Professional Documents
Culture Documents
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
Transformer Connections
Overcurrent Protection
Directional Protection of Parallel Transformers
Earth Faults on Transformer Windings
Transformer Connections
A2
EP
A1
A2
EP
A1
a2
ES
a1
A2
IP
EP
A1
a2
ES
a1
IS
Transformer Connections
a a2
A
C1
A2
a1
c1
C2
C B1
A2
B2
A1 a1
B1
C
C2
9
C1
b1
c1
A1
B2 B
a2
b2
c2
b1
b2
c2
c
a
Phase displacement
Yy0
Dd0
Zd0
Phase displacement
Yy6
Dd6
Dz6
Yd1
Dy1
Yz1
Yd11
Dy11
Yz11
Group 1
0
Group 2
180
Group 3
30
Group 4
30
10
Transformer Connections
A Phase
Windings
B Phase
Windings
C Phase
Windings
A2
B2
C2
A1
Low
Voltage
Windings
a1
a2
B1
b1
b2
C1
c1
c2
Dy 11
12
11
30
12
Dy 11
a
A Line Designation
30
13
Dy 11
14
Dy 11
15
Dy 11
a2
A2
a1
c1 b1
C2
16
A1
B1
B2
c2
B
b2
Dy 11
A2
B2
17
C2
A1
a1
a2
B1
b1
b2
C1
c1
c2
18
Fuse
kVA
Full load
current (A)
Rated
current (A)
Operating time at
3 x rating(s)
100
5.25
16
3.0
200
10.5
25
3.0
300
15.8
36
10.0
500
26.2
50
20.0
1000
52.5
90
30.0
1500/5
51
50
1MVA
3.3/0.44kV
51
N
64
19
1500/5
51
N
50
N
1000/5
5MVA
11/3.3kV
51
N
64
1000/5
3.3kV
20
Overcurrent Protection
21
Requirements
Fast operation for primary short circuits
Discrimination with downstream protections
Operation within transformer withstand
Non-operation for short or long term overloads
22
HV
Source
LV
50
51
50 set to 1.2 - 1.3 x through fault level
23
Transient Overreach
Concerns relay response to offset waveforms (DC
transient)
Definition
I 1 - I2
x 100
I2
I2
D.C
.
I1
24
I1 = Steady state
rms
pick up
current
I2 = Fully offset
rms
pickup
current
51
51
51
HV2
HV1
LV
HV1
HV2
Time
LV
IF(LV)
IF(HV)
1.2IF(LV)
25
Curren
t
I3
I3
0.866 I 3
I3
26
HV relay
0.4 sec
LV relay
0.866 I3
27
I3
Parallel Transformers
Directional Relays (1)
51
67
Grid supply
Feeders
51
67
51
28
51
Parallel Transformers
Directional Relays (2)
51
51
Grid supply
Bus
Section
Feeders
51
51
29
51
30
IP
PR
Protective
Relay
IF
3
> Transformer Protection
2
3
.I FL
. I FL
31
. I FL
Star Side
0.8
IF
0.7
0.6
51
0.5
Overcurrent
Relay
0.4
0.3
Delta Side
0.2
0.1
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
p.u..
Star Side
IF
7
6
51
Overcurrent
Relay
4
3
Delta Side
2
1
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
p.u..
33
IF
9
8
7
6
IP
IN
IP
5
4
3
2
IN
34
p.u..
I=
I
2
3
Differential
Relay
Setting = IS
35
Thus 59% of
20%
41%
30%
28%
40%
50%
17%
7%
51N
51 51 51
36
51N
51 51 51
51N
Protected
Zone
REF
LV restricted E/F
protection trips
both HV and LV breaker
Recommended setting : 10%
rated
39
40
Source
Protected zone
REF
RCT
RCT
RL
IF
RL
IS
VS
RL
ZM
RST
R
RL
VS = IF (RCT + 2RL)
A very high voltage develops across the relay circuit and the CTs.
Causes damage to insulation of CT, secondary winding and
relay.
