1.

IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS,


ELEVATIONS, AND LOCATIONS SHOWN ON DRAWING(S). ANY DISCREPANCIES SHALL
BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE BASF CONSTRUCTION SUPERVISOR, CONSTRUCTION MGR. OR ENGINEER BEFORE PROCEEDING WITH WORK
2. BENCHMARK ELEVATION DATUM CAN BE OBTAINED USING BASF SITE SURVEY MONUMENTS LOCATED THROUGH OUT THE SITE. NORTH WORKS USES IGLD 1955 DATUM
3. IT IS THE CONTRACTORS RESPONSIBILITY TO INSURE THAT ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE BASF TECHNICAL STANDARDS LISTED ON THIS
DRAWING
4. ALL NEW STEEL, BOLTS, ANCHOR BOLTS, & HARDWARE TO BE HOT-DIPPED GALVANIZED.
UTILITY
POLE(S)

10

TYP.
14'-3"

BASF STRUCTURAL STEEL SPECIFICATIONS


2'-0"

10

2. N-S-CL-502 - ALLOWABLE COMPRESSIVE LOADS, WT BRACING


3. N-S-CL-508 - COLUMN BASE PLATE DETAILS
4. N-S-CL-514 - FRAMED BEAM CONNECTIONS
5. N-S-CL-516 - BEAM TO COLUMN MOMENT CONNECTIONS
6. N-S-CL-519 - BRACING CONNECTION DETAILS

36" DIA.

20

A
EXISTING

1
X2
W8

CONCRETE NOTES:
30

STEEL
STRUCTURE

W6X16
POSTS

1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND ELEVATIONS PRIOR TO

7'
0"

(TYP)

STARTING ANY WORK AND SHALL RESOLVE ANY DISCREPANCIES TO THE

C6X8.
2

GUY WIRE(S)
C6X8.
2

C6X8.
2

C6X8.
2

SATISFACTION OF THE OWNER'S CONSTRUCTION ENGINEER.


2. CONCRETE SHALL ATTAIN A MINIMUM COMPRESSIVE STRENGTH

& ANCHOR
POINTS (TYP)

OF 4000 PSI AND SHALL BE MANUFACTURED AND PLACED


PER BASF TECH STD N-S-CL-412M AND THE LATEST ACI 318 BUILDING

60

CODE REQUIREMENTS FOR REINFORCED CONCRETE.

40

NEW CONC.
FOUNDATION(S)

SCALE 1"= 20'


0"

4'
0"

1. N-S-CL-500M - SPECIFICATIONS FOR STRUCTURAL STEEL

CONDUIT
(TYP)

50

2'-0"

3. ALL REINFORCING SHALL CONFORM TO ASTM A615, GRADE 60.

70

4. CRUSHED LIMESTONE SHALL CONFORM TO 21-AA GRADATION SPECIFICATION


BY MICHIGAN DEPARTMENT OF TRANSPORTATION AND SHALL BE COMPACTED
TO 95% MAXIUM DENSITY OF MOSTURE CONTENT TO MODIFIED
4'-9"

4'-9"

TH. SHT.
(TYP.)

4'-9"

PROCTOR METHOD D-15557.

80

SEE
DET. 2 & 3

5. CAST-IN-PLACE CONCRETE SHALL CONFIRM TO THE LATEST ACI

90

STANDARD 318 AND 301 SPECIFICATIONS FOR STRUCTURAL CONCRETE.


6. ALL CONCRETE SHALL BE CONSOLIDATED BY VIBRATION.
7. CONTRACTOR SHALL FURNISH ALL DEWATERING EQUIPMENT TO MAINTAIN

PARTIAL PLAN VIEW

8. DURING CONSTRUCTION IF ANY UNDERGROUND STRUCTURES ARE ENCOUNTERED,

1"

A-325 A.B.
(8 EA REQ'D)

T.O.S. 594.4'
CONT. FIELD VERIFY
STEEL WILL BE 1/2" MAX
DISTANCE FROM LOWEST
POINT OF BOTH CONDUITS
SHIM THE GAP FOR
FINAL SUPPORT AND
NOT INTERFERE WITH

10. CHAMFER ALL EXPOSED EDGES 3/4 INCH UNLESS OTHERWISE NOTED.
11. UNLESS OTHERWISE NOTED, MINIMUM LAP SPLICE LENGTHS TO BE AS FOLLOWS:
(A) VERTICAL BARS IN FOUNDATION WALLS (INCLUDING DOWELS) - 40 DIAMETERS
(B)

