2006

PESOS POR PISOS


Piso T
1 299.23
2 280.42
3 280.42
4 280.42
PERIODO FUNDAMENTAL
h
n
C
T
T
13.2 35 0.377 < 0.7
Art. 17.2
FACTOR DE AMPLIFICACIN SSMICA
T 0.377
Tp 0.60
C* 3.977
C 2.50
FUERZA CORTANTE EN LA BASE
Z U C S P R V
0.4 1 2.50 1.20 1140.48 8 171.07
Correccion 0.313 > 0.125 ok
FUERZAS CORTANTE DE SISMOX
Piso Altura (m) V (T) F
i
(T)
1 3.3 171.07 18.133 18.53851779
2 6.6 171.07 33.986 34.45567938
3 9.9 171.07 50.980 51.68351907
4 13.2 171.07 67.973 68.91135876
EXCENTRICIDAD ACCIDENTAL
e
x
= 0.9350 m
e
y
= 0.935 m
Art. 17.4
0.275
0.9325
2014
PESOS POR PISOS
Piso T
1 299.23
2 280.42
3 280.42
4 280.42
PERIODO FUNDAMENTAL
h
n
C
T
T
13.2 35 0.377 < 0.7 Art. 17.4
FACTOR DE AMPLIFICACIN SSMICA
T 0.377
Tp 0.6
C 2.5
FUERZA CORTANTE EN LA BASE
Z U C S P R
0.35 1 2.5 1.15 1140.48 8
Correccin 0.3125 > 0.125 ok
FUERZAS CORTANTE DE SISMO
Piso Altura (m) V (T) F
i
(T)
1 4.3 0.32
2 3.3 0.00
3 3.3 0.00
4 3.3 0.00
0.375
EXCENTRICIDAD ACCIDENTAL
ex #REF!
ey #REF!
0.275
Zona
3
2
1
Tabla N 3 (Art. 10)
CATEGORA DE LAS EDIFICACIONES
CATEGORA DESCRIPCIN
A
Edificaciones
Edificaciones esenciales cuya funcin no debera
interrumpirse inmediatamente despus que ocurra un
B
Edificaciones
Edificaciones donde se renen gran cantidad de
personas como teatros, estadios, centros
C Edificaciones comunes, cuya falla ocasionara
D
Edificaciones
Edificaciones cuyas fallas causan prdidas de menor
cuanta y normalmente la probabilidad de causar
V
143.45
Tabla N1 (Art. 5)
FACTORES DE ZONA
Tabla N2
Parmetros del Suelo
Z Tipo Descripcin T
P
(s)
0.40 S
1
Roca o suelos muy rgidos 0.40
0.30 S
2
Suelos intermedios 0.60
0.15 S
3
Suelos flexibles o con estratos de granespesor 0.90
S
4
Condiciones excepcionales
FACTOR U
1.5
1.3
1
(*)
Tabla N1 (Art. 5)
FACTORES DE ZONA
S
1.00
1.20
1.40