You are on page 1of 6

PHOTOVOLTAIC SYSTEM

PV SYSTEM SUMMARY:

THIS PROJECT COMPLIES WITH THE FOLLOWING:


2013 CALIFORNIA BUILDING CODE (CBC) / 2013 INTERNATIONAL BUILDING CODE (IBC)
2013 CALIFORNIA ELECTRICAL CODE (CEC) / 2013 NATIONAL ELECTRICAL CODE (NEC)
AS ADOPTED BY CITY OF ONTARIO

ROOF MOUNT RESIDENTIAL PHOTOVOLTAIC SYSTEM


SYSTEM SIZE

SITE LOCATION:

CITY NOTES:

STC: 36 X 265 = 9540W DC


PTC: 36 X 235.6 = 8481.6W DC

MODULE

36 X SUNMODULE, SW 265 MONO BLACK, 265W


MODULES

INVERTER

1 X SMA SB 5000TL-US-22 & 1 X SMA SB 3000TL-US-22


INVERTERS

ROOF

COMP TILE ROOF

TILT

R1 & R2 - 5 PITCH

AZIMUTH

R1 - 270 & R2 - 90

ALL SOLAR ENERGY SYSTEM EQUIPMENT SHALL BE SCREENED TO THE


MAXIMUM EXTENT POSSIBLE AND SHALL BE PAINTED A COLOR SIMILAR
TO THE SURFACE UPON WHICH THEY ARE MOUNTED
VISIBLE PORTIONS OF THE SOLAR PANEL SUPPORT STRUCTURE AND ANY EXPOSED
ELECTRICAL CONDUITS, BOXES AND PANELS WILL NOT BE EXPOSED, AND WILL BE
COLORED MATCHED TO EXISTING ROOF OR SURROUNDING HOME.

INSTALLATION NOTES:
THE PV BREAKER SHALL NOT EXCEED 120% OF THE ALLOWABLE BACK FEED OF THE MAIN
SERVICE BUSS RATING.
PV WIRE SHALL BE USED ON DC RUNS FOR UNGROUNDED/TRANSFORMERLESS
INVERTERS.
INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR TO COMMENCING WORK.

RAFTER/TRUSS SIZE

2" X 4" RAFTERS @ 24" O.C

ATTACHMENT TYPE

QUICK MOUNT ATTACHMENTS

UTILITY

SOUTHERN CALIFORNIA EDISON (SCE)

SITE LOCATION

HOUSE AERIAL VIEW:

TABLE OF CONTENTS
PV-1

SYSTEM SUMMARY, NOTES, SITE LOCATION AND


HOUSE AERIAL VIEW

PV-2

SITE PLAN / ROOF PLAN WITH MODULES LAYOUT

PV-3

DETAILS, MATERIAL LIST AND LABELS

PV-4

ELECTRICAL CALCULATION, EQUIP. ELEVATION &


SINGLE LINE DIAGRAM

PV-5

DATA SHEET: MODULE AND INVERTER

PV-6

DATA SHEET: MOUNT & RAIL

CLIENT:

REVISIONS:

XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx

DESCRIPTION

TITLE:

DATE:
DATE

12/22/2015

REVISION
DESIGN
BY:

XXX

JOB
NO.:

BAC-XXX

SYSTEM SUMMARY,
NIOTES, SITE
LOCATION AND
HOUSE AERIAL VIEW

SHEET:

PV-1

ROOF AREA STATEMENT


ROOF
PROPERTY LINE

1
2

3'-3"

MODULES
PITCH AZIMTUH ROOF AREA ARRAY AREA
QTY
818.87 SQ FT 421.53 SQ FT
5
270
24
644.48 SQ FT 211.97 SQ FT
12
5
90

3'

ROOF LINE

24 SUNMODULE SW 265
MONO BLACK MODULES

3'
12 SUNMODULE SW 265
MONO BLACK MODULES

EXTERNAL CONDUIT RUN


3'

ATTACHMENT POINTS
@ 48" O.C. MAX (TYP)
24 SUNMODULE SW 265
MONO BLACK MODULES

ATTACHMENT POINTS
@ 48" O.C. MAX (TYP)

