Ducted Split Air Conditioner

SERVICE MANUAL
MODELS: LN-0880CC LN-1080CC LN-1380CC LN-1580CC LN-2080CC

Contents
Model Number Nomenclature...............................................................................................2 General Data ..........................................................................................................................3 Dimensions ............................................................................................................................5 Wiring Diagram ......................................................................................................................6 Troubleshooting Guide .........................................................................................................8 Features of Controller .........................................................................................................20 Exploded View and Replacement Parts List .....................................................................25

Model Number Nomenclature

LN-1080CC

C: Convertible H: Horizontal Flow D: Down Flow C: Cooling Only H: Heat Pump Development Sequence 1 : 115/60/1 5 : 200-220/50/1 8 : 380-415/50/3 B : 220/60/3 2 : 220/60/1 6 : 220-240/50/1 9 : 380-415/60/3 C : 440-460/50/3 3 : 208-230/60/1 7 : 100/50(60)/1 A : 220/50/3 D : 440-460/60/3

03 : 3 ton 04 : 4 ton 05 : 5 ton 06 : 6.25 ton

Nominal cooling capacity 08 : 7.5 ton 15 : 15 ton 09 : 8.5 ton 18 : 17.5 ton 10 : 10 ton 20 : 20 ton 13 : 12.5 ton 25 : 25 ton

LG Ducted Split Air Conditioner

General Data
Table-1
Models Cooling (Btu/h) (W) (kcal/h) (Watt) (PH,Hz,V) (Amps) (Amps) (Watt) (Btu/hr.W) (m3/min) ( /hr) dB(A) (dB(A),1m) LN-0880CC 78,000 22,854 19,656 Option(9/18kW) 3/380-415/50 16.5 21 8,200 9.5 75 / 121 7.5 88 O O O O O O(With E/Heater) O O Variable Speed Auto-Restart O O O O 9.52 2/17FPI 1809.4 1.65 9.52 2/17FPI 1100 0.84 Propeller 2/526 Direct 900 1260*1120*635 1245*930*650 140(307) 160(353) 15.88 25.4 12/24 LN-1080CC 108,000 31,644 27,216 Option(9/18kW) 3/380-415/50 20 30 11,200 9.6 100 / 130 11 90 O O O O O O(With E/Heater) O O Variable Speed Auto-Restart O O O O 9.52 2/17FPI 2076 1.9 9.52 2/17FPI 1100 0.84 Propeller 2/526 Direct 900 1260*1120*635 1245*930*650 150(331) 169(373) 12.7*2 19.05*2 12/24

Capacity

Electric Heater Electrical Data Voltage Running Current Cooling M.C.A Power Input Cooling Performance EER Cooling Air Circulation (Indoor/Outdoor) Moisture Removal Noise Cooling Outdoor Wired Remote Controller Time Delay Safety Function Vertical Air-flow Direction control Horizontal Air-flow Directioon control Cooling Operation Mode Heating Operation Mode Air Circulation Mode Soft Dry Operation Fan Speeds Auto-Operation Sleep Mode Timer Setting (24-Hour on/off) Forced Operation Self-Diagnosis Function Tube Size Row/FPI Length Face Area Tube Size Row/FPI Length Face Area Type No. used/Diameter Drive Type RPM Indoor unit (WxHxD) Outdoor unit (WxHxD) Indoor unit Outdoor unit Liquid Gas Without S/Parts

Features

(steps)

(mm) (mm) (m2) (mm) (mm) (m2)

Outdoor Coil

Indoor Coil

Outdoor Fan

Dimensions Net Weight Service Valve Stuffing

(mm) (mm) kg(Ibs) kg(Ibs) (mm) (mm) (20FT/40FT)

1) Test Condition of ARI Rated Cooling Capacity : Ambient:95F , Air entering temprature : 80F DB and 67F WB 2) ARI standard 210/240 or 360 for EER 270 for Sound

General Data
Table-2
Models Cooling (Btu/h) (W) (kcal/h) (Watt) (PH,Hz,V) (Amps) (Amps) (Watt) (Btu/hr.W) (m3/min) ( /hr) dB(A) (dB(A),1m) LN-1380CC 132,000 38,676 33,264 Option(18/36kW) 3/380-415/50 24 34 13,300 9.9 124 / 140*2 13.5 92 O O O O O O(With E/Heater) O O Variable Speed Auto-Restart O O O O 9.52 9.52 2/17FPI 2/17FPI 1809.4 1809.4 1.65 1.65 9.52 LN-1580CC 159,000 46,587 40,068 Option(18/36kW) 3/380-415/50 33 42 16,200 9.8 150 / 121*2 16.5 LN-2080CC 215,000 62,995 54,180 Option(18/36kW) 3/380-415/50 42 54 22,000 9.8 199 / 130*2 20 -

