Professional Documents
Culture Documents
Licensee
Conditions of use
This is a licensed electronic copy of a document where copyright is owned or managed by
Standards Australia International. Your licence is a single user licence and the document may not
be stored, transferred or otherwise distributed on a network. You may also make one paper copy
of this document if required.
Web Check-up
AS 1670.1-1995 Fire detection, warning, control and intercom systems - System
design, installation and commissioning - Fire
Licensed to LUU MINH LUAN on 25 Feb 2002
AS 1670.11995
(Incorporating Amendment Nos 1, 2, 3 and 4)
Australian Standard
80.0
100.0
20.0
20.0
300.0
500.0
1
2
2
1
2
2
1530.0
80.0
200.0
40.0
20.0
600.0
1000.0
3470.0 3.47A
Less loads that de-energize on alarm
Aircon relays 20.0 2 40
Electric locks 100.0 4 400.0
440.0
Total alarm load IA (mA) 3030.0 3.03A
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
AS 1670.11995
Standards Australia www.standards.com.au
68
Required battery capacity at end of battery life = (I
Q
24) + (I
A
0.5)
= (1.53 24) + (3.03 0.5)
= 36.72 + 1.52
= 38.42 Ah
Therefore required new battery capacity = 38.24 1.25
= 47.8 Ah
Rounded up to nearest available battery = 50.0 Ah
D2 PRIMARY POWER SOURCE CALCULATIONS
(a) Battery charger current calculation:
Battery charger requirement = Battery charged for 24 h to
(see Clause 8.2.3(c)) provide 5 I
Q
+ 0.5I
A
Ah requirement = (5 I
Q
) + (0.5 I
A
)
= (5 1.53) + (0.5 3.03)
= 7.65 + 1.515
= 9.17 Ah
Battery charging current required =
e 24
9.17
= 0.48 A
(e is battery efficiency, say 0.8 for this example)
(b) Power supply requirement:
Choose the greater of
(i) I
A
+ non-battery-backed ancillary alarm loads
Item Unit I in mA Quantity Total A
I
A
3.03
Non-battery-backed ancillary
alarm loads:
Door holders 50.0 4 0.2
3.23A
OR
(ii) I
Q
+ non-battery-backed quiescent loads
Item Unit I in mA Quantity Total A
I
Q
1.53
Non-battery-backed quiescent loads:
Door holders 50.0 6 0.3
1.83A
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
AS 1670.11995
www.standards.com.au Standards Australia
69
Therefore the required power supply rating = 3.23A
Where the power supply is also used as the charger, the battery charger requirement must be
added to the minimum power supply requirement to obtain the minimum power supply
rating.
If the power supply is used as the battery charger the rating is:
= I
A
+ battery charger current requirement
= 3.23A + 0.48A
= 3.71A
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
AS 1670.11995
Standards Australia www.standards.com.au
70
APPENDIX E
FIRE ALARM SYMBOLS
(Normative)
The following symbols are commonly used to indicate on drawings the various items of
equipment:
Heat detector (exposed or surface
mounted)
Fire indicator panel
Heat detector in concealed
spaces
Repeater panel
Heat detector within air duct Mimic panel
Line detector Subindicator panel
Smoke detector (exposed or
surface mounted)
Remote control
equipment
Smoke detector in concealed
spaces
Addressable device
Smoke detector within air duct Manual call point
Smoke detector with sampling
device
Storage batteries
Remote visual indicator Fire alarm bell
Smoke detector (beam type
transmitter)
Electromagnetic door
holder
Smoke detector (beam type
receiver)
Pressure switch
Flame detector Flow switch
End of line device Smoke sampling system
( = sampling point)
Smoke alarm Alarm zone designation
Heat alarm Device address
Circuit wiring
Sounder
Loudspeaker
* If other than Type A, note B, C, D, or E.
Type of smoke detector, e.g. I = ionization, P = photoelectric, CO = carbon monoxide.
Substitute zone number as appropriate.
Type of flame detector, e.g. IR = infrared, UV = ultraviolet.
