S3 / S6 COMPRESSOR STATIONS

SPECIAL SPECIFICATION

NATIONAL IRANIAN GAS COMPANY


(N.I.G.C.)

THIS DOCUMENT IS OUR PROPERTY AND SHALL NOT BE USED NOR REPRODUCED WITHOUT OUR WRITTEN AUTHORIZATION

01.24

CE DOCUMENT EST NOTRE PROPRIETE ET NE DOIT ETRE NI UTILISE, NIREPRODUIT SANS NOTRE AUTORISATION ECRITE.

92/98 bd Victor Hugo


92115 CLICHY - FRANCE
Tlphone 01.41. 06.30.00
Tlex 620 428 SOFRGAZ
Fax 01.47.37.16.27
E-mail sz.clichy@sofregaz.fr

H.V.A.C.
(ADDENDUM)

Date :
25/10/01
Rv./Amend.
0

Etablis./Establ.
Ph. PETER
Vrif/Check
V. TIRILLY

Projet/Project
EMISSION POUR/ISSUE FOR
Ph. PEZE
First Issue
Approbat./Approval N RC291.SP.000.2000.0001
V. TIRILLY

Page 1/12

REVISION RECORD

Revision

Date

Established

Checked

Project

Approved

Issue for

25/10/01

PPT

VTY

PZE

VTY

First Issue

01.02

Rv.

Date
0

Amend.

25/10/01
Date

N RC291.SP.000.2000.0001

Page : 2/12

S3/S6 COMPRESSOR STATION


ADDENDUM SPECIFICATION HVAC
TECHNICAL PARAMETERS

ITEM
No.

DESIGNATION

SUPPLY FOR S3
SZ REQUIREM.

DATA

COMMENTS

CONFORMITY

CODES, REGULATIONS AND SPECIFICATION

CODES AND REGULATIONS

ASHRAE / NFPA

OK

OFFICIAL LANGUAGE

ENGLISH

OK

REQUISITION

SUPPLY

OK

SPECIAL SPECIFICATION

DESIGN

OK

6
7

PACKAGED AIR CONDITIONER

8
9

TYPE

10

MANUFACTURER

11

REVERSIBILITY (HEAT PUMP)

COMPACT

OK

HITECSA

OK

NO

OK

12
13

AIR TREATMENT UNIT

14

FILTERS

15

PRE FILTER CAPACITY

70% gravimetric

YES

OK

16

FILTER CAPACITY

90% gravimetric

YES

OK

17

STATIC PRESSURE DROP

< 200 Pa

YES

OK

18

MAXIMUM FRONT VELOCITY

< 2.5 m/s

YES

OK

REQUIRED

PROVIDED

OK
OK

19
20

COOLING COIL

21

DIRECT EXPANSION

22

SEAMLESS COPPER TUBES WITH ALUMINIUM OR

23

COPPER FINS

REQUIRED

COPPER/ALU

24

GALVANIZED STEEL CONDENSATE WATER BASIN

REQUIRED

Stainless Steel

OK

25

REQUIRED CAPACITY

5% OVER CAP.

included (*)

OK

26

(*) in ISO temperature conditions

27

SUPPLY FAN

28

DOUBLE INLET CENTRIFUGAL TYPE

REQUIRED

YES

OK

29

FAN DRIVING DEVICE

REQUIRED

V belt coupling

OK

30

ANTIVIBRATION MOUNTINGS

REQUIRED

PROVIDED

OK

31

FAN SPEED

1400 rpm

OK

32

FAN DISCHARGE VELOCITY MEASURED

YES in duct

OK

HERMETIC

OK

< 10 m/s

33
34

CONDENSING UNIT COMPRESSOR

35

MOTOR COMPRESSORS

36

COMPRESSOR TYPE

37

MULTI INDEPENDANT COMPRESSOR CIRCUITS

REQUIRED

Two circuits

OK

38

CRANK CASE HEATER

REQUIRED

PROVIDED

OK

39
40

REFRIGERANT CIRCUIT

41

FILTER DRIER, SIGHT GLASS, COMPRESSOR

42

DISCHARGE SERVICE VALVE

REQUIRED

to be confirmed

43

REFRIGERANT

R22/R134 A

R 22

OK

REQUIRED

PROVIDED

OK

44
45

CASING

46

PAINTED STEEL FRAME WITH THERMAL AND

47

ACOUSTIC INSULATION PANEL

48
49

1-1

50

1-1-1

CONTROL BUILDING
AIR PACKAGED CONDITIONNER ACV 2402

51

MODEL

52

QUANTITY

ACV 2402
2

OK

53

QUANTITY IN OPERATION

OK

REQUIRED

YES

OK

240000

263396 (*)

