MINDSPACE BUILDING NO.

4
GND Floor
srl.No Panel Details Controller Status
1 Router -1 PXG-80N RUN
2 Router -2 PXG-80N RUN
3 Integrator-1 PXC-00U RUN
4 Integrator-2 PXC-00U RUN
6 DDC STP PXC-12.D NO Access
8 DDC DG Panel PXC-12.D ?
1ST Floor
srl.No Panel Details Controller Status
1 DDC-AHU-1F1 PXC-12 RUN
2 DDC-AHU-1F2 PXC-12 RUN
3 DDC-AHU-1F3 PXC-12 RUN
4 DDC-AHU-1F4 PXC-12 Program Corrupt
2ND Floor
srl.No Panel Details Controller Status
1 DDC-AHU-2F1 PXC-12 RUN
2 DDC-AHU-2F2 PXC-12 Program Corrupt
3 DDC-AHU-2F3 PXC-12 RUN
4 DDC-AHU-2F4 PXC-12 RUN
3RD Floor
srl.No Panel Details Controller Status
1 DDC-AHU-3F1 PXC-12 RUN & SERVICE MODE
2 DDC-AHU-3F2 PXC-12 RUN
3 DDC-AHU-3F3 PXC-12 Program Corrupt
4 DDC-AHU-3F4 PXC-12 RUN
4TH Floor
srl.No Panel Details Controller Status
1 DDC-AHU-4F1 PXC-12 RUN
2 DDC-AHU-4F2 PXC-12 RUN
3 DDC-AHU-4F3 PXC-12 Program Corrupt
4 DDC-AHU-4F4 PXC-12 RUN
5TH Floor
srl.No Panel Details Controller Status
1 DDC-AHU-5F1 PXC-12 RUN
2 DDC-AHU-5F2 PXC-12 RUN
3 DDC-AHU-5F3 PXC-12 RUN
4 DDC-AHU-5F4 PXC-12 RUN
6TH Floor
srl.No Panel Details Controller Status
1 DDC-AHU-6F1 PXC-12 RUN
2 DDC-AHU-6F2 PXC-12 RUN & SERVICE MODE
3 DDC-AHU-6F3 PXC-12 RUN
4 DDC-AHU-6F4 PXC-12 RUN
7TH Floor
srl.No Panel Details Controller Status
1 DDC-AHU-7F1 PXC-12 RUN
2 DDC-AHU-7F2 PXC-12 RUN
3 DDC-AHU-7F3 PXC-12 RUN
8TH Floor
srl.No Panel Details Controller Status
1 DDC-AHU-8F1 PXC-12 RUN
2 DDC-AHU-8F2 PXC-12 RUN
3 DDC-AHU-8F3 PXC-12 RUN
TERRACE ( Needs to be edited)
srl.No Panel Details Controller Status
1 HRW-2 PXC-12 RUN
2 CHILLER PUMP PXC-12 RUN
3 CHILLER PANEL(C-1) PXC-36 RUN & SERVICE MODE
4 CHILLER-2 PXC-36 RUN & SERVICE MODE
5 CHI INT-1 PXC-00U RUN & SERVICE MODE
6 CHI-INT-2 PXC-00U RUN & SERVICE MODE
7 CT & CONDENSER PANEL PXC-52 RUN & SERVICE MODE
8 HRW 1 PXC-12 RUN & SERVICE MODE
9 VENTILATION-1 PXC-12 RUN
10 VENTILATION-2 PXC-12 NO CHK
11 VENTILATION-3 PXC-12 NO CHK
12 HRW-3 PXC-12 RUN
13 HRW-4 PXC-12 NO CHK
Remarks
3-PIN power socket missing
Remarks
4F3
4F2
4F1
Remarks
5F2
5F3
5F1
5F4
Remarks
6F2
6F4
Remarks
Shows 7F3
Shows 7F3
Shows 7F4
Remarks
Shows 8F3
Shows 8F2
Shows 8F1
Shows 8F4
Remarks
9F3
9F1
9F4
Remarks
10F3
10F2
10F1
Remarks
11F3
11F2
11F1
Remarks
Panel got shorted with 230V ph.
