TB2-5
P1-TB3-13 / TB3-5
P1-TB3-14 / TB1-6
P1-TB3-15 / TB1-8
P1-TB3-16 / TB2-6
P1-TB3-17 / TB2-8
P1-TB3-18 / TB3-6
P1-TB3-19 / TB3-8

Page 11 of 18

DC-1, TRIP-1, TCS

CB

CPD KN17 SC51 SH12


CPD KN17 SC51 SH12
CPD KN17 SC51 SH12
CPD KN17 SC51 SH12
CPD KN17 SC51 SH12
CPD KN17 SC51 SH12
CPD KN17 SC51 SH12
CPD KN17 SC51 SH12
CPD KN17 SC51 SH12
CPD KN17 SC51 SH12
CPD KN17 SC51 SH12
CPD KN17 SC51 SH12

Cables between SWYD to Kiosk-CR

INTERCONNECTION CABLE DETAILS FOR


PROJECT

EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)


Date

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201

AREVA T&D INDIA LTD.


CABLE NO.

SL.
NO

220KV BUS COUPLER (BAY #01)

SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

Prepared by

VVG

Checked by

VVG

Revision

31.08.2011

01

Approved by
Ferrule Nos.

INTERCONNECTION DETAILS

ROUTING DETAILS

APPLICATION

CORE

FROM

TO

FROM

TO

NAG
REMARK

REF. DRAWING. NO :
SHEET NO.

CABLES BETWEEN SWITCHYARD TO KIOSK-CR


11

01

2011

P1

2-1 CB

24CX2.5

45

1,2
3,4
5,6
7,8
9,10
11,12
13
14
15
16
17
18
19-24

TB3-32
TB3-33
TB3-34
TB3-35
TB3-36
TB3-37
TB3-38
TB3-39
TB3-40
TB3-41
TB3-42
TB3-43
SPARE

TB4-15
TB4-16
TB4-24
TB1-20
TB2-20
TB3-20
TB1-21
TB1-23
TB2-21
TB2-23
TB3-21
TB3-23

2-1 CB-TB4-15 / TB3-32


2-1 CB-TB4-16 / TB3-33
2-1 CB-TB4-24 / TB3-34
2-1 CB-TB1-20 / TB3-35
2-1 CB-TB2-20 / TB3-36
2-1 CB-TB3-20 / TB3-37
2-1 CB-TB1-21 / TB3-38
2-1 CB-TB1-23 / TB3-39
2-1 CB-TB2-21 / TB3-40
2-1 CB-TB2-23 / TB3-41
2-1 CB-TB3-21 / TB3-42
2-1 CB-TB3-23 / TB3-43

P1-TB3-32 / TB4-15
P1-TB3-33 / TB4-16
P1-TB3-34 / TB4-24
P1-TB3-35 / TB1-20
P1-TB3-36 / TB2-20
P1-TB3-37 / TB3-20
P1-TB3-38 / TB1-21
P1-TB3-39 / TB1-23
P1-TB3-40 / TB2-21
P1-TB3-41 / TB2-23
P1-TB3-42 / TB3-21
P1-TB3-43 / TB3-23

DC-2, TRIP-2, TCS, Manual Trip-2

CPD KN17 SC51 SH13


CPD KN17 SC51 SH13
CPD KN17 SC51 SH13
CPD KN17 SC51 SH13
CPD KN17 SC51 SH13
CPD KN17 SC51 SH13
CPD KN17 SC51 SH13
CPD KN17 SC51 SH13
CPD KN17 SC51 SH13
CPD KN17 SC51 SH13
CPD KN17 SC51 SH13
CPD KN17 SC51 SH13
CPD KN17 SC51 SH13

