FIRE - Fire Sprinkler Hydraulics Calculation Program


pReJkEr Class nr 666

Elite Software Development, Inc.


TRIO MALL Page 2

General Project Data Report


General Data
Project Title:
Designed By:
Code Reference:
Client Name:
Address:
Company Name:
Company Address:
Phone:
Building Name:
Contact at Building:

TRIO MALL
SINNEMAR CONTRACTING
NFPA-13
ALI MOHAMED DAKHAN
KUWAIT
SINNEMAR

Project File Name:


Date:
Approving Agency:
Phone:
City, State Zip Code:
Representative:
City And State:

TRIO MALL

Building Owner:
Phone at Building:

trio.fiw
January 01, 2014
KFD

Project Data
Description Of Hazard:
Design Area Of Water Application:
Default Sprinkler K-Factor:
Inside Hose Stream Allowance:
In Rack Sprinkler Allowance:

Ordinary 1
1500
5.60
0.00
0.00

ft
K
gpm
gpm

Sprinkler Specifications
Make:
Size:

Sprinkler System Type:


Wet
Maximum Area Per Sprinkler:
130 ft
Default Pipe Material:
SCHED 40 WET STEEL
Outside Hose Stream Allowance:
0.00 gpm

Model:
Temperature Rating:

0 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID:
Hydrant Elevation:
Test Flow Rate:
Calculated System Flow Rate:
Available Inflow Residual Pressure:

Date Of Test:
0
0.00
809.50
0

ft
gpm
gpm
psi

Static Pressure:
Test Residual Pressure:
Calculated Inflow Residual Pressure:

0.00 psi
0.00 psi
61.75 psi

Calculation Project Data


Calculation Mode:
HMD Minimum Residual Pressure:
Number Of Active Nodes:
Number Of Active Pipes:
Number Of Active Sprinklers:

Active Version 6.0.179

Demand
13.50 psi
22
21
14

Minimum Desired Flow Density:


Number Of Inactive Pipes:
Number Of Inactive Sprinklers:

1000 Pipe Capacity

0.15 gpm/ft
0
0

Wednesday, January 01, 2014

FIRE - Fire Sprinkler Hydraulics Calculation Program


pReJkEr Class nr 666

Elite Software Development, Inc.


TRIO MALL Page 3

Fire Sprinkler Input Data


Node Input Data
Sprinkler
KFactor (K)

Pressure
Estimate (psi)

Node
Elevation
(feet)

Non-Sprinkler
Discharge
(gpm)

Sprinkler

5.50

13.50

10.00

0.00

Sprinkler

5.50

14.83

10.00

0.00

Sprinkler

5.50

19.83

10.00

0.00

No Discharge

N/A

24.49

10.00

0.00

Sprinkler

5.50

22.40

10.00

0.00

Sprinkler

5.50

16.79

10.00

0.00

Sprinkler

5.50

15.30

10.00

0.00

No Discharge

N/A

26.15

10.00

0.00

Sprinkler

5.50

23.92

10.00

0.00

10

Sprinkler

5.50

17.95

10.00

0.00

11

Sprinkler

5.50

16.37

10.00

0.00

12

No Discharge

N/A

27.69

10.00

0.00

13

Sprinkler

5.50

25.24

10.00

0.00

14

Sprinkler

5.50

18.47

10.00

0.00

15

Sprinkler

5.50

20.82

0.00

0.00

16

No Discharge

N/A

30.54

10.00

0.00

17

No Discharge

N/A

57.67

10.00

0.00

18

Sprinkler

32.00

65.06

-10.00

0.00

19

No Discharge

N/A

57.81

10.00

0.00

20

No Discharge

N/A

63.40

-3.00

0.00

21

Sprinkler

32.00

69.42

-20.00

0.00

22

No Discharge

N/A

61.75

2.00

0.00

Node No.

Node Description

Active Version 6.0.179

Area Group

1000 Pipe Capacity

Wednesday, January 01, 2014

FIRE - Fire Sprinkler Hydraulics Calculation Program


pReJkEr Class nr 666

Elite Software Development, Inc.


