UNITECH MACHINES LIMITED

COMPLIANCE REPORT
M/s NTPC Comments through letter ref: CC:9575151:1018 , Dated: 12/10/2012

DOC. No. 9575-151-PVI-G-069 on Rev-00, I/O LIST


S.No.

M/s NTPC comments

UML Resolution

1.

Separate signals shall be provided


for Battery-Chager-1 and BatteryCharger-2

Noted & Revised

2.

For all diesel engine operated


pumps, ON feedback, OFF
feedback, lube oil pressure low,
engine over speed and cooling
water temp. high shall also be
included in I/O list.

Noted & incorporated

For all battery and battery chargers,


analog signals like charger voltage,
charger current, battery voltage etc
shall be provided and alarm signals
like battery fuse blown, battery
charger I/P out of range, battery
charger surge protection failure etc
shall also be provided.

Noted & incorporated

Separate signals shall be provided


for battery charger-1 and battery
charger-2.

Noted & Revised

Analog signals for LT incomer like


current and voltage shall also be
included in the list.

Noted & incorporated

Signals from flow switch shall also


be considered in I/O list.

Digitally signed
Signature Not
Verified
by sujeet
kumar

Noted &

Date: 2012.11.05
18:05:12 IST
incorporated
Reason: CAT I
Location:
NTPCEOC

I/O List of PLC System


Project
Client
Vendor
Package
NTPC Doc. No.
S. No.

: 2 X 660 MW, MOUDA, STPP STAGE II


: M/s. NTPC
: Unitech Machines Limited
: FIRE DETECTION & PROTECTION SYSTEM
: 9575-151-PVI-G-069

Tag No.

Drive No.