Capacity

Electric Heater Electrical Data Voltage Running Current Cooling M.C.A Power Input Cooling Performance EER Cooling Air Circulation (Indoor/Outdoor) Moisture Removal Noise Cooling Outdoor Wired Remote Controller Time Delay Safety Function Vertical Air-flow Direction control Horizontal Air-flow Directioon control Cooling Operation Mode Heating Operation Mode Air Circulation Mode Soft Dry Operation Fan Speeds Auto-Operation Sleep Mode Timer Setting (24-Hour on/off) Forced Operation Self-Diagnosis Function Tube Size Row/FPI Length Face Area Tube Size Row/FPI Length Face Area Type No. used/Diameter Drive Type RPM Indoor unit (WxHxD) Outdoor unit (WxHxD) Indoor unit Outdoor unit Liquid Gas Without S/Parts

Features

(steps)

(mm) (mm) (m2) (mm) (mm) (m2)

Outdoor Coil

92 92 O O O O O O O O O O O(With E/Heater) O(With E/Heater) O O O O Variable Speed Variable Speed Auto-Restart Auto-Restart O O O O O O O O 9.52 9.52 9.52 9.52 2/17FPI 2/17FPI 2/17FPI 2/17FPI 1809.4 1809.4 1809.4 1809.4 1.65 1.65 1.65 1.65 9.52 9.52

Indoor Coil

Outdoor Fan

Dimensions Net Weight Service Valve Stuffing

(mm) (mm) kg(Ibs) kg(Ibs) (mm) (mm) (20FT/40FT)

3/17FPI 3/17FPI 3/17FPI 1100 1400 1300 0.84 1.07 1.42 Propeller Propeller Propeller 2/526 2/526 2/526 2/526 2/526 2/526 Direct Direct Direct Direct Direct Direct 900 900 900 900 900 900 1260*1120*635 1560*1120*635 1460*1653*818 1245*930*650 1245*930*650 1245*930*650 1245*930*650 1245*930*650 1245*930*650 160(373) 170(375) 210(463) 2*160(2*353) 2*160(2*353) 2*169(2*373) 12.7 12.7 15.88 15.88 15.88 15.88 25.4 25.4 25.4 25.4 25.4 25.4 9/20 7/16 4/9

1) Test Condition of ARI Rated Cooling Capacity : Ambient:95F , Air entering temprature : 80F DB and 67F WB 2) ARI standard 210/240 or 360 for EER 270 for Sound

Dimensions
LN-0880CC/LN-1080CC/LN-1380CC/LN-1580CC/LN-2080CC 1. Indoor unit
Unit Dimensions
MODEL A B C D E F G H I J K L M LN-0880CC LN-1080CC 49.6(1,260) 25(635) 44.1(1,120) 14.2(362) 14(356) 13.4(340) 10.8(274) 23.3(593) 2(51) 7.1(180) 7.9(200) 2(51) 22.1(562) LN-1380CC 49.6(1,260) 25(635) 44.1(1,120) 9.8(248) 18.5(470) 13.4(340) 10.8(274) 23.3(593) 2(51) 7.1(180) 7.9(200) 2(51) 22.1(562)

Unit: inch(mm)
LN-1580CC 61.4(1,500) 25(635) 44.1(1,120) 10.6(269) 18.5(470) 15.7(398) 8.4(214) 23.3(593) 2(51) 7.1(180) 7.9(200) 2(51) 22.1(562) LN-2080CC 57.5(1,460) 25.6(650) 65.1(1,653) 12.7(332) 24.3(617) 19.2(487) 11.8(299) 29.2(740) 2(51) 7.1(180) 7.9(200) 2(51) 22.1(562)

D A E

F G

I H

J K M L B

2. Outdoor unit Unit: inch(mm) LN-0880CC, LN-1080CC LN-1380CC, LN-1580CC LN-2080CC


1245

Each model of these three models(LN-1380CC/ LN-1580CC/LN-2080CC) is operated with the doubled of the right outdoor unit.
130 930 70.5

350 435 750 650

750

Wiring Diagram
LN-0880CC

LN-1080CC

Wiring Diagram
LN-1380CC/LN-1580CC/LN-2080CC

Troubleshooting Guide
In general, possible trouble is classified in two causes. The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application. Unit runs but ineffective cooling

Ineffective Cooling or Heating

Check of cold (warm) air circulation for smooth flow.

