You are on page 1of 15

Jar Workshop and Manufacturing Building

Phase-1

MANUFACTURING BUILDING
ELECTRICAL NOTES
1

Contractor must check the quantities according to the drawings before Bidding and shall be
responsible for his price without additional cost.

Supply, Installation, Testing & commissioning of all electrical works As per drawing, schedules
and specification are included.

Wiring, Sleeves, Manholes, Cables tray, Duct banks, Conduits, Boxes, Main Junction Boxes,
Hangers/Supports, Fitting For a complete system are included

Exposed run conduit will be EMT (Electrical metallic tube) complete with all accessories screw
type, flexible liquid tight metal if required and Concealed conduit in wall or incased on
concrete will be PVC NEMA TC 2 Or TC 8, EPT-A , SAPPCO or approved equal.

Exposed conduit inside Electric & Mechanical rooms shall be galvanized Rigid steel conduit.

Building wire THWN / Riyadh, Jeddah wire or Middle East Co.

Panel board GE, Electra type or Mitsubishi. Made in Japan.

Any civil work such as excavation, drilling, back-filling, red tiles, fine sand, Concrete, duct
banks, manhole or hand hole are included, shall be done by Electromechanical contractor.

Disconnect switches will be Esq. Type or G.E. or approved equal.

10

Cables tray and ladder 1.5mm thickness mill galvanized steel with cover.

11

Wiring devices shall be Legrand Pass & Seymour type, U.S.A made or approved equal.

12

Fire alarm system will be conventional pyrotronics type or simplex or notifier.type OR as existing

13

Telephone cables & devices shall be orthotics products or approved equal.

14

Small hand hole 50 x 50 x 80cm are included for the outdoor lighting And site works.

15

Outdoor lighting cable shall be type XLPE ins., P.V.C sheathed single or Multi core

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

16

Feeder cable type shall be Riyadh,Jeddah cable XLPE / PVC 1 KV/0.6 KV or approved equal.

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

S.No

Description Of Work

Unit

Quantity

Price

Amount

MANUFACTURING BUILDING
III ELECTRICAL WORK
1

Electrical Installations
Include for the complete installation as described
in the specification and as shown on drawing to
give acomplete system that is acceptable to the
engineer and local authorities the quantities
mentioned in the boq are indicative for the works
involved
The tendered shall allow for all items required to
complete the work to the satisfaction of the
engineer and local authorities liaise with saudi
electrical company (sec) for supplying inculding
connecting to existing electric grid,cables,duct
banks,manholes,sleeves,cables,all civil
work,excavations,drilling,back filling,finishing,
and installation of
mv 13.8/0.4 kv,transformer,rmu,and include for
connection of sec supplied cables to meter cabinet
including termination

1.1

Transformer 13.8/0.4 kv ,1000 kva


Inculding allcables connecting to existing electric
grid,and all civil work.

Lot

1.2

Electrical power duct bank inculding all civil


work as per drawing and specifications for :-

Lot

1.3

Eectrical power manholes inculding all civil work


as per drawing and specifications

Lot

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

S.No

Description Of Work

Unit

Quantity

Price

Amount

Page Total Amount


2

LIGHTING FIXTURES AND SWITCHES


Supply,install, connect and test the following
lighting fixtures
, all according to drawing and specification the
item including conducting,wiring,cables,emt
pipes,lighting fixtures, wirring,cables, inculding
any civil work and all fixing accessories that
neededto provide perfect operation condition.

2.1

FENCE LIGHTING 2x26 WATT HIGH


COMPACT F. LAMP.IP65.

EA

132

2.2

STREET LIGHTING POLE WITH 250 WATT


LAMP 6-8 METER HIGH.IP65.

EA

18

2.3

WALL MOUNTED FLOOD LIGHTING 250w


HIGH PRESSURE SODIUM
WEATHERPROOF,IP65.

