Professional Documents
Culture Documents
StatorWindingsusing80pFLine
Couplers
02/01/2013
Hydroprojectownerscanuse80pFlinecouplers,installedinmanyrotatingmachines,tomeasurepartial
dischargeanddetectsignalsfromdeeperinsidethewinding.Thismethodcanprovideamorereliable
assessmentofinsulationconditionthantraditionalmonitoringsystems.
ByStefanKornhuber,MatthiasBoltzeandGregTopjian
Withinthestatorwindingsofrotatingmachines,partialdischarge(PD)signalsthatcomefromdeepinsidethe
machine,awayfrominstalledmeasuringpoints(orcouplers),areattenuatedinamplitudebecauseofthelow
passbehaviorofthesignalpathalongthewinding.1Thus,thecouplersonlypickupthelowerfrequencycontents
ofthesignal.
Manyrotatingmachinescomeequippedwith80pFlinecouplersthatcanbeusedtoperformonlinePD
measurements.2ThesePDdetectorshavea50load,formingahighpassfilterstartingatabout40MHz.PDis
measuredinthefrequencyrangeofseveraltensofMHz.Becauseofthis,theinternaldischargesaremeasured
withpoorsensitivitybythe80pFlinecouplers,andtheresultingPDpatternisdominatedbytheendwinding
discharges.
AmorepromisingmethodologyismeasuringPDinpicocoulomb(pC)accordingtoInternationalElectrotechnical
Commissionstandard60270.3Withthismethodology,readingofPDactivitydependslessonthepulseshape.
Thatprovidesmoresensitivitytointernaldischarges,leadingtoabetterandmorereliableassessmentofthe
entireinsulationstate.4
Bysignalconditioning,itispossibletomaintainthesignallowpassprocessingnecessaryforpCmeasurement.
Additionally,thetestvoltagesignalcanbederivedforsynchronization,enablingphaseresolvedPDpattern
analysis.ThebenefitofthisistoalsoacquireinnerPDandmeasurethisPDagainstachargethatcanbe
calibratedaccordingtoIEC60270,allowingtheplantownertocomparemeasurementswithqualityassurance
checks.
Comparativemeasurementsatageneratorstatorwithlargercouplingcapacitorsillustratethefeasibilityofcharge
measurementsvia80pFlinecouplers.5Thisarticlepresentsfurtherideasforcharacterizingtheintegration
behavioranddiscussescalibrationquestions.
Withrespecttothepermanentlyinstalled80pFlinecouplers,thehighpassfilterbehaviorwouldleadtoa
remarkablelossofsignalarea(charge)whenthePDsignalpassesthatcoupler.Thiscanbefurtherillustratedif
thehighpasstimeconstantof80pFx50=4nsisconsideredinrelationtothepulsePDdurationofabout1
s.Thementionedlinecouplershowsastrongdifferentiatingbehavior.2Thathampersthemeasurementofthe
apparentchargeandreducesthesensitivitytoPDsignalsfromdeepinsidethestatorwinding.
Thebasicideatoovercomethelossofsignalareaistocompensateforthehighpassfilterbehaviorbyan
appropriatelowpassfilteringofhigherorderinthesignalpath.Thissignalprocessingallowsthechargetobe
recoveredandtheintegrationerrorminimized.
Forthatpurpose,Dobledevelopedalinecouplermatchingunitin2010thatincludesalowpassfilterwitha
frequencyof500kHz.Thatmoduleprovidesanelectronicopampcircuitwithlowimpedanceinputthatintegrates
thecapacitivecouplercurrentandgivesoutthecorrespondinglowvoltagesignalofthehighvoltagesignalfor
synchronizingthephaseresolvedPDpattern.Thismatchingunitcaneasilybeconnectedtothelowvoltagepart
ofthe80pFcouplerssimplyusingscrewsandcables.
Figure2showstheresultingphaseresolvedPDpatternsandtheassociatedreadingoftheapparentcharge.The
goodcorrelationoftheobtainedpatternsandthemeasuredapparentchargevaluesisthefirstindicatorofthe
feasibilityofchargemeasurementsusingthe80pFlinecouplers.
Acomparisonoftheindicatedchargevaluesshowsageneraltrendofmeasuredchargedecreasingwithahigher
upperfrequencylimit.Theexceptionisthelastrowofthetable.IndependentofthesettingsofthePDdetector,
theupperfrequencylimitofthetotalsignalchainismaintainedat500kHzprovidedbythelowpass.5
Atthe80pFcouplerwithoutthelowpassfilter,thechargereadingislowerevenintheIECfrequencyrangeof
thedetectorasaresultofthehighpassfilterbehaviorandthelossofsignaltimearea.Theseresultsgiveafirst
impression,ofwhichintegrationerrorscanbeexpectedunderrealconditionswherethemeasuringfrequencies
havetobematchedaccordingtotheactualcircumstancesofthemachine.Notethattheseresultsareonlyan
examplebecausetheyaredependentontheindividualPDsignalshape(seeFigure1onpage39)andmustnot
begeneralized.
TheresultsofthisanalysisshowthatTIisveryshortatthe80pFcoupler,finallyresultinginanintegrationerror
thatisnotnegligible.ThechargereadingatthePDdetectorwoulddeviate,especiallyincaseswheretheactual
PDimpulseshapesaremuchlongerthanthecalibrationpulses.
The80pFcouplerincombinationwithlowpassfilteringshows,again,muchbetterresults.Bythismeans,itcan
bedemonstratedthatitispossibletoperformproperchargemeasurementsevenwithsmallcoupling
capacitance.Theintegrationerrorofthesemeasurementswouldstaywithinreasonablelimits.Integrationtimes
(TI)ofabout1scorrespondtotheapparentchargemeasurementaccordingtoIECstandard60270.
