DIgSILENT Project:

PowerFactory
13.2.339 Date: 1/28/2011

Harmonics Calculation Unbalanced, 3-phase (ABC) Busbars and Branches


Nominal Frequency 50.00 Hz Output Frequency 50.00 Hz Calculate THD Rated to Fundamental Frequency Values (IEEE)

Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 1
Rated Bus-voltage Distortion Current Active Power cosphi
Voltage 50.00 Hz RMS Sum 50.00 Hz Tot. 50.00 Hz RMS 50.00 Hz Tot. 50.00 Hz Total Loading
[kV] [p.u.] [p.u.] [p.u.] [%] [%] [A] [ ] [kW] [MW] [-] [-] [%]
B1
0.40 1.00 0.00 1.11 4.24 11.50
Cub_2 /Lne Line 201.53 126.88 0.13 0.91 0.58 0.00
Cub_3 /Lne Line(1) 0.00 0.00 0.00 1.00 1.00 0.00
Cub_4 /Lne Line(2) 120.07 75.24 0.08 0.91 0.64 0.00
Cub_5 /Tr2 2-Winding Transformer 321.59 -202.12 -0.20 -0.91 -0.60
B2
0.40 0.83 0.00 2.13 81.46 157.18
Cub_1 /Lod Comp 187.98 95.77 0.01 0.89 0.06
Cub_2 /Lod LIght 13.55 6.98 0.01 0.90 0.68
Cub_3 /Lne Line 201.53 -102.76 -0.02 -0.89 -0.09 0.00
B3
0.40 1.00 0.00 1.11 4.24 11.50
Cub_1 /Lod General Load(2)
Cub_2 /Lod General Load(3)
Cub_3 /Lne Line(1) 0.00 -0.00 -0.00 -1.00 -1.00 0.00
B4
0.40 0.88 0.00 1.69 46.55 92.84
Cub_1 /Lod Comp1 92.60 49.97 0.03 0.89 0.26
Cub_2 /Lod Light1 27.47 14.99 0.01 0.90 0.80
Cub_3 /Lod General Load(6)
Cub_4 /Lne Line(2) 120.07 -64.96 -0.04 -0.89 -0.36 0.00
Terminal
15.00 1.00 0.00 1.01 0.27 0.67
Cub_2 /Xnet External Grid 8.58 202.12 0.20 0.91 0.70
Cub_1 /Tr2 2-Winding Transformer 8.58 202.12 0.20 0.91 0.70