You are on page 1of 8

Cerberus AlgoRex

Fire detection system CS1140


Interactive / AnalogPLUS / Collective

• Modular, microprocessor-controlled fire detection system


• Processes the signals from fire detectors from widely varying
detection systems such as:
– interactive fire detectors, series DS1150
– AnalogPLUS fire detectors, series DS1130
– collective fire detectors, series DS1100
– addressable fire detectors, series MS7i/MS9i
• Highest system availability through decentralized signal
evaluation in control unit and detectors
• Parametrisation as required by the application
• Emergency power operating period 12 to 24 hours, optionally
up to 72 hours
• Integrated emergency operation electronics
• Control console can be connected separately or built–in
into the control unit housing
• Several control consoles can be operated with each control unit
• Designed for optimum installation efficiency and commissioning

Fire & Security Products


Siemens Building Technologies Group
System overview

Control console CT1142 Optional text display External interface


and control terminals to drive LEDs
B3Q580 / B3Q590 (for mimic display
panels) or relays

C4Bus LON4Bus

Interactive detector bus for


series DS1150 fire detectors
Alarm devices
Fire detection system
control unit
CI1142/CC1142/CC1143

Alarm reception
centre
CPU (Fire department)
T-tap

AnalogPLUS detector bus for


I4Bus
series DS1130 fire detectors Fire control
installations

Line Control
module module
Autonomous
extinguishing area

T-tap VdS periphery:


Fire department
FBF control panel
Collective detection line for FSK
series DS1100 fire detectors Fire department
HM key cabinet
Main fire alarm box

Pager system
Mains (protocol ESPA 4.4.4)

Printer

Maintenance PC

Interactive and AnalogPLUS comparison

Interactive AnalogPLUS
Algorithms can be selected for each detector ● –
Response behaviour can be selected for each detector ● ●
Detector operation monitored ● ●
Automatic self test ● –
The detector transmits any variation from the quiescent value (drift) ● ●
Application error warning by the detector ● ●
Free allocation of logical addresses ● ●
Automatic measured value compensation ● –
Multi4detector linking ● ●

Fire & Security Products


Siemens Building Technologies Group
Signal registration – Detector bus / Detection line

The control unit registers signals from automatic fire detectors, manual call points and
input modules via detector bus or detection line and carries out decentralized control
functions via output modules.
All three detector systems can be connected to the CS1140 system.

Series DS1150 Interactive fire detectors have a unique evaluating and decision logic based on algo4
rithms. They provide the highest level of detection reliability and differentiate clearly
between genuine fire and deceptive phenomena.

Series DS1130 AnalogPLUS is an addressable detector system in which detector sensitivity can be
selected centrally. Intelligent signal evaluation (alarm verification, comparison and
evaluation of signals from several detectors).

Series DS1100 Collective fire detectors with traditional technology for communication and signal eval4
uation (one address per detection line, only alarm signal). The detectors have the
same first4class sensor system as the other DS11 detectors.
Furthermore, it is possible to integrate existing parts of systems with detectors from
series MS6, MS7, MS9 and MS24.

MS7i, MS9i These addressable detection lines can be integrated as parts of existing systems.

Evaluation – Alarm – Operation – Control

Parameterization The modification of control unit organization to changed customers’ requirements is no


problem.

Control outputs Freely programmable control outputs are available for fire control installations. Driver
and/or relay outputs as required.

Real time clock Automatic summer/winter switchover by means of an integrated real time clock. With
its own emergency power supply.

Event memory Up to 1000 events can be arranged, stored and recalled chronologically and accord4
ing to message category.

Emergency operation Emergency operation functions are integrated in the important function modules.
As a result, the system can continue to signal fire even if a component malfunctions.

Extinguishing activation An extinguishing section can be activated via the EExtinguishing" control module.
Several extinguishing sections can be activated from one control unit.

System flexibility The structure of the C4Bus network permits the connection of several control units and
control consoles. These stations can be mounted in the same housing or in separate
housings. The location is chosen according to where it is easiest for operation or
installation.
However, the fire detection system can be extended even further. Several C4Bus net4
works can be combined to a danger management system by means of the data link
ECerloop/Cerban".

Fire & Security Products


Siemens Building Technologies Group
Expansion up to a complex fire detection system

Control console CPU Control unit


CT1142 CC1142/CC1143

Maximum 16 stations can be connected to


the C4Bus (length of C4Bus max. 1800m):
C4Bus − up to 4 CPUs (CI1142/CC1143)
− up to 12 control consoles (CT1142)
− 1 Gateway (CK1142)

Control unit Gateway Gateway


CI1142 CK1142
CPU

Cerloop/Cerban

Gateway Danger
(further management
C4Bus network) system

ÁÁÁÁÁÁÁÁÁÁ
Types of control units (CPU)

ÁÁÁÁÁÁÁÁÁÁ CI1142 CC1142 CC1143

ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Number of detectors up to 800 up to 1000 up to 2000

ÁÁÁÁÁÁÁÁÁÁ
Number of line and control up to 16 up to 16 up to 16
modules

ÁÁÁÁÁÁÁÁÁÁ
Control console

ÁÁÁÁÁÁÁÁÁÁ
permanently built4in and additionally
mounted in separate housing
built4in and/or mounted
in separate housing

ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Metal housing, type H38G200 H38G300 H47... H67... H98...

ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Dimensions WxHxD [mm]

ÁÁÁÁÁÁ ÁÁÁÁÁÁ 515x602x100 515x602x155 434x735x300 434x1130x300 600x2012x300

ÁÁÁÁÁÁ

Fire & Security Products


Siemens Building Technologies Group
Operation

1
Cerberus® CT11
2
FIRE BRIGADE called Total:05
ALARM 01 AUTOM. FIRE DETECTOR
building 10
1st floor room 105
05 MANUAL CALL POINT
building 10
1st floor staircaise
F1: function F2: detail C: end

Acknowledge
3
Reset

Information Isolation Alarms Faults 7 8 9 F1


Premises Alarm device Alarm device Alarm device
manned off active fault 4 5 6 F2
Alarm delay Remote alarm Remote alarm Remote transmission
off off active fault 1 2 3 ok
Detector test Control function System System
mode off on fault 0 C

Illuminated keys enable clear, guided operation even in an emergency.


Function and recall commands which cannot be carried out by means of separate
keys, can be selected using menus accessed via plain text display.
Operating access is via password or key.

Illuminated alarm panel (1) When an alarm event is received the red text EALARM" lights up.

Plain language display (2) Automatic plain text information on events, event location, counter4measures as well
as operating mode and operator infos is displayed on the large liquid crystal display
(LCD).
The LCD background lights up red for alarm and yellow for fault and operating
functions.
The display mode complies with EN54: 2 alarm events can be displayed simulta4
neously on the LCD.

Messages A user text is displayed for each event to provide precise location information.
User texts are prepared for each specific system.
Standard texts are available for type of signal, infos on operation etc.
Even special language symbols can be indicated on LCD without difficulty.

Counter–measures text An individual counter4measures text can be allocated to each zone.


When an event occurs, the texts are displayed upon command.
In each control unit (CPU), up to 16 freely4programmable counter4measures texts are
available.

Alarm scroll key (3) If several events are signalled, the information can be recalled one4by4one.

Indicator fields (4) 4 categories of messages: Information, Isolation, Alarms and Faults.

Emergency operation Emergency operation is a permanent component of the control console. This ensures
operation, which complies with standards, even if the processor in the control console
is malfunctioning.

Fire & Security Products


Siemens Building Technologies Group
Interfaces

The control console has interfaces for:


− parallel indicators and/or mimic display panels
− logging printer and/or pager system
− external key switch

Line length up to 1000m / max. 8 addresses

Control
console

Parallel
indicators
Printer Pager Mimic display panel(s)
system

Control consoles available

B3Q460 B3Q480 B3Q560


International Nordic Asian

Auxiliary equipment

Information Fire department Operating unit Parallel indicators


Cover module control panel „Extinguishing” (24JxJ2 LEDs)
H23B010 H23B040 B3Q321 B3Q440 B3R051

Options

Plexiglass door Inscriptions sets


Control consoles in H26G... / Inscriptions for dis4
H28G... housings which are play and operating
particularly exposed can be elements are pro4
fitted with a lockable Plexi4 vided separately on
glass door to prevent tam4 strips for insertion.
pering. These are available
in more than 20 lan4
guages.

Fire & Security Products


Siemens Building Technologies Group
Mounting possibilities of control consoles

Metal housing H28G200

520

300
Auxiliary
Auxiliary equipment
equipment
70
Control
Door H28T130
console
Metal housing with fire plan
H28G200 with compartment
door H28T110
Mounted in metal housing H28G200 with door.
Installation possibility for auxiliary equipment.

Plastic housing 125 Standard application in the attractive plastic


H23G230 housing. Installation of auxiliary equipment in a
H23G230, H26G220 separate plastic housing.
366

H26G220

219
Auxiliary
equipment
76
Control
console

Control unit housings Housing


H47G...

Door
H47T...

Built into the door of the control unit. Installation of the control console and auxiliary
Possibility of installing auxiliary equipment. equipment with adapter plate in any 19" housing.

Fire & Security Products


Siemens Building Technologies Group
Technical data

Control unit CI1142/CC1142/CC1143 CT1142


Control console Key module
− B3Q460 − KABAJ8 #100 (option)
− B3Q480 − Nordic fire department lock
built4in
Protection category
(EN60529 / IEC529)
− in housing H38/H47/H67/H98 IP40 −
− in housing H26G220 − IP52
− in housing H28G200 − IP40
Colour
− housing H38/H47/H67/H98 RAL7035 light grey −
− housing H26G220 − Pantone 421 grey
− housing H28G200 − RAL7035 light grey
− door H28T... − 1E110 dark grey
− front surface − Pantone 421 grey
− keys/display panel − Pantone 424, 427 grey
Operating temperature 0...+50°C 0°...+50°C
Storage temperature −20...+60°C −20°...+60°C
Humidity max. 95%, max. 95%,
no condensation no condensation
(IEC7214343, class 3K5) (IEC7214343, class 3K5)
Standards EN5442, EN5444 EN5442

Bus / Detection line Interactive AnalogPLUS Collective


DS1150 DS1130 DS1100
Number of addresses up to 128 up to 128 1
Number of wires 2 2 2
Network structure Master/Slave Master/Slave –
Loop line yes yes no
Short circuit proof yes yes no
T4tap yes yes no

E Siemens Building Technologies AG


8 Subject to change

Fire & Security


Document no. Products
e1335c Catalogue S11
Siemens Building Technologies Group
Edition 12.2001 Section 7

You might also like