You are on page 1of 2

Date :

26 April, 2016

Reference:

DC Inmedio

Issued by :

Dumitriu Mircea

S2GDA + 1 x HCR51
Unit inlet air temperature
Unit inlet air relative humidity
Unit airflow
ESP

24.0
50.0
5330
0

C
%
m/h
Pa

Sea level
Refrigerant
Unit power supply

0 m
R410A
400 V/3 ph/50 Hz

Unit performances
Unit
S2GDA + 1 x HCR51
Total cooling capacity
22.8
Sensible cooling capacity
21.0
SHR
0.92
Off coil air temperature
12.3
Off coil air relative humidity
99.2
Room SPL (@ 2m, f.f)
61.2
Condensing temperature
54.0

kW
kW
C
%
dB(A)
C

Unit power input


Unit EER
System power input
System EER
Internal filter class (EN779 std)
Width
Depth
Height
Weight

8.12
2.81
9.22
2.47
G4
750
750
1950
270

kW
kW

mm
mm
mm
kg

Fans
Quantity
Type
Power supply
Power input

1 n
Normal
400 V/3 ph/50 Hz
1 x 1.34 kW

Operating Ampere
Full load Ampere
Locked rotor Amp.
Room fan modulation (%)

1 x 2.15 A
1 x 4.00 A
1 x 0.10 A
8.5

Compressors
Quantity
Power supply
Power input

1 n
400 V/3 ph/50 Hz
1 x 6.78 kW

Compressors COP
Operating Ampere
Full load Ampere
Locked rotor Amp.

3.36
1 x 12.34 A
1 x 16.20 A
1 x 101.00 A

Relevant data for each CONDENSER


Condenser model
HCR51
Version
Standard
Air discharge
Vertical
Power supply
230 V/1 ph/50 Hz
Variex
Yes
Heat load
29.6
Outdoor air temperature
45.0
Condenser airflow (@ max speed)
17000
Condenser actual airflow
17000
Condenser ESP (@ max speed)
0

kW
C
m/h
m/h
Pa

Max outdoor SPL (@ 5m,f.f.)


Actual outdoor SPL (@ 5m,f.f.)
Power input
Full load Ampere
Locked rotor Amp.
Width
Depth
Height
Weight

53.0
53.0
1.10
5.00
9.60
1112
2340
907
93

dB(A)
dB(A)
kW
A
A
mm
mm
mm
kg

Cooling capacities are gross. To obtain the net cooling capacities the fan heat load must be subtracted

Declared performances for only cooling units according to EN 14511:2011. Products in accordance with the following Direc
2006/42/EC; 2004/108/EC;2006/95/EC; 97/23/EC
Rel. 9.1

Page: 1 / 1

Date :

26 April, 2016

Reference:

DC Inmedio

Issued by :

Dumitriu Mircea

S2GDA + 1 x HCR51
OPTIONS
Electrical heating
Max heating capacity
FLA
Inlet air temperature
Inlet air relative humidity

5.85
8.4
12.3
99.2

kW
A
C
%

Outlet air temperature


Outlet air relative humidity

15.5 C
81.0 %

Humidifiers
Quantity
1 n
Max capacity steam
1x4.5 Kg/h
Min capacity steam
1x2.7 Kg/h
Type of Humidifier
electrodes immersed

Rel. 9.1

Power supply
Nominal power input
Max absorbition current

400/3/50
1x3 kW
1x4.6 A