TRIO MALL Page 4

Fire Sprinkler Input Data


Pipe Input Data
Nominal
Diameter
(inch)

Type
Group

Nominal
Length
(feet)

Fitting
Length
(feet)

SCHED 40 WET STEEL

1.000

10.00

0.00

10.00

120

SCHED 40 WET STEEL

1.000

10.00

0.00

10.00

120

SCHED 40 WET STEEL

1.250

15.00

0.00

15.00

120

SCHED 40 WET STEEL

1.250

6.00

0.00

6.00

120

SCHED 40 WET STEEL

1.000

10.00

0.00

10.00

120

SCHED 40 WET STEEL

1.000

10.00

0.00

10.00

120

SCHED 40 WET STEEL

2.000

10.00

0.00

10.00

120

SCHED 40 WET STEEL

1.250

6.00

0.00

6.00

120

10

SCHED 40 WET STEEL

1.000

10.00

0.00

10.00

120

10

11

SCHED 40 WET STEEL

1.000

10.00

0.00

10.00

120

12

SCHED 40 WET STEEL

2.500

10.00

0.00

10.00

120

12

13

SCHED 40 WET STEEL

1.250

6.00

0.00

6.00

120

13

14

SCHED 40 WET STEEL

1.000

10.00

0.00

10.00

120

12

16

SCHED 40 WET STEEL

3.000

30.00

0.00

30.00

120

16

17

SCHED 40 WET STEEL

4.000

60.00

1010.00

1070.00

120

17

18

SCHED 40 WET STEEL

4.000

60.00

0.00

60.00

120

17

19

SCHED 40 WET STEEL

6.000

12.00

0.00

12.00

120

19

20

SCHED 40 WET STEEL

6.000

12.00

0.00

12.00

120

20

21

SCHED 40 WET STEEL

4.000

60.00

0.00

60.00

120

19

22

SCHED 40 WET STEEL

6.000

20.00

0.00

20.00

120

14

15

SCHED 40 WET STEEL

1.000

10.00

0.00

10.00

120

Beg.
Node

End.
Node

Pipe Description

Active Version 6.0.179

Fitting
Data

99ET

1000 Pipe Capacity

Total
CFactor
Length (gpm/inch(feet)
psi)

Wednesday, January 01, 2014

FIRE - Fire Sprinkler Hydraulics Calculation Program


pReJkEr Class nr 666

Elite Software Development, Inc.


TRIO MALL Page 5

Fire Sprinkler Output Data


Overall Node Groupings Output Data
Pipe Segment
Beg.
End.
Node
Node

Pipe
Type
Group

Pipe
Flow Rate
(gpm)

Sprinkler Flow
At Beg. Node
(gpm)

Non-Sprinkler Flow
Out (+)
In (-)
(gpm)
(gpm)

Beg. Node
Residual
Pressure (psi)

Imbalance
Flow At Beg.
Node (gpm)

-20.21

20.21

0.00

0.00

13.50

0.00000

2
2

1
3

0
0

20.21
-41.39

21.18

0.00

0.00

14.83

0.00001

3
3

2
4

0
0

41.39
-65.88

24.49

0.00

0.00

19.83

0.00003

4
4
4

3
5
8

0
0
0

65.88
70.07
-135.95

0.00

0.00

0.00

24.49

0.00000

5
5

4
6

0
0

-70.07
44.05

26.03

0.00

0.00

22.40

0.00005

6
6

5
7

0
0

-44.05
21.51

22.53

0.00

0.00

16.79

0.00001

-21.51

21.51

0.00

0.00

15.30

0.00000

8
8
8

4
9
12

0
0
0

135.95
72.46
-208.41

0.00

0.00

0.00

26.15

0.00000

9
9

8
10

0
0

-72.46
45.55

26.90

0.00

0.00

23.92

0.00006

10
10

9
11

0
0

-45.55
22.25

23.30

0.00

0.00

17.95

0.00001

11

10

-22.25

22.25

0.00

0.00

16.37

0.00001

12
12
12

8
13
16

0
0
0

208.41
76.36
-284.77

0.00

0.00

0.00

27.69

0.00000

13
13

12
14

0
0

-76.36
48.73

27.63

0.00

0.00

25.24

0.00006

14
14

13
15

0
0

-48.73
25.10

23.64

0.00

0.00

18.47

0.00002

15

14

-25.10

25.10

0.00

0.00

20.82

0.00001

16
16

12
17

0
0

284.77
-284.77

0.00

0.00

0.00

30.54

0.00000

17
17
17

16
18
19

0
0
0

284.77
258.12
-542.89

0.00

0.00

0.00

57.67

-0.00002

18

17

-258.12

258.12

0.00

0.00

65.06

0.00138

19

17

542.89

0.00

0.00

0.00

57.81

0.00001

Active Version 6.0.179

1000 Pipe Capacity

Wednesday, January 01, 2014

FIRE - Fire Sprinkler Hydraulics Calculation Program


pReJkEr Class nr 666

Elite Software Development, Inc.


