KARNATAKA POWER TRANSMISSION CORPORATION LIMITED

Office of the
Executive Engineer (Ele)
R.T (Addl), Division,
Rajajinagar, Bangalore-10.

Power Transformer Test Report


Location
Date of Testing

:
:

66/11kV Sub Station, BWSSB


16.09.2014

I. NAME PLATE DETAILS


1 Make

RIMA

2 Maker's Sl.No

1238/8

3 Class

4 Rated Power

15 P.O No

66/11kV

16 Year of MFG.

2003

12.5 MVA

17 No. of Taps

17

5 Rated Voltage

66000/11000

18 Core & Winding (kg)

17,050

6 Rated Current

109.3/656.1

19 Transport Wt. (kg)

31,050

7 Phase

3/3

20 Total Mass Wt. (kg)

37,065

8 Frequency

50

21 Oil Quantity (Litre)

11,560

9 Connection Symbol

Dyn11

22 Weight of Oil (kg)

10,115

10 Impedance Voltage

9.01%

10XIn

11 Temp. Rise oil (C)

50

23 Symmetrical Short
Circuit Current

12 Temp. Rise Wdg.(C) :

55

25 Max.S.C Duration

13 Type of Cooling

ONAN

26 IS Standard

14

Rated Insulation

2026-1977

140kV/325kVP
28/75kVP

I TRANSFORMER PHYSICAL INSPECTION


1
2
3
4

Physical Appearance
Air Released in H.V.Bushings
Air Released in L.V.Bushings
Air Released in Bucholz Relay

NORMAL
YES
YES
YES

:
:
:
:

II. INSULATION RESISTANCE TEST RESULTS


1 Megger Used

5 kV Motorised

2 H.V.Continuity

OK

3 L.V.Continuity

OK

Terminals

20 sec

60 sec.

120 sec.

UNIT

Winding Temperature

1 HV to LV

500000

500000

500000

Mega Ohms

34C

2 HV to Gnd.

500000

500000

500000

Mega Ohms

34C

3 LV to Gnd.

500000

500000

500000

Mega Ohms

34C

66/11kV BWSSB, T.K.Halli Sub-station