You are on page 1of 1

Amps X 100 BB-1A (Nom. kV=220, Plot Ref.

kV=220)
.5

10

30

50

100

300

500

1K

3K

5K

1K

10K
1K

500

500

300

300

T201-HV-SBEF - G
OC1
100

100

HV SBEF
ABB
REF615
CT Ratio 600:1
Inst = 400 (5 - 400 xCT Sec)
Time Delay = 0.5 s

50

30

50

30

10

.5

.5

.3

.3

D05-RP - G
OC1
120MVA T/F
ABB
REF615
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.3
3x = 1.89 s, 5x = 1.28 s, 8x = 0.989 s

.1

.05

.03

.1

.05

.03

.01
.5

10

30

50

100

300

500

1K

Amps X 100 BB-1A (Nom. kV=220, Plot Ref. kV=220)


N7733-220/33/11kV
Project:
Location:
Contract:
Engineer:
Filename:

CASE-1.5 EF

220/33/11kV Zakher Grid


Zakher Area of Al Ain
N7733
JM
C:\Users\joshi\Desktop\LATEST RELAY SETTING\DUBAI\TRANSCO-Supercede 01.03.1

Date:
SN:
Rev:
Fault:
Circuit:

08-03-2016
LARSENTRN2
Base
Ground
120MVA T/F, HV SBEF

3K

5K

.01
10K

ETAP Star 12.5.0C

Seconds

Seconds

10