New Site External alarm implementation guide


For new site External we have two scenario:
1. ZTE ODU External Alarm Configuration (With Sceco)
2. ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset)

ZTE ODU External Alarm Configuration (With Sceco)


Alarm

Designation

No.
1

Door Cabinet Open(WHITE /

DDF
SLOT
1

BLUE)
2

High Temperature(WHITE /
Tower Light Failure

Rectifier Alarm (WHITE /

AC Power Fail(WHITE / GRAY)

Connected directly to

Sensor - DDF 2 - BBU SA

Connected directly to

Sensor - DDF 3 - BBU SA

BBU SA Card
4

BROWN)
5

Sensor - DDF 1 - BBU SA

BBU SA Card

Alarm(WHITE / GREEN)
4

Connected directly to

Connection

BBU SA Card

ORANGE)
3

Remarks

From B201 SIB Board

X15 - DDF 4 - BBU SA

(Power Unit) - X15 port


5

From B201 SIB Board

X16 - DDF 5 - BBU SA

(Power Unit) - X16 port


6

Environmental Over

Humidity(RED / BLUE)
7

DC Low Voltage alarm(RED /


SMOKE Alarm(RED / Green)

X16 - DDF 6 - BBU SA

(Power Unit) - X16 port


7

ORANGE)
8

From B201 SIB Board


From B201 SIB Board

X17 - DDF 7 - BBU SA

(Power Unit) - X17 port


8

From B201 SIB Board

X17 - DDF 8 - BBU SA

(Power Unit) - X17 port

<>
All Rights reserved, No Spreading abroad without Permission of ZTE

Internal Use Only

ZTE ODU External Alarm Drawing (With Sceco)


ODU Cabinet

Door 1 sensor

Door open alarm


DDF Port 1

Door 2 sensor
AC1(1500W) alarm cable

High tep. Alarm


DDF Port 2

AC2(1500W) alarm cable


AC3(500W) alarm cable

Smoke alarm
DDF Port 8

SA card
(BS8800)

D
D
F

B201 Module

B201 X17
Port(NC/COM)

B201 X24
Port

Rectifier alarm
DDF Port 4

B201 X15 Port(NC/COM)

AC power fail alarm


DDF Port 5

B201 X16 Port(NC/COM)

Environmental over humidity alarm


DDF Port 6

B201 X16 Port(NC/COM)

DC Low voltage alarm


DDF Port 7

virtual

Actual

Smoke sensor

B201 X17 Port(NC/COM)

Tower

Medium light alarm cable


Tower Light Failre Alarm
DDF Port 3

Control
box

Junction
box

Low light alarm cable


Low light alarm cable

NodeB(BS8800) part:

SA card
(BS8800)

D
D
F

For New site External alarm we through BS8800 SA card report to EMS/OMC.all external alarm sensor
should be connect to SA card through DDF terminal.before connect sensor,please make loop back test
from DDF to OMC,make sure 8channel no any cross.it very important for test external alarm.
External alarm connection :
SA card-------SA cable(B3 connector)---------SA E1 Cable----------DDF-------each sensor
1. SA cable :material code: 052740402435 DS-91228-001|Digital Signal Cable

<>
All Rights reserved, No Spreading abroad without Permission of ZTE

Internal Use Only

2.SA E1 Cable: material code: 052740402185 DS-91223-002|Digital Signal Cable

We used core color(new)

<>
All Rights reserved, No Spreading abroad without Permission of ZTE

Internal Use Only

3.connection picture:

<>
All Rights reserved, No Spreading abroad without Permission of ZTE

Internal Use Only


No1. Door Cabinet Open(WHITE / BLUE)(in DOU cabinet)
ODU Cabinet

SA card
(BS8800)

Door open alarm


DDF Port 1

Door 1 sensor
Door 2 sensor

D
D
F

Door1 and Door2 Sensor cable need parallel connect to DDF port1
Door 1 Sensor :

Door2 Sensor

Door 1&Door 2 Sensor cable :


<>
All Rights reserved, No Spreading abroad without Permission of ZTE

Internal Use Only

No 2.High Temperature(WHITE / ORANGE) (in DOU cabinet)


ODU Cabinet

High tep. Alarm


DDF Port 2

AC1(1500W) alarm cable


AC2(1500W) alarm cable
AC3(500W) alarm cable

SA card
(BS8800)

D
D
F

AC1&AC2&AC3 Alarm cable need parallel connect to DDF port2


1.AC1(1500W)alarm cable:(Location:in Door1 up area Port:NC/COM)