Check of outdoor coil (heat exchanger) & the fan operation.

Check heat load increase in cooling operation.

Dirty indoor coil (heat exchanger.)

Unexpected residue Check gas leakage.

Added electrical utencil Malfunction of fan. Repair gas leak.

Clogging of air filter.

Replacement of unit if the unit is beyond repair.

Check of inside gas pressure.

Obstruction at air outlet.

Adjust refrigerant charge.

Countermeasure against above trouble. Malfunction of compressor. Check clogging in refrigeration circuit. Satisfactory operation with temperature difference of inlet & outlet air ; COOLING : 7~10C HEATING : 15~17C Replacement of compressor

Repair clogging in refrigeration circuit.

Troubleshooting Guide
Fails to Start

Check power source.

Check of circuit breaker and fuse.

Check control switch setting.

Check control switch.

Compressor only fails to start.

Fan only fails to start. Electric heater is not energized Improper wiring.

Drop of power voltage.

Loose terminal connection. Defect of fan motor capacitor.

Defect of compressor capacitor.

Improper wiring

Irregular motor resistance Capacitor check.

() ()

Irregular motor insulation

Replacement of capacitor. Replacement of fan motor.

Improper electric heater Irregular motor resistance ( ) Regular but fails to start. Replacement of electric heater. Replacement of compressor. Replacement of compressor

Irregular motor insulation ( )

Troubleshooting Guide
VOLTAGE LIMITS
NAME PLATE RATING 380 - 415 V MINIMUM 342 V MAXIMUM 456 V

1. No cooling and heating operation performed


1) Both the blower and the compressor do not work
WHAT TROUBLED Other parts except the unit COMPLAINTS Electric supply interrupted Defective power wiring Cut off power fuse HOW TO CHECK Measure power sypply with a tester in case that the same power source is supplied to other equipment except the unit, what and where troubled can be discovered by checking the operation of other equipment. Measure it with a tester. REMEDY Repair a switch box and relative instrument. Replacement of fuse Request a power supplier to repair.

Too low voltage

Check the power source. Use a thick cable if necessary. Replace it if necessary.

Magnetic switch for compressor & fan motor

Control point is on condition of "OFF" due to trouble. Troubled or defective contactor

Make short-circuit, then measure it with tester.

Operating switch

Check it with the eyes or tester.

Repair or replace it.

2) Only Indoor blowers do not work


WHAT TROUBLED Motor COMPLAINTS Over heated Wiring short Defected Cut- OFF of wiring Short circuited on operation HOW TO CHECK Check it with tester REMEDY Repair or replace it.

Capacitor

Check it with a tester.

Replace it.

Electric wiring

Check it with a tester.

Rewiring or Repair.

10

Troubleshooting Guide
3) Only outdoor fan does not work
WHAT TROUBLED Motor Electric Wiring COMPLAINTS Over-heated Wire short Cut off of wiring Short circuited on operation HOW TO CHECK Check how it is insulated. Check it with a tester. REMEDY Repair or replace it. Rewiring or repair.

4) Only compressor does not work


WHAT TROUBLED Magnetic switch for compressor motor Compressor motor COMPLAINTS Defective contact, magnetic coil troubled. Troubled over-heated (layer short) Troubled or defective contact or operating Defective connection or disconnection of the circuit for compressor. HOW TO CHECK Check it with the eyes on with a tester. Check how it is insulated. REMEDY Repair or replace it.

Replace or repair the compressor. Replace it if necessary. Rewiring or push reset button.

High pressure switch (Option part) Electric circuit

Check it with a tester.

Check it with a tester.

11

Troubleshooting Guide
2. The Units discontinue after the operation started
WHAT TROUBLED Outdoor coil COMPLAINTS Coil is dirty *1 HOW TO CHECK Checking REMEDY Wash it by means of something like chemical washing. Extract air by vacuum pump, then replenish (charge) the refrigerant.

In-condensable gas blended.