A1
A1, A4
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
AS 1670.11995
www.standards.com.au Standards Australia
71
FIGURE E1 TYPICAL SINGLE LINE DRAWING
FIGURE E2 TYPICAL ADDRESSABLE SINGLE LINE DRAWING
A1
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
AS 1670.11995
Standards Australia www.standards.com.au
72
APPENDIX F
COMMISSIONING TEST REPORT
(Normative)
THE AUTOMATIC FIRE DETECTION AND ALARM SYSTEM
INSTALLED AT:
(Premises) ____________________________________________________________
____________________________________________________________
______________________________ Postcode __________________
Owner or Owners Authorized Agent:
________________________________________________________________________
________________________________________________________________________
__________________________________________ Postcode __________________
* NEW
* MODIFICATION TO SYSTEM
* ADDITION TO
(* Cross out those not applicable)
Date of commissioning tests _______________________________________________
Name and address of commissioning company, company stamp, or company name
in BLOCK LETTERS
________________________________________________________________________
________________________________________________________________________
___________________________________________ Postcode _________________
Commissioning person. Name (print) __________________________________
Signature: ____________________________________
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
AS 1670.11995
www.standards.com.au Standards Australia
73
N
O
T
A
P
P
L
I
C
A
B
L
E
Y
E
S
N
O
INSTRUCTIONS:
This form is to be used in conjunction with
(a) operator's manual;
(b) installer's statement(s);
(c) 'as-installed' drawings; and
(d) detector test records,
to provide a complete description of the installed system and its tested performance at
the time of its commissioning into service.
SYSTEM INFORMATION
Tick relevant box
(a) Ensure that all detectors used in the system are
(i) listed in the operator's manual;
(ii) compatible with the installed AZF, particularly ensuring that the
permitted number of detectors on each circuit is not exceeded;
and
(iii) installed in an environment for which they are suitable.
(b) Check that the primary power source for the system has been
provided in accordance with AS 3000, and that the isolating switch
disconnects at active conductors.
(c) Check that the detector and the FIP locations are in accordance with
the appropriate clauses of this Standard, AS 1670.
(d) Alarm zone circuit:
(i) Measure each alarm zone circuit voltage, and ensure each is
within the equipment manufacturer's specifications.
(ii) Insulation resistance of all installation wiring measured in
accordance with AS 3000 or similar approved method and
record the worst case result in the logbook.
(e) Open circuit and short circuit 'the end of line device' on each alarm
zone circuit, or conduct other appropriate tests to ensure that fault
and alarm conditions are operating correctly on all alarm zone
facilities on other sections of the control and indicating equipment.
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
AS 1670.11995
Standards Australia www.standards.com.au
74
N
O
T
A
P
P
L
I
C
A
B
L
E
N
O
Y
E
S
(f) FIP test to be carried out as follows:
(i) Operate each alarm test, fault test, isolate and reset facility
provided for each alarm zone facility to determine correct
operation.
(ii) Operate the primary power source switch on and off at least
five times to check the system will not cause a false alarm from
primary power source interruptions.
(g) Detector testing to be carried out as follows:
Test each installed detector or sampling point with an approved
in-situ tester, and ensure that each detector has operated in the
correct range, and the alarm has indicated on the control and
indicating equipment and, if applicable, at the detector tested.
(ii) Confirm that response of the system does not exceed 6 s from
the time the detector operates until the master alarm facility
registers the alarm (while in normal mode) on each zone, or
32 s when AVF is fitted.
(iii) Record tests on detector test record as required by AS 1851.8
and attach to the report.
(h) Check the operation of each manual call point and all other actuating
devices.
(i) For flame detectors, perform the following:
(i) Check that the number and type of detectors provide adequate
protection of the area.
(ii) Check that there are no 'blind' spots in areas protected.
(iii) Check that detectors are rigidly fixed.
(iv) Check that detectors are properly connected to compatible
control and indicating equipment.
(v) Check that detector lenses are clean and adequately protected
from dust and extraneous radiation sources where these are
present.
(vi) Test the detection response to a flame source or simulated
flame.
(j) For smoke detection sampling systems, perform the following:
(i) Measure the response time of all sampling points using smoke
placed at each sampling point.
(ii) Check the back-up power supply capacity.
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
AS 1670.11995
www.standards.com.au Standards Australia
75
Y
E
S
N
O
N
O
T
A
P
P
L
I
C
A
B
L
E
(iii) Check the operation of alarm settings and indicators.
(iv) Check the operation of remote indication of alarm and fault
signals.
(v) Check the operation of airflow failure indicators.
(vi) Check the operation of the system (signal) failure indicators.
(vii) Check the isolate/reset functions.
(viii) Check the fault and alarm test facilities.
(k) Test each ancillary function by operating the alarm zone facility(ies),
associated with the ancillary function.
(l) Alarm signalling:
(i) Check that the master alarm facility is able to receive the alarm
signal by operating each alarm zone facility.
(ii) Check that the master alarm facility initiates an alarm to the fire
control station equipment.
(m) Battery supply:
(i) Check that both the primary and secondary power sources are
of a suitable type and capacity complying with the requirements
of Clause 8.2.
(ii) Perform a float voltage check according to the battery
manufacturer's recommendation to ensure that the charger type
and setting is correct.
Type of battery connected..........................................................
Float voltage/ required...............................................................
Charger type .............................................................................