Magnitude of peak voltage VP is given by an approximate formula
(based on experimental results)
VP = 2 2VK (VF - VK)
Where VF = Swgr. Fault Rating in amps x Z of relay circuit
CT ratio
43
RST
VM
VS
RR
Metrosil Characteristic
V = CI
1MVA
(5%)
11000V
415V
1600/1
RCT = 4.9
Calculate :
1) Setting voltage (VS)
80MVA
2) Value of stabilising
resistor required
3) Effective setting
1600/1
RCT =
4.8
RS
2 Core 7/0.67mm
(7.41/km)
100m Long
45
MCAG14
IS = 0.1
Amp
4) Peak voltage
developed by CTs
for internal fault
Solution (1)
Earth fault calculation :Using 80MVA base
Source impedance = 1 p.u.
Transformer impedance = 0.05 x 80 = 4 p.u.
1
Total impedance = 14
1 P.U.
1
p.u.
4
I1 = 1 = 0.0714 p.u.
14
I1
4
I2
4
I0
Sequence Diagram
46
= 111296 Amps
IF
= 3 x 0.0714 x 111296
= 23840 Amps (primary)
= 14.9 Amps (secondary)
Solution (2)
47
Solution (3)
Weber/m2 (Tesla)
(multiply by Kv to obtain RMS
secondary volts)
1.6
1.2
0.8
0.4
0.04
0.08
0.12
AT/mm
(multiply by Ki to obtain total
exciting current in Amps)
48
Kv
Ki
Line &
Neutral CT
158
0.341
Earth CT
236
0.275
Solution (4)
(3) Effective setting IP = CT ratio x (IS + IMAG)
Line & Neutral CTs
Flux density at 93.6V = 93.6 = 0.592 Tesla
158
From graph, mag. Force at 0.592 Tesla = 0.015 AT/mm
Solution (5)
(4)
50
Parallel Transformers
T1
N A B C
Bus Section
T2
415 Volt
Switchboard
51
Parallel Transformers
CT in Earth
N A BC
T1
51N
Bus Section
Open
T2
51N
52
415 Volt
Switchboard
Parallel Transformers CT in
Earth and Neutral
N A BC
T1
51N
Bus Section
Open
T2
51N
53
415 Volt
Switchboard
Parallel Transformers
Residual Connections
NA BC
T1
F2
Bus section
Will maloperate if bus section is open
for fault at F1 T2
F1
51 50
200/5
10MVA
33/11kV
51
N
600/5
64
600/5
5/5A
55
87
Differential Protection
56
Differential Protection
Overall differential protection may be justified for
larger transformers (generally > 5MVA).
Provides fast operation on any winding
Measuring principle :
Based on the same circulating current principle as the
restricted earth fault protection
However, it employs the biasing technique, to maintain
stability for heavy through fault current
Differential
Current
I1
BIAS
BIAS I
2
I1 - I2
OPERATE
I1 - I2
RESTRAIN
OPERATE
I1 + I2
2
58
Mean Through
Current
Differential Protection
PROTECTED ZONE
HV
LV
Differential Connections
P1
P2
A2
A1
60
a1
a2
P2
P1
Use of Interposing CT
P1
S1
P2
A2
A1 a1
P1
S2
S1 P1
R
R
R
Interposing CT provides :
Vector correction
Ratio correction
Zero sequence compensation
> Transformer Protection
P2
S2
S2
61
a2
P2
S1
15MVA
66kV / 11kV
A2
A1 a1
a2
800/5
P2
P1
S2
S2
S1
Dy1
150/5
P1
S1
P2
A2
A1 a1
a2
P2
S2
P1
S2
4.37A
4.92A
S1
S2 P1
(2.56)
S1
P2
(5)
R
R
= 62.7 kV
= 138 Amp
Secondary current
= 4.6 Amp
64
1200:5
B
C
800:5
175/145/30 MVA
230/115/13.8 kV
YNynd1
230kV
+5%/-15%
19 taps
2000:5
c
Grounding
transformer
inside the
protection zone
a
a
B
b
B
c
B
Yd11 software
interposing CT
Ydy0 software
interposing CT