Air intruded into the refrigerant pipe line *1

In the event that difference between the saturating temperature corresponding to high pressure and the temperature of air discharged from the outdoor coil is more than 15C, incondensable gas may be blended. Check it with a pressure gauge.

High pressure switch (Option part)

Improper adjustment

Read just it to normal operating pressure. (Note) Don't alternate the specified adjusting pressure. If the adjusted pressure exceed the specified range, it will cause a great accident. Replenish the refrigerant. Repair the spot where it is leaked. If reversed, connect interchanged wires to each terminal. Power wirings.

Refrigerant

A shortage of refrigerant amount. * 2

Check pressure

Outdoor Fan

Reverse rotation of fan Obstacle Air short circuit *1

Confirm the wind blowing out upward. Check it with eyes.

Note: Use an appropriate measuring instrument for readjustment. *1: High-pressure switch moves. *2: Low- pressure switch moves.

12

Troubleshooting Guide
3. The unit is working, but not cooling and heating sufficiently (Both blower and compressor are working)
WHAT TROUBLED Load COMPLAINTS Much Cooling or Heating load HOW TO CHECK Heat load increased. Window or door has many cracks or gaps. Checking REMEDY Do necessary disposal respectively.

Air flow

Obstacle disturbs Intake of uniform airflow. Reverse rotation of blower. Shortage in the charged refrigerant. Improper or foreign bodies

Correct it.

Short air volume

Checking

Correct it.

Refrigerant

Coil inlet pipe is frosted

Recharge it. (Repair the leakage spot). Correct or clear the foreign bodies. Cleaning

Air passage

Checking Checking

Air filter

Clogged with dust

4. All the functions are performed as specified, but very noisy and vibrant
WHAT TROUBLED Compressor COMPLAINTS Liquid refrigerant flooding back from the evaporator. HOW TO CHECK REMEDY Check for refrigerant over-charge. Check to see if the intake air temperature is extremely cold. Check for insufficient air flow quantity. Checking Replace the compressor Repair or replace it. Clear the foreign bodies.

Faulty Discharge valve and suction valve. Blower Fan broken. Foreign matters intruded. Screws Electric troubles (Magnetic contactor) Looseness or fail-off of screws Defective contact. Defective contact point. Rusting and foreign matters in the iron core contact face. Defective contact of the operating switch. Improper installation

Checking

Checking

Correct Repair and clean or replace it.

Checking

Others

Checking

Correct it.

13

Electronic parts Troubleshooting Guide


Possible trouble 1
Is the input voltage of transformer AC220V?
YES

: The unit does not operate.


NO

1. Check the Fuse. 2. Check the wiring of AC220V.

Is the output voltage of transformer AC24V & AC13V?


YES

NO

1. Exchange the transformer. 2. Check the connector of transformer.

Is the output voltage of IC02D(7805) on the main PCB DC5V?


YES

NO

1. Exchange IC02D(7805) on the main PCB. 2. Check the D01D~D05D, R05C on the main PCB.

Is the output voltage of IC01D(7812 ) on the main PCB DC12V?


YES

NO

1. Exchange IC01D(7812) on the main PCB. 2. Check the D01D~D05D, R05C on the main PCB.

Is the output voltage of IC01A(7036) on the main PCB DC5V?


YES

NO

1. Exchange IC01A(7036) on the main PCB.

OSC vibration?

NO

1. Exchange OSC. 2. Check the pattern around OSC on the main PCB.

YES

1. Exchange main PCB ASS'Y

Possible trouble 2
Is the power ON?
YES

: The remote-controller does not operate.


NO

1. Exchange or exchange FUSE. 2. Check the input voltage of Main PCB ASS'Y.

Is the input voltage of remote-controller DC12V?


YES

NO

1. Check or exchange the IC01D on the Main PCB. 2. Check or exchange the Connector (RED, BROWN) of the remote controller.

1. Exchange remote-controller 2. Check or exchange the Main PCB ASS'Y.

14

Electronic parts Troubleshooting Guide


Possible trouble 3
Is the connection between MAIN PCB and remote-controller correct?
YES YES

: Key input of remote-controller does not respond.


NO

1. Check or repair Connector wiring. 2. Exchange the Connector.

Is any key on the remote-controller keeping pressed?


NO

1. Replace the pressed key. 2. Exchange the Knob or Key.

Is there Check(F**) on the remote controller LCD?