OK
OK

54

REDUNDANCY

55

NOMINAL COOLING CAPACITY PER UNIT (*)

56

NOMINAL HEATING CAPACITY (KW)

40

57

NOMINAL AIR FLOW PER UNIT (m3/h)

to be confirmed

58

BUILT IN ELECTRIC COIL CAPACITY (KW)

59

POWER

Rev. 0

item 1-1-18
380-3-50

RC291.SP.000.2000.0001

380-3-50

OK

Pages 3/12

S3/S6 COMPRESSOR STATION


ADDENDUM SPECIFICATION HVAC
TECHNICAL PARAMETERS

ITEM
No.
60

DESIGNATION

SUPPLY FOR S3
SZ REQUIREM.

CONFORMITY

OK

OK

(*) in ISO temperature conditions (BTU/H)

61
62
63
64

1-1-2

AIR CONDITIONNER BASE FRAME WITH INLET


AND OUTLET LOUVERS AS WELL AS DUCT
OUTSIDE LOUVRE CONNECTIONS
QUANTITY

REQUIRED

65

1-1-3

TRANSFORMATION REC/CIR

REQUIRED

66
67

DATA

QUANTITY
1-1-4

2
2
1 set in option

DUCT

68

DUCT DIAM 630

69

ELBOW DIAM 500

OPTION 1

70

DUCT DIAM 560

OPTION 1

71

DUCT DIAM 500

OPTION 1

72

DUCT DIAM 400

OPTION 1

73

DUCT DIAM 350

OPTION 1

74

DUCT DIAM 300

OPTION 1

75

DUCT DIAM 250

OPTION 1

OPTION 1
1 in option

OPTION 1

DUCT CONNECTION

1 set in option

OPTION 1

1-1-7

INSULATION 25MM FIB AIR

1 set in option

OPTION 1

79

1-1-8

ACCESS. FOR INSULATION (SET)

1 set in option

OPTION 1

80

1-1-9

FLEXIBLE DUCT

1 set in option

OPTION 1

81

1-1-10

VOLUME DAMPERS

1 set in option

OPTION 1

82

1-1-11

FIRE DAMPER

1 set in option

OPTION 1

83

1-1-12

PRESSURE RELIEF DAMPERS

1 set in option

OPTION 1

84

1-1-13

DUCT SUPPORT

1 set in option

OPTION 1

85

1-1-14

REGULATION EQUIPMENT

REQUIRED

one PLC with TT


for control &
automatisme

87

1-1-15

BLOWING LOUVRE + PLENUM

1 set in option

OPTION 1

88

1-1-16

RETURN LOUVRE + PLENUM

1 set in option

OPTION 1

89

1-1-17

SEALS (SET)

1-1-18

DUCT HEATER 6KW

OK

93

1-1-19

SCRAWING (SET)

REQUIRED

1 set

OK

94

1-1-20

FRESH AIR SYSTEM

REQUIRED

OK

76

1-1-5

TEE FOR MAIN DUCT CONNECTION

77

1-1-6

78

86

QUANTITY

90
91

COMMENTS

REQUIRED

QUANTITY

92

OK

OK

REQUIRED

QUANTITY

95
96

1-2

97
98

1-2-1

WORKSHOP BUILDING
AIR PACKAGED CONDITIONNER
MODEL

99

QUANTITY

100

COOLING CAPACITY PER UNIT (BTU/H)

101

HEATING CAPACITY (KW)

102

POWER

103
104
105
106
107
108
109
110

OK

90000

90000

OK

35

27

OK

380-3-50

380-3-50

OK

AIR FLOW (m3/h)


1-2-2

1-2-3
1-2-4

111
112
113

ACV 1001
1

QUANTITY
2

REQUIRED

2
REQUIRED
1
REQUIRED

OK

1
one PLC with TT
for control &
automatisme
1

OK

OK

ROOM AIR CONDITIONER UNIT

114

TYPE

115

MANUFACTURER

116

HEAT PUMP (REVERSIBILITY)

Rev. 0

to be confirmed

AIR CONDITIONNER BASE FRAME WITH INLET


AND OUTLET LOUVERS AS WELL AS DUCT
OUTSIDE LOUVRE CONNECTIONS
QUANTITY
BLOWING PLENUM WITH LOUVER
QUANTITY
REGULATION EQUIPMENT

RC291.SP.000.2000.0001

WINDOWS

OK

ZENITH AIR

OK

YES

OK

Pages 4/12

S3/S6 COMPRESSOR STATION


ADDENDUM SPECIFICATION HVAC
TECHNICAL PARAMETERS

ITEM
No.