TRIO MALL Page 6

Fire Sprinkler Output Data


Overall Node Groupings Output Data (cont'd)
Pipe Segment
Beg.
End.
Node
Node

Pipe
Type
Group

Pipe
Flow Rate
(gpm)

Sprinkler Flow
At Beg. Node
(gpm)

Non-Sprinkler Flow
Out (+)
In (-)
(gpm)
(gpm)

Beg. Node
Residual
Pressure (psi)

Imbalance
Flow At Beg.
Node (gpm)

19
19

20
22

0
0

266.61
-809.50

20
20

19
21

0
0

-266.61
266.61

0.00

0.00

0.00

63.40

-0.00001

21

20

-266.61

266.61

0.00

0.00

69.42

0.00134

22

19

809.50

0.00

0.00

-809.50

61.75

Active Version 6.0.179

1000 Pipe Capacity

Wednesday, January 01, 2014

FIRE - Fire Sprinkler Hydraulics Calculation Program


pReJkEr Class nr 666

Elite Software Development, Inc.


TRIO MALL Page 7

Fire Sprinkler Output Data


Overall Pipe Output Data
Beg.
End.
Node

Nodal
KFactor
(K)

Elevation
(feet)

Spk/Hose
Discharge
(gpm)

Nom. Dia.
Residual
Inside Dia.
Pressure
C-Value
(psi)

Q (gpm)
Velocity
(fps)

F. L./ft
(psi/ft)
Fittings
Type-Grp

Pipe-Len.
Fit-Len.
Tot-Len.
(ft)

PF-(psi)
PE-(psi)
PV-(psi)