NO

YES

1. Remove cause of Check. 2. Reenergize the power supply.

Is the input power voltage of remote-controller DC12V?


YES

NO

1. Check or exchange IC01D (7812) on the MAIN PCB.

Is there OSC vibration on the remote-controller PCB?


YES

NO

1. Exchange OSC 2. Check the pattern around OSC on the remote-controller PCB.

Do Keys have troubles?

YES

1. Check Keys. 2. Repair or exchange Key.

NO

Exchange remote-controller.

Possible trouble 4
Are there trouble in LCD parts?
NO

: LCD display on the remote-controller shows some trouble.


YES

1. Check crack, damage of LCD. 2. Check LCD pattern.

Is there trouble in the remote-controller PCB ASS'Y?


NO

YES

1. Check or repair all IC with dust or moisture on the PCB. 2. Exchange remote-controller PCB.

Exchange remote-controller.

15

Electronic parts Troubleshooting Guide


Possible trouble 5
: No cooling operation performed.
NO

Is the unit operating?

1. Press power ON/OFF button.

YES

Is the cooling mode?

NO

1. Press cooling operation key. 2. After reenergizing power supply, press power "ON/OFF" button.

YES

Set Temp. < Room Temp.?

NO

1. Set flowing. 'Set Temp. < Room Temp.'

YES

Is the output voltage of Micom's 4PIN on the MAIN PCB DC0V?


YES

NO

1. Check or exchange IC02D. 2. Check 3-minutes time delay.

Is the voltage between 1PIN of CN-COMP and NEUTRAL 220V?


YES

NO

1. Check or exchange RY4.

Is the magnetic contactor for compressor OK?


YES

NO

1. Check the wiring of Magnetic contactor. 2. Exchange Magnetic contactor.

1. Check Compressor and Capacitor for Compressor. NOTE: 3 model has not capacitor for compressor.

16

Electronic parts Troubleshooting Guide


Possible trouble 6
: No heater operation performed.
NO

Is the heater operation?

1. Select heater operation mode.

YES

Is the heater LCD "ON"?

NO

1. Reconnetting power supply. press Heater Key.

YES

Set temp. > Room temp.?

NO

1. Set following. 'Set temp. > Room temp.'

YES

Is the output voltage of Micom's 13PIN on the MAIN PCB 5V?


YES

NO

1. Check or exchange IC01D, IC02D on the MAIN PCB.

Is the voltage between 1PIN of CN6 and NEUTRAL 220V?


YES

NO

1. Check or exchange RY13.

Is the magnetic contactor for heater OK?


YES

NO

1. Check the wiring of Magnetic contactor. 2. Exchange Magnetic contactor.

Check or exchange E/Heater.

17

Electronic parts Troubleshooting Guide


Possible trouble 7
Is the indoor fan operation?

: No humidifier operation performed.


NO

1. Press cooling or fan operation or heater operation key.

YES

Is the HUMID LCD "ON"?

NO

1. Press humidifier Key.

YES

Is the output voltage of Micom's 3PIN on the MAIN PCB 5V?


YES

NO

1. Check or exchange IC02D on the MAIN PCB.

Is the voltage between 1PIN of CN5 and NEUTRAL 220V?


YES

NO

1. Check or exchange RY3.

Is the magnetic contactor for humidifier OK?

NO

1. Check the wiring or Magnetic contactor. 2. Exchange Magnetic contactor.

YES

Check the humidifier.

18

Electronic parts Troubleshooting Guide


Possible trouble 8
: Indoor motor does not operate.

Is the unit operating?

NO

1. Press power ON/OFF button. 2. Reconnect the power supply.

YES

Is the output voltage of Micom's 10PIN on the MAIN PCB 5V?


YES

NO

1. Check or exchange IC01D, IC02D on the main PCB.

Is the voltage between 1PIN of CN8 and NEUTRAL 220V?


YES

NO

1. Check or exchange RY10.

Is the "Power relay" for indoor motor OK?


YES

NO

1. Check the wiring of "Power relay". 2. Exchange "Power relay".

Check the indoor motor.

Possible trouble 9

: Outdoor motor does not operate.

Is it cooling operation?

NO

1. Press power "ON/OFF" button. 2. Select cooling operation.

YES

Is the compressor operating?