Date:- 12.10.2012
UML DOC. NO.-P308-I-038
REV-01

Description

Location

Interfacing

Annunciatio

Signal
Form

Signal/
Contact Type

MCC

DI

NO

MCC

DI

NC

MCC

DI

NO

1
1

Signal Source

DI

AI

DO

n IN OWS

Booster Pump House

A
1

Booster Pump -1 MCC feeder on feedback

Booster Pump -1 MCC feeder off feedback

Booster Pump-1 MCC feeder Disturbance

Booster Pump-1 emergency stop command from field

EPBS

DI

NC

Booster Pump-1 Start command from PLC

PLC

DO

NO

Booster Pump-1 Stop command from PLC

PLC

DO

NC

BP-M-01

Booster Pump House

Booster Pump-1 Overload Trip Operated

NTPC MCC

UML

NTPC MCC

MCC

DI

NO

YES

PT-102

Booster Pump-1 Running

PT

AI

4 to 20 mA

YES

PT-101

Booster Pump-1 motor start/ fail to start *

PT

AI

4 to 20 mA

YES

10

PLC

YES

Booster Pump -1 selected in the manual mode

11

Booster Pump DE MCC feeder On feedback

NTPC MCC

MCC

DI

NO

12

Booster Pump DE MCC feeder Off feedback

NTPC MCC

MCC

DI

NC

13

Booster pump lube oil pressure low from DECP

EP

DI

NO

14

Booster Pump engine overspeed from DECP

EP

DI

NO

15

Booster pump cooling water temp. high from DECP

EP

DI

NO

16

Booster Pump-1 DE fuel oil tank level low from DECP

EP

DI

NO

17

Booster Pump-1 engine start failure from DECP

EP

DI

NO

18

Booster Pump-1 control supply healthy from DECP

DECP-01

DI

NO

19

DI

NO

Booster Pump-1 main control relay feedback from


DECP
Booster Pump-1 local/remote selection from DECP

DECP-01

20

DECP-01

DI

NO

21

Booster Pump-1 Stop command from DECP

DECP-01

DI

NC

22

Booster Pump-1 Start command from PLC

PLC

DO

NO

23

Booster Pump-1 Stop command from PLC

PLC

DO

NC

24

Booster Pump-1 Running annunciation in DECP

PLC

DO

NO

25

Booster Pump fail to start annunciation in DECP

PLC

DO

NO

UML

YES

YES

26

PT-103

Booster Pump diesel engine start/ fail to start*

PT

AI

4 to 20 mA

27

PT-104

Booster Pump Running

PT

AI

4 to 20 mA

PLC

29

FS-101

Booster Pump BP-M-01 start

30

FS-101

Booster Pump BP-M-01 / BP-DE-01 fails to start

31

32

33

34

35
36

28

Booster Pump selected in the manual mode

YES

FS

DI

NO

Float Cum Boost Charger-1 Fail/Trip

UML

BC-1

DI

NO

Float Cum Boost Charger-1 DC over voltage

UML

BC-1

DI

NO

UML

BC-2

DI

NO

Float Cum Boost Charger-2 DC over voltage

UML

BC-2

DI

NO

Battery under voltage

UML

BC-1

DI

NO

Battery earth fault

UML

BC-1

DI

NO

37

Battery Isolated

UML

BC-1

DI

NO

38

Charger - trouble

UML

BC-1

DI

NO

39

Battery on load

UML

BC-1

DI

NO

40

Battery fuse blown

UML

BC-1

DI

NO

41

Battery charger I/P out of range

UML

BC-1

DI

NO

42

Battery charger surge protection failure

UML

BC-1

DI

NO

43

Battery charger voltage

UML

BC-1

AI

4-20mA

BP-DE-01

Booster Pump House Float Cum Boost Charger-2 Fail/Trip

Page 2 of 5

AO

Remark

I/O List of PLC System


Project
Client
Vendor
Package
NTPC Doc. No.
S. No.

: 2 X 660 MW, MOUDA, STPP STAGE II


: M/s. NTPC
: Unitech Machines Limited
: FIRE DETECTION & PROTECTION SYSTEM
: 9575-151-PVI-G-069

Tag No.

Drive No.

Date:- 12.10.2012
UML DOC. NO.-P308-I-038
REV-01

Description

Location

Interfacing

Signal Source

Signal
Form

Signal/
Contact Type

Annunciatio
DI

AI

DO

n IN OWS

44

Battery charger current

UML

BC-1

AI

4-20mA

45

Battery voltage

UML

BC-1

AI

4-20mA

46

Battery under voltage

UML

BC-2

DI

NO

47

Battery earth fault

UML

BC-2

DI

NO

48

Battery Isolated

UML

BC-2

DI

NO

49

Charger - trouble

UML

BC-2

DI

NO

50

Battery On load

UML

BC-2

DI

NO

51

Battery fuse blown

UML

BC-2

DI

NO

52

Battery charger I/P out of range

UML

BC-2

DI

NO

53

Battery charger surge protection failure

UML

BC-2

DI

NO

54

Battery charger voltage

BC-2

AI

4-20 mA

55

Battery charger current

BC-2

AI

4-20 mA

56

Battery voltage

BC-2

AI

4-20 mA

1
1

Total

37

11

Foam Pump House

B
1

Foam Pump - 1 MCC feeder on feedback

Foam Pump - 1 MCC feeder off feedback

FP-M-01

Foam Pump House

MCC

DI

NO

MCC

DI

NC

Foam Pump-1 MCC feeder Disturbance

MCC

DI

NO

Foam Pump-1 emergency stop command from field

EPBS

DI

NC

PLC

DO

NO

PLC

DO

NC

MCC

DI

NC

YES

PT

AI

4 to 20 mA

YES

PLC

YES

NTPC MCC

Foam Pump-1 Start command from PLC


Foam Pump-1 Stop command from PLC

UML

Foam Pump-1 Overload Trip Operated

PT-F-01

Foam Pump-1 Running signal/ Fail to start*


Foam Pump - 1 selected in the manual mode

1
1

10

Foam pump DE MCC ON feedback

NTPC MCC

MCC

DI

NO

11

Foam pump DE MCC OFF feedback

NTPC MCC

MCC

DI

NC

12

Booster pump lube oil pressure low from DECP

EP

DI

NO

13

Booster pump engine overspeed from DECP

EP

DI

NO

14

Booster pump cooling water temperature high from


DECP

EP

DI

NO

EP

DI

NO

15

Foam Pump-1 DE fuel oil tank level low from DECP

YES

16

Foam Pump-1 engine start failure from DECP

EP

DI

NO

17

Foam Pump-1 control supply healthy from DECP

DECP-01

DI

NO

18

Foam Pump-1 main control relay feedback from DECP

DECP-01

DI

NO

19

Foam Pump-1 local/remote selection from DECP

DECP-01

DI

NO

20

Foam Pump Stop command from DECP

DECP-01

DI

NO

21

Pump running annunciation in DECP

PLC

DO

NO

22

Pump fail to start annunciation in DECP

PLC

DO

NO

23

Foam Pump-1 Start command from PLC

PLC

DO

NO

24

Foam Pump-1 Stop command from PLC

PLC

DO

NC

25

Foam Pump selected in manual mode

UML

Page 3 of 5

PLC

YES

AO

Remark

I/O List of PLC System


Project
Client
Vendor
Package
NTPC Doc. No.
S. No.

: 2 X 660 MW, MOUDA, STPP STAGE II


: M/s. NTPC
: Unitech Machines Limited
: FIRE DETECTION & PROTECTION SYSTEM
: 9575-151-PVI-G-069

Tag No.

Drive No.