<>
All Rights reserved, No Spreading abroad without Permission of ZTE

Internal Use Only


2.AC2(1500W)alarm cable:(Location:in Door2 up area Port:NC/COM)

3.AC3(500W)alarm cable:(Location:in Door2 down area Port:NC/COM)

4.alarm cable in ODU location

<>
All Rights reserved, No Spreading abroad without Permission of ZTE

Internal Use Only

No 3.Tower Light Failure Alarm(WHITE / GREEN)-on tower


SA card
(BS8800)

D
D
F

Tower

Medium light alarm cable


Tower Light Failre Alarm
DDF Port 3

Control
box

Junction
box

Low light alarm cable


Low light alarm cable

Tower lignht Alarm cable(alarm output in control box) need connect to DDF port3
Medium light(1pcs) /low light(2pcs) cable (Brow/blue) connect to Junction box alarm input terminal,
From Junction box connect to Control box alarm input terminal, From Control box alarm output
connect to DDF port3 terminal. For detail connection please reference installation and operation
manual in the box.

<>
All Rights reserved, No Spreading abroad without Permission of ZTE

Internal Use Only

No 4. Rectifier Alarm (WHITE / BROWN)


No 5. AC Power Fail(WHITE / GRAY)
No 6.Environmental Over Humidity(RED / BLUE)
No 7.DC Low Voltage alarm(RED / ORANGE)

SA card
(BS8800)

D
D
F

Rectifier alarm
DDF Port 4

B201 X15 Port(NC/COM)

AC power fail alarm


DDF Port 5

B201 X16 Port(NC/COM)

Environmental over humidity alarm


DDF Port 6
DC Low voltage alarm
DDF Port 7

B201 X16 Port(NC/COM)

B201 X17 Port(NC/COM)

Rectifier Alarm From X15 NC/COM connect to DDF port4


AC Power Fail From X16 NC/COM connect to DDF port5
Environmental Over Humidity From X16 NC/COM connect to DDF port6
DC Low Voltage alarm From X17 NC/COM connect to DDF port7

Below description detail how to setting external alarm in ZXDU68 B201 system.

About the relay alarm of the ZXDU68B201 power supply system


The boards of the zxdu68 B201system is integrated in the signal transfer box. Figure as below:
shown the board layout.
<>
All Rights reserved, No Spreading abroad without Permission of ZTE

Internal Use Only

1. Network interface board(IP/SNMP);


2. Modem power board(MPB);
3. Signal interface board(SIB)
And the signal interface board provides external communication interfaces and monitoring
unit signal interfaces. The signal board is shown in figure as below. Refer to table for the
signal board interfaces description.
Figure signal board:

Table signal interface name


Interface

Interface name

X4

Battery 1 temperature

Interface

Interface name

X21

RS485 interface

X5

Battery 2 temperature

X22

Rs232 interface

X12

Temperature control

X23

Flood alarm

X14

Input relays 1,2,3,4

X24

Smoke alarm

X15

Out relays 1,2

X25

Ambient temperature

X16

Out relays 3,4

X26

Intrusion alarm

X17

Out relays 5,6

Then the relays alarm function need to three interface: X15X16X17.


So the relays alarm function of the signal interface definition as belowTable-1:
Interface

Pin

Signal
definition

Signal description

Relay alarm definition


(monitor parameters)

X15
Output relays
1,2

2NO

Relay output 2-NO(normally open)

A3

2COM

Relay output 2-Common end

A3

2NC

Relay output 2-NC(normally closed)

A3

<>
All Rights reserved, No Spreading abroad without Permission of ZTE

10

Internal Use Only

X16
Output
relays3,4

X17
Output relays
5,6

1NO

Relay output 1-NO

--

1COM

Relay output 1-Common end

--

1NC

Relay output 1-NC

--

4NO

Relay output 4-NO

A5

4COM

Relay output 4-Common end

A5

4NC

Relay output 4-NC

A5

3NO

Relay output 3-NO

A2

3COM

Relay output 3-Common end

A2

3NC

Relay output 3-NC

A2

6NO

Relay output 6-NO

A4

6COM

Relay output 6-Common end

A4

6NC

Relay output 6-NC

A4

5NO

Relay output 5-NO

A5

5COM

Relay output 5-Common end

A5

5NC

Relay output 5-NC

A5

The relays alarm function has two options on the signal board, one relay output-NO(normal open)
and one relay output-NC(normal close). So need to know the BTS interface alarm definition
which it is NO or NC.
If it is NO, and connect relay alarm cables step:
1 One group relay out need two signal cables , and one terminal connect with relay out ON and
relay output common end on the signal board interface, another terminal connect with the
BTS interface.
NO
COMMON

DDF

2 Other relays alarm as above the connection step, until it finished.


After finished to connect the signal cables , and set parameters in the monitor.
Step:
1check the monitor screen, find the CTRL menu.

