 Electrical Specifications

Model

DVP10SX11R/T

Item

DVP08SM11N

DVP08SN11R/T

DVP08SP11R/T

MC

DVP16SP11R/T

1
4

Power supply voltage

MPU: 24V DC (-15% ~ 20%) (with DC input reverse polarity protection),


Expansion Unit: supplied by the MPU

Fuse

2A / 250V AC

Power Consumption

1W

1.5W

1.5W

at 500 V DC (Between all inputs / outputs and earth)

>5M

Noise Immunity

ESD: 8KV Air Discharge


EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz~1GHz, 10V/m

MC

The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N
(All DVP units should be grounded directly to the ground pole).

Environment

Operation: 0C ~ 55C (temperature), 50 ~ 95% (humidity), Pollution degree 2;


Storage: -25C ~ 70C (temperature), 5 ~ 95% (humidity); D/A output operation: 0C ~ 50C
(temperature)

Vibration / Shock
Resistance

Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
64

88 / 68

MC
1

Grounding

138 / 133

Power supply for AC loads

Power Circuit Protection Fuse (3A)

Power On pilot indicator

Emergency stop
The machinery must provide a quick manual method
disconnecting all system power.

Circuit isolation device (System Power Disconnect)


Utilize the electromagnetic contactor and the relay to be the
isolation unit of the power circuit to prevent the possible
instability of the system when the power is supplied on and off.

DVP PLC MPU (main processing unit)

Grounding

Power supply:
AC: 100 ~ 240V AC, 50/60Hz
DC: 24V DC

2W

Insulation Resistance

Weight (approx.) (g)

G uard
Limit

5W

devices, therefore the breakdown of either one device would consequently be detrimental to the whole auto
control system, and danger will thus be resulted. Please use the recommended wiring below for the power
input:

 Electrical Specifications

90 / 70

96 / 76

N
7

The input signal of the input point is the DC power DC input. There are two modes of DC type wiring: SINK and
SOURCE, defined as follows:

Approvals

SA/SX/SC PLC

 /

 OPEN TYPE/

 Input Point Wiring


Sink = Current flows into the common terminal S/S


DVP DVP-SX 10 4DI+2DO+2AI+2AO SA/SX/SC
2CH 12-bit / 2CH 12-bit /
/ 2

Sinkin g

Electrical Specification of Input Point

Electrical Specification of Output Point

Input Type

DC (SINK or SOURCE)

Output Type

Relay-R

Input Current

24V DC 5mA

Current
Specification

1.5A/1 point
(5A/COM)

0.3A/1 point @ 40C; When the output of Y0


and Y1 is high-speed pulse, Y0 and Y1 =
30mA

Voltage
Specification

Below 250V
AC, 30V DC

30V DC

Active Level

Off
On,
X0,X1: above 18.5V DC
X2,X3: above 16.5V DC

Loop Equivalent Circuit of Input Point

75VA
(Inductive)

Maximum
Loading

90 W
(Resistive)

Responding
Time

When the output of Y0 and


Y1 is high-speed pulse, Y0
and Y1 = 0.9W (Y0 = 32kHz,
Y1 = 10kHz)

9W/1 point

About 10 ms

DVP10SX11R

24V
DC
+20%
-15%

Point
DI AI

DVP10SX11T

4
4

10

SINK
+5V

+24V

S/S

OV

S/S

X0

X1

X2

3 PLC

24VDC

X0

Sink Type

Loop Equivalent Circuit of Input Point

Wiring Loop

Output

Type
DI

24G

DC Type
(DC Signal IN)

SINK Mode

Input

mm

24VDC

Off On 20us Y0 and Y1 are specified


On Off 30us points for high-speed pulse

 Model Name & I/O Configuration


Power

Wiring Loop

+24V

About 10ms (An


adjustment range of 0 ~ 20
ms could be selected
through D1020 and D1021)

