STRUCTURAL DESIGN CRITERIA

ITEM
1.0

SHEET NO.:
CHECKED BY:
ENGR. MARK ELSON LUCIO
REF.

REMARKS

SCOPE

This document covers the STRUCTURAL DESIGN CRITERIA for the FOUR-STOREY OFFICE WAREHOUSE PROJECT
located at Sta. Rosa De Lima Street, Barangay Bagong Ilog, Pasig City.

2.0

STRUCTURAL DESIGN CRITERIA


2.1 LANGUAGE
All drawings, calculation sheets, and documents shall be written in English.
2.2 UNIT OF MEASUREMENT
Unit of measurement for design work shall be in the International System (SI) and Metric System, unless
otherwise noted.
2.3 REFERENCES
The requirements contained in the latest edition of the following codes and standard shall form a part of this
CRITERA, in the manner and to the extent specified herein.
2.3.1

Local & International Codes and Standards

(1)

NSCP2010

(2)

Design, fabrication and erection of structural steel


AISC

13th edition

NSCP 2010
(3)

National Structural Code of the Philippines

"Specification for Design Fabrication and Erection of Structural Steel

National Structural Code of the Philippines, Volume I

Design and placement of concrete (for building)


ACI 318-08 "Building Code Requirements for Reinforced Concrete"
NSCP 2010

(4)

Design loads
NSCP 2010

(5)

National Structural Code of the Philippines, Volume I

National Structural Code of the Philippines, Volume I

Welding design and procedure


AWS D1.1-1992 American Welding Society

2.3.2

Material Standards
ASTM
"American Society for Testing and Materials"

CONCRETE DESIGN
COMPUTED BY:
CUETO, LORENZ ANTHONY P.
B-6
DARIO, MARTHA ARKIENE S.
MANDI, LOUIE JENESIS S.
RAMOS, OLIVER R. JR.
REYES, KHERJEE O.
STRUCTURAL DESIGN CRITERIA

ITEM

SHEET NO.:
CHECKED BY:
ENGR. MARK ELSON LUCIO
REF.

REMARKS

2.4 MAJOR MATERIALS


2.4.1 Concrete
The compressive strength of concrete at 28 days monitored by cylinder test
STRUCTURE

fc

Beams and Slabs


Columns
Footings

3000 psi / 21 Mpa


4000 psi / 28 Mpa
4000 psi / 28 Mpa

2.4.2 Reinforcing Steel Bars


Reinforcing steel bars shall be deformed bars conforming to ASTM A615
DIAMETER SIZE
20mm and smaller
25mm and larger

GRADE
GRADE 40
GRADE 60

fy
276 MPa (40,000 psi)
414 MPa (60,000 psi)

2.4.3 Structural Steel


Structural steel shall conform to ASTM A36
2.4.4 Connection Bolt for Structural Steel
Connection bolts shall be high strength bolts conforming to ASTM A325 or equivalent.
2.4.5 Anchor Bolt
Base material of anchor bolt shall conform to ASTM 325
2.5 LOADINGS
2.5.1

General
The following types of loads shall be considered:
a) Gravity Loads
a. Live Load (LL)
b. Dead Load (DL)
b) Wind Load (W)
c) Seismic Load (EQ)

2.5.2

Gravity Loads

FLOOR

AREA

ROOF

------------

SUPER IMPOSED DEAD LOAD


Material
psf
GI + Insulation
2.00
Purlins
3.00
Self-weight
5.00
Misc.
2.00
Ceiling
5.00
Total
17.00

LIVE LOAD
kPa
0.10
0.14
0.24
0.10
0.24
0.82

psf

kPa

20.89

1.00

CONCRETE DESIGN
COMPUTED BY:
CUETO, LORENZ ANTHONY P.
B-6
DARIO, MARTHA ARKIENE S.
MANDI, LOUIE JENESIS S.
RAMOS, OLIVER R. JR.
REYES, KHERJEE O.
STRUCTURAL DESIGN CRITERIA