Ydy0 software
interposing CT
65
P645
66
(5 15 )
2
230 = 218 .5kV
100
100
IFLC,HV
175 10 6
=
= 462 .41A
3 218 .5 103
IFLC,TV
175 106
=
= 7321 .47 A
3
3 13.8 10
IFLC,LV
175 10 6
=
= 878.58 A
3
3 115 10
K amp ,HV
Inom,HV
800
=
=
= 1.730
IFLC,HV 462 .41
K amp ,TV =
67
Inom,LV
2000
=
= 0.273
IFLC,LV 7321 .47
K amp ,LV
Inom,LV
1200
=
=
= 1.366
IFLC,LV 878 .58
2
nominal MVA, tap 1
Idiff/Inom
1.5
66.7% of nominal MVA, tap 1
66.7% of nominal MVA, tap 19
0.5
0
0
68
0.5
1.5
2
Ibias/Inom
2.5
3.5
1200:5
1200:5
a
A
a
b
a
B
P643
69
70
Connections Check
Arbitrary Current Distribution
P1
S1
P2
A2
A1 a1
P1
S2
R
R
R
P2
S2
S2
71
a2
S1
P1
P2
S1
Connections Check
Add Delta Winding Current
P1
S1
P2
A2
A1 a1
P1
S2
R
R
R
P2
S2
S2
72
a2
S1
P1
P2
S1
Connections Check
Complete Primary Distribution
P1
S1
P2
A2
A1 a1
P1
S2
R
R
R
P2
S2
S2
73
a2
S1
P1
P2
S1
Connections Check
Complete Secondary Distribution
P1
S1
P2
A2
A1 a1
P1
S2
R
R
R
P2
S2
S2
74
a2
S1
P1
P2
S1
P2
A1
A2
a1
a2
P2
P1
S2 S1
S2 S1 T2 T1 P1 P2
75
P1
P2
A1
A2
a1
P2
P1
S2 S1
S2 S1 P1 P2
76
EARTHING
TRANSF.
900/1
TO DIFFERENTIAL
RELAY
77
EARTHING
TRANSF.
300/1
1/0.33
TO DIFFERENTIAL
RELAY
78
A2
a2
P1
P2
S1
P1
S1
S2
P2
REF
P2
S2
P1
S1
S2
To differential relay
79
Restricted earth
fault relay
64
Bias windings
87
80
87
87
Differential relay
operating windings
T1
PHASE a
PHASE b
PHASE c
A
A
G
T1
G G
BEF
T2
T3
J
T4
Rb
2
H H H
Rb
2
Rb
2
Ro
Ro
Ro
OVERALL DIFFERENTIAL
RELAY
81
300/5
63MVA
132KV
25MVA
11KV
1600/5
50MVA
33KV
1000/5
4.59
5.51
10.33
2.88
2.88
Yd11(+30)
R
R
Interposing CT provides :
Vector correction
Ratio correction
Zero sequence compensation
83
Numeric
Relay
Ratio
correction
Vectorial
correction
Virtual interposing CT
84
Differential
element
Virtual interposing CT
Transformer Magnetising
Characteristic
Twice
Normal
Flux
Normal
Flux
Normal
No Load
Current
No Load Current
at Twice Normal
Flux
85
+ m
Im
- m
86
Im
2m
87
88
89
90
91
Protection of Auto-Transformer by
High Impedance Differential Relays
(a) Earth Fault Scheme
A
B
C
87
92
High impedance
relay
Protection of Auto-Transformer by
High Impedance Differential Relays
(b) Phase and Earth Fault Scheme
A
B
C
a
b
c
87 87 87
n
93
94
Inter-Turn Fault
CT
E
Load
Shorted
turn
- 11,000 / 240
- 11,000 / 1
- 1 / 11,000
95
10
Fault current in short
circuited turns
80
Fault current
(multiples of
rated current)
60
6
Primary input current
40
20
0
5
10
15
20
25
96
Primary current
(multiples of
rated current)
3 x internal pipe
diameter (minimum)
Conservator
5 x internal pipe
diameter (minimum)
Oil conservator
3 minimum
Transformer
97
Buchholz Relay
Petcock
Counter balance
weight
Alarm bucket
Mercury switch
Oil level
To oil
conservator
From transformer
Trip bucket
Aperture adjuster
Drain plug
98
Deflector plate
Overfluxing Protection
99
Overfluxing
Generator transformers
Grid transformers
Usually only a problem during run-up or shut down, but can be
caused by loss of load / load shedding etc.