Model

S/S
So urcing

On Off,
X0~X3 below 8V DC
Responding
Time

Transistor-T
X0

Point
AI

DO AO

-20 ~ 20mA
2
2
DC24V/5 mA range(-1,000 ~ +1,000)
Sink or Source
-10 ~ +10V
2
range(-2,000 ~ +2,000) 2

Warning

ENGLISH

wiring, troubleshooting and peripherals. Other detail information about programming and commands is compatible
with SA/SC/SX series; please see PLC Application Manual. For more information about the optional peripheral,
please see individual product manual.
 This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the
enclosure, so as to avoid the hazard to users and the damage to the PLC.
 Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the PLC.
Check all the wiring prior to power up. To avoid any electromagnetic noise, make sure the PLC is properly
grounded
. DO NOT touch terminals when power on.

+24 V

24VDC

AO

Relay

Resistor

-20 ~ 20mA
(range:-2,000 ~ +2,000)
-10 ~ +10V
(range:-2,000 ~ +2,000)

DC Type
(DC Signal IN)

17
18
19
20
21
22

24 G

SOUR CE
+5V

+24V

S/ S

OV

S/S

X0

X1

X2

24VD C

X0

Source Type

DVP-**-**-11-R

3.1 PLC Mounting Arrangements and Wiring Notes

1. There are two kinds of DVP-SX Series PLC output


modules: Relay and Transistor. For relevant electrical
specification, please refer to the function specification.
2. Be careful with the connection of the common
terminals when wiring outputs. For example, when
wiring DVP12SX11R, output terminal Y0 uses one
common terminal C0, Y1 uses C1, as shown below:

L O AD
Y0

Installation of the DIN rail:

When installing the DVP series

The DVP-PLC can be secured to a cabinet by using the

PLC, make sure that it is

DIN rail that is 35mm high with a depth of 7.5mm. When

installed in an enclosure with

mounting the PLC on the DIN rail, be sure to use the

sufficient space (as shown

end bracket to stop any side-to-side motion of the PLC,

below) to its surroundings so as

thus to reduce the chance of the wires being pulled

to allow heat dissipation.

LED

RY

Thank you for choosing DELTAs PLC DVP series. The DVP-SX series is a 10-point (4DI+2DO+2AI+2AO)

and gently push up the clip. To remove it, pull down the

special main processing unit. Besides the same commands and functions as DVP-SA/SX/SC series, 2-CH

retaining clip and gently pull the PLC away from the DIN

12-bit analog voltage/current input and 2-CH 12-bit analog voltage/current output are all bipolar. There is

rail. As shown on the right:

P OW E R
C0

R E LAY O UT P U T

LOAD

D
D

DV P
MP

C0 Y0 C1 Y1

Y0

T
R
G

LED

<0.3A

Action indication: When the output point is active, the


corresponding indicator at the front will be on.
3. Isolated circuit: The optical coupler is used to isolate
signals between PLC internal circuits and input
modules.

C0

TRANSISTOR OUTPUT

D > 50 mm

built-in 2-digit 7-segment display corresponds to internal register directly to display PLC station or
Wiring:

 Product Profile and Outline

22-16AWG

1
2
3
4
5
6
7
8
9
Units: mm

10
11
12

13
Battery replacement: Please change the battery within 3 minutes, or the 14
internal data of the PLC (including the program area, RTC and latched
15
registers) could be lost or destroyed.
16
17
18
19
20
21
22

Status indicator: POWER, RUN,


ERROR, BAT.LOW
RUN/STOP switch
2-digital 7-segment display
Digital I/O terminal
DIN rail clip
Analog I/O terminals
I/O point indicators
COM1 (RS-232) (Rx) indicator
COM2 (RS-485) (Tx) indicator
COM1 (RS-232)
Communication port (Slave)
Nameplate
Expansion port
Mounting hold of the expansion
unit
DIN rail (35mm)
Expansion unit clip
COM2 (RS-485)
Communication port
DC Power input
2 pin removable terminal
(standard accessory)
Power input cable
(standard accessory)
Battery Cover
Battery socket connection
Battery mount

< 1.5mm

1. Please use 22-16AWG (1.5mm) wiring (either single or multiple core) for
I/O wiring terminals. The specification for the terminals is as shown on
the left. PLC terminal screws should be tightened to between 1.95
kg-cm (1.7 in-lbs). Use 60/75C copper conductor only.
2. I/O signal wires or power supply should not run through the same
multi-wire cable or conduit.