<>
All Rights reserved, No Spreading abroad without Permission of ZTE

11

Internal Use Only


2press the button ENTER of the monitor.

3 Entering the password: 0000.

4 Enter the setup parameter system: 1. Setup Para, press the Enter button.

5 Find the Alarm Para in the Setup Para.

6 Enter the Alarm Para menu, find the 1.Set Relay to Enter

7 And find the relays alarm parameter. According to the relays alarm requirements, set the relay
<>
All Rights reserved, No Spreading abroad without Permission of ZTE

12

Internal Use Only


alarm.

Setup procedures
If the relay alarm connected the X15(1,2) of the signal board, it mean what it is SMR Alarm.
So the relay alarm parameter set A2.
Refer to above the Table-1.
Figure (set parameter:

No 8. SMOKE Alarm(RED / Green)


ODU Cabinet

Smoke alarm
DDF Port 8

SA card
(BS8800)

B201 X17
Port(NC/COM)

B201 X24
Port

Smoke sensor

D
D
F

Smoke alarm From Smoke sensor first connect to X24then X17 NC/COM connect to DDF port8

<>
All Rights reserved, No Spreading abroad without Permission of ZTE

13

Internal Use Only


ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset)

Alarm

DDF

DRY Contact Alarm

SLOT

Connection

Designation

Connection

No.

Connected directly to BBU SA


1

Door Cabinet Open(WHITE / BLUE)

Sensor - DDF 1 - BBU SA


Card
Connected directly to BBU SA

High Temperature(WHITE / ORANGE)

Sensor - DDF 2 - BBU SA


Card
From B201 SIB Board

Rectifier Alarm (WHITE / GREEN)

X15 - DDF 3 - BBU SA


(Power Unit) - X15 port
From B201 SIB Board

AC Power Fail(WHITE / BROWN)

X16 - DDF 4 - BBU SA


(Power Unit) - X16 port

Environmental Over Humidity(WHITE /


5

From B201 SIB Board


5

GRAY)

X16 - DDF 5 - BBU SA


(Power Unit) - X16 port
From B201 SIB Board

DC Low Voltage alarm(RED / BLUE)

X17 - DDF 6 - BBU SA


(Power Unit) - X17 port
From Generator Control Port

Generator Fault(RED / ORANGE)

Generator Control - DDF 7 - BBU SA


connected directly to SA Card
From the Storage Tank

Generator Low Fuel(RED / GREEN)

Storage Tank Sensor - DDF 8 - BBU SA


Connected directly to SA Card

ZTE ODU External Alarm Drawing (With Genset)


ODU Cabinet

Door open alarm


DDF Port 1

High tep. Alarm


DDF Port 2

Door 1 sensor
Door 2 sensor
AC1(1500W) alarm cable
AC2(1500W) alarm cable
AC3(500W) alarm cable

B201 Module
SA card
(BS8800)

D
D
F

Rectifier alarm
DDF Port 3

B201 X15 Port(NC/COM)

AC power fail alarm


DDF Port 4

B201 X16 Port(NC/COM)

Environmental over humidity alarm


DDF Port 5
DC Low voltage alarm
DDF Port 6

B201 X16 Port(NC/COM)

B201 X17 Port(NC/COM)

virtual
Generator
Actual

Generator Fault
DDF Port 7

Generator

Generator Low Fuel


DDF Port 8

Genterator tank

<>
All Rights reserved, No Spreading abroad without Permission of ZTE

14

Internal Use Only


For alarm No.1No.6,please refer ZTE ODU EXTERNAL ALARM CONFIGURATION TEST
(With Sceco) installation.
No7. Generator Fault(RED / ORANGE)
No8 Generator Low Fuel(RED / GREEN)
SA card
(BS8800)

D
D
F

Generator
Generator Fault
DDF Port 7

Generator

Generator Low Fuel


DDF Port 8

Genterator tank

<>
All Rights reserved, No Spreading abroad without Permission of ZTE