You are on page 1of 60

Substation Automation Products

Transformer protection RET670


Differential protection

1MRG019259

Chapter 03

Contents

ABB Group
September 10, 2015 | Slide 2

Application

Factors that affect a transformer protection

Differential protection function

Differential and bias currents

Zero sequence elimination

Operating characteristics

Blocking criteria

Internal external fault discriminator

On-load tap-changer compensation

Switch onto fault

Supervision Open CT and differential current

In and output signals

Settings

Monitored data

Chapter 03

Application
Transformer differential protection

ABB Group
September 10, 2015 | Slide 3

The majority of all transformer failures


are caused by winding faults

The differential protection is

the main protection in case of winding


failure

a unit protection limited by used CTs

fast, sensitive and secure

2nd harmonic and waveform block restraint


to avoid unwanted tripping for inrush

5th harmonic to avoid unwanted tripping for


overexcitation

Chapter 03

Application
Differential protection (TxWPDIF, 87T)

Phase differential protection function

single or multi-breaker arrangement,

protects one or two objects,

with or without tap-changer position


monitor,

with or without loaded delta winding,

Power transformer,

ABB Group
September 10, 2015 | Slide 4

Two or three windings

Auto-transformer,

Shunt reactor,

Generator transformer block,

Phase shifting transformer

Chapter 03

Application
Differential protection (T2WPDIF, 87T)

RET670

Two-winding differential protection


function with

Up to 4 three-phase CT inputs

Up to 2 instances

One on-load tap-changer

. . .

RET670

ABB Group
September 10, 2015 | Slide 5

RET670

Chapter 03

Application
Differential protection (T3WPDIF, 87T)

RET670

Three-winding differential protection


function with

Up to 6 three-phase CT inputs

Up to 2 instances

Up to 2 on-load tap-changers

. . .

RET670
RET670

ABB Group
September 10, 2015 | Slide 6

Chapter 03

Application
Differential protection (TxWPDIF, 87T)