 Analog Input/Output Point Wiring


Note 1:
Voltage input
-10V~+10V

CH0

100K
V+
I+
COM

*3

CH0

250

100K

Shielded*1
AG

3.2 Wiring Notes

Current input
-20mA~+20mA

 Power Input Wiring

24VDC OV

S/ S X0

X1

X2

V+
I+
COM

Shielded*1

*5

voltage output
-10V~+10V

AC drive, recorder,
scale valve...

AC drive, recorder,
scale valve...

CH1

250

100K
AG

CH0

shielding cable *1

current output
-20mA~20mA

20.4V~28.8V

100K

CH1
*2

DVP-SX series input power supply is DC input. Please take a note of listed items when operating DVP-SX.
Series.
1. Please make sure the power is at terminals 24V DC and 0V (power range is 20.4V DC ~ 28.8V DC). When
voltage is lower than 20.4V DC, PLC will stop operating, all outputs will turn Off and ERROR LED will flash
continuously.
2. If the power-off time is less than 10ms, the PLC still operates unaffectedly. If the power-off time is too long or
the power voltage drops, the PLC will stop operating and all the outputs will be Off. Once the power is
restored, the PLC will return to operate automatically. (There are latched auxiliary relays and registers
inside of the PLC, please be aware when programming.)

CH1

V+
I+
COM

CH0

V+
I+
COM

CH1

shielding cable *4

DC Input Type
2A

terminal of
power module

DC /DC

5V

DC24V

class 3 grounding
(100 or less)

 Safety Wiring
Since the PLC is in control of numerous devices, motion of either one device could affect the motion of other

24+
24-

DC/DC
converter

DVP10SX11R/T DVP08SM11N DVP08SN11R/T DVP08SP11R/T DVP16SP11R/T

24V DC-15% ~ 20%

2A/250V AC

5W
1W
1.5W
1.5W
2W

5M / 500V DC

DVP-**-**-11-T

To secure the PLC to the DIN rail, place it onto the rail

user-defined code.

 Output Point Wiring

 Installation & Wiring

loose. At the bottom of the PLC is a small retaining clip.

 Introduction

11
12
13
14
15
16

Type
DO

SOURCE Mode

 This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation &

RUN/STOP
2
I/O
DIN

2
3
4
5
6
7

X0

S/S

I/O
/
COM1 (RS-232)
(Rx)
COM2 (RS-485)
(Tx)
COM1 (RS-232)
(Slave)

DIN (35mm)

COM2 (RS-485)
(Master/Slave)

2 pin

Source = Current flows out of common terminal S/S

+15V
AG
-15V

Please isolate analog input and other power


wiring.
Note 2:
If input signal is in current, please short out
between V+ and I+ terminals.
Note 3:
If the noise interference from loaded input wiring
terminal is significant, please connect a
capacitor with 0.1 ~ 0.47F 25V for noise
filtering.
Note 4:
Please isolate analog output and other power
wiring.
Note 5:
If the noise interference from loaded input wiring
terminal is significant, please connect a
capacitor with 0.1 ~ 0.47F 25V for noise
filtering.
Note 6:
Please connect
power module terminal and
analog output module terminal to system
earth point and make system earth point be
grounded or connects to machine cover.
Warning:
DO NOT wire to the No function terminal

/
/
, g

ESD: 8KV Air Discharge


EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz ~ 1GHz, 10V/m

L,N PLC
0C ~ 55C50 ~ 95% 2
-25C ~ 70C5 ~ 95%D/A 0C ~ 50C
IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC68-2-27 (TEST Ea)
138 / 133