Charger set at ...........................................................................
(n) Check that all alarm zone facilities have been correctly labelled and
that the alarm zone is immediately apparent from the labelling.
(o) Check that 'as-installed' drawings have been correctly marked up and
that they are consistent with the installation. Check that the operator's
manual is relevant to the installation.
(p) Ensure that the results of the commissioning tests are recorded in the
system logbook.
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
AS 1670.11995
Standards Australia www.standards.com.au
76
APPENDIX G
STANDARD FORM OF STATEMENT OF COMPLIANCE FOR FIRE ALARM
SYSTEMS
(Normative)
1 Name of building ........................................................................................................
2 Situated at .................................................................................................................
3 I/We have installed in the above building
an alteration to the system of ..................................................................
a system of (Brand Name)
4 System connected to the ...........................................................................................
monitoring service provider by a permanent , non-permanent connection
5 Date of connection ....................................................................................................
6 Describe any ancillary equipment installed and connected to the control and
indicating equipment .................................................................................................
...................................................................................................................................
...................................................................................................................................
7 Current drain of ancillary loads powered from the CIE power supply
...................................................................................................................................
...................................................................................................................................
8 Primary power source voltage ....................................................................................
9 Battery type and capacity ........................................................................................
10 Is maintenance agreement held for the system? ........................................................
11 Has operator's handbook been supplied? ..................................................................
12 Has logbook been supplied? ......................................................................................
13 Have 'as-installed' drawings been supplied? .............................................................
14 Portion of building not protected by this system ........................................................
...................................................................................................................................
...................................................................................................................................
...................................................................................................................................
A1
A1
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
AS 1670.11995
www.standards.com.au Standards Australia
77
15 I/We hereby certify that the installation has been thoroughly tested from each
actuating device and that a test of the transmission of the alarm signal to the
monitoring service provider has been satisfactorily carried out. I/We further certify
that the whole system and all components called up in Clause 1.3 in connection
therewith are installed entirely in accordance with the current requirements of
AS 1670.1, except with regard to the following details which have already been
approved*.
..........................................................................................................................................
..........................................................................................................................................
..........................................................................................................................................
Dated ......................................................... (Signature) ..............................................
Installing Company .........................................................................................................
Zone of
protection
Number and type of actuating devices
Thermal Smoke Flame
Alarm
zone
Number
of
actuating
devices
per zone
A B C D E Ionization
Photo-
electrical
IR UV
Manual
call
point
Other
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Total
Number
* If no exception strike out the words underlined.
Indicate with a number in brackets the number of actuating devices in concealed spaces.
Add addressable loop number in brackets where applicable.
A1
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
Standards Australia
Standards Australia is an independent company, limited by guarantee, which prepares and publishes
most of the voluntary technical and commercial standards used in Australia. These standards are
developed through an open process of consultation and consensus, in which all interested parties are
invited to participate. Through a Memorandum of Understanding with the Commonwealth government,
Standards Australia is recognized as Australias peak national standards body.
Australian Standards
Australian Standards are prepared by committees of experts from industry, governments, consumers
and other relevant sectors. The requirements or recommendations contained in published Standards are
a consensus of the views of representative interests and also take account of comments received from
other sources. They reflect the latest scientific and industry experience. Australian Standards are kept
under continuous review after publication and are updated regularly to take account of changing
technology.
International Involvement
Standards Australia is responsible for ensuring that the Australian viewpoint is considered in the
formulation of international Standards and that the latest international experience is incorporated in
national Standards. This role is vital in assisting local industry to compete in international markets.
Standards Australia represents Australia at both ISO (The International Organization
for Standardization) and the International Electrotechnical Commission (IEC).
Electronic Standards
All Australian Standards are available in electronic editions, either downloaded individually from our Web
site, or via on-line and CD ROM subscription services. For more information phone 1300 65 46 46 or
visit us at
www.standards.com.au
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.
GPO Box 5420 Sydney NSW 2001
Administration Phone (02) 8206 6000 Fax (02) 8206 6001 Email mail@standards.com.au
Customer Service Phone 1300 65 46 46 Fax 1300 65 49 49 Email sales@standards.com.au
Internet www.standards.com.au
ISBN 0 7262 9754 2 Printed in Australia
L
i
c
e
n
s
e
d
t
o
L
U
U
M
I
N
H
L
U
A
N
o
n
2
5
F
e
b
2
0
0
2
.
S
i
n
g
l
e
u
s
e
r
l
i
c
e
n
c
e
o
n
l
y
.
S
t
o
r
a
g
e
,
d
i
s
t
r
i
b
u
t
i
o
n
o
r
u
s
e
o
n
n
e
t
w
o
r
k
p
r
o
h
i
b
i
t
e
d
.