Low impedance type

Low requirements on CTs

No need for interposing transformers


magnitude, phase angle correction and zero
sequence is implemented in the IED

ABB Group
September 10, 2015 | Slide 7

Using the fundamental frequency components

Features to detect

turn-to-turn faults

open CT

Tap-changer position monitoring for increased


sensitivity

Differential current supervision

Switch on to fault feature

Chapter 03

Common unbalances Overview


Factors that affect a transformer protection

Unbalances to be handled due to other


factors than faults in the transformer

Currents that flow on only one side of


the power transformer

Magnetizing currents that flow on only the


power source side

Normal magnetizing currents

Inrush magnetizing currents

Overexcitation magnetizing currents

Currents that cannot be transformed to


the other windings

ABB Group
September 10, 2015 | Slide 8

Zero sequence currents

Error in the power transformer turns ratio


due to OLTC

Chapter 03

Common unbalances Overview


Factors that affect a transformer protection

Unbalances to be handled due to other


factors than faults in the transformer

Inequality of the instrument current


transformers

Different ratings of current transformers

Different types of current transformers

Different relative loads on


instrument transformers

Different relative currents on


CT primaries

Different relative burdens on


CT secondaries

Different DC time constants of the


fault currents

ABB Group
September 10, 2015 | Slide 9

Different time of occurrence, and degree,


of CT saturation

Chapter 03

Inrush current
Factors that affect a transformer protection

ABB Group
September 10, 2015 | Slide 10

Source impedance

Size of the transformer

Location of energized winding

Inner 10 to 20 times of Irated

Outer 5 to 10 times of Irated

Connection of windings

Point of wave when the switch closes

Magnetic properties of the core

Remanence of the core

Pre-insertion resistors or switch-synch

Chapter 03

Energizing inrush
Factors that affect a transformer protection

IL1
IL2
IL3

Switch-on

High current peak and long DC time constant

Risk for CT saturation

Phase currents may differ considerably

Different harmonic levels in different phases

2nd harmonic

ABB Group
September 10, 2015 | Slide 11

Typical magnetizing
inrush current
waveform
60 MVA, 140/40 kV,
YNd

Chapter 03

Sympathetic inrush
Factors that affect a transformer protection

T2

T1

Energizing transformer T2

Inrush at T1 can appear and long DC time constant

Maximum after some delay

Oscillations between T1 and T21MRG004868

2nd harmonic

ABB Group
September 10, 2015 | Slide 12

T1 inrush current
waveform

Chapter 03

Recovery inrush and overexcitation


Factors that affect a transformer protection

ILx

ABB Group
September 10, 2015 | Slide 13

Clearing of external fault near the


transformer

The voltage at the terminals recovers to


its normal levels

Inrush currents

2nd harmonic

Overexcitation results from

Overvoltage and/or

Low frequency

Could be harmful and an overexcitation


protection should be considered

5th harmonic

Chapter 03

Current transformer saturation


Factors that affect a transformer protection
ILw1x
ILw2x
Idiffx
2nd harmonic

False differential current during external faults due to CT saturation

DC offset will produce phase shift between primary and secondary current

Current includes harmonics that may disturb the protection operation

ABB Group
September 10, 2015 | Slide 14

Chapter 03

Current transformer saturation


Factors that affect a transformer protection

Delay for heavy internal faults as a consequence of harmonic distortion of


the fault currents

Due to initial heavy saturation, the harmonic restrain can delay/prevent


immediate operation of the restrained (percentage) differential protection

ABB Group
September 10, 2015 | Slide 15

Chapter 03

Zero sequence current transformation


Factors that affect a transformer protection

Three phase or two phase faults

Delta-Wye Winding Effects on Primary Current


Ref. ANSI/IEEE C37.91, IEEE Guide for Protective
Relay Applications to Power Transformers

ABB Group
September 10, 2015 | Slide 16

Positive and negative sequence


components are transformed
between the windings (incl. phase
shift)

Single phase fault

Zero sequence currents is not


correctly transformed

False differential currents needs


to be eliminated

Chapter 03

References
Differential protection (TxWPDIF, 87T)

Internal adaptation to power transformer


vector group, turns ratio and CT ratio

Magnitude reference

Yd

All currents (differential, bias) are transferred


to the reference side and expressed in
primary Amperes

Phase reference

Dy

Yy

Dd

ABB Group
September 10, 2015 | Slide 17

First winding (usually HV)

first star-connected winding HV MV LV

if no star winding, first delta-connected winding


HV MV LV

All current currents are phase shifted with


respect to the reference side

Chapter 03

Differential currents
Differential protection (TxWPDIF, 87T)

Phase segregated

Fundamental frequency differential currents is calculated as:


or

ABB Group
September 10, 2015 | Slide 18

Where the coefficients A, B and C depend on

winding connection type,

transformer vector group and

zero sequence current elimination set on or off

Chapter 03

A, B and C matrices
Differential protection (TxWPDIF, 87T)
Type and vector group

Zero sequence reduction

YN

0o

yn

0o

d1

-30o

Set Off

Set On

Matrix for reference


winding
Not applicable

yn2 -60o

d5 -150o

Not applicable

Not applicable

d11 +30o

ABB Group
September 10, 2015 | Slide 19

Chapter 03

Bias currents
Differential protection (TxWPDIF, 87T)

ABB Group
September 10, 2015 | Slide 20

Higher currents might lead to unbalance currents other than faults

CT saturation due to high through fault currents

High load and tap-changer in end-position etc

Its necessary to stabilize the differential protection

The bias current is defined as

the highest fundamental frequency current amongst all phase currents (high,
medium and low voltage side)

and common for all three operate-restrain characteristics

referred to magnitude reference side (W1)

and specific for single breaker application:

Chapter 03

Bias currents
Differential protection (TxWPDIF, 87T)

Bias currents in multi-breaker arrangements

Through-fault stability (external fault)

Ideal CTs, external current summation stable

+A

+B

Idiff

-A -B
To Diff Prot
+A -A -B -B
IDIFF = +B -B = 0
IBIAS = MAX(-B; +B)

ABB Group
September 10, 2015 | Slide 21

Ibias

Chapter 03

Bias currents
Differential protection (TxWPDIF, 87T)

Through-fault stability (external fault)

Real CTs, external current summation loss of information and risk for
unwanted trip due to false differential current and insufficient stabilization

+A

+B

Idiff

-A -B
To Diff Prot
+A -A -B error -B error
IDIFF = +B -B error = error
IBIAS = MAX(-B error; +B)

ABB Group
September 10, 2015 | Slide 22

Ibias

Chapter 03

Bias currents
Differential protection (TxWPDIF, 87T)

Through-fault stability (external fault)

Real CTs, internal current summation higher security

+A

+B

Idiff

-A -B
To RET 670
+A
-A -B error
TxWPDIF

Ibias

ABB Group
September 10, 2015 | Slide 23

to IBIAS calculation

IDIFF = = +A -A -B error +B = error

to IDIFF & IBIAS calculation

IBIAS = MAX(-B error; +B; +A; -A -B error)

Chapter 03

Bias currents
Differential protection (TxWPDIF, 87T)

The bias current for multi-breaker application is defined as

CT1

the highest fundamental frequency current amongst all phase currents from
CT1, CT2 and the sum.