64

SINK SOURCE

24V DC 5mA

Off On,

X0
X2

X1 18.5V DC
X3 16.5V DC

On Off,
X0~X3 8V DC

10ms D1020 D1021

0 ~ 20ms

I/O

DVP10SX11R
DVP10SX11T

24VDC
+20%
-15%

-T
@ 40C
5A/COM 0.3A/1
, Y0Y1 30mA

250V AC,30V DC

90W
10 ms

30V DC

75VA

DI

9W/1

Off On 20us
On Off 30us

Y0Y1 0.9W
Y050KHzY110KHz
Y0Y1

AI
-20 ~ 20mA

DC24V/5 mA (
Sink Source
(

96 / 76

-R
1.5A/1

90 / 70


DI AI

88 / 68

-1,000 ~ +1,000)
-10 ~ +10V
-2,000 ~ +2,000)

DO AO
2

DO

AO

~ 20mA
(-20-2,000
~ +2,000)
~ +10V
(-10-2,000
~ +2,000)


3.1

DVP-**-**-11-R

35mm DIN
PLC
PLC
PLC
PLC

PLC

Y0

PLC

DIN

LED

1.

LOAD

DV P
MP

22-16AWG (1.5mm)
PLC 1.95kg-cm (1.7 in-lbs)
60/75C
2.

-1 0V~+10 V

*2

*1

S/S

X0

X1

10 0K

*5

X2

...

5V

-10V~+10V

CH0
CH0

V+
I+
COM

*1

CH1

*4

DC24V

PLC
(DVPPS01/DVPPS02)



MC
1

8
2

MC
1





N
7

CH 1

25 0

AG

10 0K
V+
I+
COM

10 0K

CH1

-20mA~ +20mA

-20mA~20mA

2A

Guard
Limit

CH 0

25 0

AG

20.4V~ 28.8 V

DC/DC

V+
I+
COM

*1

10 0K

CH0
*3

24V DC 0V 20.4V DC ~ 28.8V DC 20.4V DC PLC


OffERROR LED
10ms PLC PLC
OffPLC PLC

MC

1.

24 VDC OV

(3A)

DVPPS01/DVPPS02

(AC)100 ~ 240V AC, 50/60Hz


(DC)24V DC

DC DC SINK SOURCE
Sink = S/S
Source = S/S

V+
I+
COM

CH1

3.

2
V+ I+

0.1 ~ 0.47 F 25V


4

0.1 ~ 0.47F 25V


6

24+
24 -

DC/DC

+15V
AG
-15V

DC Signal IN

SA/SX/SC PLC

 OPEN TYPE/
:

 /


DVP DVP-SX 10 4DI+2DO+2AI+2AO SA/SX/SC
2CH 12-bit / 2CH 12-bit /
/ 2

2
3
4
5
6
7

mm

10

3 PLC

11
12
13
14
15

+5V

+24V

X0

SINK

SINK

OV

S/S

X0

X1

X2

24V DC
Sink Ty pe

16

DC Signal IN

+24 V

24 G

19
X0

18

SOUR CE
+5V

S/ S

SOURCE

17

24VDC

+24V

OV

S/S

X0

X1

X2

24 VDC
Sourc e Ty pe

MC

2W

18.5V DC
16.5V DC

On Off,
X0~X3
8V DC

DVP10SX11R

24V DC
+20%
-15%

N
7


96 / 76

DC DC SINK SOURCE
Sink = S/S
Source = S/S
S/S

X0

Sinking

-T
0.3A/1 @ 40C
, Y0Y1 30mA

S/S
Sourcing

X0

30V DC

75VA

 I/O

90 / 70

90W
10 ms

10ms D1020 D1021

0 ~ 20ms

5A/COM

250V AC,30V DC

9W/1

MC


L

-R
1.5A/1

Y0 Y1
0.9W(Y0 50KHz Y1 10KHz)
Y0Y1

Off On 20us
On Off 30us

+2 4V

24V D C
24 G

(DC Signal IN)

