Enter Enter Enter Enter Enter

De rating
UPS Load Backup In DC Voltage Inverter Factor of
UPS Capacity in VA Power Factor Hour of UPS Efficiency Batteries

10000 0.8 ###


2 384 0.9 0.65

De rating
factor of
Backup Time Batteries
<0.5 Hour 0.45 AH= UPS CAPACITY IN VA X LO
1 Hour 0.55 DC VOLTGE of UPS X INVE
2 Hours 0.65
3 Hours 0.75
>4 Hours 0.85
AH Availabl
DC voltage
Accenta 1KVA 36 Exide/Amaraon/GY
Accenta 2KVA 96 Exide
Accenta 3KVA 96 Exide
Accenta 6KVA 240 Amaraon/GY
Accenta 10KVA 240 Exide/Amaraon/GY
Renata I 5 KVA 192 Exide/Amaraon/GY
Renata I 10 KVA 384 Exide/Amaraon/GY
Renata I 15 KVA 384 Exide/Amaraon/GY
Renata I 20 KVA 384 Amaraon
Proacta 10 KVA 384 Exide/Amaraon/GY
Proacta 15 KVA 384 Exide
Proacta 20 KVA 384 Exide/Amaraon
Proacta 20 KVA 384 Exide/GY
Renata-300- 3Phase
( 10 KVA -300 KVA 360 Amaraon
Renata-Cyclone- 3Phase
( 10 KVA -200 KVA 720 Exide/GY
Renata-Cyclone T- 3Phase
( 10 KVA -200 KVA 624

LOAD power Factor


Accenta 0.7
Renata i/Proacta 0.8
Renata 300 / Cyclone 0.8
No of 12V
AH Batteries
Required Required

71 32

UPS CAPACITY IN VA X LOAD POWER FACTOR X BACKUP IN HOUR


DC VOLTGE of UPS X INVERTOR EFFICIENCY X BATTERY DERATING FACOR

AH Available
SMF TUBULAR
7 40 Exide /southern /GY
15 50 Exide
17 60 Exide /southern /GY
18 66 Exide
26 75 Exide /southern /GY
42 80 Southern
65 100 Exide /southern /GY
75 120 Southern /GY
84 130 Exide /southern /GY
100 150 Exide /southern /GY
120 200 Exide /southern /GY
130
150

160

200
BATTERY AH CALCULATION

Derating
Backup factor of
Time Batteries AH= UPS CAPACITY IN VA X LOAD POWER FACTOR X BACKUP IN HOUR
<0.5 Hour 0.45 DC VOLTGE of UPS X INVERTOR EFFICIENCY X BATTERY DERATING FACOR
1 Hour 0.55
2 Hours 0.65 DC VOLTTAGE = NO OF BATTERIES X 12 V
3 Hours 0.75 INVERTOR EFFICIENCY = 95%
>4 Hours 0.85 LOAD POWER FACTOR = 0.7

Required AH Nearest AH Available


750 X 0.7 x 1
for 750VA 60 Minits backup 36 x 0.95 x 0.55 Required - 28 AH - 3 No's We Offer 12 V/26 AH- 3 No's

1000 X 0.7 x 1
for 1KVA 60 Minits backup 36 x 0.95 x 0.55 Required - 37 AH- 3 No's We Offer 12V/42AH - 3No's

10000 X 0.7 x 1
for 10 KVA 30 Minits backup 240 x 0.95 x 0.55 Required - 56 AH / 20 No's We Offer 12V/65AH - 20 No's

20000 X 0.7 x 1
for 20 KVA 30 Minits backup 240 x 0.95 x 0.55 Required - 112 AH / 20 No's We Offer 12V/65AH/ 2 x 20 No's
BATTERY AH CALCULATION

Derating
Backup factor of
Time Batteries AH= UPS CAPACITY IN VA X LOAD POWER FACTOR X BACKUP IN HOUR
<0.5 Hour 0.45 DC Voltage X INVERTOR EFFICIENCY X BATTERY DERATING FACOR
1 Hour 0.55
2 Hours 0.65 Load Power factor of E&C Accenta UPS = 0.7
3 Hours 0.75 DC Voltage :- 96 VDC ( No of Batteries x 12V )
>4 Hours 0.85 BacK up Required :- 2 Hours
Invertor Efficiency : 93%

Required AH Nearest AH Available


2000X 0.7 x 2 48 AH
for 2 KVA -2 hours backup 96 x x 0.93 x 0.65 2 x 26 AH ( 52 AH )

We are offering 12V/ 26 AH - 2 x 8 No's SMF Batteries

Annamalai K.S
Electronics & Controls Power Systems Pvt Ltd,
29-A,2nd Phase,Industrial Area, Peenya,
Bangalore-560058.
Ph -080-; 3242 9511 ;2837 9401; Fax -2839 1587
Mobile –  093412 63968
BATTERY AH CHART
REQUIRED
DESCRIPTION PARAMETER UNIT BACK-UP HR AH

UPS CAPACITY 200 VA Enter the UPS capacity 10 minuts 2 AH


POWER FACTOR 0.8 PF Required Change the pf 15 minuts 3 AH
INV EFFICIENCY 90 % Required Change the Efficiency 30 minuts 5 AH

Enter the No-of


NO OF BATTERY 3 Nos Battery You offered 60 minuts 9 AH
BATTERY END VOLTAGE 10.5 VDC 90 mints 13 AH
BATTERY LOW CUTT-OFF 31.5 VDC 2 Hour 16 AH
DISCHARGE POWER 178 VA 3 Hour 21 AH
DISCHARGE CURRENT 6 A 4 Hour 27 AH
5 Hour 33 AH
6 Hour 39 AH
8 Hour 51 AH
10 Hour 63 AH

AH= UPS CAPACITY IN VA X LOAD POWER FACTOR X BACKUP IN HOUR


DC VOLTGE of UPS X INVERTOR EFFICIENCY X BATTERY DERATING FACOR

De rating
factor of
Backup Time Batteries
<0.5 Hour 0.45
1 Hour 0.55
2 Hours 0.65
3 Hours 0.75
>4 Hours 0.85
Required Total VAH

88 VAH
113 VAH
185 VAH

317 VAH
484 VAH
564 VAH 960
752 VAH
967 VAH
1195 VAH
1401 VAH
1847 VAH
2257 VAH

106