You are on page 1of 3

Thermodynamic Properties of Absorption System

State Point Chemical Composition Point


1 Water vapor Generator 1 output
2 Water vapor Generator 2 output to Condenser
3 Water Vapor Generator 2 output
4 Water Vapor Condenser Input
5 Water (Saturated Liquid) Condenser Output
6 Water (Saturated Liquid) Expansion Valve Output
7 Water vapor Evaporator Output
8 Water/LiBr Absorber Output
9 Water/LiBr Pump Output
10 Water/LiBr Heat Exchanger 2 output
11 Water/LiBr Heat Exchanger 1 output
Generator 1 output to Heat
12 Water/LiBr Exchanger 1
Heat Exchanger 1 output to
13 Water/LiBr Generator 2
14 Water/LiBr Generator 2 input
Generator 2 output to Heat
15 Water/LiBr Exchanger 2
Heat Exchanger 2 output to Pressure
16 Water/LiBr Reducing Valve
17 Water/LiBr Absorber Input
18 Syngas Generator 1 In
19 Syngas Generator 1 Out
Cooling Water
20 (For Cooling Load) Evaporator In
Cooling Water (For
21 Cooling Load) Evaporator Out
22 Cooling Water Absorber CW In

23 Cooling Water Absorber CW out to Condenser CW In


24 Cooling Water Condenser CW out
Thermodynamic Properties of Absorption System
o
T( C) X(%) h (kJ/kg) P (mm of Hg) P(kPa)
200 - 2790.90 600 80
105 - 2680.65 600 80
90 - 2660.10 52.5 7
90 - 2660.10 52.5 7
40 - 167.50 52.5 7
7.5 - 31.50 6.5 0.87
25 - 2547.30 6.5 0.87
40 50 -145 6.5 0.87
41 50 -144.95 600 80
90 50 -42.00 600 80
130 50 58.00 600 80

200 55 393.09 600 80

150 55 62.00 600 80


95 55 -43.00 52.5 7

105 61 -30.00 52.5 7

56 61 -135 52.5 7
43 61 -150 6.5 0.87
500 - - 760 101.325
250 - - 760 101.325

30 - 125.70 760 101.325

20 - 83.90 760 101.325


30 - 125.70 760 101.325

33 - 138.20 760 101.325


35.7 - 147.30 760 101.325
m (kg/s)
0.1
0.09
0.1
0.1
0.19
0.19
0.19
1
1
1
1

0.9

0.9
0.9

0.81

0.81
0.81
15
15

41

41
41