You are on page 1of 49

RIG SAFETY SYSTEMS

KNOW YOUR RIG & EQUIPMENT

AREAS COVERED:

QUICK CLOSE VALVE SYSTEM MANUAL CALL STATIONS TOTAL RIG SHUTDOWN WATERMIST FIRE SUPPRESSION NOVEC FIRE SUPPRESSION

QUICK CLOSE VALVE CONTROL SYSTEM

PURPOSE OF QUICK CLOSE VALVE SYSTEM


Provides a means of instantly shutting off selected systems in event of an emergency On this rig, primarily used to shut off fuel feeds Valves are manually operated, hydraulically activated, spring loaded valves Independent to power supplies

HYDRAULIC IMPULSE VALVES

HYDRAULIC IMPULSE VALVE

IMPULSE VALVE LOCATIONS?

AFT OF ENGINE ROOMS STBD COLUMN 3 DECK 3 PORT COLUMN 4 DECK 3 START AIR COMPRESSOR ROOM OUTSIDE E-GEN ROOM

QUICK CLOSING VALVE ASSEMBLY

QUICK CLOSING VALVES ARE EMPLOYED:

ENGINE ROOM 1-4 FUEL OIL DAY & SETTLING TANKS PT & STBD PONTOON FUEL OIL TANKS CONTAMINATED DRAIN TANKS ENGINE LUBE OIL TANKS BASE OIL TANK E-GEN FUEL OIL DAY TANK

MANUAL CALL STATIONS

PURPOSE OF MANUAL CALL STATIONS...?


TO PROVIDE A MEANS OF ALERTING THE ENTIRE RIG THAT THERE IS A FIRE TO AUTOMATICALLY INFORM THE BRIDGE OF THE FIRES LOCATION

ACCOMMODATION MANUAL CALL POINT

MANUAL CALL POINT

MANUAL CALL POINT

MANUAL CALL POINT...?

TOTAL RIG SHUTDOWN

DIRECT ALARM

DIRECT TO PA/GA SYSTEM, BYPASSING F & G PANEL

TOTAL RIG SHUTDOWN

PURPOSE OF SYSTEM
TO INITIATE TOTAL SHUTDOWN OF THE RIG ON ABANDONMENT

TOTAL RIG SHUTDOWN: EQUIPMENT LOCATIONS?


4 MASTER BUTTONS ON BRIDGE - MUST BE ARMED TO PRIME: 4 BUTTONS AT FWD LIFEBOAT STATION 4 BUTTONS AT AFT LIFEBOAT STATION

BRIDGE ARMING STATIONS

ACTIVATION POINT

ACTIVATION POINT SIGN

WATER MIST FIRE SUPPRESSION SYSTEM

KEY FEATURES

Total flooding system Machine spaces: dry pipe system with manually operated remote & local activation Accommodation: wet pipe system with automatically released nozzleheads Primary water supply: potable water ring main Secondary water supply: fire water system

AREAS COVERED BY WATERMIST SYSTEM

ENGINE ROOMS 1-4 ACCOMMODATION THRUSTER ROOMS 1-8 PONTOON PUMP ROOMS PONTOON AUXILIARY PUMP ROOMS PAINT LOCKER

WATER MIST LOCAL ACTIVATION POINT

WATER MIST LOCAL ACTIVATION POINT

MACHINE SPACE WATERMIST SYSTEM LOCAL ACTIVATION


VERIFY FIRE SOUND GENERAL ALARM BY NEAREST MANUAL CALL POINT CLOSE ALL VENTILATION TO THE SPACE ON FIRE CONFIRM ALL DOORS ARE CLOSED CONFIRM LOCAL ACTIVATION STATION PRESS ACTIVATION BUTTON DO NOT RE-ENTER AREA

ECR WATERMIST CONTROL PANEL

WATERMIST PUMP ROOM

MOTORISED SECTION VALVES

MOTORISED SECTION VALVE (MACHINE SPACES)

SECTION VALVE MANUAL ACTIVATION

ACCOMMODATION SYSTEM SECTION VALVE

NOVEC FIRE SUPPRESSION SYSTEM

WHAT IS NOVEC?

NOVEC 1230 fluid is an environmentally friendly replacement for Halon used as a gaseous fire suppressant agent Used in spaces where water is impractical Converts to gas immediately at room temperature Suppresses fires via its cooling effect Leaves no residue and will not affect sensitive high value electronic components

AREAS COVERED BY NOVEC


THRUSTER VFD ROOMS 1-8 DRILLING SWITCHBOARD ROOM DP BACKUP ROOM BRIDGE EMERGENCY GENERATOR ROOM ENGINE CONTROL ROOM

NOVEC REMOTE RELEASE STATION SIGN

NOVEC REMOTE RELEASE STATION

NOVEC LOCAL FIRE EXTINGUISHING BATTERY

NOVEC LOCAL FIRE EXTINGUISHING BATTERY

NOVEC BOTTLES

NOVEC RELEASE SIREN

HOW TO ACTIVATE NOVEC SYSTEM


SOUND GENERAL ALARM BY NEAREST MANUAL CALL POINT CONFIRM ALL PERSONNEL HAVE EVACUATED SPACE CLOSE ALL VENTILATION TO THE SPACE ON FIRE CONFIRM ALL DOORS ARE CLOSED CONFIRM LOCAL ACTIVATION STATION PULL PIN ON BOTTLE A PULL LEVER UP AND OPEN FULLY PULL PIN ON BOTTLE B PULL LEVER UP AND OPEN FULLY NOVEC WILL BE RELEASED INTO SPACE WITHIN 30 SECONDS DO NOT RE-OPEN DOOR

NOVEC ACTIVATION POINTS


THRUSTER VFD ROOMS: Remote - Adjacent Rooms Local - Aft Fire Suppression Rooms

DRILLING SWITCHBOARD ROOMS: Remote Thruster VFD Rooms #7 & #8 Local Thruster Transformer Room #6

DP BACKUP ROOM:

NOVEC ACTIVATION POINTS

BRIDGE:
Remote Bridge Access Corridor Local Upper Deck by Helipad Stairs

EMERGENCY GENERATOR ROOM:


Rm Remote Main deck by Door, Rig Air Compressor Local Mechanics Workshop

ENGINE CONTROL ROOM:


Remote Engine Start Air Compressor #1, Mud Pump Rm Local Port Drilling Transformer Room

IN CONCLUSION

You might also like