SINK
+5V

+24V

S/ S

DI

AI

DO AO

-20 ~ 20mA

DC24V/5 mA
Sink Source

-1,000 ~ +1,000 2
-10 ~ +10V
-2,000 ~ +2,000 2

2
2

DO

AO

-20 ~ 20mA

-2,000~ +2,000
-10 ~ +10V

-2,000~ +2,000

20
21
22

RUN/STOP
2
I/O
DIN
I/O
/
COM1 (RS-232)
(Rx)
COM2 (RS-485)
(Tx)
COM1 (RS-232)
(Slave)

DIN (35mm)

COM2 (RS-485)
(Slave)

2 pin

24 G

S OUR CE
+5 V

+24V

< 1.5mm

1.

2.

POWER
C0

2.

2.

LOAD

DV P
MP

Y0

T
R
G

LE D

<0.3A

PLC

DVP10SX11R Y0
C0 Y1 C1

/ 22-16 AWG (1.5mm)


PLC 1.95kg-cm (1.7 in-lbs) 60/75C

TRANSIS TOR OUTPUT

-10V~+10V

CH0
*3

*1

100K
V+
I+
COM

CH0

250
100K
AG

CH1
*2

-2 0mA~+2 0mA

*1

100K
V+
I+
COM

CH1

250
100K
AG

*5

-10V~+10V

CH0

*1

V+
I+
COM

CH0

V+
I+
COM

CH1

20 .4V ~2 8.8 V

-2 0mA~20mA
24VDC OV

S/ S

X0

X1

DC/DC

CH1

X2

2A
5V

...

PLC
DVPPS01/DVPPS02

*4

DC2 4V

24+
24 -

DC/DC

PLC

C0 Y0 C1 Y1

C0

...

X2

DVP-**-**-11-T

24V DC 0V 20.4V DC ~ 28.8V DC 20.4V DC PLC


OffERROR LED
10ms PLC PLC
OffPLC PLC

X1


1.

RELAY OUTPUT

3.2
SX

X0

1. DVP-S
Y0

RY

D > 50 mm

22-16AWG

S/S

Source Type

LOAD

OV

24VDC

X0

DVP-**-**-11-R

PLC

PLC

X2

35mm DIN
PLC
PLC
PLC PLC

PLC

X1

24V D C

3.1
DIN

X0

+ 24V

(DC Signal IN)

LED

S/S

Sink Ty pe

SINK

OV

24 V DC

X0

SOURCE

+24V

S/S

88 / 68

Guard
Limit

24G

64

Off On,

X0, X1
X2, X3

DVP10SX11T

24VDC

138 / 133

24V DC 5mA

L,N PLC
0C ~ 55C50 ~ 95% 2
-25C ~ 70C5 ~ 95%D/A 0C ~ 50C
IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC68-2-27 (TEST Ea)

SINK SOURCE

DVP16SP11R/T

S/S
Sourcing

/
/
, g

S/S

Sinking

X0


MC
4

ESD: 8KV Air Discharge


EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz~1GHz, 10V/m

DI AI

X0

S/S

DVP10SX11R/T DVP08SM11N DVP08SN11R/T DVP08SP11R/T

24V DC-15% ~ 20%)

2A / 250V AC

5W
1W
1.5W
1.5W

5M / 500V DC

PLC

(3A)

DVPPS01/DVPPS02

(AC)100 ~ 240V AC, 50/60Hz


(DC)24V DC


5

C0 Y0 C1 Y1

< 0. 3A

C0

TRANSISTOR OUTPUT

...

Y0

T
R
G

LED

D > 50 mm

RELAY OUTPUT

DV P-* *-**-11-T

3.2

2.

2.

< 1.5mm

SX

POWER
C0

22-16AWG

RY

PLC

PLC

DVP10SX11R Y0
C0 Y1 C1

1. DVP-S
LOAD

+1 5V
AG
-15 V

3.

2
V+ I+

0.1 ~ 0.47 F 25V


4

0.1 ~ 0.47F 25V


6