LRR

To avoid over speed


This relay is necessary when
MHG is in service but kept in
operation when EHG controls

Upon action, HPCV & IPCV are


closed completely for 1.4 sec
max

conditions
Load throw off more than 50%
rated load
Remaining load less than 20 %
of rated load
Frequency more than 49 hz

LRR measures electrical load


rejections of the generator
Any load rejection is acquired
instantaneously by LRR and
transformed to an electrical
pulse

This pulse energizes two SOVs


One sov connects aux sec oil to
drain causing a rapid closure of
HP & IPCVS

Second sov connects IPCV sec


oil to drain
This close IPCVs faster than
first sov action (due to its
hydraulic characteristics)

IP Trimming device
During sudden load throw off,
HP cvs will close immediately to
control the load while IP cvs are
wide open

IP &LP share max load out of


the balance load
Causes HPT exh pr & temp to
rise

To contain HPT exh temp


trimming device is provided

conditions
HP exh pr

- 32 k.sc

Generator load < 20 % of rated


load

While trimming device is in


operation ,IP control valves are
closed and not tend to open
unless HP controls are opened
wide