12

01

2012

P1

2-1 CB

7CX2.5

45

1,2
3,4
5,6
7

TB3-20
TB3-22
TB3-23
SPARE

TB4-21
TB4-22
TB4-18

2-1 CB-TB4-21 / TB3-20


2-1 CB-TB4-22 / TB3-22
2-1 CB-TB4-18 / TB3-23

P1-TB3-20 / TB4-21
P1-TB3-22 / TB4-22
P1-TB3-23 / TB4-18

REMOTE CLOSING, MANL TRIP-1

CPD KN17 SC51 SH12


CPD KN17 SC51 SH12
CPD KN17 SC51 SH12

13

01

2013

P1

2-1 CB

5CX2.5

45

1,2
3,4
5

TB3-44
TB3-45
SPARE

TB4-24
TB4-23

2-1 CB-TB4-24 / TB3-44


2-1 CB-TB4-23 / TB3-45

P1-TB3-44 / TB4-24
P1-TB3-45 / TB4-23

TRIP-2

CPD KN17 SC51 SH13


CPD KN17 SC51 SH13

14

01

2014

2-1 CTA JB

P1

10CX2.5

25

1,2
3,4
5,6
7,8
9,10

TB5-1
TB5-5
TB5-9
TB5-11
SPARE

TB1-1
TB1-3
TB1-5
TB1-7

P1-TB1-1 / TB5-1
P1-TB1-3 / TB5-5
P1-TB1-5 / TB5-9
P1-TB1-7 / TB5-11

2-1 CTA JB-TB5-1 / TB1-1


2-1 CTA JB-TB5-5 / TB1-3
2-1 CTA JB-TB5-9 / TB1-5
2-1 CTA JB-TB5-11 / TB1-7

BUS BAR PROTECTION

CPD KN17 SC51 SH19


CPD KN17 SC51 SH19
CPD KN17 SC51 SH19
CPD KN17 SC51 SH19

15

01

2015

2-1 CB

P1

5CX2.5

45

1
2
3
4
5

TB5-3
TB7-4
TB7-12
SPARE
SPARE

TB5-13
TB5-14
TB5-15

P1-TB5-13 / TB5-3
P1-TB5-14 / TB7-4
P1-TB5-15 / TB7-12

2-1 CB-TB5-3 / TB5-13


2-1 CB-TB7-4 / TB5-14
2-1 CB-TB7-12 / TB5-15

DI FOR BB PROTECTION

CPD KN17 SC51 SH20


CPD KN17 SC51 SH20
CPD KN17 SC51 SH20

16

01

2016

2-189A

P1

5CX2.5

80

1
2
3
4
5

TB4-27
TB4-28
TB3-4
SPARE
SPARE

TB5-16
TB5-17
TB5-18

P1-TB5-16 / TB4-27
P1-TB5-17 / TB4-28
P1-TB5-18 / TB3-4

2-189A-TB4-27 / TB5-16
2-189A-TB4-28 / TB5-17
2-189A-TB3-4 / TB5-18

DI FOR BB PROTECTION

CPD KN17 SC51 SH20


CPD KN17 SC51 SH20
CPD KN17 SC51 SH20

17

01

2017

2-189B

P1

5CX2.5

55

1
2
3
4
5

TB4-27
TB4-28
TB3-4
SPARE
SPARE

TB5-19
TB5-20
TB5-21

P1-TB5-19 / TB4-27
P1-TB5-20 / TB4-28
P1-TB5-21 / TB3-4

2-189B-TB4-27 / TB5-19
2-189B-TB4-28 / TB5-20
2-189B-TB3-4 / TB5-21

DI FOR BB PROTECTION

CPD KN17 SC51 SH20


CPD KN17 SC51 SH20
CPD KN17 SC51 SH20

18

01

2018

BB2

P1

5CX2.5

100

1,2
3,4
5

TB1-13
TB1-14
SPARE

TB5-11
TB5-12

P1-TB5-11 / TB1-13
P1-TB5-12 / TB1-14

BB2-TB1-13 / TB5-11
BB2-TB1-14 / TB5-12

DC SUPPLY

CPD KN17 SC59 SH04


CPD KN17 SC51 SH20

C1

10CX2.5

25

1,2
3,4
5,6
7,8
9,10

TB3-4
TB3-8
TB3-12
TB3-9
SPARE

TB1-1
TB1-3
TB1-5
TB1-7

C1-TB1-1 / TB3-4
C1-TB1-3 / TB3-8
C1-TB1-5 / TB3-12
C1-TB1-7 / TB3-9

2-1 CTA JB-TB3-4 / TB1-1


2-1 CTA JB-TB3-8 / TB1-3
2-1 CTA JB-TB3-12 / TB1-5
2-1 CTA JB-TB3-9 / TB1-7

METERING

CPD KN17 SC65 SHT07


CPD KN17 SC65 SHT07
CPD KN17 SC65 SHT07
CPD KN17 SC65 SHT07

CONTROL PANEL
19

01

2019

2-1 CTA JB

201-BUS COUPLER_05.09.2011

Page 12 of 18

Cables between SWYD to Kiosk-CR

INTERCONNECTION CABLE DETAILS FOR


PROJECT

EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)


Date

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201

AREVA T&D INDIA LTD.


