You are on page 1of 1

KEY PLAN

INSTALLATION DETAILES FOR


SALAMANDER

ANSUL R-102 SINGLE TANK SYSTEM PIPING INFORMATION (3 GALLON)


DATA

SECTIONS

SALAMANDER

1F
1F

6 IN.
(15cm)

8 IN.
18 IN.
12 IN. (20cm) Min .
(45cm)
4 IN.(10cm)
Max. (30cm)
Min.
12 IN.(30cm) Max.

1F

SALAMANDER

THE NOZZLE(1F) MUST BE


ORIENTATED SO THE NOZZLE TIP
FLATS ARE PARALLEL WITH THE
GRATE LEFT TO RIGHT CENTERLINE (

SPECIAL NOTE- ALL LOW


PROXIMITY NOZZLES SHALL BE
WITH METAL BLOW OFF CAPS.

PIPE SIZE

19cm

1N

71x46cm

SALAMANDER

79x44cm

2W

50x35cm

51x35cm

1F

1N

69x57cm

PIPE DROP TO
GRIDDLE(2120)

MAX. ALLOWED
PER LINE

3/8 in.

12.2 m.

11

DUCT BRANCH LINE

3/8 in.

2.4 m.

PLENUM BRANCH
LINE

3/8 in.

1.2 m.

APPLIANCE BRANCH
LINE

3/8 in.

3.7 m.

CONDUIT FOR
MANUAL PULL
STATION

1/2 in.

46 m.

20

CONDUIT FOR
DETECTION LINE

1/2 in.

45.7 m.

16

2x3 GALLON ANSUL


AGENT TANK

PIPE SIZE

MAX.
ALLOWED
LENGTH PER
LINE

TEES

FLOW

MAX.
ALLOWED PER
LINE

MAX. ALLOWED
PER LINE

MAX. ALLOWED
PER LINE

SUPPLY LINE

3/8 in.

9.7 m.

22

DUCT BRANCH LINE

3/8 in.

2.4 m.

PLENUM BRANCH
LINE

3/8 in.

1.2 m.

APPLIANCE BRANCH
LINE

3/8 in.

3.7 m.

CONDUIT FOR
MANUAL PULL
STATION

1/2 in.

46 m.

20

CONDUIT FOR
DETECTION LINE

1/2 in.

45.7 m.

16

2W
c,

BAKERY
COOLER

CLIENT

EXHAUST SPIGOT NOZZLE


PLENUM NOZZLE

REPRESENTATIVE:

RESIDENT ENGINEER:

DETECTOR/FUSIBLE LINK

STEEL WIRE/CONDUIT LINE

SUBMITTAL No:

ITEM:

TRANSMITTAL REF:

DATE:

RESIDENT ENGINEER

DECISION:

NOTES:1. SCHEDULE 40 3/8" SIZE BLACK STEEL PIPES AND FITTINGS


FOR AGENT DISCHARGE PIPE WORK. INSTALLATION TO BE
STRICTLY IN ACCORDANCE WITH ANSUL DESIGN /INSTALLATION
MANUAL (WHICH IS FULLY IN COMPLIANCE WITH NFPA 17A & AS
PER UL 300 STANDARDS).

This check is for general conformance with the design


concept and it does not relieve the Contractor of its
obligation under the contract.

DATE

R.E. SIGNATURE

3. GAS/ELECT. SUPPLY TO ALL GAS/ELECT. OPERATED APPLIANCE


TO SHUT OFF IN THE EVENT OF ANSUL ACTIVATION BY OTHERS.
4. ANSUL SYSTEM WILL BE PROVIDED WITH 02 SETS OF NO / NC
CHANGEOVER SNAP SWITCHES TO ACHIEVE POINT 3.
ALL OTHER RELATED WORKS EXCLUDED.
5. DETECTION LINE INSTALLATION WILL BE FUSIBLE LINK,
AUTOMATIC/MECHANICAL WITH SS ROPE INSIDE 20MM STD EMT
CONDUIT AND ANSUL STD PULLY ELBOWS.