ITEM

FLOOR

AREA
Stairs
Restroom

Office
Basketball
Court
Utilities
Stairs
Warehouse

Restroom

Utilities
Stairs
Warehouse

Restroom

Utilities

SUPER IMPOSED DEAD LOAD


Material
psf
Topping + Finish
48
Topping + Finish
50
Ceiling + Utilities
5
Partitions
84
Total
139
Topping + Finish
50
Ceiling + Utilities
5
Total
55
Topping + Finish
5
Ceiling + Utilities
5
Total
10
Topping + Finish
50
Ceiling + Utilities
5
Total
55
Topping + Finish
48
Topping + Finish
35
Ceiling + Utilities
5
Total
40
Topping + Finish
50
Ceiling + Utilities
5
Partitions
84
Total
139
Topping + Finish
50
Ceiling + Utilities
5
Total
55
Topping + Finish
48
Topping + Finish
35
Ceiling + Utilities
5
Total
40
Topping + Finish
50
Ceiling + Utilities
5
Partitions
84
Total
139
Topping + Finish
50
Ceiling + Utilities
5
Total
55

SHEET NO.:
CHECKED BY:
ENGR. MARK ELSON LUCIO
REF.

REMARKS

LIVE LOAD
kPa
2.30
2.42
0.24
4.04
6.70
2.42
0.24
2.66
0.27
0.24
0.51
2.42
0.24
2.66
2.30
1.65
0.24
1.89
2.42
0.24
4.04
6.70
2.42
0.24
2.66
2.30
1.65
0.24
1.89
2.42
0.24
4.04
6.70
2.42
0.24
2.66

psf
100

kPa
4.80

50

2.40

50

2.40

75

3.60

100

4.80

100

4.80

250

12.00

50

2.40

100

4.80

100

4.80

250

12.00

50

2.40

100

4.80

CONCRETE DESIGN
COMPUTED BY:
CUETO, LORENZ ANTHONY P.
B-6
DARIO, MARTHA ARKIENE S.
MANDI, LOUIE JENESIS S.
RAMOS, OLIVER R. JR.
REYES, KHERJEE O.
STRUCTURAL DESIGN CRITERIA

ITEM
FLOOR

AREA
Stairs
Restroom
Office
Electrical &
Generator
Room

Utilities
Garage
Walkway
Loading Bay

2.5.3

SUPER IMPOSED DEAD LOAD


Material
psf
Topping + Finish
48
Topping + Finish
50
Partitions
84
Total
134
Topping + Finish
50

kPa
2.30
2.42
4.04
6.46
2.42

Topping + Finish

50

2.42

Partitions
Total
Topping + Finish
Partitions
Total
Topping + Finish
Topping + Finish
Topping + Finish
Partitions
Total

70
120
50
5
55
50
50
50
64
114

3.33
5.75
2.42
0.24
2.66
2.42
2.42
2.42
3.07
5.49

ENGR. MARK ELSON LUCIO


REF.

REMARKS
LIVE LOAD

Wind Load
Location

SHEET NO.:
CHECKED BY:

Pasig City, Metro Manila

Zone

Basic Wind Speed, V

200 kph

Occupancy Category

Standard Occupancy

Importance Factor, Iw

1.00

Structural Type

Building

Directionality Factor, Kd

0.85

Enclosure Classification

Enclosed Building

Roof Type

Flat Pratt Roof

psf
100

kPa
4.80

50

2.40

50

2.40

150

7.20

100

4.80

100
100

4.80
4.80

100

4.80

CONCRETE DESIGN
COMPUTED BY:
CUETO, LORENZ ANTHONY P.
B-6
DARIO, MARTHA ARKIENE S.
MANDI, LOUIE JENESIS S.
RAMOS, OLIVER R. JR.
REYES, KHERJEE O.
STRUCTURAL DESIGN CRITERIA

ITEM
2.5.4

Seismic Load

Seismic Factors
Seismic Importance Factor, I
Soil Profile Type
Seismic Zone
Seismic Zone Factor, Z
Seismic Source Type
R
Near Source Factor, Na
Near Source Factor, Nv
Seismic Coefficient, Ca
Seismic Coefficient, Cv

1.00
SE
4
0.40
A
8.5
1.0
1.2
0.4 Na
0.64 Nv

SHEET NO.:
CHECKED BY:
ENGR. MARK ELSON LUCIO
REF.

REMARKS