1
2

5.50
10.00
20.21
5.50
10.00
21.18
SCHED 40 WET STEEL

13.50
14.83

1.00
1.049
120

20.21
7.50

0.13271
----0

10.00
0.00
10.00

1.327
0.000
0.379

2
3

5.50
10.00
21.18
5.50
10.00
24.49
SCHED 40 WET STEEL

14.83
19.83

1.00
1.049
120

41.39
15.36

0.49991
----0

10.00
0.00
10.00

4.999
0.000
1.589

3
4

5.50
10.00
24.49
0.00
10.00
0.00
SCHED 40 WET STEEL

19.83
24.49

1.25
1.380
120

65.88
14.13

0.31070
----0

15.00
0.00
15.00

4.660
0.000
1.344

4
5

0.00
10.00
0.00
5.50
10.00
26.03
SCHED 40 WET STEEL

24.49
22.40

1.25
1.380
120

70.07
15.03

0.34833
----0

6.00
0.00
6.00

2.090
0.000
1.521

5
6

5.50
10.00
26.03
5.50
10.00
22.53
SCHED 40 WET STEEL

22.40
16.79

1.00
1.049
120

44.05
16.35

0.56096
----0

10.00
0.00
10.00

5.610
0.000
1.799

6
7

5.50
10.00
22.53
5.50
10.00
21.51
SCHED 40 WET STEEL

16.79
15.30

1.00
1.049
120

21.51
7.99

0.14897
----0

10.00
0.00
10.00

1.490
0.000
0.429

4
8

0.00
10.00
0.00
0.00
10.00
0.00
SCHED 40 WET STEEL

24.49
26.15

2.00
2.067
120

135.95
13.00

0.16596
----0

10.00
0.00
10.00

1.660
0.000
1.137

8
9

0.00
10.00
0.00
5.50
10.00
26.90
SCHED 40 WET STEEL

26.15
23.92

1.25
1.380
120

72.46
15.54

0.37054
----0

6.00
0.00
6.00

2.223
0.000
1.626

9
10

5.50
10.00
26.90
5.50
10.00
23.30
SCHED 40 WET STEEL

23.92
17.95

1.00
1.049
120

45.55
16.91

0.59702
----0

10.00
0.00
10.00

5.970
0.000
1.925

10
11

5.50
10.00
23.30
5.50
10.00
22.25
SCHED 40 WET STEEL

17.95
16.37

1.00
1.049
120

22.25
8.26

0.15858
----0

10.00
0.00
10.00

1.586
0.000
0.459

8
12

0.00
10.00
0.00
0.00
10.00
0.00
SCHED 40 WET STEEL

26.15
27.69

2.50
2.469
120

208.41
13.97

0.15395
----0

10.00
0.00
10.00

1.540
0.000
1.313

12
13

0.00
10.00
0.00
5.50
10.00
27.63
SCHED 40 WET STEEL

27.69
25.24

1.25
1.380
120

76.36
16.38

0.40836
----0

6.00
0.00
6.00

2.450
0.000
1.806

13
14

5.50
10.00
27.63
5.50
10.00
23.64
SCHED 40 WET STEEL

25.24
18.47

1.00
1.049
120

48.73
18.09

0.67640
----0

10.00
0.00
10.00

6.764
0.000
2.203

18.47

1.00

25.10

0.19813

10.00

1.981

14

5.50

Active Version 6.0.179

10.00

23.64

1000 Pipe Capacity

Wednesday, January 01, 2014

FIRE - Fire Sprinkler Hydraulics Calculation Program


pReJkEr Class nr 666

Elite Software Development, Inc.


TRIO MALL Page 8

Fire Sprinkler Output Data


Overall Pipe Output Data (cont'd)
Beg.
End.
Node

Nodal
KFactor
(K)

Elevation
(feet)

Spk/Hose
Discharge
(gpm)

Nom. Dia.
Residual
Inside Dia.
Pressure
C-Value
(psi)

Q (gpm)
Velocity
(fps)

F. L./ft
(psi/ft)
Fittings
Type-Grp

Pipe-Len.
Fit-Len.
Tot-Len.
(ft)

PF-(psi)
PE-(psi)
PV-(psi)

15

5.50
0.00
25.10
SCHED 40 WET STEEL

20.82

1.049
120

9.32

----0

0.00
10.00

-4.330
0.584

12
16

0.00
10.00
0.00
0.00
10.00
0.00
SCHED 40 WET STEEL

27.69
30.54

3.00
3.068
120

284.77
12.36

0.09524
----0

30.00
0.00
30.00

2.857
0.000
1.028

16
17

0.00
10.00
0.00
0.00
10.00
0.00
SCHED 40 WET STEEL

30.54
57.67

4.00
4.026
120

284.77
7.18

0.02536
99ET
0

60.00
1010.00
1070.00

27.130
0.000
0.347

17
18

0.00
10.00
0.00
32.00
-10.00
258.12
SCHED 40 WET STEEL

57.67
65.06

4.00
4.026
120

258.12
6.51

0.02114
----0

60.00
0.00
60.00

1.268
-8.660
0.285

17
19

0.00
10.00
0.00
0.00
10.00
0.00
SCHED 40 WET STEEL

57.67
57.81

6.00
6.065
120

542.89
6.03

0.01137
----0

12.00
0.00
12.00

0.136
0.000
0.245

19
20

0.00
10.00
0.00
0.00
-3.00
0.00
SCHED 40 WET STEEL

57.81
63.40

6.00
6.065
120

266.61
2.96

0.00305
----0

12.00
0.00
12.00

0.037
-5.629
0.059

20
21

0.00
-3.00
0.00
32.00
-20.00
266.61
SCHED 40 WET STEEL

63.40
69.42

4.00
4.026
120

266.61
6.72

0.02245
----0

60.00
0.00
60.00

1.347
-7.361
0.304

19
22

0.00
10.00
0.00
0.00
2.00
0.00
SCHED 40 WET STEEL

57.81
61.75

6.00
6.065
120

809.50
8.99

0.02382
----0

20.00
0.00
20.00

0.476
3.464
0.544

Active Version 6.0.179

1000 Pipe Capacity

Wednesday, January 01, 2014

FIRE - Fire Sprinkler Hydraulics Calculation Program


pReJkEr Class nr 666

Elite Software Development, Inc.


TRIO MALL Page 9

Fire Sprinkler Output Data


Overall Sprinkler Output Data
Flowing
Sprinkler
Node No.