12. ALL GROUT UNDER BEAM/JOIST BEARING PLATES TO BE NON-SHRINK, NON-METALLIC TYPE.
13. NOTIFY OWNER TO ENGAGE A QUALIFIED GEOTECHNICAL ENGINEER TO INSPECT ALL
FOOTING EXCAVATIONS TO ASCERTAIN THE SUITABILITY OF THE FOUNDATION SOIL
14. UNLESS OTHERWISE NOTED, REINFORCING BARS TO HAVE MINIMUM
CONCRETE COVER AS FOLLOWS:

W 6X16

W 6X16

(TYP.)

11'
1 9/
16 "

HORIZONTAL BARS IN GRADE BEAMS, WALLS, AND SLABS - 48 DIAMETERS

FOUND.

DETAIL

(A)

CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH:

(B)

CONCRETE EXPOSED TO EARTH OR WEATHER:

SCALE : NONE

# 5 BARS AND SMALLER

1 1/2 INCHES

OTHERS
(C)
TOP FND. EL.
583.19'

1"

BASEPLATE
DET. 1
TH. SHT.
(TYP.)

ENSURE BEAM
DOES NOT
INTERFERE
W/ GUY WIRE
(CONT. FIELD
VERIFY)

F.F. EL.
583.0'

CONCRETE NOT EXPOSED TO EARTH OR WEATHER:


3/4 INCHES

GRADE BEAM TIES & STIRUPS

1 1/2 INCHES

BASF TECHNICAL STANDARDS:


N-S-CL-412M SPECIFICATION FOR CONCRETE CONSTRUCTION
N-S-CL-400 SITE CLEARANCE AND GENERAL EARTHWORK
N-S-CL-402 EXCAVATION AND BACKFILL FOR CONCRETE WORK,ETC
N-S-CL-411 DESIGN AID-CONCRETE REBAR DEV,ETC

3'-0" w/

N-S-CL-413 NON SHRINK GROUT


10

(4) #4 BARS VERT.


#4 @12" HORIZ.
(TYP. 2 PLCS)

DEWATERING NOTES

C6X8.2

UTI
LI
TY POLE

6"

6"

3'
6"
MI
N.(
TYP)

GRADE

6" COMPACTED
21AA STONE
(TYP)

SECTION

2 INCHES

SLABS
CLAMP CONDUIT
W/ U-BOLT - SHIM
AS NECESSARY

MARK THE AREA, AND SUBMIT EXCAVATION REQUEST TO SITE SERVICES MANAGER
FOR APPROVAL. ALLOW 14 DAYS FROM GENERATION OF REQUEST TO APPROVAL.

BLDG. 61T
NORTH MAIN SUBSTATION

2. DEWATERING MAY BE NECESSARY. CHECK WITH BASF CONSTRUCTION DEPT. AS TO WHERE


ON SITE TO DEWATER. NEVER ALLOW DISPLACED WATER ENTER SITE STORM WATER SEWER
SYSTEM - TAKE NECESSARY PRECAUTIONS.

GUY
WIRE

10

SCALE : NONE

1. BEFORE EXCAVATION BEGINS OWNING DEPARTMENT OR CONSTRUCTION SUPERVISOR


SHALL GENERATE AN EXCAVATION PERMIT REQUEST AND SEND IT TO ENGINEERING
DESIGNER. DESIGNER WILL PERFORM A UTILITY BACKGROUND CHECK, FIELD VERIFY,

W 6X16

SEE ANCHOR
BOLT DETAIL
4 TH. SHT.

3 INCHES

T
4
X
9
W

SEE
DET. 2 & 3
TH. SHT.

UNLESS NOTED OTHERWISE. ALL WELDED WIRE FABRIC TO BE OF ASTM A185.

GUY WIRES

9
X
4
T

4'
0"

(
TYP)

W8X21

ALL CONCRETE EXPOSED TO WEATHER SHALL BE AIR ENTRAINED.

1" NON SHRINK


GROUT

9"

(TYP)

9. ALL REINFORCING STEEL TO BE DEFORMED BARS OF ASTM A615, GRADE 60,

EM BDM T.

4'-0"

THE CONSTRUCTION ENGINEER SHALL BE IMMEDIATELY INFORMED.