EA

21

2.4

FLOURESCENT RECESSED LIGHT WITH


PRISMATIC DIFFUSER 4x20w IP20

EA

100

2.5

RECESSED DOWN LIGHTER, 60w 220 VOLT


WATERPROOF

EA

29

2.6

HIGH BAY SURFACE MOUNTED LIGHTING


FIXTURE WITH CHAIN INDUSTRIAL TYPE
400w 220 VOLT

EA

100

2.7

EMERGENCY LIGHTING 2X50 WATTS WITH


BACKUP BATTERY 3.0 HR.

EA

15

2.8

EXIT LIGHTING WITH SELF CONTAINED


EMERGENCY SUPPLY, 1x20W, 3HR

EA

10

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

S.No

Description Of Work

Unit

Quantity

Price

Amount

Page Total Amount


3

POWER OUTLETS& SWITCHES


Rate and price shall be supply and install the
following power outlets&switches including
wiring, cables,pipes emt,outlets,conduits, boxes,
pvc or steel, junction boxes, connectors,cables
tray, any civil work ,hanger/supports, all
fittings,end bell, testing , commissioning, and
everything required for a complete system
according to drawings and specifications.

3.1

DUPLEX OUTLET 220 VOLT, 20A

EA

71

3.2

HAND DRAYER OUTLET 20A

EA

3.3

DISCONNECT SWITCH (1 PH)

EA

36

3.4

DISCONNECT SWITCH (3 PH)

EA

3.5

FAN

EA

3.6

MOTOR GATE POWER OUTLET

EA

3.7

Combination Socket 60a ,Ip55, Inculding


Wiring,Cables ,Cables Tray,Emt Pipes As Per
Drawing And Specification

EA

51

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

S.No

3.8

Description Of Work

Unit

Quantity

Lot

CIRCUIT BREAKERS
Main c. Br. ( 1250 ) amp inside nema 1r
enclosure.ip65.weatherproof.

EA

MDB
Main breaker 1250 amp / 1600 af , 3ph , 4 wire,
60 hz, flush or surface mounted,
Branches :-

EA

Electrical cables tray , as per drawing and


specification, and everything required for a
complete system according to drawings and
specifications.

Price

Amount

Page Total Amount


4

DISTRIBUTION PANELS:
Rate and price shall be supply and install the
following panel boards including screw, washers,
nuts, clamps,boxes,connectors,
hanger/supports,duct banks,manholes,sleeves,emt
pipes,cables tray,all civil work, all fittings,end
bell, all civil work such as excavation, drilling,
back filling, concrete and any accessories,
testing,commissioning,and everything required fo
a complete system according to drawings and
specifications.

4.1

4.2

250/ 250AMP
300/ 400AMP
300/ 300AMP
160/ 160AMP
40/ 63 AMP
63/ 100 AMP
200/ 250AMP

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

3P
3P
3P
3P
3P
3P
3P

2 NOS
2 NOS
1 NOS
1 NOS
1 NOS
1 NOS
4 NOS

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

S.No

Description Of Work

Unit

Quantity

EA

EA

EA

EA

EA

Price

Amount

Page Total Amount


4.3

PB-PS1
Main breaker 300 amp / 400 af , 3ph , 4 wire, 60
hz, flush or surface mounted,
Branches :60 AMP 3 P 30 NOS
32AMP 1 P 9 NOS
32AMP 3 P 1 NOS

4.4

PB-PS2
Main breaker 300 amp / 400 af , 3ph , 4 wire, 60
hz, flush or surface mounted,
Branches :60 AMP 3 P 34 NOS
32AMP 1 P 8 NOS

4.5

PB-S
Main breaker 63 amp / 100 af , 3ph , 4 wire, 60
hz, flush or surface mounted,
Branches :32 AMP 1 P 24 NOS

4.6

PB-O
Main breaker 160 amp / 160 af , 3ph , 4 wire, 60
hz, flush or surface mounted,
Branches :20AMP 1 P 29 NOS
50 AMP 3 P 2 NOS
32 AMP 1 P 6 NOS

4.7

PB-L
Main breaker 250 amp / 250 af , 3ph , 4 wire, 60
hz, flush or surface mounted,
Branches :32 AMP 1 P 52 NOS

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

S.No

Description Of Work

Unit

Quantity

4.8

PB-G
Main breaker 40 amp / 63 af , 3ph , 4 wire, 60 hz,
flush or surface mounted,
Branches :-