DESIGNATION

SUPPLY FOR S3
SZ REQUIREM.

DATA

CONFORMITY

COMMENTS

117
118

COMPRESSOR

119

HERMETICALLY SEALED MOTOR

REQUIRED

HERMETIC

OK

120

FACTORY LUBRICATED

REQUIRED

YES

OK

PERMANENT CLEANABLE FILTER

REQUIRED

YES

OK

CENTRIFUGAL BLOWER

REQUIRED

YES

OK

R 22

R 22

OK

REQUIRED

YES

OK

121
122
123
124
125
126

REFRIGERANT CIRCUIT

127

CONTROL PANEL (fans and coils switches, tem-

128

perature selector)

129
130
131

2-1

SWITCHGEAR BUILDING

132

MODEL

133

QUANTITY

134

COOLING CAPACITY PER UNIT (BTU/HR)

135

HEATING CAPACITY (KW)

136

POWER

WP 12 B
4

24000

12000

Deviation
Accepted

>3

3,37

OK

230/1/50

230/1/50

OK

137

SUPPORT

REQUIRED

YES

OK

138

SEALING

REQUIRED

YES

OK

139
140

2-2

MCC GAS COOLER BUILDING

141

MODEL

142

QUANTITY

143

COOLING CAPACITY PER UNIT (BTU/HR)

144

HEATING CAPACITY (KW)

145

POWER

WP 18 B
2

OK

18000

18000

OK

5,12

OK

230/1/50

230/1/50

OK

146

SUPPORT

REQUIRED

YES

OK

147

SEALING

REQUIRED

YES

OK

148
149

2-3

HV SUBSTATION 20kV BUILDING

150

MODEL

151

QUANTITY

152

COOLING CAPACITY PER UNIT (BTU/hr)

153

HEATING CAPACITY (KW)

154

POWER

WP 18 B
4

OK

18000

18000

OK

>3

5,12

OK

230/1/50

230/1/50

OK

155

SUPPORT

REQUIRED

YES

OK

156

SEALING

REQUIRED

YES

OK

157
158

2-4

ADMINISTARTION BUILDING

159

MODEL

160

QUANTITY

161

COOLING CAPACITY PER UNT (BTU/HR)

162

HEATING CAPACITY (KW)

163

POWER

WP 18 B
13

13

OK

18000

18000

OK

>3

5,12

OK

230/1/50

230/1/50

OK

164

SUPPORT

REQUIRED

YES

OK

165

SEALING

REQUIRED

YES

OK

166
167

2-5

WORKSHOP BUILDING

168

MODEL

169

QUANTITY

170

COOLING CAPACITY PER UNIT BTU/HR

171

HEATING CAPACITY (KW)

172

POWER

WP 18 B
5

OK

18000

18000

OK

>3

5,12

OK

230/1/50

230/1/50

OK

173

SUPPORT

REQUIRED

YES

OK

174

SEALING

REQUIRED

YES

OK

175

Rev. 0

RC291.SP.000.2000.0001

Pages 5/12

S3/S6 COMPRESSOR STATION


ADDENDUM SPECIFICATION HVAC
TECHNICAL PARAMETERS

ITEM
No.
176

2-6

DESIGNATION

SUPPLY FOR S3
SZ REQUIREM.