4"PROJ.

3/4" X 13"L

STEEL FRAMING PLAN

EXISTING ELECRICAL
CONDUITS (TYP)

100

A DRY EXCAVATION UNTIL BACKFILL IS COMPLETED.

BLDG. 61T
NORTH MAIN SUBSTATION

8"

6"

4"

EXISTING

CHANNEL
2"

BASE
PLT.(S)

2"

3/16"

C6X8.2

4 EA THREADED
ROD PER SUPPT.
1/2"X12"L W/ NUTS
& WASHERS
ALL MATERIAL
HOT DIPPED
GALVANIZED (TYP)

2"

3/4" C.S.
PLATE

1/4" C.S.

SECTION

R
O
F
D
E
U
SS
I

SCALE : NONE

PLATE

10/13/15

DAR

09/29/15

DAR

No

DATE

BY

SCALE : NONE

DETAIL

SCALE : NONE

COL. BASE PLATE

T64401.DGN 10/13/2015 9:36:41 AM

DETAIL

QUANTITY: TWO (2)

ISSUED FOR APPROVAL/REVIEW


CHK APP APP

DESCRIPTION

ORIGINATION

BY

DATE

DRAWN

DAR

9-29-15

DESIGN

DAR

9-29-15

CHECKED

Civ. Eng.

BY

MH

9-29-15

SCALE : NONE

CHANNEL BASE PLATE

CHANNEL BASE PLATE

QUANTITY: EIGHT (8)

DRAWING NUMBER

0154-60A-C2-T64401

BASF RECORDS ARE FOR REFERENCE ONLY. THEY MAY OR MAY NOT REFLECT WHAT
IS ACTUALLY IN THE FIELD. THE POSSIBILITY OF ENCOUNTERING "UNKNOWN" OBJECTS

SITE

OR STRUCTURES IS REAL AND SHOULD BE CONSIDERED BEFORE AN EXCAVATION


OCCURS. IF ANYTHING UNUSUAL (OBSTRUCTION, ODOR, COLOR, CONSISTANCY OF FILL)
IS ENCOUNTERED DURING THE EXCAVATION OR DRILLING PROCESS, STOP WORK
IMMEDIATELY AND CONTACT A BASF REPRESENTATIVE. IF WORK CANNOT CONTINUE,
CONTACT BASF REPRESENTATIVE TO EVALUATE A NEW POSITION TO EXCAVATE OR
DRILL. DO NOT ATTEMPT TO EXCAVATE OR DRILL ON THE BASF WYANDOTTE SITE
WITHOUT PRIOR UTILITY BACKGROUND CHECK AND BASF APPROVAL.
SCALE 1/2" = 1'-0"
0

REV

ASSEMBLY

BASF WYANDOTTE SITE EXCAVATION DISCLAIMER:

NORTH MAIN SUBSTATION


CONDUCTOR SUPPORT
PLAN

DATE

50

MOVED COL. SUPPORT EAST TO 4FT FROM POLE

REVISIONS

APPROVAL

DETAIL

DB

30

.
A
I
"D
8
5/ LE
O
H
P)
TY
(

40

2"

1'
0"

1'
4"

A.
DI
8" E
/
7 L
HO P)
TY
(

8"

1'
0"

GRADE

2"

2"

2"

2"

F.F. EL. 583.0'

BLOCK
WALL

20

10"

SCALE 1"= 10'


0"

TOP FND. EL.


583.19'

SCALE 3/8" = 1'-0"


5

10

10

10

NUMBER

CAD INFORMATION

THIS DRAWING AND DESIGN,INCLUDING,BUT NOT LIMITED TO ALL PATENTABLE

PROJECT No.

FEATURES SEPARATELY OR COLLECTIVELY SHOWN ARE THE PROPERTY OF BASF

SITE

CORPORATION AND ARE NOT TO BE REPRODUCED IN WHOLE OR IN PART, NOR


EMPLOYED FOR ANY PURPOSE OTHER THAN SPECIFICALLY PERMITTED IN WRITING

SCALE

1/4"=1'

BY BASF CORPORATION.THIS DRAWING IS LOANED SUBJECT TO RETURN ON DEMAND.

SCALE 1/8" = 1'-0"


5

TYPE

APPRO. No.

SCALE 1/4" = 1'-0"


0

LOCATION

20

10

10