Professional Documents
Culture Documents
SWITCH GEAR
A great demand of electricity is a notable feature of modern civilisation. Most of the
energy is required for lighting, heating, domestic appliances, industrial electrical machinery
and electrical traction. This importance of electric supply has constructed such
circumstances that we must secure the power system from large faults and provide
protection to the machineries and devices used and to ensure maximum continuity of the
power supply. For this purpose, machines such as generators and motors are needed to be
switched on and off many times. Means provided to achieve this are called ‘Switch gears’.
“The appratus used for switching, controlling and protecting electrical circuits and
equipments is known as switchgear.”
The term switchgear, used in association with the electric power system, or grid,
refers to the combination of electrical disconnects, fuses and/or circuit breakers used to
isolate electrical equipment. Switchgear is used both to de-energize equipment to allow
work to be done and to clear faults downstream. Switchgear is a non-count noun, much like
the software term “code,” and is never used as “switchgears.”
The very earliest central power stations used simple open knife switches, mounted
on insulating panels of marble or asbestos. Power levels and voltages rapidly escalated,
making open manually-operated switches too dangerous to use for anything other than
isolation of a de-energized circuit. Oil-filled equipment allowed arc energy to be contained
and safely controlled. By the early 20th century, a switchgear line-up would be a metal-
enclosed structure with electrically-operated switching elements, using oil circuit breakers.
Today, oil-filled equipment has largely been replaced by air-blast, vacuum, or SF6
equipment, allowing large currents and power levels to be safely controlled by automatic
equipment incorporating digital controls, protection, metering and communications.
Typically switchgear in substations is located on both the high voltage and the low
voltage side of large power transformers. The switchgear located on the low voltage side of
the transformers in distribution type substations, now are typically located in what is called
a Power Distribution Centre (PDC). Inside this building are typically smaller, medium-voltage
(~15kV) circuit breakers feeding the distribution system. Also contained inside these Power
Control Centres are various relays, meters, and other communication equipment allowing
for intelligent control of the substation.
For industrial applications, a transformer and switchgear (Load Breaking Switch Fuse
Unit) line-up may be combined in housing, called a unitized substation or USS.
Switchgear for low voltages may be entirely enclosed within a building. For
transmission levels of voltage (high voltages over 66 kV), often switchgear will be mounted
outdoors and insulated by air, though this requires a large amount of space. Gas- [or oil- or
vacuum-] insulated switchgear used for transmission-level voltages saves space, although it
has a higher equipment cost.
A piece of switchgear may be a simple open air isolator switch or it may be insulated
by some other substance. An effective although more costly form of switchgear is gas
insulated switchgear (GIS), where the conductors and contacts are insulated by pressurized
sulphur hexafluoride gas (SF6). Other common types are oil [or vacuum] insulated
switchgear. A simple fuse used at our home, or a toggle switch is a simple low tension
switch gear.
By interrupting rating (maximum short circuit current that the device can safely
interrupt)
o Circuit breakers can open and close on fault currents
o Load-break/Load-make switches can switch normal system load currents
o Isolators may only be operated while the circuit is dead, or the load current is
very small.
By voltage class:
o Low voltage (less than 1,000 volts AC)
o Medium voltage (1,000–35,000 volts AC)
o High voltage (more than 35,000 volts AC)
By insulating medium:
o Air
o Gas (SF6 or mixtures)
o Oil
o Vacuum
By construction type:
o Indoor (further classified by IP (Ingress Protection) class or NEMA enclosure
type)
o Outdoor
o Industrial
o Utility
o Marine
o Draw-out elements (removable without many tools)
o Fixed elements (bolted fasteners)
o Live-front
o Dead-front
o Open
o Metal-enclosed
o Metal-clad
o Metal enclose & Metal clad
o Arc-resistant
By interrupting device:
o Fuses
o Air Blast Circuit Breaker
o Minimum Oil Circuit Breaker
o Oil Circuit Breaker
o Vacuum Circuit Breaker
o Gas (SF6) Circuit breaker
By operating method:
o Manually-operated
o Motor-operated
o Solenoid/stored energy operated
By type of current:
o Alternating current
o Direct current
By application:
o Transmission system
o Distribution.
ESSENTIAL FEATURES OF SWITCH GEARS
[Photograph of a Substation]
DIFFRENT SWITCH GEARS
Switch gear covers a wide range of equipment concerned with switching and
interrupting currents under both normal and abnormal conditions. It includes switches,
fuses, circuit breakers, relays and other equipments. A brief account of these devices is
given below.
Oil Switch
FUSES: A fuse is a short piece of wire or thin strip which melts when excessive current flows
through it for sufficient time. It is inserted in series with the circuit to be protected. Under
normal operating conditions, the fuse element it at a temperature below its melting point.
Therefore, it carries the normal load current without overheating. However, when a short
circuit or overload occurs, the current through the fuse element increases beyond its rated
capacity. This raises the temperature and the fuse element melts (or blows out),
disconnecting the circuit protected by it.