NO

YES

1. Set following. Set temp. < Room temp. 2. Wait, if the unit has operating with 3-minute time delay.

1. Check wiring for outdoor motor and magnetic contactor. 2. Check outdoor motor & capacitor.

19

Features of Controller
1. Main Controller Circuit Diagram

20

2. Feature of Main Controller

21

3. Feature of Remote-Controller PCB ASS'Y

4. Feature of Remote-Controller LCD

22

5. Error Mode & Corrective Method


Error mode F01 Cause of error Sensing condition of error Method of SVC Remark OPEN/SHORT of Voltage of sensing: Over 4.8V room temp. Voltage of sensing: Less than sensor 0.5V OPEN/SHORT of Voltage of sensing: Over 4.8V indoor pipe temp. Voltage of sensing: Less than 0.5V sensor Communication Error F03 Communication interruption between remote controller and Main PCB for 2 minutes. Room 1. Check the voltage of "CO1H" temp.(25C) on the remote controller. = DC 2.5V 2. Check the temp. sensor of remtote controller. 1. Check the voltage between PIN 3 Pipe temp.(25C) and 4 of CN-A cycle/CN-B cycle. = DC 2.2V 2. Check the temp. sensor of indoor pipe. 1. Check the connecting wire between main PCB remote controller. 2. Check the input voltage of remote-controller. 3. Check the wiring of remote-controller. 1. Check the voltage between PIN 1 and 2 of CN-A cycle/CN-B cycle ON the main PCB. 2. Check the temp. sensor of remtote controller. 1. Check the voltage between PIN 1 and 3 of CN-TEMP OUT on the main PCB. 2. Check the temp. sensor of outdoor room. Input voltage of remote-controller = DC 12V

F02

F04

OPEN/SHORT of Voltage of sensing: Over 4.8V Voltage of sensing: Less than outdoor pipe 0.5V sensor OPEN/SHORT of Voltage of sensing: Over 4.8V Voltage of sensing: Less than outdoor room 0.5V temp. sensor

Pipe temp.(25C) = DC 2.5V

F05

Room temp.(25C) = DC 2.2V

6. Principal part list of controller


Model LN-0880CC LN-1080CC LN-1380CC LN-1580CC LN-2080CC Main PCB ASM Remote controller Pipe Sensor A Pipe Sensor B Return Air Sensor Power Trans Remark

6871A20085G 6711A20043A 6323A20002N

6323AQ3214M 6171AQ2138D Cooling Only (Option) Cooling Only

6871A20085H 6711A20043A 6711A20002N

6323A20002P 6323AQ3214M 6171AQ2138D (Option)

7. Principal part list of Main PCB ASM


No 1 2 3 4 5 Part No 0ITO874000E 6920AQ9033F 6212AQ9002J 6900AQ9028D 6102A90001A Part Name MICOM(Main) Relay Oscillator Fuse Varistor Remarks MICOM

8. Principal part list of Remote Controller


No 1 2 3 Part No OITO641010B 6304A30001C 6871A10022M Part Name Remark MICOM(Remote Controller) MICOM LCD Remote C PCB ASM Cooling Only

23

9. Explanation of principal function


s Flow Chart
START(Power supply)
YES

1. Initialize "micom". 2. A/D convert. 3. Main PCB: Waiting cooling operation. 4. Remote controller: Waiting input. Dehumidification Mode?
A YES YES

NO

Heater operation mode?

YES

Power ON?

NO

Dehumidification operating
YES NO

NO

Set Temp. > Indoor Temp.

YES

Cooling Mode?

Stop condition? Heater operating

YES

YES

YES

NO

Go to A Set Temp. < Indoor Temp.

NO

Stop condition?

YES YES

YES

Go to A

Time delay mode

NO

Cooling operating

Fan only operating

NO

Stop condition?

NO

Stop condition?

