Important Note:
All Nexans installations shall be completed in accordance with (IAW) the relevant
standards. Different countries have different applicable standards. Some regions
use a hybrid of them so depending on your location the relevant standards shall
be followed. It is important to always check for the latest versions of standards as
they are constantly being updated.
For more information about installation procedures please contact Technical
Support Department of Nexans Cabling Solutions.
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
Installation may require special tools like saw, cutting machine, screw driver etc.
Make sure safety protection method is provided.
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
EN 50174-2
EN 50600-2-4
ANSI/TIA-569-B-2008
Where there is a requirement to keep other cable types away from data cables
the separation must be such that it cannot be inadvertently changed. For
example both the data cables should be held together with velcro and power
should be tie wrapped in place to maintain the separation distances required.
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
Before installation:
Where the pathway system provides continuous support, the cables must
not be stacked more than 150mm.This is to prevent crush damage to the cables
at the bottom. EN50174-2 4.4 refers.
Use the Nexans installation software toolkit to calculate the size of containment
you need, this is available at http://www.nexans.co.uk/eservice/UKen_GB/navigateproduct_540160551/LAN_Calculation_Toolkit.html
120 System
240 System
120x100mm
>500 3mm Fiber patch cords
>400 3.7mm MPO trunk cables or MPO patch cords
240x100mm
>1000 3mm Fiber patch cords
>800 3.7mm MPO trunk cables or MPO patch cords
Make sure the pathway systems have smooth surfaces and also be free of burrs,
sharp edges or projections that can damage cable insulation and be free of
pressure points that may degrade the transmission performance of the installed
system.
Pathways made from tray-work shall be positioned to provide a minimum
clearance of 25 mm from the fixing surface and to provide as much working
space as possible above the tray (minimum 150mm) to enable access during
installation and accommodate the maximum stacking height of cables.
SLAB
150mm
Min
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
Pathways
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
Attached to Cable Ladder or upper ceiling or Auxiliary Framing Bar is the most
common way for mounting:
Trapeze support:
The trapeze supporting bracket is used to attach 120/240 channel to ceiling
from above. It is a straight bracket with 2 x M 20 threaded rod and fasteners to
enable fitting of the main channel mounting bracket from overhead ceiling in
your data centers.
High strength Expansion
screws
Max Loading: 1000kg
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
A wide range of mounting hardware is provided to ensure the fiber guider could
be mounted under any circumstance in data centers and IT rooms.
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
Cabinet/Rack support :
Use Cabinet/Rack support kit to attach Channel on your standard Cabinet.
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
120mm
Equal Tee
120mm
Equal Cross
120mm
Elbow
120mm
Vertical Tee
120mm
45Internal/External Bends
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
120 series:
10
240mm
Equal Tee
240mm
Equal Cross
240mm
Elbow
240mm
45Internal/External Bends
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
240 series:
11
240mm to120mm
Reducer
240mm to120mm
Unequal Cross
240mm to 120mm
Unequal Tee
Nexans Fibre Trunking System Important remark: Installation is to be performed by qualified service personnel
12