PDU
EPS 01B
REMARK: Power distribution is different, we have fuses and 14 loads. We dont need terminals to make DC
connections.
Page 2
PDU
LOAD DISTRIBUTION
Page 3
PDU
LOAD DISTRIBUTION
LOAD 0: FAN; 15 A
LOAD 1: BBU; 15 A
LOAD 4: RTN; 5 A
LOAD 5: FAN; 5 A
Page 4
PDU
LOAD DISTRIBUTION
LOAD 8: RRU 1; 20 A
LOAD 9: RRU 2; 20 A
LOAD 10: RRU 3; 20 A
Page 5
DC BATTDC BATT+
DC EMUA
DC RTN
PG
ALARMS
DC RRU 1
DC RRU 1
DC RRU 1
Page 6
GENERAL VIEW
REMARK: We dont have insulations for cable holes in this new APM, to make the connections we have
to remove the cover of the holes to put the cable in the right hole.
Page 7
SHELTER
UTP/LIQUID
SENSOR
DC EMUA
AC PDB
PGND
EXTERNAL
BUS BAR
DC RTN
SECTOR 1
FIBER
RTN IF
SECTOR 2
FIBER
RTN IF
SECTOR 3
FIBER
Page 8
GENERAL VIEW
REMARK: We passed the DC EMUA cable under the APM, throw the APMs base.
Page 9
GROUNDING BARS
RIGHT SIDE
GROUNDING
BAR
REMARK: The new grounding bar is located next the 3 rd PSU in the right side of the APM. It has 4 bolts for
connection. And we have another one in the left side with 4 bolts too.
Page 10
GROUNDING BARS
RIGHT SIDE
BBU
GROUNDING
EMUA
GROUNDING
Page 11
GROUNDING BARS
BBU EMUA GROUNDING
BBU RIGHT
SIDE BOLT
EMUA
Page 12
GROUNDING BARS
LEFT SIDE
PDU
RTN 620
EXTERNAL
GROUNDING
BAR
Page 13
GROUNDING BARS
LEFT SIDE
WRIST
STRAP
REMARK: Wrist strap connection is located below AC output box, in the left side of the APM.
Page 14
BATTERY BANK
DC CONNECTION
SPLICE BETWEEN
APM AND
MINISHELTER
CABLES
REMARK: We used a tubular terminal to make the connection between APM and minishelter battery
cables, finally we covered this with heatshrink for protection.
Page 15
BATTERY BANK
DC CONNECTION
Page 16
SENSORS CONNECTION
TEMPERATURE AND HUMIDITY
REMARK: The shape of the humidity and temperature sensor has changed a little but the installation is
the same.
Page 17
SENSORS CONNECTION
TEMPERATURE AND HUMIDITY
REMARK: The sensor cover has two holes, we must separate humidity and temperature connections
and pass the cables throw these holes.
Page 18
SENSORS CONNECTION
LIQUID LEVEL SENSOR
LIQUID
SENSOR
REMARK: APMs base is different, we have to attach the liquid sensor with one plastic belt to the left side of the base.
We can use for this operation one hole that is located in the middle of the intern border behind the base cover.
Page 19
APM
GENERAL VIEW
Page 20
OUTDOOR LABELLING
ANTENNA
SECTOR 1:
Jumper A ANT_0A
Jumper B ANT_0B
SECTOR 2:
Jumper A ANT_1A
Jumper B ANT_1B
SECTOR 3:
Jumper A ANT_2A
Jumper B ANT_2B
REMARK: Each box of auxiliary material has 4 sets of outdoor labels for the antenna jumpers.
Page 21
OUTDOOR LABELLING
ANTENNA AND RRU VIEW
ANTENNA
RRU
Page 22