YES

YES

Go to A

Go to A

24

Exploded View and Replacement Parts List


1. Indoor Unit
Exploded View (LN-08/10/13/15/2080CC)

359012

354210

713269 145610 W4400

261704

W6920

268714 346810 249951

552111

330870

25

Exploded View and Replacement Parts List


2. Outdoor Unit
Exploded View (LN-08/10/13/15/2080CC)

554031

W0CZZ

649950

W6920

346811

435311

559010

26

552203

554160

566001

Exploded View and Replacement Parts List


Replacement Parts List LN-0880CC
LOCATION No. W4400 W0CZZ 554160 554031 249951 649950 330870 354210 559010 359012 435311 346811 346810 145610 145610 268714 W6920 694790 566001 713269 261704 552111 552203 DESCRIPTION BELT, V CAPACITOR, DRAWING COMPRESSOR ASSY, FINAL CONDENSER ASSY, BENT CONTROL BOX ASSEMBLY, INDOOR CONTROL BOX ASSY, OUTDOOR DRAIN PAN ASSEMBLY EVAPORATOR ASSY, FIRST FAN ASSEMBLY, PROPELLER FAN, SIDE GRILLE ASSY, DISCHARGE(OUTDOOR) MOTOR ASSEMBLY, OUTDOOR MOTOR ASSY, INDOOR PULLEY ASSEMBLY PULLEY ASSY PWB(PCB) ASSY, MAIN RELAY REMOTE CONTROLLER ASSY SWITCH, MAGNET THERMISTOR ASSY TRANSFORMER, POWER TUBE ASSY, CAPILLARY VALVE, SERVICE VALVE, SERVICE LN-0880CC 4400A30001V 2H00841J 5417A20007F 5403AP2618H 4995A10043D 4995AP2608K 3087A20009B 5421A20029C 0A00026B 5835A20001A 2A00144P 4680AP2610B 4681A20018B 3A00217R 4561A30001L 6871A20085G 6920AP3400A 6711A20043A 2A01031A 6323A20002N 6171AQ2138D 5211A20297K 2A00468C 2A00469H QUANTITY 1 2 1 4 1 1 2 1 4 1 2 2 1 1 1 1 2 1 1 1 1 1 1 1

27

Specification of components
Replacement Parts List LN-1080CC
LOCATION No. W4400 W0CZZ 554160 554031 249951 649950 330870 354210 559010 359012 435311 346811 346810 145610 145610 268714 W6920 694790 566001 713269 261704 552111 552203 DESCRIPTION BELT,V CAPACITOR,DRAWING COMPRESSOR CONDENSER ASSY,BENT CONTROL BOX ASSEMBLY,INDOOR CONTROL BOX ASSY,OUTDOOR DRAIN PAN ASSEMBLY EVAPORATOR ASSY,FIRST FAN ASSEMBLY,PROPELLER FAN,SIDE GRILLE ASSY,DISCHARGE(OUTDOOR) MOTOR ASSEMBLY,INDOOR MOTOR ASSEMBLY,OUTDOOR PULLEY ASSEMBLY PULLEY ASSY PWB(PCB) ASSY,MAIN RELAY REMOTE CONTROLLER ASSY SWITCH,MAGNET THERMISTOR ASSY THERMISTOR ASSY TRANSFORMER,POWER TUBE ASSY,CAPILLARY VALVE,SERVICE VALVE,SERVICE LN-1080CC 4400A30002M 2H00841J 5417A20008G 5403AP2618B 4995A10043C 4995A20080D 3087A20009B 5421A20029D 0A00026B 5835A20003A 2A00144P 4681A20025C 4680AP2610B 3A00217R 4561A30002B 6871A20085H 6920AP3400A 6711A20043A 2A01031A 6323A20002N 6323A20002P 6171AQ2138D 5211A20297E 2A00499E 2H01890M QUANTITY 1 2 2 4 1 1 1 2 2 1 2 2 2 1 1 1 2 1 2 1 1 1 2 2 2

28

Exploded View and Replacement Parts List


Replacement Parts List LN-1380CC
LOCATION No. W4400 W0CZZ 554160 554031 249951 649950 330870 354210 559010 359012 435311 346811 346810 145610 268714 W6920 694790 566001 713269 261704 552111 552203 DESCRIPTION BELT, V CAPACITOR, DRAWING COMPRESSOR CONDENSER ASSY, BENT CONTROL BOX ASSEMBLY, INDOOR CONTROL BOX ASSY, OUTDOOR DRAIN PAN ASSEMBLY EVAPORATOR ASSY, FIRST FAN ASSEMBLY, PROPELLER FAN, SIDE GRILLE ASSY, DISCHARGE(OUTDOOR) MOTOR ASSEMBLY, INDOOR MOTOR ASSEMBLY, OUTDOOR PULLEY ASSEMBLY PULLEY ASSY PWB(PCB) ASSY, MAIN RELAY REMOTE CONTROLLER ASSY SWITCH, MAGNET THERMISTOR ASSY THERMISTOR ASSY TRANSFORMER, POWER TUBE ASSY, CAPILLARY VALVE, SERVICE VALVE, SERVICE LN-1380CC 4400A30002M 2H00841J 5417A20007H 5403AP2618H 4995A10043C 4995AP2608M 3087A20009D 5421A20029B 0A00026B 5835A20003B 2A00144P 4681A20025C 4680AP2610B 3A00217R 4561A30002A 6871A20085H 6920AP3400A 6711A20043A 2A01031A 6323A20002N 6323A20002P 6171AQ2138D 5211A20297T 2A00468C 2A00469H QUANTITY 1 4 2 8 1 2 2 1 4 1 4 1 4 1 1 1 1 1 2 1 1 1 2 2 2

