Amps X 100 33kV(BB-2) SWGR-A (Nom. kV=33, Plot Ref.

kV=33)
.5

10

30

50

100

300

500

1K

3K

5K

1K

500

500

300

300

H17-RP - G
OC1

100

100

33kV B/S
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.39
3x = 2.46 s, 5x = 1.67 s, 8x = 1.29 s

50

30

Seconds

10K
1K

50

30

10

10

22015 A, 1.16 s

0.272 s

0.204 s
.5

.5

.3

H03-RP - G
OC1
33kV O/G-SWGR-A
ABB
REF615
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.3
3x = 1.89 s, 5x = 1.28 s, 8x = 0.989 s

.1

.05

.03

H08-RP - G
OC1

.3

120MVA I/C
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.51
3x = 3.21 s, 5x = 2.18 s, 8x = 1.68 s

.1

.05

.03

.01
.5

10

30

50

100

300

500

1K

Amps X 100 33kV(BB-2) SWGR-A (Nom. kV=33, Plot Ref. kV=33)


N7733-ZAKHER
Project:
Location:
Contract:
Engineer:
Filename:

3K

5K

ETAP Star 12.5.0C

CASE:2.2 EF

220/33/11kV Zakher Grid


Zakher Area of Al Ain
N7733
JM
C:\Users\joshi\Desktop\LATEST RELAY SETTING\DUBAI\TRANSCO-Supercede 01.03.1

Date:
SN:
Rev:
Fault:
Circuit:

.01
10K

21-01-2016
LARSENTRN2
Base
Ground
120MVAMVSBEF,33kVI/C,BS,OG