Professional Documents
Culture Documents
CONTENTS
1. Concept of Ferroresonance
2. Example of Ferroresonance
4. Indicators of Ferroresonance
5. Managing Ferroresonance
6. Mitigation techniques
7. Conclusion
CONCEPT OF FERRORESONANCE
What is resonance ?
I = E/(jXL jXc)
What is ferroresonance ?
EXAMPLE OF FERRORESONANCE
WOUND PT- CB GRADING CAPACITANCE
OPEN-DELTA PT
Concerns for ferroresonance in open-delta PTs exist
During energization of the unloaded stepdown transformer Following interruption of a single line-to-ground fault on the low side of the transformer.
Mitigation Options 1. Replacing PTs with (CCVTs). 2. Installing PTs that are rated for line-to-line system voltage. 3. Installing a resistor in the broken-delta.
The most common events leading to ferroresonance are :1. Manual switching of an unloaded, cable-fed, three-phase transformer where only one phase is closed .
2. Manual switching of an unloaded, cable-fed, three-phase transformer where one of the phases is open.
3. One or two riser-pole fuses may blow leaving a transformer with one or two phases open. Single-phase reclosers may also cause this condition.
INDICATORS OF FERRORESONANCE
Common indicators of ferroresonance are as follows:1. Audible noise.
2. Overheating.
4. Flicker
MANAGING FERRORESONANCE
Strategies for dealing with ferroresonance include :1. Preventing the open-phase condition
MITIGATION OF FERRORESONANCE
Ferroresonance is prevented by:1. Use a delta connected primary VT.
3. Purchase a VT designed to operate at much lower induction values, so that the saturation point is at least twice the system voltage.
8. Eliminate fuses. Rely on feeder breaker for fault interruption. Various measures to prevent inadvertent fuse operation.
CONCLUSION
The impact of ferroresonance can vary from relay or control misoperation to catastrophic equipment failure. By being aware of the various situations where ferroresonance can occur, appropriate mitigation strategies can be designed before equipment is put into service and problems develop.
Capacitor voltage transformers are protected by ferroresonance suppression circuits installed by the manufacturer. Depending on the application, high speed suppression of the transient ferroresonant oscillations may be needed, which requires a more sophisticated FSC.