DATA

COMMENTS

CONFORMITY

GATE HOUSE

177

MODEL

178

QUANTITY

179

COOLING CAPACITY PER UNIT (BTU/hr)

180

HEATING CAPACITY (KW)

181

POWER

WP 18 B
2

OK

18000

18000

OK

5,12

OK

230/1/50

230/1/50

OK

182

SUPPORT

REQUIRED

YES

OK

183

SEALING

REQUIRED

YES

OK

184
185

EXHAUST FANS

186
187

3-1

CONTROL BUILDING

188

Extract fan toilet room 510 m3/h

OK

189

Extract fan battery room 1600 m3/h

OK

1
75990

1
1

1
75000
18,5
350
1000
1400
90
1
1

OK
OK
OK
OK
OK
OK
OK
OK
OK

OK

OK

2
1
1
1
1

2
1
1
1
1

OK
OK
OK
OK
OK

OK

190
191

3-2

SWITCHGEAR & GENERATOR BUILDING

192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212

HELICOID FAN WITH ALUMINIUM IMPELLERS


Quantity
Air flow (m3/h)
Motor power (KW)
Over pressure (Pa)
Rotation speed (rpm)
Fan diameter (mm)
Noise level (dB)
Fan support
Protective louvre
Inlet air louvre (2000*2000)
Quantity
Accessories for louvre
Quantity
Motorised inlet damper
Quantity
Air inlet duct (2*2 >> diam. 1,4)
Flexible duct
Air extract duct
PLC temperature sensor

213

provided air flow in S6 : 68000 m3/h

< 1000

(*) required air flow in S6 : 67595 m3/h

214
215

3-3

216

ADMINISTRATION BUILDING
Extract fan toilet room 300 m3/h

217
218

3-4

WORKSHOP BUILDING

219

Extract fan toilet room 510 m3/h

OK

220

Extract fan boiler room 3000 m3/h and gravity damper

OK

OK

3 KW

3 KW

OK

OK

1,2 KW

1,5 KW

OK

OK

3 KW

3 KW

OK

OK

221
222

3-5

223

GATE HOUSE
Extract fan toilet room 130 m3/h

224
225
226

ELECTRICAL RADIATORS

227
228

4-1

ADMINISTRATION BUILDING

229

HEATING CAPACITY

230

QUANTITY

231

HEATING CAPACITY

232

QUANTITY

233
234
235

4-2

WORKSHOP BUILDING

236

HEATING CAPACITY

237

QUANTITY

238

Rev. 0

RC291.SP.000.2000.0001

Pages 6/12

S3/S6 COMPRESSOR STATION


ADDENDUM SPECIFICATION HVAC
TECHNICAL PARAMETERS

ITEM
No.
239

4-3

DESIGNATION

SUPPLY FOR S3
SZ REQUIREM.

DATA

CONFORMITY

3 KW

2,5 KW

OK

OK

2.5 KW

2.5 KW

OK

OK

COMMENTS

GATE HOUSE

240

HEATING CAPACITY

241

QUANTITY

242
243

4-4

WAREHOUSE BUILDING

244

HEATING CAPACITY

245

QUANTITY

246
247

ELECTRICAL EQUIPMENT (BULK)