If CT rating >> rated current of the winding a risk of unwanted desensitizing (over-biasing) of the differential protection.

There is a possibility to scale the bias contribution from CT1 and CT2
(parameter: CTxRatingWy) to prevent over-biasing.

Irated Wx

CT2
to IBIAS calculation

ABB Group
September 10, 2015 | Slide 24

to IDIFF & IBIAS calculation

Chapter 03

Bias currents
Differential protection (TxWPDIF, 87T)

The bias current for multi-breaker application is calculated

and the maximum value is selected (1 out of 27 for a 3 winding multibreaker arrangement).

ABB Group
September 10, 2015 | Slide 25

Chapter 03

Bias currents
Differential protection (TxWPDIF, 87T)

Multi-breaker application example

When 1pu primary current flows through the T-side CT, this should
contribute a 1pu component to the bias calculation

Irated_CT1: 1000 A
Irated_W1: 500 A
CT1

W1

Without action the bias contribution


from CT1 is 1000 A (2pu)

By applying scaling factor:

CT1RatingW1: 1000

The bias contribution from the CT will be

I(RatedCurrentWy / CTxRatingWy) = 1000 (500/1000) = 500 A (1pu)

ABB Group
September 10, 2015 | Slide 26

Chapter 03

Zero sequence elimination


Differential protection (TxWPDIF, 87T)

Elimination of zero sequence currents is


necessary to avoid unwanted trips for
external earth faults when

zero sequence currents

1.

2.

ABB Group
September 10, 2015 | Slide 27

1.

cannot flow to the other side of the transformer

2.

can only flow on one side of the transformer

Removing the zero sequence currents


decreases the sensitivity for internal faults but

the bias currents are treated in the same way


this compensates to some degree

Setting per winding:

On/Off

Chapter 03

Operating characteristic Unrestrained


Differential protection (TxWPDIF, 87T)

Unrestrained, non-stabilized,
instantaneous limit

Independent of bias current

No doubt that the fault is internal

No blocking criteria

Setting: IdUnre

IdUnre

ABB Group
September 10, 2015 | Slide 28

1.0 - 50.0 times IBase

IBase (RatedCurrentW1): rated


current of winding 1 (A)

Chapter 03

Operating characteristic Operate-Restrain


Differential protection (TxWPDIF, 87T)

Operate unconditionally

Start:

IdMin

Section 3

Section 2

Section 1

Operate conditionally

Restrain

Section 1

IdMin, independent of bias currents

Normal currents

Natural differential currents due to


off-nominal on-load-tap changer
position

Section 2

ABB Group
September 10, 2015 | Slide 29

Differential and bias currents are


above the operate-restrain
characteristic

Minor slope to cope with false


differential currents due to high
load

Chapter 03

Operating characteristic Operate-Restrain


Differential protection (TxWPDIF, 87T)

Section 3

Operate unconditionally

Higher tolerance to substantial CT


saturation at high trough fault
currents

IdMin

ABB Group
September 10, 2015 | Slide 30

The slope:

Settings:

Section 3

Section 2

Section 1

Operate conditionally

IdMin

Restrain

0.05 0.60 times IBase

Endsection1 and 2

SlopeSection2 and 3

IBase (RatedCurrentW1): rated


current of winding 1 (A)

Chapter 03

Operating characteristics Blocking criteria


Differential protection (TxWPDIF, 87T)
IDL3
IDL2

Phase segregated feature

Waveform restrain or

Harmonic restrain

IDL1

IBias

ABB Group
September 10, 2015 | Slide 31

Second or fifth harmonic blocking

All three work in parallel and can


block the differential protection
function phase-wise

Instantaneous differential currents are


calculated and used in the analysis

The same equations are used as for


the fundamental differential
calculations (IDL1-L3)

Chapter 03

Operating characteristics Waveform restrain


Differential protection (TxWPDIF, 87T)

IL1

Typical magnetizing
inrush current
waveform

IL2
IL3

60 MVA, 140/40 kV,


YNd

Based on pattern recognition algorithm

Looks for intervals with low rate-of-change in the instantaneous


differential currents

Typical to power transformer and shunt reactor inrush currents

No settings

Bundled and phase segregated output signals (BLKWAVLx)