Flux V
f
Effects of overfluxing :
V = kf
2m
CAUSES
Low frequency
High voltage
Geomagnetic disturbances
EFFECTS
101
Ie
V K
f
Trip and alarm outputs for clearing prolonged overfluxing
Alarm : Definite time characteristic to initiate corrective action
Trip : IDMT or DT characteristic to clear overfluxing condition
Settings
Pick-up 1.5 to 3.0 i.e.
102
V/Hz Characteristics
Enables co-ordination with plant withstand characteristics
t = TMS
(M - 1)2
10000
t=TMS/(M-1)2
1000
100
TMS = 12
TMS = 8
10
TMS= 4
TMS = 2
TMS = 1
1
1.05
1.15
1.25
1.35
1.45
1.55
M = (V/f)/Setting
P4283ENa
103
Overfluxing Relay
Ex
VT
AVR
104
R
L
Circuit breaker
position repeat relay
RL1-1
VAA relay
Lower AVR
DC
DC
Inhibit AVR
raise
Alarm
RL2-1
Alarm
RL2-2
105
106
110
50
100
150
200
Hottest Spot Temperature (C)
107
250
Overheating Protection
Trip
I load
Alarm
TD
setting
Top oil of
power
transformer
On
Fan
control
I load
Off
On
Pump
control
Off
Temp. indication
Heater
Local
Thermal
replica
108
Temperature
sensing resistor
Remote
Overload Protection
Current based
Flexible characteristics
Single or dual time constant
Reset facility
Non-volatile
Time
Current
109
Thermal Overload
Dual Characteristic (1)
Trip time (s)
10000
Single
characteristic:
= 120 mins
1000
Dual
characteristic
100
10
110
2
3
4
5
6
Current (multiple of thermal setting)
Single
characteristic:
= 5 mins
q
P
IREF
TripTime = ln
2
I K q
TRIP
I REF
where
qP
qTRIP
= trip threshold
Thermal Overload
IEEE Std. C57.91-1995 (1)
Oil exponent
Top oil
time constant
Top oil
Temperature
Hot spot
Temperature
Square of current
112
TO
I2
Coolant (oil/air)
Temperature a
R
m
a
Winding time
constant
Winding
exponent
=
H
TO
spot
Transformer Feeders
114
Protection of Parallel
Transformer Feeders
Higher voltage
busbar
Z
OC
OC
FTS
FTS
REF
REF
DP
DP
Bh
Bh
WT
WT
REF
DOC
REF
SBEF
2 stage
SBEF
2 stage
OC
OC
Load
115
Lower voltage
busbar
Load
DOC
CTs
CTs
HV LV
CTs
CTs
TRIP
Feeder
Differential
Protection
PILOTS
Feeder
Differential
Protection
Transformer
Differential
Protection
UNSTABILISE
TRIP
TRIP
116
Transformer Feeders
FEEDER
PW
PILOTS
PW
117
P1
S1
P2
P2
S2
23
24
25
26
27
28
II
ii
III
iii
MCTH
MBCI
27
28
MFAC
14
19
17
17
PILOTS
18
19
18 17
19
1
+ MVTW
02
13
14
-
118
S1
A
B
C
17
19
23
24
25
26
27
28
S2
MCTH 23
17
P1
MBCI
18
24
25
26
27
28
23
24
25
26
27
28
Power transformer
P540
Scheme
Ratio
correction
Vectorial
correction
Virtual interposing CT
119
Virtual interposing CT