248
249

5-1

CONTROL BUILDING

250

Cable for HVAC equipment Supply 3G2,5

1 set in option

OPTION 2

251

Cable for HVAC equipment Supply 3G4

1 set in option

OPTION 2

252

Cable for HVAC main equipment Supply

1 set in option

OPTION 2

253

HVAC Electrical panel

1 in option

OPTION 2

254
255

5-2

SWITCHGEAR BUILDING

256

Cable for HVAC equipment Supply 3G4

257

HVAC Electrical panel

1 set in option

OPTION 2

1 in option

OPTION 2

258
259

5-3

GENERATOR BUILDING

260

Cable for HVAC equipment Supply 3G4

261

HVAC Electrical panel

1 set in option

OPTION 2

1 in option

OPTION 2

262
263

5-4

MCC GAS COOLER BUILDING

264

Cable for HVAC equipment Supply 3G4

265

HVAC Electrical panel

1 set in option

OPTION 2

1 in option

OPTION 2

266
267

5-5

HV SUBSTATION 20kV BUILDING

268

Cable for HVAC equipment Supply 3G4

269

HVAC Electrical panel

1 set in option

OPTION 2

1 in option

OPTION 2

OPTION 2

270
271

5-6

ADMINISTRATIONBUILDING

272

Cable for HVAC equipment Supply 3G2,5

1 set in option

273

Cable for HVAC main equipment Supply 3G4

1 set in option

OPTION 2

274

HVAC Electrical panel

1 in option

OPTION 2

275
276

5-7

WORKSHOP BUILDING

277

Cable for HVAC equipment Supply 3G2,5

1 set in option

OPTION 2

278

Cable for HVAC equipment Supply 3G4

1 set in option

OPTION 2

279

Cable for HVAC main equipment Supply

1 set in option

OPTION 2

280

HVAC Electrical panel

1 in option

OPTION 2

OPTION 2

281
282

5-8

GATE BUILDING

283

Cable for HVAC equipment Supply 3G2,5

1 set in option

284

Cable for HVAC equipment Supply 3G4

1 set in option

OPTION 2

285

HVAC Electrical panel

1 in option

OPTION 2

OPTION 2

286
287

5-9

WAREHOUSE BUILDING

288

Cable for HVAC equipment Supply 3G2,5

1 set in option

289

Cable for HVAC equipment Supply 3G4

1 set in option

OPTION 2

290

HVAC Electrical panel

1 in option

OPTION 2

Rev. 0

RC291.SP.000.2000.0001

Pages 7/12

S3/S6 COMPRESSOR STATION


ADDENDUM SPECIFICATION HVAC
TECHNICAL PARAMETERS

ITEM
No.

DESIGNATION

SUPPLY FOR S6
SZ REQUIREM.

DATA

COMMENTS

CONFORMITY

CODES, REGULATIONS AND SPECIFICATION

CODES AND REGULATIONS

ASHRAE / NFPA

OK

OFFICIAL LANGUAGE

ENGLISH

OK

REQUISITION

SUPPLY

OK

SPECIAL SPECIFICATION

DESIGN

OK

6
7

PACKAGED AIR CONDITIONER

8
9

TYPE

10

MANUFACTURER

11

REVERSIBILITY (HEAT PUMP)

COMPACT

OK

HITECSA

OK

NO

OK

12
13

AIR TREATMENT UNIT

14

FILTERS

15

PRE FILTER CAPACITY

70% gravimetric

YES

OK

16

FILTER CAPACITY

90% gravimetric

YES

OK

17

STATIC PRESSURE DROP

< 200 Pa

YES

OK

18

MAXIMUM FRONT VELOCITY

< 2.5 m/s

YES

OK

REQUIRED

PROVIDED

OK
OK

19
20

COOLING COIL

21

DIRECT EXPANSION

22

SEAMLESS COPPER TUBES WITH ALUMINIUM OR

23

COPPER FINS

REQUIRED

COPPER/ALU

24

GALVANIZED STEEL CONDENSATE WATER BASIN

REQUIRED

Stainless Steel

OK

25

REQUIRED CAPACITY

5% OVER CAP.

included (*)

OK

26

(*) in ISO temperature conditions

27

SUPPLY FAN

28

DOUBLE INLET CENTRIFUGAL TYPE

REQUIRED

YES

OK

29

FAN DRIVING DEVICE

REQUIRED

V belt coupling

OK

30

ANTIVIBRATION MOUNTINGS

REQUIRED

PROVIDED

OK

31

FAN SPEED

1400 rpm

OK

32

FAN DISCHARGE VELOCITY MEASURED

YES in duct

OK

HERMETIC

OK

< 10 m/s

33
34

CONDENSING UNIT COMPRESSOR

35

MOTOR COMPRESSORS

36

COMPRESSOR TYPE

37

MULTI INDEPENDANT COMPRESSOR CIRCUITS

REQUIRED

Two circuits

OK

38

CRANK CASE HEATER

REQUIRED

PROVIDED

OK

39
40

REFRIGERANT CIRCUIT

41

FILTER DRIER, SIGHT GLASS, COMPRESSOR

42

DISCHARGE SERVICE VALVE

REQUIRED

to be confirmed

43

REFRIGERANT

R22/R134 A

R 22

OK

REQUIRED

PROVIDED

OK

44
45

CASING

46

PAINTED STEEL FRAME WITH THERMAL AND

47

ACOUSTIC INSULATION PANEL

48
49

1-1

50

1-1-1

CONTROL BUILDING
AIR PACKAGED CONDITIONNER ACV 2402

51

MODEL

52

QUANTITY

ACV 2402
2

OK

53

QUANTITY IN OPERATION

OK

REQUIRED

YES

OK

240000

263396 (*)

OK
OK

54

REDUNDANCY

55

NOMINAL COOLING CAPACITY PER UNIT (*)

56

NOMINAL HEATING CAPACITY (KW)

40

57

NOMINAL AIR FLOW PER UNIT (m3/h)

to be confirmed

58

BUILT IN ELECTRIC COIL CAPACITY (KW)

59

POWER

Rev. 0

item 1-1-18
380-3-50

RC291.SP.000.2000.0001

380-3-50

OK

Pages 8/12

S3/S6 COMPRESSOR STATION


ADDENDUM SPECIFICATION HVAC
TECHNICAL PARAMETERS

ITEM
No.
60

DESIGNATION

SUPPLY FOR S6
SZ REQUIREM.

