You are on page 1of 9

LOCAL 08 D MEZANINE

Fire Sprinkler Reports

for

Prepared By:
Ing. Giann Urriola
ARTEL

30/1/15

Fire - Fire Sprinkler Hydraulics Calculation Program


IMDC, Inc.
Winter Park, FL 32789-4944

Elite Software Development, Inc.


Local 08 D Mezanine
Page 2

General Project Data Report


General Data
Project Title:
Designed By:
Code Reference:
Client Name:
Address:
Company Name:
Company Address:
Phone:
Building Name:
Contact at Building:
Address Of Building:

Local 08 D Mezanine
Ing. Giann Urriola

Project File Name:


Date:
Approving Agency:
Phone:
City, State Zip Code:
Representative:
City And State:

ARTEL

Megamall

Mezanine..fiw
30/1/15

Building Owner:
Phone at Building:
City, State Zip Code:

Project Data
Description Of Hazard:
Design Area Of Water Application:
Default Sprinkler K-Factor:
Inside Hose Stream Allowance:
In Rack Sprinkler Allowance:

Ordinary 2
1500
8.00
250.00
0.00

Sprinkler Specifications
Make:
Size:

ft
K
gpm
gpm

1/2

Sprinkler System Type:


Wet
Maximum Area Per Sprinkler:
130 ft
Default Pipe Material:
SCHED 40 WET STEEL
Outside Hose Stream Allowance:
0.00 gpm

Model:
Temperature Rating:

174 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID:
Hydrant Elevation:
Test Flow Rate:
Calculated System Flow Rate:

Date Of Test:
0 ft
0.00 gpm
94.15 gpm

Static Pressure:
Test Residual Pressure:
Calculated Inflow Residual Pressure:

0.00 psi
0.00 psi
38.62 psi

Calculation Project Data


Calculation Mode:
HMD Minimum Residual Pressure:
Number Of Active Nodes:
Number Of Active Pipes:
Number Of Active Sprinklers:

Demand
7.00 psi
7
6
3

C:\Users\GCARLOS1\Desktop\Mezanine..fiw

Minimum Desired Flow Density:


Number Of Inactive Pipes:
Number Of Inactive Sprinklers:

0.20 gpm/ft
0
0

viernes, 30 de enero de 2015, 12:11 p. m.

Fire - Fire Sprinkler Hydraulics Calculation Program


IMDC, Inc.
Winter Park, FL 32789-4944

Elite Software Development, Inc.


Local 08 D Mezanine
Page 3

Fire Sprinkler Input Data


Node Input Data
Area Group
Branch Dia.
(in)

Sprinkler
KFactor (K)
Branch Len.
(ft)

Pressure
Estimate (psi)
Branch Stnd
Fittings

Node Elev (ft)


Branch NonStnd Fittings
(ft)

Non-Sprinkler
Flow (gpm)
Branch Sprk
KFactor (K)

No Discharge
----

---0.000

N/A
0.0

38.62
----

0.00
0.0

0.00
0.00

10

No Discharge
----

---0.000

N/A
0.0

27.67
----

0.00
0.0

0.00
0.00

15

No Discharge
----

---0.000

N/A
0.0

26.72
----

0.00
0.0

0.00
0.00

20

Sprinkler
----

---0.000

8.00
0.0

23.92
----

0.98
0.0

0.00
0.00

25

No Discharge
----

---0.000

N/A
0.0

13.41
----

0.00
0.0

0.00
0.00

30

Sprinkler
----

---0.000

8.00
0.0

13.16
----

0.00
0.0

0.00
0.00

35

Sprinkler
----

---0.000

8.00
0.0

10.56
----

0.00
0.0

0.00
0.00

Node
No.

Node Description
Branch Description

C:\Users\GCARLOS1\Desktop\Mezanine..fiw

viernes, 30 de enero de 2015, 12:11 p. m.

Fire - Fire Sprinkler Hydraulics Calculation Program


IMDC, Inc.
Winter Park, FL 32789-4944

Elite Software Development, Inc.