ABB Group
September 10, 2015 | Slide 32

Chapter 03

Operating characteristics Harmonic restrain


Differential protection (TxWPDIF, 87T)

1. Inrush
IL1
IL2
IL3

IN

1.

inrush currents or

2.

currents caused by overexcitation (high


voltage/low frequency)

Overexcitation could be harmful but this


phenomenon should be handled by the
overexcitation protection

The analysis is performed after operaterestrain-characteristic start

The ratio I2/I1 and I5/I1 is calculated per


phase

Bundled and phase segregated output


signals (BLK2HLx and BLK5HLx)

2. Overexcitation

ILx

ABB Group
September 10, 2015 | Slide 33

Required to prevent unwanted tripping due


to magnetizing (false differential currents)

Chapter 03

Operating characteristics Cross-blocking


Differential protection (TxWPDIF, 87T)
IDL2/3

IDL1
Phase L1
blocked

cross-block
Not affected

Ibias

Ibias

Inrush currents in separate phases of a power transformer may differ


considerably and

each phase will most likely have different harmonic levels and waveform

If a blocking condition is active in one phase (harmonic or waveform)

ABB Group
September 10, 2015 | Slide 34

This condition can block the differential protection in other two phases

But only if the differential protection in that phase have started

Chapter 03

Blocking criteria Summary


Differential protection (TxWPDIF, 87T)

Waveform inrush

ABB Group
September 10, 2015 | Slide 35

Settings: None

Second harmonic inrush, CT


saturation

Settings: Settable level in % of


fundamental frequency

Default setting: 15.0%

Fifth harmonic overexcitation

Settings; settable level in % of


fundamental frequency

Default setting: 25.0%

Cross-blocking between phase

Settings: On/Off

Default setting: On

Chapter 03

Internal external fault discriminator - Overview


Differential protection (TxWPDIF, 87T)

The level of negative sequence currents


are normally very low in a healthy
system

Increasing levels is a fault indicator

Positive and negative sequence


quantities follow the same laws

Transformed in the same way by a power


transformer

The same way to compensate for vector


group and turns ratio

Possible to compare the currents on HV


and LV (MV) side

RET670

ABB Group
September 10, 2015 | Slide 36

The point of fault is a fictitious source of


the negative sequence current

Chapter 03

Internal external fault discriminator - Overview


Differential protection (TxWPDIF, 87T)

The fault position can be determined by


comparing the flow directions on all sides

Theoretically a symmetrical fault will not


cause negative sequence currents but

due to the DC component the component


will be present

The protected transformer must be


loaded, if not its not possible to
determine direction

Objective

RET670

ABB Group
September 10, 2015 | Slide 37

Three direction comparisons for a three


winding transformer

Use negative sequence currents

Create a sensitive internal/external fault


discriminator

Chapter 03

External fault
Internal external fault discriminator

RET670

ABB Group
September 10, 2015 | Slide 38

External fault

The negative sequence currents are 180o out of phase (IED reference
direction: towards the object)

Magnitude are close to identical

Chapter 03

Internal fault
Internal external fault discriminator

RET670

Internal fault

ABB Group
September 10, 2015 | Slide 39

The residual currents are approximately in phase

Chapter 03

Operating characteristics
Internal external fault discriminator

The directional comparison is

performed if the magnitude of both


phasors are > IMinNegSeq

not performed during transformer


energization

To guarantee good sensitivity:

ABB Group
September 10, 2015 | Slide 40

IMinNegSeq must not be set too high

Settings:

Relay operate angle (NegSeqROA)


30 90o

Minimum current (IminNegSeq)


0.02 0.20

Chapter 03

CT saturation
Internal external fault discriminator
4

CT saturation might cause


phase angles 180o or 0o

Approximately 5 ms time to
saturation of the main CT is
sufficient

2
5

ABB Group
September 10, 2015 | Slide 41

The figure shows a test


1.

7 ms: Internal fault declared

2.

12 ms: Trip command issued

3.

Definitely an internal fault

4.

Excursion due to CT
saturation

5.