JUNCTION BOX
JB

JUNCTION BOX

LC INV1 INV2

JB

MSP

12 SUNMODULE SW 265
MONO BLACK MODULES
PROPOSED MODULES

EXISTING
MSP

MSP ACD FM

R-2
11'-8"
R-1
17'-10"

SMA SB 3000TL-US
INVERTER
SMA SB 5000TL-US
INVERTER
LOAD CENTER
FINANCE METER
AC DISCONNECT
EXISTING MSP

DRIVE WAY

W 4TH ST

SITE PLAN

ROOF PLAN WITH MODULES LAYOUT

SCALE: 1/16" = 1'-0"

CLIENT:

SCALE: 3/32" = 1'-0"

REVISIONS:

XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx

DESCRIPTION

TITLE:

DATE:
DATE

2
SHEET:

12/22/2015

REVISION
DESIGN
BY:

XXX

JOB
NO.:

BAC-XXX

SITE PLAN / ROOF PLAN


WITH MODULES LAYOUT

PV-2

MATERIAL LIST

QUICK MOUNT
ATTACHMENTS

LABELS
ALL PLACARDS SHOULD BE WITH WHITE LETTERING IN RED BACKROUND WITH A MIN. OF 3/8"
LETTERING HEIGHT AND USING ARIAL OR SIMILAR FONT, NON-BOLD AND ALL CAPITAL LETTERS

PV MODULE

"L" BRACKET
MODULE
MOUNTING
RAIL

QTY

EQUIPMENT

36

SUNMODULE
SW 265 MONO
BLACK, SOLAR
MODULES

SMA, SB
5000TL-US-22
INVERTER WITH
INTEGRATED
DISCONNECT

MAX. DC INPUT VOLTAGE :


MAX. DC INPUT CURRENT :
MAX. AC OUTPUT VOLTAGE RANGE :
MAX. AC OUTPUT CURRENT :
MAX. AC POWER OUPUT :
CEC EFFICIENCY :

600V
15A
211-264V
22A
5000W
96.5%

SMA, SB
3000TL-US-22
INVERTER WITH
INTEGRATED
DISCONNECT

MAX. DC INPUT VOLTAGE :


MAX. DC INPUT CURRENT :
MAX. AC OUTPUT VOLTAGE RANGE :
MAX. AC OUTPUT CURRENT :
MAX. AC POWER OUPUT :
CEC EFFICIENCY :

600V
15A
211-264V
15A
3000W
96%

JUNCTION BOX

600VDC, NEMA 4X, UL LISTED

AC
DISCONNECT

600VAC, 60A, NEMA 3R, UL LISTED

LOAD CENTER

240VAC, 125A UL LISTED

PV BREAKER

2 POLE, 240V, 40A

METER

LGATE 101 CPF METER

70'

CONDUIT

3/4" EMT CONDUIT

66

ATTACHMENTS

QUICKMOUNTATTACHMENTS

200'

RAIL

UNIRAC

64

MID CLAMPS

16

END CLAMPS

4"

ROOF
2
SS LAG BOLT

PV-4

2" X 6" RAFTERS @ 24" O.C

ATTACHMENT DETAIL

DESCRIPTION
OPEN CIRCUIT VOLTAGE (Voc) :
MAX. POWER VOLTAGE (Vmp) :
SHORT CIRCUIT CURRENT (Isc) :
MAX. POWER CURRENT (Imp) :
PTC RATING :

LABEL: INSTALLED AC AND DC DISCONNECTS

LABEL: MAIN SERVICE PANEL EXISTING


SUBPANEL, AND EXISTING EQUIPMENT TIED INTO.
39.0V
30.8V
9.31A
8.69A
235.6V
LABEL: INSTALLED JUNCTION BOXES,
COMBINER BOXES AND GUTTER BOXES.

LABEL: INSTALLED DC JUNCTION BOX

LABEL: INSTALLED SUBPANELS AND FUSE


BOXES.
LABEL: INSTALLED INVERTER

PV MODULE
QUICK MOUNT
ATTACHMENTS

MODULE
MOUNTING RAIL
"L" BRACKET

SS LAG BOLT

ENLARGED DETAIL

LABEL: INSTALLED JUNCTION BOXES,


COMBINER BOXES AND GUTTER BOXES.

LABEL: MAIN SERVICE PANEL

LABEL: AC, DC DISCONNECT OR


OTHER DISCONNECTING MEANS.

