You are on page 1of 1

PRESSURE EQUIPMENT

INSPECTION REQUIREMENTS
IDENTIFICATION
Unit:
Upstream-Unit 82
Tag No:
U-A8300
Equipment Name:
Condensate Pre-cooler
VESSEL/CONFINED SPACE ENTRY REQUIRED: YES NO
CLEANING & PURGING REQUIREMENTS
Water Wash Caustic Wash Fuel Gas Purge Air Purge
Steaming N2 Purge Other: As Per Operations Requirements
OPENING FOR INSPECTION
an !a"s #es No
$nternal an !a"s #es No
Channel Co%er #es No
&un'le (emo%e' #es No
Other Opening #es No Remove header plugs of 0 tu!es from !oth ends" as
recommended !# inspection$
Comments: %$ Arrange for header plug gas&ets accordingl#$
SUPPORT SERVICES REQUIRED FOR INSPECTION
)emister (emo%e' #es No
Schoepentoeter (emo%e #es No
(asching (ings (emo%e #es No
Sca**ol'ing (equire' #es No
echanical Cleaning #es No 'u!e h#dro (et cleaning and air-dr#ing as per inspection$
+ighting (equire' #es No
Comments: %$ Provide 230 ) AC po*er source *ith 2 outlets at the plug header$
2$ Provide plant air hose at the channel head *ith +, or %, coupling as per inspection$
INSPECTION
,isual $nspection #es No Plugs" -as&et area and plug holes etc$
Ultrasonic $nspection #es No U' on header !o.es$
)"e Penetrant #es No
agnetic Particle #es No
$($S Test #es No /R/0 test on tu!es *here plugs have !een removed$
(a'iograph" #es No
Comments: 'he actual num!er of tu!es to !e inspected !# /R/0 ma# change as per inspector1s
discretion$
ADDITIONAL REQUIREMENTS
-"'ro.Pneumatic Test #es No
P(, Ser%icing #es No As per PR) testing schedule$
Other #es No
Comments
Pneumatic test to !e carried out at 3 !ar g to chec& plug lea&s$
MANPOWER
/atargas $nspector #es No % 2atargas /nspector
N)E Technicians #es No /R/0 team 3 U' 'echnicians$
$nspection Time 3 '*elve-hour shifts to cover set-up" inspection" and anal#sis and 4eld
reporting$
PREPARED BY
Signature:
Name:
Title:
Date:
________________________________
________________________________
________________________________
________________________________

You might also like