CABLE NO.

SL.
NO

220KV BUS COUPLER (BAY #01)

SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

ROUTING DETAILS

Prepared by

VVG

Checked by

VVG

Revision

31.08.2011

01

Approved by
Ferrule Nos.

INTERCONNECTION DETAILS

APPLICATION

CORE

FROM

TO

FROM

TO

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15-19

TB1C-7
TB1P1-1
TB1P1-2
TB1P1-4
TB1P1-5
TB1P1-7
TB1P1-8
TB1P1-10
TB1P1-11
TB1P1-13
TB1P1-14
TB1P1-16
TB1P1-17
TB1P1-19
SPARE

TB5-9
TB5-10
TB5-2
TB6-10
TB6-2
TB7-10
TB7-2
TB3-28
TB4-26
TB4-28
TB4-32
TB4-43
TB4-34
TB4-33

2-1 CB-TB5-9 / TB1C-7


2-1 CB-TB5-10 / TB1P1-1
2-1 CB-TB5-2 / TB1P1-2
2-1 CB-TB6-10 / TB1P1-4
2-1 CB-TB6-2 / TB1P1-5
2-1 CB-TB7-10 / TB1P1-7
2-1 CB-TB7-2 / TB1P1-8
2-1 CB-TB3-28 / TB1P1-10
2-1 CB-TB4-26 / TB1P1-11
2-1 CB-TB4-28 / TB1P1-13
2-1 CB-TB4-32 / TB1P1-14
2-1 CB-TB4-43 / TB1P1-16
2-1 CB-TB4-34 / TB1P1-17
2-1 CB-TB4-33 / TB1P1-19

C1-TB1C-7 / TB5-9
C1-TB1P1-1 / TB5-10
C1-TB1P1-2 / TB5-2
C1-TB1P1-4 / TB6-10
C1-TB1P1-5 / TB6-2
C1-TB1P1-7 / TB7-10
C1-TB1P1-8 / TB7-2
C1-TB1P1-10 / TB3-28
C1-TB1P1-11 / TB4-26
C1-TB1P1-13 / TB4-28
C1-TB1P1-14 / TB4-32
C1-TB1P1-16 / TB4-43
C1-TB1P1-17 / TB4-34
C1-TB1P1-19 / TB4-33

NAG
REMARK

REF. DRAWING. NO :
SHEET NO.

CABLES BETWEEN SWITCHYARD TO KIOSK-CR


20

01

2020

C1

2-1 CB

19CX2.5

45

DI OF CB & TROUBLES

CB

CPD KN17 SC65 SHT08


CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08

21

01

2021

2-1 89A

C1

14CX2.5

80

1
2
3
4
5
6
7
8
9
10
11
12-14

TB1-9
TB1-10
TB1-11
TB1-3
TB1-6
TB3-24
TB3-25
TB4-48
TB4-49
TB1-1
TB1-2
SPARE

TBOD1-9
TBOD1-10
TBOD1-12
TBOD1-14
TBOD1-13
TBOD1-16
TBOD1-15
TBOD1-19
TBOD1-21
TB10-1
TB10-2

C1-TBOD1-9 / TB1-9
C1-TBOD1-10 / TB1-10
C1-TBOD1-12 / TB1-11
C1-TBOD1-14 / TB1-3
C1-TBOD1-13 / TB1-6
C1-TBOD1-16 / TB3-24
C1-TBOD1-15 / TB3-25
C1-TBOD1-19 / TB4-48
C1-TBOD1-21 / TB4-49
C1-TB10-1 / TB1-1
C1-TB10-2 / TB1-2

2-1 89A-TB1-9 / TBOD1-9


2-1 89A-TB1-10 / TBOD1-10
2-1 89A-TB1-11 / TBOD1-12
2-1 89A-TB1-3 / TBOD1-14
2-1 89A-TB1-6 / TBOD1-13
2-1 89A-TB3-24 / TBOD1-16
2-1 89A-TB3-25 / TBOD1-15
2-1 89A-TB4-48 / TBOD1-19
2-1 89A-TB4-49 / TBOD1-21
2-1 89A-TB1-1 / TB10-1
2-1 89A-TB1-2 / TB10-2