CONFORMITY

OK

OK

(*) in ISO temperature conditions (BTU/H)

61
62
63
64

1-1-2

AIR CONDITIONNER BASE FRAME WITH INLET


AND OUTLET LOUVERS AS WELL AS DUCT
OUTSIDE LOUVRE CONNECTIONS
QUANTITY

REQUIRED

65

1-1-3

TRANSFORMATION REC/CIR

REQUIRED

66
67

DATA

QUANTITY
1-1-4

2
2
1 set in option

DUCT

68

DUCT DIAM 630

69

ELBOW DIAM 500

OPTION 1

70

DUCT DIAM 560

OPTION 1

71

DUCT DIAM 500

OPTION 1

72

DUCT DIAM 400

OPTION 1

73

DUCT DIAM 350

OPTION 1

74

DUCT DIAM 300

OPTION 1

75

DUCT DIAM 250

OPTION 1

OPTION 1
1 in option

OPTION 1

DUCT CONNECTION

1 set in option

OPTION 1

1-1-7

INSULATION 25MM FIB AIR

1 set in option

OPTION 1

79

1-1-8

ACCESS. FOR INSULATION (SET)

1 set in option

OPTION 1

80

1-1-9

FLEXIBLE DUCT

1 set in option

OPTION 1

81

1-1-10

VOLUME DAMPERS

1 set in option

OPTION 1

82

1-1-11

FIRE DAMPER

1 set in option

OPTION 1

83

1-1-12

PRESSURE RELIEF DAMPERS

1 set in option

OPTION 1

84

1-1-13

DUCT SUPPORT

1 set in option

OPTION 1

85

1-1-14

REGULATION EQUIPMENT

REQUIRED

one PLC with TT


for control &
automatisme

87

1-1-15

BLOWING LOUVRE + PLENUM

1 set in option

OPTION 1

88

1-1-16

RETURN LOUVRE + PLENUM

1 set in option

OPTION 1

89

1-1-17

SEALS (SET)

1-1-18

DUCT HEATER 6KW

OK

93

1-1-19

SCRAWING (SET)

REQUIRED

1 set

OK

94

1-1-20

FRESH AIR SYSTEM

REQUIRED

OK

76

1-1-5

TEE FOR MAIN DUCT CONNECTION

77

1-1-6

78

86

QUANTITY

90
91

COMMENTS

REQUIRED

QUANTITY

92

OK

OK

REQUIRED

QUANTITY

95
96

1-2

97
98

1-2-1

WORKSHOP BUILDING
AIR PACKAGED CONDITIONNER
MODEL

99

QUANTITY

100

COOLING CAPACITY PER UNIT (BTU/H)

101

HEATING CAPACITY (KW)

102

POWER

103
104
105
106
107
108
109
110

OK

90000

90000

OK

35

27

OK

380-3-50

380-3-50

OK

AIR FLOW (m3/h)


1-2-2

1-2-3
1-2-4

111
112
113

ACV 1001
1

QUANTITY
2

REQUIRED

2
REQUIRED
1
REQUIRED

OK

1
one PLC with TT
for control &
automatisme
1

OK

OK

ROOM AIR CONDITIONER UNIT

114

TYPE

115

MANUFACTURER

116

HEAT PUMP (REVERSIBILITY)

Rev. 0

to be confirmed

AIR CONDITIONNER BASE FRAME WITH INLET


AND OUTLET LOUVERS AS WELL AS DUCT
OUTSIDE LOUVRE CONNECTIONS
QUANTITY
BLOWING PLENUM WITH LOUVER
QUANTITY
REGULATION EQUIPMENT

RC291.SP.000.2000.0001

WINDOWS

OK

ZENITH AIR

OK

YES

OK

Pages 9/12

S3/S6 COMPRESSOR STATION


ADDENDUM SPECIFICATION HVAC
TECHNICAL PARAMETERS

ITEM
No.

DESIGNATION

SUPPLY FOR S6
SZ REQUIREM.