External fault region

Chapter 03

Internal external fault discriminator Features


Differential protection (TxWPDIF, 87T)

Discriminates between internal and


external faults with high dependability

Detects even minor faults with high


sensitivity and high speed

The feature is used in two sub


functions:
1. Unrestrained negative sequence
differential protection (NSUNR)

Turn-to-turn fault at the end of the


common winding
(Courtesy of Croatian Utility HEP)

ABB Group
September 10, 2015 | Slide 42

2. Sensitive negative sequence protection


(NSSENS)

Chapter 03

Traditional differential protection


Simplified logical diagram

ABB Group
September 10, 2015 | Slide 43

1MRG004867

Chapter 03

Unrestrained NS differential protection


Simplified logical diagram

Dependent on the traditional differential protection

A restrained start is required and the internal / external fault discriminator


categorizes the fault as internal Trip

The blocking supervision is bypassed if the fault is declared: Internal

ABB Group
September 10, 2015 | Slide 44

Chapter 03

Sensitive NS turn-to-turn fault protection


Simplified logical diagram
Blocking condition:
2nd harmonic, 5th harmonic,
waveblock and crossblock

Negative sequence
internal/external
fault discriminator

Internal
I- start &
internal

&
&

>1
Bias
<150%

TRIP

Unrestrained
Restrained

START

Independent of the traditional differential protection, no restrained start is required

The decision must be confirmed several times in order to secure the decision before
a trip is placed

Nevertheless, the operating time is about 40 ms for very low level turn-to-turn faults

The protection is blocked when the bias currents >150%

ABB Group
September 10, 2015 | Slide 45

Chapter 03

On-line compensation for OLTC General


Differential protection (TxWPDIF, 87T)

ABB Group
September 10, 2015 | Slide 46

Without OLTC information, fixed ratio is used when


calculating the differential currents

As turns ratio changes off nominal (due to OLTC


movement), the currents will change and false differential
currents will appear

TxWPDIF has a feature to monitor the tap-position and


dynamically compensate the equation above

i.e. if the tap-changer is placed on W1, the no-load


voltage Ur_W1 will be treated as a function of the actual
tap position

OLTC must be considered when selecting IdMin

Typically IdMin-setting is 0.30 - 0.40 but if position


information is available the settings could be halved

Chapter 03

On-line compensation for OLTC


Differential protection (TxWPDIF, 87T)

YLTC (TCL or TCM) is the interface between the OLTC and


TxWPDIF

T2WPDIF can be compensated for one OLTC

T3WPDIF can be compensated for one or two OLTC

Inputs: Tap position information

mA input signal (requires MIM-input HW-module),

binary input signals (TCLYLTC, max 32 steps) or

coded binary, BCD or Gray coded

Outputs: to be used by TxWPDIF

Actual tap position (TCPOS TAPOLTCx, Integer)

OLTC alarm (POSERRAL OLTCxAL)

Whenever OLTCxAL = 1 (true)

ABB Group
September 10, 2015 | Slide 47

Actual IdMin will be increased depending of the OLTC settings

Chapter 03

Switch on to fault feature


Differential protection (TxWPDIF, 87T)
Typical magnetizing inrush current
waveform (red) and voltage (blue)

Built-in SOTF feature - only active when energizing the transformer

Ensures faster tripping when energizing a faulted transformer (severe fault)

Based on the fact: different shape of the current when energizing a healthy
transformer compared to switch on to a fault

Instantaneous increase in current

ABB Group
September 10, 2015 | Slide 48

The waveform block will reset and temporary disable the blocking signals Fast
operation of the differential protection

When SOTF disabled: Waveform the other blocking features are completely
independent from each other

Chapter 03

Supervision Differential current alarm


Differential protection (TxWPDIF, 87T)

The differential current level is continuously


monitored

When all three phase differential currents


are above:

IdMin
IDiffAlarm

ABB Group
September 10, 2015 | Slide 49

IDiffAlarm (<IdMin) and

tAlarmDelay have elapsed

the output signal IDALARM is set

Application

warning if the differential level approaches


trip level (due to the tap-changer position)

desensitize the differential function using


logic and OLTCxAL input

Settings:

IDiffAlarm:

0.05 1.00 times IBase

tAlarmDelay:

0.00 60.0 s

Chapter 03

Supervision Open CT detection


Differential protection (TxWPDIF, 87T)

Objective:

ABB Group
September 10, 2015 | Slide 50

To prevent maloperation due loss of single phase


secondary current

The feature

must operate within 10 ms to ensure differential


protection blocking

is based on sudden drop to zero in one phase and


no change in the others

is enabled about 1 minute after entering normal load


conditions (IBias >10% of rated current)

and disabled at high currents (>110% of rated current


i.e. overload, external faults, inrush conditions)