DC, CONTROL, I/L

22

01

2022

2-1 89B

C1

14CX2.5

55

1
2
3
4
5
6
7
8
9
10
11
12-14

TB1-9
TB1-10
TB1-11
TB1-3
TB1-6
TB3-24
TB3-25
TB4-48
TB4-49
TB1-1
TB1-2
SPARE

TBOE1-1
TBOE1-2
TBOE1-4
TBOE1-6
TBOE1-5
TBOE1-8
TBOE1-7
TBOE1-10
TBOE1-9
TB10-3
TB10-4

C1-TBOE1-1 / TB1-9
C1-TBOE1-2 / TB1-10
C1-TBOE1-4 / TB1-11
C1-TBOE1-6 / TB1-3
C1-TBOE1-5 / TB1-6
C1-TBOE1-8 / TB3-24
C1-TBOE1-7 / TB3-25
C1-TBOE1-10 / TB4-48
C1-TBOE1-9 / TB4-49
C1-TB10-3 / TB1-1
C1-TB10-4 / TB1-2

2-1 89B-TB1-9 / TBOE1-1


2-1 89B-TB1-10 / TBOE1-2
2-1 89B-TB1-11 / TBOE1-4
2-1 89B-TB1-3 / TBOE1-6
2-1 89B-TB1-6 / TBOE1-5
2-1 89B-TB3-24 / TBOE1-8
2-1 89B-TB3-25 / TBOE1-7
2-1 89B-TB4-48 / TBOE1-10
2-1 89B-TB4-49 / TBOE1-9
2-1 89B-TB1-1 / TB10-3
2-1 89B-TB1-2 / TB10-4

DC, CONTROL, I/L

23

01

2023

2-1 89A

C1

14CX2.5

80

1
2
3
4
5
6
7
8
9
10
11
12-14

TB3-1
TB3-2
TB4-26
TB1-14
TB1-13
TB3-21
TB3-22
TB3-23
TB4-45
TB4-46
TB4-47
SPARE

TB1C-9
TB1P1-20
TB1P1-22
TB1O1-1
TB1O1-2
TB1C-10
TB1O1-4
TB1O1-5
TB1C-11
TB1O1-7
TB1O1-8

C1-TB1C-9 / TB3-1
C1-TB1P1-20 / TB3-2
C1-TB1P1-22 / TB4-26
C1-TB1O1-1 / TB1-14
C1-TB1O1-2 / TB1-13
C1-TB1C-10 / TB3-21
C1-TB1O1-4 / TB3-22
C1-TB1O1-5 / TB3-23
C1-TB1C-11 / TB4-45
C1-TB1O1-7 / TB4-46
C1-TB1O1-8 / TB4-47

2-1 89A-TB3-1 / TB1C-9


2-1 89A-TB3-2 / TB1P1-20
2-1 89A-TB4-26 / TB1P1-22
2-1 89A-TB1-14 / TB1O1-1
2-1 89A-TB1-13 / TB1O1-2
2-1 89A-TB3-21 / TB1C-10
2-1 89A-TB3-22 / TB1O1-4
2-1 89A-TB3-23 / TB1O1-5
2-1 89A-TB4-45 / TB1C-11
2-1 89A-TB4-46 / TB1O1-7
2-1 89A-TB4-47 / TB1O1-8

DI OF ISO & E/S

CPD KN17 SC65 SHT08


CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08

24

01

2024

2-1 89B

C1

14CX2.5

55

1
2
3
4
5
6
7
8
9
10
11
12-14

TB3-1
TB3-2
TB4-26
TB1-14
TB1-13
TB3-21
TB3-22
TB3-23
TB4-45
TB4-46
TB4-47
SPARE

TB1C-12
TB1O1-10
TB1O1-11
TB1O1-13
TB1O1-14
TB1C-13
TB1O1-16
TB1O1-17
TB1C-14
TB1O1-19
TB1O1-20

C1-TB1C-12 / TB3-1
C1-TB1O1-10 / TB3-2
C1-TB1O1-11 / TB4-26
C1-TB1O1-13 / TB1-14
C1-TB1O1-14 / TB1-13
C1-TB1C-13 / TB3-21
C1-TB1O1-16 / TB3-22
C1-TB1O1-17 / TB3-23
C1-TB1C-14 / TB4-45
C1-TB1O1-19 / TB4-46
C1-TB1O1-20 / TB4-47

2-1 89B-TB3-1 / TB1C-12


2-1 89B-TB3-2 / TB1O1-10
2-1 89B-TB4-26 / TB1O1-11
2-1 89B-TB1-14 / TB1O1-13
2-1 89B-TB1-13 / TB1O1-14
2-1 89B-TB3-21 / TB1C-13
2-1 89B-TB3-22 / TB1O1-16
2-1 89B-TB3-23 / TB1O1-17
2-1 89B-TB4-45 / TB1C-14
2-1 89B-TB4-46 / TB1O1-19
2-1 89B-TB4-47 / TB1O1-20

