De rating
UPS Load Backup In DC Voltage Inverter Factor of
UPS Capacity in VA Power Factor Hour of UPS Efficiency Batteries
De rating
factor of
Backup Time Batteries
<0.5 Hour 0.45 AH= UPS CAPACITY IN VA X LO
1 Hour 0.55 DC VOLTGE of UPS X INVE
2 Hours 0.65
3 Hours 0.75
>4 Hours 0.85
AH Availabl
DC voltage
Accenta 1KVA 36 Exide/Amaraon/GY
Accenta 2KVA 96 Exide
Accenta 3KVA 96 Exide
Accenta 6KVA 240 Amaraon/GY
Accenta 10KVA 240 Exide/Amaraon/GY
Renata I 5 KVA 192 Exide/Amaraon/GY
Renata I 10 KVA 384 Exide/Amaraon/GY
Renata I 15 KVA 384 Exide/Amaraon/GY
Renata I 20 KVA 384 Amaraon
Proacta 10 KVA 384 Exide/Amaraon/GY
Proacta 15 KVA 384 Exide
Proacta 20 KVA 384 Exide/Amaraon
Proacta 20 KVA 384 Exide/GY
Renata-300- 3Phase
( 10 KVA -300 KVA 360 Amaraon
Renata-Cyclone- 3Phase
( 10 KVA -200 KVA 720 Exide/GY
Renata-Cyclone T- 3Phase
( 10 KVA -200 KVA 624
71 32
AH Available
SMF TUBULAR
7 40 Exide /southern /GY
15 50 Exide
17 60 Exide /southern /GY
18 66 Exide
26 75 Exide /southern /GY
42 80 Southern
65 100 Exide /southern /GY
75 120 Southern /GY
84 130 Exide /southern /GY
100 150 Exide /southern /GY
120 200 Exide /southern /GY
130
150
160
200
BATTERY AH CALCULATION
Derating
Backup factor of
Time Batteries AH= UPS CAPACITY IN VA X LOAD POWER FACTOR X BACKUP IN HOUR
<0.5 Hour 0.45 DC VOLTGE of UPS X INVERTOR EFFICIENCY X BATTERY DERATING FACOR
1 Hour 0.55
2 Hours 0.65 DC VOLTTAGE = NO OF BATTERIES X 12 V
3 Hours 0.75 INVERTOR EFFICIENCY = 95%
>4 Hours 0.85 LOAD POWER FACTOR = 0.7
1000 X 0.7 x 1
for 1KVA 60 Minits backup 36 x 0.95 x 0.55 Required - 37 AH- 3 No's We Offer 12V/42AH - 3No's
10000 X 0.7 x 1
for 10 KVA 30 Minits backup 240 x 0.95 x 0.55 Required - 56 AH / 20 No's We Offer 12V/65AH - 20 No's
20000 X 0.7 x 1
for 20 KVA 30 Minits backup 240 x 0.95 x 0.55 Required - 112 AH / 20 No's We Offer 12V/65AH/ 2 x 20 No's
BATTERY AH CALCULATION
Derating
Backup factor of
Time Batteries AH= UPS CAPACITY IN VA X LOAD POWER FACTOR X BACKUP IN HOUR
<0.5 Hour 0.45 DC Voltage X INVERTOR EFFICIENCY X BATTERY DERATING FACOR
1 Hour 0.55
2 Hours 0.65 Load Power factor of E&C Accenta UPS = 0.7
3 Hours 0.75 DC Voltage :- 96 VDC ( No of Batteries x 12V )
>4 Hours 0.85 BacK up Required :- 2 Hours
Invertor Efficiency : 93%
Annamalai K.S
Electronics & Controls Power Systems Pvt Ltd,
29-A,2nd Phase,Industrial Area, Peenya,
Bangalore-560058.
Ph -080-; 3242 9511 ;2837 9401; Fax -2839 1587
Mobile – 093412 63968
BATTERY AH CHART
REQUIRED
DESCRIPTION PARAMETER UNIT BACK-UP HR AH
De rating
factor of
Backup Time Batteries
<0.5 Hour 0.45
1 Hour 0.55
2 Hours 0.65
3 Hours 0.75
>4 Hours 0.85
Required Total VAH
88 VAH
113 VAH
185 VAH
317 VAH
484 VAH
564 VAH 960
752 VAH
967 VAH
1195 VAH
1401 VAH
1847 VAH
2257 VAH