Could not be chkd due to no supply in socket
Could not be chkd due to no supply in socket
POWER SUPPLY CABLE MISSING,NO 3-PIN PLUG
Could not be chkd due to no supply in socket
Legends: Colour
RUN
DEAD
RUN & SERVICE MODE
NO CHK
NO Access
;
Sensor check list BUILDING 4.(MIND SPACE)
FIRTST FLOOR
AHU-1F1
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-1F3
COLOUR LEGENDS Sl.no Sensors Checked
OK 1 RH-TEMP-1
FAULTY 2 PRESSURE SW-1
MISSING 3 PRESSURE SW-2
RH-TEMP-1 4 PRESSURE SENSOR
PRESSURE SW 5 CO
2
SENSOR
CO
2
SENSOR
SECOND FLOOR
AHU-2F1
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-2F3
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
3 PRESSURE SW-1 QBM81-5 OK
4 PRESSURE SW-2 QBM81-5 OK
5 PRESSURE SENSOR QBM 66.202 OK
6 CO
2
SENSOR QPA2000 OK
THIRD FLOOR
AHU-3F1
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-3F3
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
FOURTH FLOOR
AHU-4F1
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-4F3
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
FIFTH FLOOR
AHU-5F1
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 Faulty
5 CO
2
SENSOR QPA2000 OK
AHU-5F3
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
SIXTH FLOOR
AHU-6F1
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-6F3
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
SEVENTH FLOOR
AHU-7F1
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-7F3
Sl.no
1
2
3
4
5
EIGHTH FLOOR
AHU-8F1
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-8F3
Sl.no
1
2
3
4
5
Note: Some CHW actators are rusted and jammed and can be only be used after servicing.
AHU-1F2
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
3 PRESSURE SW-1 QBM81-5 OK
4 PRESSURE SW-2 QBM81-5 OK
5 PRESSURE SENSOR QBM 66.202 OK
6 CO
2
SENSOR QPA2000 OK
AHU-1F4
Specs/model No. STATUS REMARKS Sl.no Sensors Checked
QFM2160 OK 1 RH-TEMP-1
QBM81-5 OK 2 PRESSURE SW-1
QBM81-5 OK 3 PRESSURE SW-2
QBM 66.202 OK 4 PRESSURE SENSOR
QPA2000 OK 5 CO
2
SENSOR
AHU-2F2
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-2F4
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-3F2
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
3 PRESSURE SW-1 QBM81-5 OK
4 PRESSURE SW-2 QBM81-5 OK
5 PRESSURE SENSOR QBM 66.202 OK
6 CO
2
SENSOR QPA2000 OK
AHU-3F4
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-4F2
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-4F4
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-5F2
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-5F4
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-6F2
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-6F4
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
AHU-7F2
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
Sensors Checked Specs/model No. STATUS REMARKS
RH-TEMP-1 QFM2160 OK
PRESSURE SW-1 QBM81-5 OK
PRESSURE SW-2 QBM81-5 OK
PRESSURE SENSOR QBM 66.202 OK
CO
2
SENSOR QPA2000 OK
AHU-8F2
Sl.no Sensors Checked Specs/model No. STATUS REMARKS
1 RH-TEMP-1 QFM2160 OK
2 PRESSURE SW-1 QBM81-5 OK
3 PRESSURE SW-2 QBM81-5 OK
4 PRESSURE SENSOR QBM 66.202 OK
5 CO
2
SENSOR QPA2000 OK
Sensors Checked Specs/model No. STATUS REMARKS
RH-TEMP-1 QFM2160 OK
PRESSURE SW-1 QBM81-5 OK
PRESSURE SW-2 QBM81-5 OK
PRESSURE SENSOR QBM 66.202 OK
CO
2
SENSOR QPA2000 OK
Note: Some CHW actators are rusted and jammed and can be only be used after servicing.
Specs/model No. STATUS REMARKS
QFM2160 OK
QBM81-5 OK
QBM81-5 OK
QBM 66.202 OK
QPA2000 OK
Compatibility Report for b4.xls
Run on 1/14/2014 8:26
The following features in this workbook are not supported by earlier versions of
Excel. These features may be lost or degraded when you save this workbook in
an earlier file format.