DI OF ISO & E/S

CPD KN17 SC65 SHT08


CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08
CPD KN17 SC65 SHT08

201-BUS COUPLER_05.09.2011

Page 13 of 18

CPD KN17 SC65 SHT10


CPD KN17 SC65 SHT10
DC SUPPLY TO BE CPD KN17 SC65 SHT10
WIRED FROM P1 CPD KN17 SC65 SHT10
PANEL
CPD KN17 SC65 SHT10
CPD KN17 SC65 SHT10
CPD KN17 SC65 SHT10
CPD KN17 SC65 SHT10
CPD KN17 SC65 SHT10
CPD KN17 SC51 SHT14
CPD KN17 SC51 SHT14
X-SPARE TB SHALL BE ARRANGED AT SITE

CPD KN17 SC65 SHT11


CPD KN17 SC65 SHT11
DC SUPPLY TO BE
CPD KN17 SC65 SHT11
WIRED FROM P1
CPD KN17 SC65 SHT11
PANEL
CPD KN17 SC65 SHT11
CPD KN17 SC65 SHT11
CPD KN17 SC65 SHT11
CPD KN17 SC65 SHT11
CPD KN17 SC65 SHT11
CPD KN17 SC51 SHT14
CPD KN17 SC51 SHT14

Cables between SWYD to Kiosk-CR

INTERCONNECTION CABLE DETAILS FOR


PROJECT

EQUIPMENT DESIGNATION
FROM

SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)


Date

OWNERS CONSULTANT
L&T S&L
EPC CONTRACTOR
L&T POWER, VADODARA
CONTRACTORS DCPL,
CONSULTANT
KOLKATA
EBOP CONTRACTOR
AREVA T&D INDIA LIMITED
DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201

AREVA T&D INDIA LTD.


CABLE NO.

SL.
NO

220KV BUS COUPLER (BAY #01)

SIZE

TO

NO. OF ESTIMATED
RUNS
LENGTH

ACTUAL

DRUM

LENGTH

DETAILS

Prepared by

VVG

Checked by

VVG

Revision

31.08.2011

01

Approved by
Ferrule Nos.

INTERCONNECTION DETAILS

ROUTING DETAILS

APPLICATION

CORE

FROM

TO

FROM

TO

NAG
REMARK

REF. DRAWING. NO :
SHEET NO.

CABLES BETWEEN SWITCHYARD TO KIOSK-CR


25

01

2025

2- B189

C1

14CX2.5

70

1
2
3
4
5
6
7
8
9
10
11
12
13
14

TB1-9
TB1-10
TB1-11
TB1-3
TB1-6
TB4-45
TB4-46
TB1-1
TB1-2
SPARE
SPARE
SPARE
SPARE
SPARE

TBOE1-11
TB0E1-12
TB0E1-14
TB0E1-15
TB0E1-16
TB0E1-19
TB0E1-21
TB10-5
TB10-6

C1-TBOE1-11 / TB1-9
C1-TB0E1-12 / TB1-10
C1-TB0E1-14 / TB1-11
C1-TB0E1-15 / TB1-3
C1-TB0E1-16 / TB1-6
C1-TB0E1-19 / TB4-45
C1-TB0E1-21 / TB4-46
C1-TB10-5 / TB1-1
C1-TB10-6 / TB1-2

2- B189-TB1-9 / TBOE1-11
2- B189-TB1-10 / TB0E1-12
2- B189-TB1-11 / TB0E1-14
2- B189-TB1-3 / TB0E1-15
2- B189-TB1-6 / TB0E1-16
2- B189-TB4-45 / TB0E1-19
2- B189-TB4-46 / TB0E1-21
2- B189-TB1-1 / TB10-5
2- B189-TB1-2 / TB10-6

DC, CONTROL, I/L

CPD KN17 SC65 SHT11


CPD KN17 SC65 SHT11
CPD KN17 SC65 SHT11
CPD KN17 SC65 SHT11
CPD KN17 SC65 SHT11
CPD KN17 SC65 SHT11
CPD KN17 SC65 SHT11
CPD KN17 SC51 SHT15
CPD KN17 SC51 SHT15