EA

Price

Amount

20 AMP 1 P 8 NOS
32 AMP 1 P 4 NOS

Page Total Amount


5

CABLES & ACCESSORIES


Rate and price shall be supply and install the
following cables including duct banks, lugs ,
galands ,conduits, boxes, pvc or steel, junction
boxes, connectors, all fittings,end bell, testing ,
commissioning, , all civil work such as
excavation, drilling, back filling, concrete and any
civil work, and everything required for a
complete system according to drawings and
specifications.
NOTES:
The contractor must check the length in the site
before supply.

5.1

7x1/C x 630mm +120mm Cu. CABLE CU


X.L.P.E./PVC

L.M

55

5.2

4x185mm2 + 1x70mm2 CU X.L.P.E./PVC

L.M

120

5.3

4x120mm2 + 1x70mm2 CU X.L.P.E./PVC

L.M

130

5.4

4x70mm2 + 1x35mm2 CU X.L.P.E./PVC

L.M

45

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

10

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

S.No

Description Of Work

Unit

Quantity

5.5

4x35mm2 + 1x16mm2 CU X.L.P.E./PVC

L.M

30

5.6

4x16mm2 + 1x6mm2 CU X.L.P.E./PVC

L.M

30

Price

Amount

Page Total Amount


6

FIRE ALARM SYSTEM


Complete System As Per Drawing And to be
matching and to be connected with Existing Fire
Alarm System In The Site, , Riser Diagram,
Inculding All Civil Work, And Specifications By
Using

6.1

Fire alarm control panel as existing ,and


connecting existing facp. With battery back-up
and battery charger

EA

6.2

Smoke detector.

EA

91

6.3

Manual break glass station.

EA

6.4

Alarm bell. 6.

EA

6.5

Weather proof alarm bell with flashing light.ip65.

EA

6.6

Heat detector.

EA

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

11

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

S.No

Description Of Work

Unit

Quantity

Price

Amount

Page Total Amount


7

TELEPHONE SYSTEM

7.1

Complete system according to weatherford


requirements, all civil work, be connected to the
existing pabx. As per drawing and specification.

Lot

7.2

TELEPHONE OUTLET RJ.-11

EA

24

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

12

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

S.No

Description Of Work

Unit

Quantity

Price

Amount

Page Total Amount


8

PUBLIC ADDRESS SYSTEM

8.1

Complete system according to weatherford


requirements, all civil work, as per drawing and
specification.

Lot

8.2

SPEAKER RECESSED TYPE 5 WATT WITH


MATCHING TRANSFORMER

EA

24

8.3

HORN SPEAKER

EA

17

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

13

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

S.No

Description Of Work

Unit

Quantity

Price

Amount

Page Total Amount


9

DATA SYSTEM

9.1

Complete system according to Rushaid


Weatherford requirements, all civil work, be
connected to the existing data panel. As per
drawing and specification.

Lot

9.2

DATA OUTLET RJ.-45

EA

23

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

14

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

Jar Workshop and Manufacturing Building


Phase-1

S.No

Unit

Quantity

Lot

11.1 Supply, install, testing, commissioning and put


into operation CCTV system complete with
CCTV Workstation, Termination and all
necessary accessories to finish works as per
drawings, specification and standard

Lot

11.2 Fixed outdoor type Camera (Weather Proof) using


75ohm coaxial cable inside 20mm heavy
gaugeRC Conduit.

EA

45

10

Description Of Work

Amount

GROUNDING SYSTEM

10.1 Supply and installation of a grounding system .


Including necessary earthwork, buried galvanized
steel foundations strips surrounding the building
to suit grounding resistivity required all counter
poise and all associated works as shown on
drawings and specification.

11

Price

CLOSED CIRCUIT TELEVISION SYSTEM


(CCTV)

Page Total Amount

Total Price For Electrical Work

Weatherford Al-Rushaid.
Al-Khobar,
K.S.A.

15

IMPACT, Consulting Engineers.


Al-Khobar,
K.S.A.

You might also like