Local 08 D Mezanine
Page 4

Fire Sprinkler Input Data


Pipe Input Data
Nominal
Diameter
(inch)

Type
Group

Fitting
Data

Nominal
Length
(feet)

Fitting
Length
(feet)

SCHED 40 WET STEEL

1.500

2ETBC

7.55

31.00

38.55

120

15

SCHED 40 WET STEEL

1.500

ET

4.92

12.00

16.92

120

15

20

SCHED 40 WET STEEL

1.000

3.28

2.00

5.28

120

10

25

SCHED 40 WET STEEL

1.000

ET

9.84

7.00

16.84

120

25

30

SCHED 40 WET STEEL

1.000

0.98

0.00

0.98

120

25

35

SCHED 40 WET STEEL

1.000

11.48

2.00

13.48

120

Beg.
Node

End.
Node

Pipe Description

10

10

C:\Users\GCARLOS1\Desktop\Mezanine..fiw

Total
CFactor
Length (gpm/inch(feet)
psi)

viernes, 30 de enero de 2015, 12:11 p. m.

Fire - Fire Sprinkler Hydraulics Calculation Program


IMDC, Inc.
Winter Park, FL 32789-4944

Elite Software Development, Inc.


Local 08 D Mezanine
Page 5

Fire Sprinkler Output Data


Group Peak Node Groupings Output Data
Pipe Segment
Beg.
End.
Node
Node

Pipe
Type
Group

Pipe
Flow Rate
(gpm)

Sprinkler Flow
At Beg. Node
(gpm)

Non-Sprinkler Flow
Out (+)
In (-)
(gpm)
(gpm)

Beg. Node
Residual
Pressure (psi)

Imbalance
Flow At Beg.
Node (gpm)

10

94.15

0.00

0.00

-94.15

38.62

10
10
10

5
15
25

0
0
0

-94.15
39.13
55.02

0.00

0.00

0.00

27.67

0.00000

15
15

10
20

0
0

-39.13
39.13

0.00

0.00

0.00

26.72

0.00000

20

15

-39.13

39.13

0.00

0.00

23.92

0.00000

25
25
25

10
30
35

0
0
0

-55.02
29.02
26.00

0.00

0.00

0.00

13.41

0.00000

30

25

-29.02

29.02

0.00

0.00

13.16

0.00000

35

25

-26.00

26.00

0.00

0.00

10.56

C:\Users\GCARLOS1\Desktop\Mezanine..fiw

viernes, 30 de enero de 2015, 12:11 p. m.

Fire - Fire Sprinkler Hydraulics Calculation Program


IMDC, Inc.
Winter Park, FL 32789-4944

Elite Software Development, Inc.


Local 08 D Mezanine
Page 6

Fire Sprinkler Output Data


Group Peak Pipe Output Data
Beg.
End.
Node

Nodal
KFactor
(K)

Spk/Hose
Elevation
Discharge
(feet)
(gpm)

Residual Nom. Dia.


Pressure Inside Dia.
(psi)
C-Value

q (gpm)
Q (gpm)
Velocity
(fps)

F. L./ft
(psi/ft)
Fittings
Type-Grp

Pipe-Len.
Fit-Len.
Tot-Len.
(ft)

PF-(psi)
PE-(psi)
PT-(psi)

5
10

0.00
0.00
0.00
0.00
0.00
0.00
SCHED 40 WET STEEL

38.62
27.67

1.50
1.610
120

0.00
94.15
14.84

0.28398
2ETBC
0

7.55
31.00
38.55

10.946
0.000
10.946

10
15

0.00
0.00
0.00
0.00
0.00
0.00
SCHED 40 WET STEEL

27.67
26.72

1.50
1.610
120

0.00
39.13
6.17

0.05595
ET
0

4.92
12.00
16.92

0.947
0.000
0.947

10
25

0.00
0.00
0.00
0.00
0.00
0.00
SCHED 40 WET STEEL

27.67
13.41

1.00
1.049
120

0.00
55.02
20.43

0.84666
ET
0

9.84
7.00
16.84

14.260
0.000
14.260

15
20

0.00
0.00
0.00
8.00
0.98
39.13
SCHED 40 WET STEEL

26.72
23.92

1.00
1.049
120

39.13
39.13
14.53

0.45069
E
0

3.28
2.00
5.28

2.380
0.426
2.806

25
30

0.00
0.00
0.00
8.00
0.00
29.02
SCHED 40 WET STEEL

13.41
13.16

1.00
1.049
120

29.02
29.02
10.77

0.25925
----0

0.98
0.00
0.98

0.255
0.000
0.255

25
35

0.00
0.00
0.00
8.00
0.00
26.00
SCHED 40 WET STEEL

13.41
10.56

1.00
1.049
120

26.00
26.00
9.65

0.21153
E
0

11.48
2.00
13.48

2.852
0.000
2.852

C:\Users\GCARLOS1\Desktop\Mezanine..fiw

viernes, 30 de enero de 2015, 12:11 p. m.