26

01

2026

2-B189

C1

10CX2.5

70

1
2
3
4
5
6
7
8
9-10

TB3-1
TB3-2
TB4-26
TB1-14
TB1-13
TB3-21
TB3-22
TB3-23
SPARE

TB1C-18
TB1N1-1
TB1N1-2
TB1N1-4
TB1N1-5
TB1C-19
TB1N1-7
TB1N1-8

C1-TB1C-18 / TB3-1
C1-TB1N1-1 / TB3-2
C1-TB1N1-2 / TB4-26
C1-TB1N1-4 / TB1-14
C1-TB1N1-5 / TB1-13
C1-TB6-1 / TB3-21
C1-TB6-2 / TB3-22
C1-TB7-18 / TB3-23

2-B189-TB3-1 / TB1C-18
2-B189-TB3-2 / TB1N1-1
2-B189-TB4-26 / TB1N1-2
2-B189-TB1-14 / TB1N1-4
2-B189-TB1-13 / TB1N1-5
2-B189-TB3-21 / TB6-1
2-B189-TB3-22 / TB6-2
2-B189-TB3-23 / TB7-18

DI OF ISO & E/S

CPD KN17 SC65 SHT09


CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09

27

01

2027

2- B289

C1

14CX2.5

85

1
2
3
4
5
6
7
8
9
10
11
12
13
14

TB1-10
TB1-9
TB1-11
TB1-3
TB1-6
TB4-45
TB4-46
TB1-1
TB1-2
SPARE
SPARE
SPARE
SPARE
SPARE

TBOF1-2
TBOF1-1
TBOF1-4
TBOF1-6
TBOF1-5
TBOF1-8
TBOF1-7
TB10-7
TB10-8

C1-TBOF1-2 / TB1-10
C1-TBOF1-1 / TB1-9
C1-TBOF1-4 / TB1-11
C1-TBOF1-6 / TB1-3
C1-TBOF1-5 / TB1-6
C1-TBOF1-8 / TB4-45
C1-TBOF1-7 / TB4-46
C1-TB10-7 / TB1-1
C1-TB10-8 / TB1-2

2- B289-TB1-10 / TBOF1-2
2- B289-TB1-9 / TBOF1-1
2- B289-TB1-11 / TBOF1-4
2- B289-TB1-3 / TBOF1-6
2- B289-TB1-6 / TBOF1-5
2- B289-TB4-45 / TBOF1-8
2- B289-TB4-46 / TBOF1-7
2- B289-TB1-1 / TB10-7
2- B289-TB1-2 / TB10-8

DC, CONTROL, I/L

CPD KN17 SC65 SHT12


CPD KN17 SC65 SHT12
CPD KN17 SC65 SHT12
CPD KN17 SC65 SHT12
CPD KN17 SC65 SHT12
CPD KN17 SC65 SHT12
CPD KN17 SC65 SHT12
CPD KN17 SC51 SHT15
CPD KN17 SC51 SHT15

28

01

2028

2- B289

C1

10CX2.5

85

1
2
3
4
5
6
7
8
9-10

TB3-1
TB3-2
TB4-26
TB1-14
TB1-13
TB3-21
TB3-22
TB3-23
SPARE

TB1C-20
TBIN1-10
TB1N1-11
TB1N1-13
TB1N1-14
TB1C-21
TB1N1-16
TB1N1-17

C1-TB1C-20 / TB3-1
C1-TBIN1-10 / TB3-2
C1-TB1N1-11 / TB4-26
C1-TB1N1-13 / TB1-14
C1-TB1N1-14 / TB1-13
C1-TB1C-21 / TB3-21
C1-TB1N1-16 / TB3-22
C1-TB1N1-17 / TB3-23

2- B289-TB3-1 / TB1C-20
2- B289-TB3-2 / TBIN1-10
2- B289-TB4-26 / TB1N1-11
2- B289-TB1-14 / TB1N1-13
2- B289-TB1-13 / TB1N1-14
2- B289-TB3-21 / TB1C-21
2- B289-TB3-22 / TB1N1-16
2- B289-TB3-23 / TB1N1-17

DI OF ISO & E/S

CPD KN17 SC65 SHT09


CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09
CPD KN17 SC65 SHT09

Note: In isolator Panel following terminals to be added. 1. TB3:25-29 and TB4:49-53


Note: DC supply for iso and ISO/E/S shall be wired from P1 to C1, in the panel at site.(BUS WIRED AT SITE),TB10-spare TBs shall be arranged