29

Exploded View and Replacement Parts List


Replacement Parts List LN-1580CC
LOCATION No. W4400 W0CZZ 554160 554031 249951 649950 330870 354210 559010 359012 435311 346811 346810 145610 268714 W6920 694790 566001 713269 261704 552111 552203 DESCRIPTION BELT, V CAPACITOR, DRAWING COMPRESSOR CONDENSER ASSY, BENT CONTROL BOX ASSEMBLY, INDOOR CONTROL BOX ASSY, OUTDOOR DRAIN PAN ASSEMBLY EVAPORATOR ASSY, FIRST FAN ASSEMBLY, PROPELLER FAN, SIDE GRILLE ASSY, DISCHARGE(OUTDOOR) MOTOR ASSEMBLY, INDOOR MOTOR ASSEMBLY, OUTDOOR PULLEY ASSEMBLY PULLEY ASSY PWB(PCB) ASSY, MAIN RELAY REMOTE CONTROLLER ASSY SWITCH, MAGNET THERMISTOR ASSY THERMISTOR ASSY TRANSFORMER, POWER TUBE ASSY, CAPILLARY VALVE, SERVICE VALVE, SERVICE LN-1580CC 4400A30002G 2H00841J 5417A20007F 5403AP2618H 4995A10043C 4995AP2608M 3087A20009F 5421A20029E 0A00026B 5835A20003B 2A00144P 4681A20025D 4680AP2610B 3A00217R 4561A30002A 6871A20085H 6920AP3400A 6711A20043A 2A01031A 6323A20002N 6323A20002P 6171AQ2138D 5211A20297T 2A00469H 2A00468E QUANTITY 1 4 2 8 1 2 2 1 4 1 4 1 4 1 1 1 1 1 2 1 1 1 2 2 2

30

Exploded View and Replacement Parts List


Replacement Parts List LN-2080CC
LOCATION No. W4400 W0CZZ 554160 554031 249951 649950 330870 354210 559010 359012 435311 346811 346810 145610 268714 W6920 694790 566001 713269 261704 552111 552203 DESCRIPTION BELT, V CAPACITOR, DRAWING COMPRESSOR CONDENSER ASSY, BENT CONTROL BOX ASSEMBLY, INDOOR CONTROL BOX ASSY, OUTDOOR DRAIN PAN ASSEMBLY EVAPORATOR ASSY, FIRST FAN ASSEMBLY, PROPELLER FAN, SIDE GRILLE ASSY, DISCHARGE(OUTDOOR) MOTOR ASSEMBLY, INDOOR MOTOR ASSEMBLY, OUTDOOR PULLEY ASSEMBLY PULLEY ASSY PWB(PCB) ASSY, MAIN RELAY REMOTE CONTROLLER ASSY SWITCH, MAGNET THERMISTOR ASSY THERMISTOR ASSY TRANSFORMER, POWER TUBE ASSY, CAPILLARY VALVE, SERVICE VALVE, SERVICE LN-2080CC 4400A30002J 2H00841J 5417A20007G 5403AP2618H 4995A10043C 4995AP2608M 3087A20009F 5421A20029H 0A00026B 5835A20003D 2A00144P 4681A20031D 4680AP2610B 3A00217S 4561A30003C 6871A20085H 6920AP3400A 6711A20043A 2A01031A 6323A20002N 6323A20002P 6171AQ2138D 5211A20297U 2A00469H 2A00468E QUANTITY 1 4 2 8 1 2 2 2 4 1 4 1 4 1 1 1 1 1 2 1 1 1 2 2 2

31

Memo

32

Memo

33

P/No.: 3828A30027Z

Novermber, 2001 Printed in Korea