VIRTUAL CONSTRUCTION

CHITTAGONG, BANGLADESH.

Concrete Test Laborator


CONCRETE TEST REPORT

Name of the Test


Aparatus Description

: Compressive Strength Test for CYLINDER.


: Wekob, 2153 Nwu Wulmstovt Bahnhofstr. 1; West Ger
Range:- 0-1500 kN SI. No. 884112
: y=1.012x+8.0368 ( BRTC/TEST/CE/2011/1213 Dt. 25/0
:Base Slab(Section A2), Nasirabad Reservoir.
: 1(Cement) : 1.725(Sand: FM-2.5) : 1.75(Stone:20mm
: Signed

Calibration Equation
Location
Mixing Ratio
Sample

Sample
Description

Diameter of
Cylinder
(mm)

Height of
Cylinder
(mm)

Date of
Casting

Date of
Crushing

Dial Gauge
Reading, x
(KN)

150

300

7-Dec-11

14-Dec-11

390

150

300

7-Dec-11

14-Dec-11

400

150

300

7-Dec-11

14-Dec-11

360

150

300

7-Dec-11

14-Dec-11

380

150

300

7-Dec-11

14-Dec-11

400

150

300

7-Dec-11

14-Dec-11

380

Name of the Test


Aparatus Description
Result

Test performed by:

: Slump Test
: Cone (Bottom dia 200mm, Upper dia 100mm, Height
: 150 mm

Md. Monir Hossain


Laboratory Technician, KWSP-C-3(Reservoir)
KOLON Engineering & Construction Ltd.
Date:

Witnessed by:

Md. Arif Ullah


Inspector, KWSP-C-3 (Reservoir)
NJS-BETS Consultants.
Date:

file name: concrete test report format

A. M. M. Maruful Haque
Inspector, KWSP-C-3 (Reservoir)
NJS-BETS Consultants.
Date:

L CONSTRUCTION LTD

TTAGONG, BANGLADESH.

rete Test Laboratory

NCRETE TEST REPORT


Date:

14-Dec-11

vt Bahnhofstr. 1; West Germany

EST/CE/2011/1213 Dt. 25/09/2011)

M-2.5) : 1.75(Stone:20mm Down) : 1 (Stone: 12 mm Down)

Actual
Reading, y
(KN)

Strength
Mpa(psi)

402.72

22.79 (3303.99)

412.84

23.36 (3387.02)

372.36

21.07 (3054.91)

392.60

22.21 (3220.97)

412.84

23.36 (3387.02)

392.60

22.21 (3220.97)

Upper dia 100mm, Height 300mm)

Requested by:

Average
Strength
Mpa(psi)

Result

22.40 (3248.64)

Satisfactory

22.60 (3276.32)

Satisfactory

Jayanta Sarkar
Engineering Incharge Concrete, Nasirabad Site.
KOLON Engineering & Construction Ltd.
Date:

Witnessed & Approved by:

Mr. Maximo L. Bugarin


Construction Specialist, KWSP.
NJS Consultants Co. Ltd.
Date:

Sample, 1
X= 390 KN
Y= 1.012x+8.0368= 402.7168
Dia of Cylinder d= 150 mm

P=

F/A= Y/((d)^2*3.142/4)=

22786.15

KN/m= 22.7862 Mpa=

23358.76

KN/m= 23.3588 Mpa=

21068.35

KN/m= 21.0684 Mpa=

22213.55

KN/m= 22.2136 Mpa=

23358.76

KN/m= 23.3588 Mpa=

22213.55

KN/m= 22.2136 Mpa=

Sample, 2
X= 400 KN
Y= 1.012x+8.0368= 412.8368
Dia of Cylinder d= 150 mm

P=

F/A= Y/((d)^2*3.142/4)=

Sample, 3
X= 360 KN
Y= 1.012x+8.0368= 372.3568
Dia of Cylinder d= 150 mm

P=

F/A= Y/((d)^2*3.142/4)=

Sample, 4
X= 380 KN
Y= 1.012x+8.0368= 392.5968
Dia of Cylinder d= 150 mm

P=

F/A= Y/((d)^2*3.142/4)=

Sample, 5
X= 400 KN
Y= 1.012x+8.0368= 412.8368
Dia of Cylinder d= 150 mm

P=

F/A= Y/((d)^2*3.142/4)=

Sample, 6
X= 380 KN
Y= 1.012x+8.0368= 392.5968
Dia of Cylinder d= 150 mm

P=

F/A= Y/((d)^2*3.142/4)=

-3303.99 psi

-3387.02 psi

-3054.91 psi

-3220.97 psi

-3387.02 psi

-3220.97 psi