Date:- 12.10.2012
UML DOC. NO.-P308-I-038
REV-01

Description

Location

Interfacing

Signal Source

Signal
Form

Signal/
Contact Type

Annunciatio
DI

AI

DO

n IN OWS

26

PT-F-02

Foam Pump-1 Running signal/ Fail to start*

PT

AI

4 to 20 mA

27

PT-F-03

Foam system for LDO tank

PT

AI

4 to 20 mA

28

PT-F-04

Foam system for HFO tank-1

PT

AI

4 to 20 mA

29

PT-F-05

Foam system for HFO tank-2

PT

AI

4 to 20 mA

30

PT-F-06

Foam system for Hydrant

PT

AI

4 to 20 mA

31

LT-F-01

Level low of Foam tank-1

LT

AI

4 to 20 mA

32

LT-F-02

Level low of Foam tank-2

LT

AI

4 to 20 mA

33

LSG

LSG

DI

NO

34

Float Cum Boost Charger-1 Fail/Trip

UML

BC-1

DI

NO

35

Float Cum Boost Charger-1 DC over voltage

UML

BC-1

DI

NO

36

Float Cum Boost Charger-2 Fail/Trip

UML

BC-2

DI

NO

37

Float Cum Boost Charger-2 DC over voltage

UML

BC-2

DI

NO

38

Battery under voltage

UML

BC-1

DI

NO

39

Battery earth fault

UML

BC-1

DI

NO

40

Battery Isolated

UML

BC-1

DI

NO

41

Charger - trouble

UML

BC-1

DI

NO

42

Battery on load

UML

BC-1

DI

NO

43

Battery fuse blown

UML

BC-1

DI

NO

44

Battery charger I/P out of range

UML

BC-1

DI

NO

45

Battery charger surge protection failure

UML

BC-1

DI

NO

46

Battery charger voltage

BC-1

AI

4-20 mA

47

Battery charger current

BC-1

AI

4-20 mA

48

Battery voltage

BC-1

AI

4-20 mA

49

Battery under voltage

BC-2

DI

NO

FP-DE-01

Foam Pump House

Level of diesel Tank

YES

1
1

1
1

50

Battery earth fault

UML

BC-2

DI

NO

51

Battery Isolated

UML

BC-2

DI

NO

52

Charger - trouble

UML

BC-2

DI

NO

53

Battery on load

UML

BC-2

DI

NO

1
1

54

Battery fuse blown

BC-2

NO

55

Battery charger I/P out of range

BC-2

NO

56

Battery charger surge protection failure

BC-2

NO

57

Battery charger voltage

BC-2

AI

4-20 mA

58

Battery charger current

BC-2

AI

4-20 mA

59

Battery voltage

BC-2

AI

4-20 mA

Total

1
36

14

LT Switchgear Signals

C
1

Switchgear disturbance

DI

NO

Breaker OPEN status

DI

NO

Breaker CLOSE status

DI

NC

DI

NO

DI

NO

Breaker OPEN command

DO

NO

Breaker CLOSE command

DO

NC

Breaker ready for remote operation


Incomer-1

Booster pump house

Overload/Trip relay operated

NTPC MCC

Page 4 of 5

Incomer-1

AO

Remark

I/O List of PLC System


Project
Client
Vendor
Package
NTPC Doc. No.
S. No.

: 2 X 660 MW, MOUDA, STPP STAGE II


: M/s. NTPC
: Unitech Machines Limited
: FIRE DETECTION & PROTECTION SYSTEM
: 9575-151-PVI-G-069

Tag No.

Drive No.

Location

Date:- 12.10.2012
UML DOC. NO.-P308-I-038
REV-01

Description

Interfacing

Signal Source

Signal
Form

Signal/
Contact Type

Current measurement

AI

4-20mA

Voltage measurement

AI

4-20mA

Annunciatio
DI

AI

DO

n IN OWS
1
1

10

Switchgear disturbance

DI

NO

11

Breaker OPEN status

DI

NO

12

Breaker CLOSE status

DI

NC

13

DI

NO

14

DI

NO

15

Breaker OPEN command

DO

NO

16

Breaker CLOSE command

DO

NC

17

Current measurement

AI

4-20mA

18

Voltage measurement

AI

4-20mA

Breaker ready for remote operation


Incomer-2

Booster Pump House Overload/Trip relay operated

NTPC MCC

Incomer-2

1
1

19

Switchgear disturbance

DI

NO

20

Breaker OPEN status

DI

NO

21

Breaker CLOSE status

DI

NC

22

DI

NO

23

Overload/Trip relay operated

DI

NO

24

Overload trip operated

DI

NO

25

Breaker OPEN command

DO

NO

26

Breaker CLOSE command

DO

NC

Bus coupler

NOTE:

Booster Pump House

Breaker ready for remote operation

NTPC MCC

Bus coupler

Total

16

Total I/O

89

29

20

Spare Channel ( 10%) for DI,DO & AI

Annunciation marked with " * " above shall be annunciated in Main Fire Alarm panel.

Page 5 of 5

AO

Remark