Fire - Fire Sprinkler Hydraulics Calculation Program


IMDC, Inc.
Winter Park, FL 32789-4944

Elite Software Development, Inc.


Local 08 D Mezanine
Page 7

Fire Sprinkler Output Data


Group Peak Sprinkler Output Data
Flowing
Sprinkler
Node No.

Area Group
Code

Sprinkler
KFactor (K)

Sprinkler
Elevation
(feet)

20
Sub Totals For Non-Group

8.00

0.98

23.92

30
Sub Totals For Non-Group

8.00

0.00

35
Sub Totals For Non-Group

8.00

0.00

Totals For All Groups

C:\Users\GCARLOS1\Desktop\Mezanine..fiw

Residual
Flowing Area
Pressure
(ft)
(psi)

Flowing
Density
(gpm/ft)

Sprinkler
Discharge
(gpm)

130.00
130.00

0.301
0.301

39.13
39.13

13.16

130.00
130.00

0.223
0.223

29.02
29.02

10.56

130.00
130.00

0.200
0.200

26.00
26.00

390.00

0.241

94.15

viernes, 30 de enero de 2015, 12:11 p. m.

Fire - Fire Sprinkler Hydraulics Calculation Program


IMDC, Inc.
Winter Park, FL 32789-4944

Elite Software Development, Inc.


Local 08 D Mezanine
Page 8

Fire Sprinkler Output Summary


Hydraulically Most Demanding Sprinkler Node
HMD Sprinkler Node Number:
HMD Actual Residual Pressure:
HMD Actual GPM:

35
10.56 psi
26.00 gpm

Sprinkler Summary
Sprinkler System Type:
Specified Area Of Application:
Minimum Desired Density:
Application Average Density:
Application Average Area Per Sprinkler:
Sprinkler Flow:
Average Sprinkler Flow:

Wet
1500.00
0.200
0.063
500.00
94.15
31.38

ft
gpm/ft
gpm/ft
ft
gpm
gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 10 - 25 )
Maximum Velocity Pressure ( In Pipe 10 - 25 )
Allowable Maximum Nodal Pressure Imbalance:
Actual Maximum Nodal Pressure Imbalance:
Actual Average Nodal Pressure Imbalance:
Actual Maximum Nodal Flow Imbalance:
Actual Average Nodal Flow Imbalance:

20.43 ft/sec
2.81 psi
0.0010
0.0000
0.0000
0.0000
0.0000

psi
psi
psi
gpm
gpm

Overall Network Summary


Number Of Unique Pipe Sections:
Number Of Flowing Sprinklers:
Pipe System Water Volume:
Sprinkler Flow:
Non-Sprinkler Flow:
Minimum Required Residual Pressure At System Inflow
Node:
Demand Flow At System Inflow Node:

C:\Users\GCARLOS1\Desktop\Mezanine..fiw

6
3
2.47 gal
94.15 gpm
0.00 gpm
38.62 psi
94.15 gpm

viernes, 30 de enero de 2015, 12:11 p. m.

Fire - Fire Sprinkler Hydraulics Calculation Program


IMDC, Inc.
Winter Park, FL 32789-4944

Elite Software Development, Inc.


Local 08 D Mezanine
Page 9

Fire Sprinkler Output Data


Hydraulic Supply/Demand Graph

50
45

Pressure psi

40

39

35
30
25
20
15
10
5
0
0.1 0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 38.62 psi
Calculated Flow Rate: 94.15 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 0.43 psi

C:\Users\GCARLOS1\Desktop\Mezanine..fiw

viernes, 30 de enero de 2015, 12:11 p. m.

You might also like