Chapter 03

Supervision Open CT detection


Differential protection (TxWPDIF, 87T)

When open CT detected

All differential functions, except the unrestrained


function, will be blocked immediately

The unrestrained function will be blocked after


tOCTUnrstDelay (< 6000 s)

An alarm will be given after tOCTAlarmDelay


(< 10 s)

Reset

ABB Group
September 10, 2015 | Slide 51

A detected open CT condition will be reset


automatically once the condition has disappeared

Symmetrical bias current within 10 110% for at least


1 minute and

this must be fulfilled at least for tOCTResetDelay


(< 10 s) to prevent maloperation at reconnection

It is not possible to externally reset the open CT


detection

Chapter 03

In- and output signals


Differential protection (TxWPDIF, 87T)

Phase currents W1 CT1


W1 CT2
Analog input signals
Phase currents W2 CT1
(SMAI group signal output)
W2 CT2
Phase currents W3 CT1
W3 CT2
Tap changer #1 position
OLTC input signal
#2 position
(YLTC function outputs)
Tap changer #1 alarm
#2 alarm
Block of function
Binary input signal
Block of restrained trip
Block of unrestrained trip
Block of unrestrained negative seq differential
Block of negative seq differential protection

ABB Group
September 10, 2015 | Slide 52

Chapter 03

In- and output signals


Differential protection (TxWPDIF, 87T)

Binary output signals


General trip
Restrained differential trip
Unrestrained differential trip
Unrestrained negative sequence differential trip
Sensitive negative sequence differential protection trip
General start
Start signal from phase Lx
Second harmonic blocking

Fifth harmonic blocking

Waveform blocking

ABB Group
September 10, 2015 | Slide 53

Chapter 03

In- and output signals


Differential protection (TxWPDIF, 87T)

Sustained differential current alarm


Open CT detected
Open CT, delayed signal
Differential current, samples, phase Lx

Differential current, RMS-value, phase Lx


Bias current
Negative sequence differential current

ABB Group
September 10, 2015 | Slide 54

Binary output signals


Analog output signals
HMI and Disturbance
recorder

Chapter 03

Differential protection settings


Overview
Two-winding
transformer
1st

instance

General settings
Rated values for winding 1
and 2 (3)
Winding 1 and 2 (3)
connection type
Phase angle between W1
and W2 (W1 and W3)
Zero sequence subtraction
on/off per winding
Multi-breaker and bias
correction W1 and W2 (W3)

On-Load tap-changer: Not


used, W1, W2 (W3)
Tap-changer data

ABB Group
September 10, 2015 | Slide 55

Chapter 03

Differential protection settings OLTC


Overview
General settings
On-load tap-changer
1st instance

Conversion data

mA, BCD, BIN, Gray, Single


OLTC Ctrl settings

Setting group 1

ABB Group
September 10, 2015 | Slide 56

Chapter 03

Differential protection settings


Group N settings
Specific settings
Operation On/Off
Switch onto fault function
Operation characteristic

Blocking

Negative sequence differential function

Open CT
Alarm settings

ABB Group
September 10, 2015 | Slide 57

Chapter 03

Monitored data
Differential protection

ABB Group
September 10, 2015 | Slide 58

Tests/Functions status/Differential
protection/ TransformerDiffxWind(PDIF,87T)

TRIP General trip

TRIPRES Restrained trip

TRIPUNRE Unrestrained trip

TRNSUNR Unrestrained NS trip

TRNSSENS Sensitive NS trip

START General start signal

STL1-3 Start signal from phase Lx

BLK2H, L1-3 Second harmonic blocking

BLK5H, L1-3 Fifth harmonic blocking

BLKWAV, L1-3 Waveform blocking

IDALARM Sustained differential currents


alarm

OPENCT Open CT detected

OPENCTAL Open CT delayed alarm

Chapter 03

Monitored data
Differential protection

ABB Group
September 10, 2015 | Slide 59

Tests/Functions status status/Differential


protection/ TransformerDiffxWind(PDIF,87T)

IDL1MAG Magnitude of differential current,


phase L1 (A)

IDL2MAG Phase L2 (A)

IDL3MAG Phase L3 (A)

IBIAS Magnitude of bias current (A, Common


for all phases)

IDNSMAG Magnitude of negative sequence


differential current (A)

Chapter 03

ABB
SA-TGroup
Training
September 10, 2015 | Slide 60

You might also like