After installing an arbitrary STEP7 option package (e.g. SIMOTION SCOUT, I / O module updates.) or dearchiving a project SCOUT runs up, but an error message indicating problems with s7proxyx.dll is output when starting the hardware configuration.
After installing an arbitrary STEP7 option package (e.g. SIMOTION SCOUT, I / O module updates.) or dearchiving a project SCOUT runs up, but an error message indicating problems with s7proxyx.dll is output when starting the hardware configuration.
After installing an arbitrary STEP7 option package (e.g. SIMOTION SCOUT, I / O module updates.) or dearchiving a project SCOUT runs up, but an error message indicating problems with s7proxyx.dll is output when starting the hardware configuration.
" Unable to load s7hprxyxdll " message output after installing a STEP7 option package
Problem / Symptom: After installing an arbitrary STEP7 option package (e.g. SIMOTION SCOUT, I/O module updates...) or dearchiving a project
SCOUT runs up, but an error message indicating problems with S7proxyx.dll is output when opening a project:
The SIMATIC Manager and/or SCOUT can no longer be started SCOUT runs up, but the system crashes with "Project new..." An error message indicating problems with S7proxyx.dll is output when starting the hardware configuration.
Remedy:
1. Terminate SCOUT and SIMATIC Manager. 2. In the STEP7 installation directory, search all s7hCompressedMetaData.cmf files (one of them is located in the s7met subdirectory and one in each project directory) and delete all these files. 3. In the directory s7bin, execute the application s7alibxx.exe.