Professional Documents
Culture Documents
Designation
No.
1
DDF
SLOT
1
BLUE)
2
High Temperature(WHITE /
Tower Light Failure
Connected directly to
Connected directly to
BBU SA Card
4
BROWN)
5
BBU SA Card
Alarm(WHITE / GREEN)
4
Connected directly to
Connection
BBU SA Card
ORANGE)
3
Remarks
Environmental Over
Humidity(RED / BLUE)
7
ORANGE)
8
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
Door 1 sensor
Door 2 sensor
AC1(1500W) alarm cable
Smoke alarm
DDF Port 8
SA card
(BS8800)
D
D
F
B201 Module
B201 X17
Port(NC/COM)
B201 X24
Port
Rectifier alarm
DDF Port 4
virtual
Actual
Smoke sensor
Tower
Control
box
Junction
box
NodeB(BS8800) part:
SA card
(BS8800)
D
D
F
For New site External alarm we through BS8800 SA card report to EMS/OMC.all external alarm sensor
should be connect to SA card through DDF terminal.before connect sensor,please make loop back test
from DDF to OMC,make sure 8channel no any cross.it very important for test external alarm.
External alarm connection :
SA card-------SA cable(B3 connector)---------SA E1 Cable----------DDF-------each sensor
1. SA cable :material code: 052740402435 DS-91228-001|Digital Signal Cable
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
3.connection picture:
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
SA card
(BS8800)
Door 1 sensor
Door 2 sensor
D
D
F
Door1 and Door2 Sensor cable need parallel connect to DDF port1
Door 1 Sensor :
Door2 Sensor
SA card
(BS8800)
D
D
F
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
D
D
F
Tower
Control
box
Junction
box
Tower lignht Alarm cable(alarm output in control box) need connect to DDF port3
Medium light(1pcs) /low light(2pcs) cable (Brow/blue) connect to Junction box alarm input terminal,
From Junction box connect to Control box alarm input terminal, From Control box alarm output
connect to DDF port3 terminal. For detail connection please reference installation and operation
manual in the box.
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
SA card
(BS8800)
D
D
F
Rectifier alarm
DDF Port 4
Below description detail how to setting external alarm in ZXDU68 B201 system.
Interface name
X4
Battery 1 temperature
Interface
Interface name
X21
RS485 interface
X5
Battery 2 temperature
X22
Rs232 interface
X12
Temperature control
X23
Flood alarm
X14
X24
Smoke alarm
X15
X25
Ambient temperature
X16
X26
Intrusion alarm
X17
Pin
Signal
definition
Signal description
X15
Output relays
1,2
2NO
A3
2COM
A3
2NC
A3
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
10
X16
Output
relays3,4
X17
Output relays
5,6
1NO
--
1COM
--
1NC
--
4NO
A5
4COM
A5
4NC
A5
3NO
A2
3COM
A2
3NC
A2
6NO
A4
6COM
A4
6NC
A4
5NO
A5
5COM
A5
5NC
A5
The relays alarm function has two options on the signal board, one relay output-NO(normal open)
and one relay output-NC(normal close). So need to know the BTS interface alarm definition
which it is NO or NC.
If it is NO, and connect relay alarm cables step:
1 One group relay out need two signal cables , and one terminal connect with relay out ON and
relay output common end on the signal board interface, another terminal connect with the
BTS interface.
NO
COMMON
DDF
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
11
4 Enter the setup parameter system: 1. Setup Para, press the Enter button.
6 Enter the Alarm Para menu, find the 1.Set Relay to Enter
7 And find the relays alarm parameter. According to the relays alarm requirements, set the relay
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
12
Setup procedures
If the relay alarm connected the X15(1,2) of the signal board, it mean what it is SMR Alarm.
So the relay alarm parameter set A2.
Refer to above the Table-1.
Figure (set parameter:
Smoke alarm
DDF Port 8
SA card
(BS8800)
B201 X17
Port(NC/COM)
B201 X24
Port
Smoke sensor
D
D
F
Smoke alarm From Smoke sensor first connect to X24then X17 NC/COM connect to DDF port8
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
13
Alarm
DDF
SLOT
Connection
Designation
Connection
No.
GRAY)
Door 1 sensor
Door 2 sensor
AC1(1500W) alarm cable
AC2(1500W) alarm cable
AC3(500W) alarm cable
B201 Module
SA card
(BS8800)
D
D
F
Rectifier alarm
DDF Port 3
virtual
Generator
Actual
Generator Fault
DDF Port 7
Generator
Genterator tank
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
14
D
D
F
Generator
Generator Fault
DDF Port 7
Generator
Genterator tank
<>
All Rights reserved, No Spreading abroad without Permission of ZTE
15