Sprinkler
KFactor (K)

Sprinkler
Elevation
(feet)

Flowing
Density
(gpm/ft)

Sprinkler
Discharge
(gpm)

1
Sub Totals For Non-Group

5.50

10.00

13.50

130.00
130.00

0.155
0.155

20.21
20.21

2
Sub Totals For Non-Group

5.50

10.00

14.83

130.00
130.00

0.163
0.163

21.18
21.18

3
Sub Totals For Non-Group

5.50

10.00

19.83

130.00
130.00

0.188
0.188

24.49
24.49

5
Sub Totals For Non-Group

5.50

10.00

22.40

130.00
130.00

0.200
0.200

26.03
26.03

6
Sub Totals For Non-Group

5.50

10.00

16.79

130.00
130.00

0.173
0.173

22.53
22.53

7
Sub Totals For Non-Group

5.50

10.00

15.30

130.00
130.00

0.165
0.165

21.51
21.51

9
Sub Totals For Non-Group

5.50

10.00

23.92

130.00
130.00

0.207
0.207

26.90
26.90

10
Sub Totals For Non-Group

5.50

10.00

17.95

130.00
130.00

0.179
0.179

23.30
23.30

11
Sub Totals For Non-Group

5.50

10.00

16.37

130.00
130.00

0.171
0.171

22.25
22.25

13
Sub Totals For Non-Group

5.50

10.00

25.24

130.00
130.00

0.213
0.213

27.63
27.63

14
Sub Totals For Non-Group

5.50

10.00

18.47

130.00
130.00

0.182
0.182

23.64
23.64

15
Sub Totals For Non-Group

5.50

0.00

20.82

130.00
130.00

0.193
0.193

25.10
25.10

18
Sub Totals For Non-Group

32.00

-10.00

65.06

130.00
130.00

1.986
1.986

258.12
258.12

21
Sub Totals For Non-Group

32.00

-20.00

69.42

130.00
130.00

2.051
2.051

266.61
266.61

1820.00

0.445

809.50

Area Group
Code

Residual
Flowing Area
Pressure
(ft)
(psi)

Totals For All Groups

Active Version 6.0.179

1000 Pipe Capacity

Wednesday, January 01, 2014

FIRE - Fire Sprinkler Hydraulics Calculation Program


pReJkEr Class nr 666

Elite Software Development, Inc.


TRIO MALL Page 10

Fire Sprinkler Output Summary


Hydraulically Most Demanding Sprinkler Node
HMD Sprinkler Node Number:
HMD Actual Residual Pressure:
HMD Actual GPM:

1
13.50 psi
20.21 gpm

Sprinkler Summary
Sprinkler System Type:
Specified Area Of Application:
Minimum Desired Density:
Application Average Density:
Application Average Area Per Sprinkler:
Sprinkler Flow:
Average Sprinkler Flow:

Wet
1500.00
0.150
0.540
107.14
809.50
57.82

ft
gpm/ft
gpm/ft
ft
gpm
gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 13 - 14 )
Maximum Velocity Pressure ( In Pipe 13 - 14 )
Allowable Maximum Nodal Pressure Imbalance:
Actual Maximum Nodal Pressure Imbalance:
Actual Average Nodal Pressure Imbalance:
Actual Maximum Nodal Flow Imbalance:
Actual Average Nodal Flow Imbalance:

18.09 ft/sec
2.20 psi
0.0001
0.0001
0.0000
0.0014
0.0001

psi
psi
psi
gpm
gpm

Overall Network Summary


Number Of Unique Pipe Sections:
Number Of Flowing Sprinklers:

21
14

Pipe System Water Volume:

65.88 gal

Sprinkler Flow:
Non-Sprinkler Flow:
Total System Demand Flow:

809.50 gpm
0.00 gpm
809.50 gpm

Minimum Required Residual Pressure At System Inflow


Node:
Demand Flow At System Inflow Node:

Active Version 6.0.179

61.75 psi
809.50 gpm

1000 Pipe Capacity

Wednesday, January 01, 2014

FIRE - Fire Sprinkler Hydraulics Calculation Program


pReJkEr Class nr 666

Elite Software Development, Inc.


TRIO MALL Page 11

Fire Sprinkler Output Data


Hydraulic Supply/Demand Graph

100
90
80

Pressure psi

70
60
50
40
30
20
10
0

0
1

10

Flowrate(x100) gpm

Adjusted Hydrant Data


Static Pressure: 0 psi
Test Residual Pressure: 0 psi
Test Flow Rate: 0 gpm

Demand Point Data


Calculated Residual Pressure: 61.75 psi
Calculated Flow Rate: 809.50 gpm
Excess Available Inflow Residual Pressure: -61.75 psi

Active Version 6.0.179

1000 Pipe Capacity

Wednesday, January 01, 2014