DATA

CONFORMITY

COMMENTS

117
118

COMPRESSOR

119

HERMETICALLY SEALED MOTOR

REQUIRED

HERMETIC

OK

120

FACTORY LUBRICATED

REQUIRED

YES

OK

PERMANENT CLEANABLE FILTER

REQUIRED

YES

OK

CENTRIFUGAL BLOWER

REQUIRED

YES

OK

R 22

R 22

OK

REQUIRED

YES

OK

121
122
123
124
125
126

REFRIGERANT CIRCUIT

127

CONTROL PANEL (fans and coils switches, tem-

128

perature selector)

129
130
131

2-1

SWITCHGEAR BUILDING

132

MODEL

133

QUANTITY

134

COOLING CAPACITY PER UNIT (BTU/HR)

135

HEATING CAPACITY (KW)

136

POWER

WP 12 B
4

24000

12000

Deviation
Accepted

>3

3,37

OK

230/1/50

230/1/50

OK

137

SUPPORT

REQUIRED

YES

OK

138

SEALING

REQUIRED

YES

OK

139
140

2-2

MCC GAS COOLER BUILDING

141

MODEL

142

QUANTITY

143

COOLING CAPACITY PER UNIT (BTU/HR)

144

HEATING CAPACITY (KW)

145

POWER

WP 18 B
2

OK

18000

18000

OK

5,12

OK

230/1/50

230/1/50

OK

146

SUPPORT

REQUIRED

YES

OK

147

SEALING

REQUIRED

YES

OK

148
149

2-3

HV SUBSTATION 20kV BUILDING

150

MODEL

151

QUANTITY

152

COOLING CAPACITY PER UNIT (BTU/hr)

153

HEATING CAPACITY (KW)

154

POWER

WP 18 B
4

OK

18000

18000

OK

>3

5,12

OK

230/1/50

230/1/50

OK

155

SUPPORT

REQUIRED

YES

OK

156

SEALING

REQUIRED

YES

OK

157
158

2-4

ADMINISTARTION BUILDING

159

MODEL

160

QUANTITY

161

COOLING CAPACITY PER UNT (BTU/HR)

162

HEATING CAPACITY (KW)

163

POWER

WP 18 B
13

13

OK

18000

18000

OK

>3

5,12

OK

230/1/50

230/1/50

OK

164

SUPPORT

REQUIRED

YES

OK

165

SEALING

REQUIRED

YES

OK

166
167

2-5

WORKSHOP BUILDING

168

MODEL

169

QUANTITY

170

COOLING CAPACITY PER UNIT BTU/HR

171

HEATING CAPACITY (KW)

172

POWER

WP 18 B
5

OK

18000

18000

OK

>3

5,12

OK

230/1/50

230/1/50

OK

173

SUPPORT

REQUIRED

YES

OK

174

SEALING

REQUIRED

YES

OK

175

Rev. 0

RC291.SP.000.2000.0001

Pages 10/12

S3/S6 COMPRESSOR STATION


ADDENDUM SPECIFICATION HVAC
TECHNICAL PARAMETERS

ITEM
No.
176

2-6

DESIGNATION

SUPPLY FOR S6
SZ REQUIREM.

DATA

COMMENTS

CONFORMITY

GATE HOUSE

177

MODEL

178

QUANTITY

179

COOLING CAPACITY PER UNIT (BTU/hr)

180

HEATING CAPACITY (KW)

181

POWER

WP 18 B
2

OK

18000

18000

OK

5,12

OK

230/1/50

230/1/50

OK

182

SUPPORT

REQUIRED

YES

OK

183

SEALING

REQUIRED

YES

OK

184
185

EXHAUST FANS

186
187

3-1

CONTROL BUILDING

188

Extract fan toilet room 510 m3/h

OK

189

Extract fan battery room 1600 m3/h

OK

1
67595

1
1

1
68000
18,5
350
1000
1400
90
1
1

OK
OK
OK
OK
OK
OK
OK
OK
OK

OK

OK

2
1
1
1
1

2
1
1
1
1

OK
OK
OK
OK
OK

OK

190
191

3-2

SWITCHGEAR & GENERATOR BUILDING

192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212

HELICOID FAN WITH ALUMINIUM IMPELLERS


Quantity
Air flow (m3/h)
Motor power (KW)
Over pressure (Pa)
Rotation speed (rpm)
Fan diameter (mm)
Noise level (dB)
Fan support
Protective louvre
Inlet air louvre (2000*2000)
Quantity
Accessories for louvre
Quantity
Motorised inlet damper
Quantity
Air inlet duct (2*2 >> diam. 1,4)
Flexible duct
Air extract duct
PLC temperature sensor