DESIGN FLOW CALCULATION


AREA: COOKING
HOOD SIZE:272(4.00x1.20)M
NOZZLE
SL.NO DESCRIPTION
QTY TYPE
TOTAL FLOW
QTY
HEIGHT
04
01
02 2W
01
DUCT
02
PLENUM
01 1N
02
02
FRYER
03
01 230
02 69-119cm
04
04
01 2120 01 25-51cm
02
GRIDDLE
05
01 1N
01 46-102cm
01
CHAR BROILER
06
01 1N
01 89-102cm
01
SOLID TOP
07
01 1F
01 30-45cm
01
SALAMANDER

a,
b,

PREP

APPLIANCE NOZZLE

2. ALL EXPOSED PIPEWORK SHALL BE CHROME SLEEVED.

SEQUENCE OF OPERATION:

1N

ANSUL EMERGENCY PULL

AGENT DISCHARGE LINE

SYSTEM CAPACITY: 2x3 GALLON


MAX FLOW : 22

1N

HOOD REF & DIMENSIONS:


272(4.00 x 1.20)M

DUMB
WAITER

COMBI
OVEN

70cm

2x230

SOLID
TOP

MAX. ALLOWED
PER LINE

ANSUL RESET
RELAY
CHAR
BROILER

MAX.
ALLOWED PER
LINE

DATA

SERVICE BAR

GRIDDLE

FLOW

ANSUL R-102 MANIFOLD TANK SYSTEM PIPING INFORMATION (6 GALLON)

ANSUL EMERGENCY PULL


FOR HOOD REF:272

FRYER

TEES

SUPPLY LINE

SECTIONS

COOKING

MAX.
ALLOWED
LENGTH PER
LINE

ANSUL AGENT TANK

FIRE STARTS IN THE PROTECTED AREA.


HEAT SENSITIVE FUSIBLE LINKS ACTIVATE THE SYSTEM OR
SOMEBODY OPERATE THE SYSTEM USING SYSTEM "MANUAL
EMERGENCY PULL".
SYSTEM MECHANISM (AUTOMAN) ACTIVATES AND APPLIANCE
ENERGY SOURCES (GAS AND /OR ELECTRIC) ARE AUTOMATICALLY
SHUT OFF BY ACCESSORY EQUIPMENT APPROPRIATE FOR THE
TYPE OF FUEL USED BY THE COOKING EQUIPMENT.

d, SYSTEM TO BE MONITORED BY BUILDING FA SYSTEM AND THUS


FIRE ALARM INITIATED.
e, EXHAUST FANS IN THE VENTILATING SYSTEM SHOULD BE LEFT ON.
SUPPLY AIR TO SHUT OFF. THE SYSTEM IS UL LISTED WITH OR
WITHOUT EXHAUST FAN OPERATION.
f, THE FIRE EXTINGUISHING AGENT IS DISCHARGED INTO THE
PLENUM,EXTRACT DUCT AND ON TO THE COOKING APPLIANCE.
g, THE AGENT AND THE HOT GREASE MIX TO FORM A FOAM. THIS
TEMPORARILY SEALS COMBUSTIBLE VAPOURS, HELPING TO
INHIBIT RE-IGNITION. THIS SEAL MUST NOT BE DISTURBED.

15

REV

DATE

DESC.

BY

AAP

Certified for coordination and compliance with the


Contract documents.

DATE

SUBCONTRACTOR

SIG.

UPPER CREST TOWER

FIRST ISSUE

26.04.15

REV

REVISION

DATE

UPPER CREST TOWER BURJ KHALIFA


DISTRICT, PLOT NO 345-392 @ DUBAI

T +971 (4) 297 1755


F +971 (4) 297 1799
@ info@pse.ae
www.pse.com

P.O. Box: 96196


Dubai, UAE

AL BARQ KITCHEN EQUIPMENTS

ANSUL R-102 SYSTEM (G.A)


(GF+5 PODIUM+H.C+37 FLOORS),
COOKING AREA, WALL TYPE
HOOD REF:272(4.00X1.20)M

Sayooj
Premalal

HAVEN FIRE & SAFETY

26.04.15
L.L.C

Fire Protection & Safety Engineers

SHEET NO:
1/3

STATUS

DRAWN BY:
DP

CHECKED BY:
JVP

DRAWING NO.

DATE
27-04-2015

SCALE

DWG NO: Q-29166/HFS/001(SHT.01-01)

REV: 0

PROJECT NO.
D113

ALB-SD-D007-5F-AS-01

REVISION
0