Manual Set Constant

(Signal Generator) Function Code 2

The output of the manual set constant is an analog signal


A
(2) developed within the function that is equal to <S1>. This func-
N
tion provides a tunable output value in engineering units.

Outputs

Blk Type Description


N R User selected constant

Specifications

Spec Tune Default Type Range Description


S1 Y 0.000 R Full Output value in engineering units

Applications
Scaler Figure 2-1 illustrates how to use the manual set constant as a
scaler. In the example, the transmitter has a range of 200 to
700 pounds per square inch. The range is scaled up 200
pounds per square inch by setting the manual set constant to
200. The summer adds <S1> and <S2> to provide an output
range of 400 to 900 pounds per square inch.

PT
20 0 -70 0
p si

S1 O U T PU T = S 1 + S 2
A
(2 ) S2 π (K) (1 5 )
N
OR
N 4 00 -9 00 psi

S 3 = 1 (G AIN O F S 1)
S1 = 200 S 4 = 1 (G AIN O F S 2)
T 01 5 82 A

Figure 2-1. Scaler Configuration

Set Point Figure 2-2 illustrates how to use the manual set constant for a
set point configuration. The transmitter range is ten to 20

WBPEEUI210504A0 2-1
inches of water. The desired set point (output of the summer
block) is 15 inches of water. By setting the manual set con-
stant to 15, the summer subtracts <S2> from <S1>. Thus,
when <S1> equals 15 inches of water, output N of the summer
block equals zero inches of water which shows the level has
reached set point.

FT
1 0 -2 0
in.H O
2

S1 ÿþýüþýûúûùøû÷ûùö

A
(2 ) S2 π (K ) (1 5 )
N ûûùýûüÿý
ÿ

N ùû
S 3 = 1 (G AIN O F S 1 )
S1 = 15 S 4 = 1 (G AIN O F S 2 )
T 01 5 83 A

Figure 2-2. Set Point Configuration

2-2 WBPEEUI210504A0