TakingintoaccountthedimensionandpriceofPDcouplingcapacitors,itcanbestatedthatthebenefitislimitedif
thecouplingcapacitanceexceedsthatofthetestobject,intheactualcaseofthelumpedcapacitanceofthe
generatorstatorwinding.Themeasuringsensitivitywouldnotincrease.
Thedeterminedcapacitancevaluesarespecificforthestatorwindingundertestandthemeasuring
configuration.Nevertheless,wecangeneralizeasfollows:100nFascouplingcapacitanceisnotnecessary,and
10nFseemstobeadequatebutisinrealitynottheoptimumcompromiseconsideringthedimensionsandprice.
TheauthorsfindthatPDcouplersaround1to2nFrepresentthemostefficientsolution80pFcouplersarenot
recommendedfornewinstallationbutareoftenpreinstalledonmachines.Tocopewiththe80pFcouplers,the
matchingunitsolutionwascreated.
PD calibration
FormostonlinePDmeasurements,thereistheprinciplechallengethatthetestobjectterminalsarenot
accessibleforcalibrationpurposes.Theinstallationofonlinecalibratorsisnotcommon.
Butfortrendingpurposes,thereistheneedtohavethemeasuringresultscomparableintermsofpC.Finally,it
doesnotmatterfortrendingiftheresultsarethesameascalibratedaccordingtoIECstandard60270,butthe
resultsofrepetitivemeasurementsmustbebasedonthesamescalefactorofthemeasuringPDdetector.Soitis
recommendedtoperformataminimumanindirectcalibrationinparallelwiththeinputofthePDdetector
connectiontothecouplerterminalbox.
Takingthepreviousresultsintoaccount,itisfurtherrecommendednottoinjectchargepulsesdirectlyfromthe
calibrator.TogetascalefactorinthesamerangeroughlyoftheIECcalibration,thepulseshouldbeinjectedvia
acapacitivechargedivider.Thisshouldconsistofaparallelcapacitorof10nFtosimulatethelumped
capacitanceofthestatorwindinganda80pFcapacitortosimulatethecouplercapacitance.
Theproposedcalibrationproceduredoesnotguaranteethemeasurementsareinaccordancetoapparent
chargecalibrationofIECstandard60270,butitfulfillsthemaintaskofPDcalibrationingeneral.Usingthis
recommendedcalibrationprocedure,themeasuringresultswillbereproducibleandcomparable.
Summary
ThedetectionofPDdeeperinsidegeneratorstatorinsulationrequiresthetransitiontochargemeasurements
withrespecttoIEC60270.Thismeansasufficientintegrationbehavioroftheentiremeasuringarrangementmust
beprovided.Onmanygenerators,80pFonlinecouplersarealreadyinstalledwithastronghighpassbehavior
thathampersthechargemeasurement.Anadditionalmodulewithswitchablelowpassofhigherordercanbe
appliedtoovercomethisobstacle.5
ComparativePDmeasurementsatarealtestobjectverifiedthefeasibilityofcomparablechargemeasurements
evenwithacouplerofsmallcapacitance.TIwasintroducedasmeasuretoevaluatetheintegrationabilityofthe
measuringsetup.Thatvaluewasdeterminedfordifferentmeasuringconfigurationswithdifferentcouplersand
processingbandwidths.Theresultsrevealedthattheintegrationtimedecreasesandtheintegrationerror
increasesifthetotalupperfrequencylimitincreasesandthecouplingcapacitancedecreases.
Inprinciple,itispossibletomeasurethePDactivityintermsofpCevenintheMHzregion.Withsome
concessionstotheintegrationerror,themeasuredvaluemightbebelow50%oftheactualone.4Thiserroris
lesscriticalifthecalibrationisperformedthoroughlybeforeeachmeasurement.Acalibrationadaptorisproposed
foranindirectcalibrationforgettingscalefactorssimilartothatoftheIECcalibration.
Amethodwasappliedtodeterminetheequivalentlumpedcapacitanceofageneratorwinding.Basingonthe
generalizedresults,recommendationsweregivenfortheselectionofcapacitancevaluesofgeneratoronlinePD
couplers.
Notes
1.Train,D.,"TheMeasurementofPartialDischargePhenomenainStatorWindings,"DobleClient
CommitteeFallMeetings,DobleEngineering,Watertown,Mass.,USA,1994.
2.Zhu,H.,V.Green,M.Sasic,andS.Halliburton,"IncreasedSensitivityofCapacitiveCouplersforIn
ServicePDMeasurementinRotatingMachines,"IEEETransactionsonEnergyConversion,Vol.14,No.4,
1999,pages11841192.
3."HighVoltageTestTechniquesPartialDischargeMeasurements,"InternationalElectrotechnical
CommissionInternationalStandard60270,ThirdEdition2000.
4.Wilson,A.,"PartialDischargeMeasurementsonRotatingMachinery:ApparentChargeTechniques,"
DobleClientCommitteeFallMeetings,DobleEngineering,Watertown,Mass.,USA,1994.
5."LineCouplerMatchingUnit,"UserManualVersion00,DobleLemkeGmbHGermany,2011.
StefanKornhuberisengineeringmanagerandMatthiasBoltzeisservicemanagerwithDobleLemkeGmbHin
Germany.GregTopjianissolutionsmanagerpartialdischargewithDobleUS.
Copy right 20072015. P ennWell Corporat ion, Tuls a, OK . A ll Right s Res erv ed. P RI VA CY P OLI CY | TE RMS
A ND CONDI TI ONS