213

provided air flow in S6 : 68000 m3/h

< 1000

(*) required air flow in S6 : 67595 m3/h

214
215

3-3

216

ADMINISTRATION BUILDING
Extract fan toilet room 300 m3/h

217
218

3-4

WORKSHOP BUILDING

219

Extract fan toilet room 510 m3/h

OK

220

Extract fan boiler room 3000 m3/h and gravity damper

OK

OK

3 KW

3 KW

OK

OK

1,2 KW

1,5 KW

OK

OK

3 KW

3 KW

OK

OK

221
222

3-5

223

GATE HOUSE
Extract fan toilet room 130 m3/h

224
225
226

ELECTRICAL RADIATORS

227
228

4-1

ADMINISTRATION BUILDING

229

HEATING CAPACITY

230

QUANTITY

231

HEATING CAPACITY

232

QUANTITY

233
234
235

4-2

WORKSHOP BUILDING

236

HEATING CAPACITY

237

QUANTITY

238

Rev. 0

RC291.SP.000.2000.0001

Pages 11/12

S3/S6 COMPRESSOR STATION


ADDENDUM SPECIFICATION HVAC
TECHNICAL PARAMETERS

ITEM
No.
239

4-3

DESIGNATION

SUPPLY FOR S6
SZ REQUIREM.

DATA

CONFORMITY

3 KW

2,5 KW

OK

OK

2.5 KW

2.5 KW

OK

OK

COMMENTS

GATE HOUSE

240

HEATING CAPACITY

241

QUANTITY

242
243

4-4

WAREHOUSE BUILDING

244

HEATING CAPACITY

245

QUANTITY

246
247

ELECTRICAL EQUIPMENT (BULK)

248
249

5-1

CONTROL BUILDING

250

Cable for HVAC equipment Supply 3G2,5

1 set in option

OPTION 2

251

Cable for HVAC equipment Supply 3G4

1 set in option

OPTION 2

252

Cable for HVAC main equipment Supply

1 set in option

OPTION 2

253

HVAC Electrical panel

1 in option

OPTION 2

254
255

5-2

SWITCHGEAR BUILDING

256

Cable for HVAC equipment Supply 3G4

257

HVAC Electrical panel

1 set in option

OPTION 2

1 in option

OPTION 2

258
259

5-3

GENERATOR BUILDING

260

Cable for HVAC equipment Supply 3G4

261

HVAC Electrical panel

1 set in option

OPTION 2

1 in option

OPTION 2

262
263

5-4

MCC GAS COOLER BUILDING

264

Cable for HVAC equipment Supply 3G4

265

HVAC Electrical panel

1 set in option

OPTION 2

1 in option

OPTION 2

266
267

5-5

HV SUBSTATION 20kV BUILDING

268

Cable for HVAC equipment Supply 3G4

269

HVAC Electrical panel

1 set in option

OPTION 2

1 in option

OPTION 2

OPTION 2

270
271

5-6

ADMINISTRATIONBUILDING

272

Cable for HVAC equipment Supply 3G2,5

1 set in option

273

Cable for HVAC main equipment Supply 3G4

1 set in option

OPTION 2

274

HVAC Electrical panel

1 in option

OPTION 2

275
276

5-7

WORKSHOP BUILDING

277

Cable for HVAC equipment Supply 3G2,5

1 set in option

OPTION 2

278

Cable for HVAC equipment Supply 3G4

1 set in option

OPTION 2

279

Cable for HVAC main equipment Supply

1 set in option

OPTION 2

280

HVAC Electrical panel

1 in option

OPTION 2

OPTION 2

281
282

5-8

GATE BUILDING

283

Cable for HVAC equipment Supply 3G2,5

1 set in option

284

Cable for HVAC equipment Supply 3G4

1 set in option

OPTION 2

285

HVAC Electrical panel

1 in option

OPTION 2

OPTION 2

286
287

5-9

WAREHOUSE BUILDING

288

Cable for HVAC equipment Supply 3G2,5

1 set in option

289

Cable for HVAC equipment Supply 3G4

1 set in option

OPTION 2

290

HVAC Electrical panel

1 in option

OPTION 2

Rev. 0

RC291.SP.000.2000.0001

Pages 12/12