Under normal operating conditions, the contacts remain closed and the circuit
breaker carries the full-load current continuously. In this condition, the e.m.f. in the
secondary winding of current transformer (C.T.) is insufficient to operate the trip coil of the
breaker but the contacts can be opened (and hence the circuit can be opened) by manual or
remote control. When a fault occurs, the resulting overcurrent in the C.T. primary winding
increases the secondary e.m.f. This energises the trip coil of the breaker and moving
contacts are pulled down, thus opening the contacts and hence the circuit. The arc
produced during the opening operation is quenched by the oil. It is interesting to note that
relay performs the function of detecting a fault whereas the circuit breaker does the actual
circuit interruption.
RELAYS: A relay is a device which detects the fault and supplies information to the breaker
for circuit interruption. It can be divided into three parts viz.
(i) The primary winding of a current transformer (C.T.) which is connected in
series with the circuit to be protected. The primary winding often consists of
the main conductor itself.
(ii) The second circuit is the secondary winding of C.T. connected to the relay
operating coil.
(iii) The third circuit is the tripping circuit which consists of a source of supply,
trip coil of circuit breaker and the relay stationary contacts. Under normal
load conditions, the e.m.f. of the secondary winding of C.T. is small and the
current flowing in the relay operating coil is insufficient to close the relay
contacts. This keeps the trip coil of the circuit breaker unenergised.
Consequently, the contacts of the circuit breaker remain closed and it carries
the normal load current. When a fault occurs, a large current flows through
the primary of C.T. This increases the secondary e.m.f. and hence the current
through the relay operating coil. The relay contacts are closed and the trip
coil of the circuit breaker is energised to open the contacts of the circuit
breaker.
Discrimination: A protection system should disconnect only the faulted part (or the smallest
possible part containing the fault) of the system in order to minimize fault consequences. It
is the quality of the protective system to distinguish between normal and abnormal
conditions and also its location i.e. within protective zone or elsewhere.
Reliability & Stability: A protection system has to care for reliable function of relays in order
to improve reliability. Reliable functionalities are planed and referred to as backup
protection. Moreover, reliability is reached by combining different protection principles, for
example distance and differential protection for transmission lines. Stability of the system is
the quality of the system due to which system remains inoperative & stable under certain
conditions.
Requirement adequateness: There is variety of faults and disturbances that exists in the
power system. It is impossible to provide protection against each and every abnormal
condition due to economical reasons. But in spite of that system must provide adequate
protection.
Simplicity & Economy: As a rule, “protection cost should not be more than 5% of the total
cost.” Protective system should be as simple as possible so that it is easily operative and
maintained.
Zones of protection
Fig: One-line diagram of a portion of an electric power system illustrating primary relaying
Figure illustrates primary relaying. The first observation is that circuit breakers are
located in the connections to each power element. This provision makes it possible to
disconnect only a faulty element. Occasionally, a breaker between two adjacent elements
may be omitted, in which event both elements must be disconnected for a failure in either
one.
The second observation is that, without at this time knowing how it is accomplished,
a separate zone of protection is established around each system element. The significance
of this is that any failure occurring within a given zone will cause the tripping (i.e. opening)
of all circuit breakers within that zone, and only those breakers. It will become evident that,
for failures within the region where two adjacent protective zones overlap, more breakers
will be tripped than the minimum necessary to disconnect the faulty element. But, if there
were no overlap, a failure in a region between zones would not lie in either zone, and
therefore no breakers would be tripped. The overlap is the lesser of the two evils. The
extent of the overlap is relatively small, and the probability of failure in this region is low;
consequently, the tripping of too many breakers will be quite infrequent. Finally, it will be
observed that adjacent protective zones of Fig. overlap around a circuit breaker. This is the
preferred practice because, for failures anywhere except in the overlap region, the
minimum number of circuit breakers needs to be tripped. When it becomes desirable for
economic or space-saving reasons to overlap on one side of a breaker, as is frequently true
in metal-clad switchgear the relaying equipment of the zone that overlaps the breaker must
be arranged to trip not only the breakers within its zone but also one or more breakers of
the adjacent zone, in order to completely disconnect certain faults. This is illustrated in Fig
given below, where it can be seen that, for a short circuit at X, the circuit breakers of zone B,
including breaker C, will be tripped; but, since the short circuit is outside zone A, the
relaying equipment of zone B must also trip certain breakers in zone A if that is necessary to
interrupt the flow of short circuit current from zone A to the fault. This is not a disadvantage
for a fault at X, but the same breakers in zone A will be tripped unnecessarily for other faults
in zone B to the right of breaker C. Whether this unnecessary tripping is objectionable will
depend on the particular application.
Websites:
[1] www.google.com
[2] www.wikipedia.com
[3] www.flickr.com
[4] www.lsis.biz