2
W 4TH ST

CLIENT:

REVISIONS:

XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx

DESCRIPTION

TITLE:

DATE:
DATE

SHEET:

12/22/2015

REVISION
DESIGN
BY:

XXX

JOB
NO.:

BAC-XXX

DETAILS, MATERIAL
LIST AND LABELS

PV-3

ELECTRICAL CALCULATIONS:
STRING 1 CIRCUIT CURRENT CALCULATION:
2 X 12 SUNMODULE 265W MODULES
CONNECTED TO 1 SMA 5000TL kW INVERTER
MAX. INVERTER OUTPUT POWER: 5000W
NOMINAL VOLATGE: 240V
RATED OUTPUT CURRENT: 22 AMPS

4 - #10 AWG, USE-2


1 - #8 AWG, BARE COPPER GROUND

OVERCURRENT PROTECTION
22.0

1.25

BREAKER CAPACITY = 30 AMPS

4 - #10 AWG, THWN-2


1 - #8 AWG, THWN-2

STRING 2 CIRCUIT CURRENT CALCULATION:


1 X 12 SUNMODULE 265W MODULES
CONNECTED TO 1 SMA 3kW INVERTER
MAX. INVERTER OUTPUT POWER: 3000W
NOMINAL VOLATGE: 240V
RATED OUTPUT CURRENT: 15 AMPS

STRING-1
12 SUNMODULE 265W
MODULES

JUNCTION
BOX

OVERCURRENT PROTECTION
12.0

1.25

15.00 AMPS

JB

BREAKER CAPACITY = 15 AMPS

TO UTILITY
POLE

BACKFEED CALCULATION
200 X 1.2 = 240 AMPS
240 - 200 = 40 MAX. BACKFEED

27.50 AMPS

SMA 5kW
INVERTER WITH
INTEGRATED
AC/DC
DISCONNECT

AC
DC

STRING-2
12 SUNMODULE 265W
MODULES

TO ARRAY

EXISTING 200A,
240VAC, MSP

LOAD
CENTER
125A,
240V

30A, 2P
240VAC
15A, 2P
240VAC

EXISTING 200A,
240VAC
DISCONNECT

FROM UTILITY
POLE

UM

60A, AC
DISCONNECT

LGATE 101
CPF METER

FM

ROOFTOP
JUNCTION BOX

TO
LOADS
FINANCE METER
MAIN SERVICE
PANEL
FM

UM

LOAD CENTER

STRING-1
12 SUNMODULE 265W
MODULES

INVERTER

JB
JUNCTION
BOX

AC DISCONNECT

AC
DC
SMA 3kW
INVERTER WITH
INTEGRATED
AC/DC
DISCONNECT

2 - #10 AWG, THWN-2


1 - #8 AWG, COPPER GROUND

DC DISCONNECT

40A, 2POLE, PV
BREAKER

(E) GEC

3 - #8 AWG, THWN-2
1 - #8 AWG, THWN-2

2 - #10 AWG, THWN-2


1 - #8 AWG, THWN-2

FLOOR

ELECTRICAL EQUIP. ELEVATION


SCALE: NTS

SINGLE LINE DIAGRAM

SCALE: NTS

CLIENT:

REVISIONS:

XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx

DESCRIPTION

TITLE:

DATE:
DATE

1
SHEET:

12/22/2015

REVISION
DESIGN
BY:

XXX

JOB
NO.:

BAC-XXX

ELECTRICAL
CALCULATION, EQUIP.
ELEVATION & SINGLE
LINE DIAGRAM

PV-4

CLIENT:

REVISIONS:

XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx

DESCRIPTION

TITLE:

DATE:
DATE

SHEET:

12/22/2015

REVISION
DESIGN
BY:

XXX

JOB
NO.:

BAC-XXX

DATA SHEET:
MODULE & INVERTER

PV-5

CLIENT:

REVISIONS:

XXX XXXX
1111, XXX STREET
XXXXX, CA XXXX
Tel: (xxx) xxx xxxx

DESCRIPTION

TITLE:

DATE:
DATE

SHEET:

12/22/2015

REVISION
DESIGN
BY:

XXX

JOB
NO.:

BAC-XXX

DATA SHEET:
MOUNT & RAIL

PV-6